BSE320_CE

3
 P-BSE320/CE - Rev. B, 99112 Protecting environment, life and property... Features Provides 8 non-monitored and galvanic isolated inputs. Easily plugged onto each other or onto other I/O modules on a standard mounting rail.  Automatic addressing of the I/O module. Designed to meet EN-54 and LPCB require  ments and conforms to CE standards. Applications The Input Module BSE-320 provides 8 non- monitored and galvanic isolated inputs for digital input devices and other controlling inputs. The I/O module is easily plugged onto a mounting rail inside the Fire Alarm Control Panel (BS-310/320) or the Controller (BC-320). The inputs have a common connection to an exter- nal source, 24V DC. Each input is activated by pull- ing the terminal to 0V, typically by an open collector output. The I/O module will automatically detect its own ad- dress, no Dip-switch or jumper settings are required. Connections The I/O module has the following connections: Screw Terminal nr. Signal 1 IN1 2 IN2 3 IN3 4 IN4 5 IN5 6 IN6 7 IN7 8 IN8 9 n.c. 10 INx-power supply Common source to all inputs (+) AutroSafe Input Module - BSE-320 Screw- terminal 1 Front view when mounted on rail Screw- terminal 10

Transcript of BSE320_CE

Page 1: BSE320_CE

8/12/2019 BSE320_CE

http://slidepdf.com/reader/full/bse320ce 1/2

P-BSE320/CE - Rev. B, 99112 Protecting environment, life and property...

Features

• Provides 8 non-monitored and galvanic isolatedinputs.

• Easily plugged onto each other or onto other I/Omodules on a standard mounting rail.

• Automatic addressing of the I/O module.• Designed to meet EN-54 and LPCB require

ments and conforms to CE standards.

Applications

The Input Module BSE-320 provides 8 non-monitored and galvanic isolated inputs for digitalinput devices and other controlling inputs.The I/O module is easily plugged onto a mountingrail inside the Fire Alarm Control Panel (BS-310/320)or the Controller (BC-320).

The inputs have a common connection to an exter-nal source, 24V DC. Each input is activated by pull-ing the terminal to 0V, typically by an open collectoroutput.

The I/O module will automatically detect its own ad-

dress, no Dip-switch or jumper settings are required.

Connections

The I/O module has the following connections:

Screw Terminal nr. Signal1 IN12 IN23 IN3

4 IN45 IN56 IN67 IN78 IN89 n.c.

10 INx-power supplyCommon source to all inputs

(+)

AutroSafe Input Module - BSE-320

Screw-terminal 1

Front view when mounted on rail

Screw-terminal 10

Page 2: BSE320_CE

8/12/2019 BSE320_CE

http://slidepdf.com/reader/full/bse320ce 2/2

Input Module, BSE-320

Autronica Fire and Security ASFire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01. Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99. Autronica Industrial Ltd., Watford, United Kingdom. Phone: 1923 23 37 68, fax: 1923 22 55 77.

Visit Autronica Fire and Security's Web site: www.autronicafire.com

Technical Specifications

Dimensions (mm) 95x89x32Weight (g) 81Materials Top and bottom: Zytel

FR7200

Snap-on mounting device:Zytel 7335S

No. of inputs per module 8 pcs, non-monitoredElectrical connection Internal system: plug-in

connectionScrew terminals (maximum

cable dimension 2,5mm 2)Mounting Onto a standard mounting

rail inside the Fire AlarmControl Panel or Controller.

Internal current consumption 24VREG: 7 mACurrent consumption controlinput

6 mA(at 24V Power ON)

Threshold voltage 4 - 7V

Maximum input voltage 0 to +32V DC

Order Numbers

Order numbers DescriptionBSE-320 Input Module

Installation Overview (example)

Schematics

Sense 1

+24V

External

24V power

External minusconnection list

Sense 2

Sense 8

Signal input 1

Signal input 2

Signal input 8

+ + -

-

1

2

8

Input module

10

Galvanicisolated

10 +24V DC fromexternal power

1-8 Signal input