Screenwall calculation series1 22/08/15 [email protected]
-‐ 1 -‐
@ Structure Geometry:Length, b= 10.000mHeight, c= 1.800m
End Restraint 1
Pier located 1b/c= 5.56c/h= 1.00
Values of Cp,n:2.40
If > 3.6 m and < 7.2 m from end 1.200.60
Cp,n = 2.40Solidity ratio, δ = 1.00
Kp = 1.00Cfig = Cp,n x kp = 2.40
Wind Class 1 0.83
@ Pressure, [p]=1.2x0.5x(41x0.83)^2x2.4 <=> [pz] = 1.668kPa
Design for a pier with 1000 x 190 mm,
L[mm] t[mm] e[mm] Df [mm]1000 190 200 300
@ Strength moment, M*= qL x 1.0 x [h/2 + e] = 1.668 x 1.8 x 1 x (1.8/2 + 0.2) = 3.30kNm
For the pier size 1000 x190 with 3R10 OR 2L10 (3.33 kNm)rods: R10 @ 400 max c/c OR L10 @ 800 max c/c ~ (3.33kNm) 3.33
@ Overturn moment , M*= qL x 1.0x[h/2+e+Df]=1.668x1.8x1x(1.8/2+0.2+0.3) = 4.20kNm
For resisting of overturn moment is needed to provide a strip footing with 900 wide strip footing x 300 deep ~ (4.59kNm).
SCREEN WALL TYPE -1 (STRIP FOOTING)
from end of wall
If < 3.6 m from end
If > 7.2 m from end
Free$End
<"2c
N1
Screenwall calculation series1 22/08/15 [email protected]
-‐ 1 -‐
@ Structure Geometry:Length, b= 5.630mHeight, c= 1.200m
End Restraint 2
Pier located 1b/c= 4.69c/h= 1.00
Values of Cp,n:1.20
If > 2.4 m and < 4.8 m from end 1.200.60
Cp,n = 1.20Solidity ratio, δ = 1.00
Kp = 1.00Cfig = Cp,n x kp = 1.20
Wind Class 2 0.91
@ Pressure, [p]=1.2x0.5x(41x0.91)^2x1.2 <=> [pz] = 1.002kPa
Design for a pier with 1000 x 190 mm,so [mm] t[mm] Df [mm] E+Df [mm]
1000 190 300 986Soil Data
Efooting[mm] F.O.S K Surcharge686 1.5 0.33 0
@ Strength moment, M*2.00kNm
For the pier size 1000 x190 with 2R10 OR 1L10 (2.09 kNm)rods: R10 @ 650 max c/c OR L10 @ 1350 max c/c ~ (2.01kNm)@ Overturn moment, M*
3.27kNm
For resisting of overturn moment is needed to provide a strip footing with 600 wide strip footing x 300 deep ~ (3.42kNm).
SCREEN WALL WITH RETAINING, V8spec, Jspec (STRIP FOOTING)
from end of wall
If < 2.4 m from end
If > 4.8 m from end
Corner
<"2c
N2
Movertun = pz × s0 ×Hpier"# $%×
Hpier
2+Efooting +Df
"
#&
$
%'+1.5Kaγ Efooting +Df( )
3
6s0 +
1.5Kaγ Efooting +Df( )2
2s0 =
Movertun = pz × s0 ×Hpier"# $%×
Hpier
2+Efooting
"
#&
$
%'+1.5Kaγ Efooting( )
3
6s0 +
1.5Kaγ Efooting( )2
2s0 =
Screenwall calculation series1 22/08/15 [email protected]
-‐ 1 -‐
@ Structure Geometry:Length, b= 7.00mHeight, c= 1.80m
End Restraint 2
Pier located 1b/c= 3.89c/h= 1.00
Values of Cp,n:1.21
If > 3.6 m and < 7.2 m from end 1.200.60
Cp,n = 1.21Solidity ratio, δ = 1.00
Kp = 1.00Cfig = Cp,n x kp = 1.21
Wind Class 1 0.83
@ Pressure, [p]=1.2x0.5x(41x0.83)^2x1.21 <=> [pz] = 0.841kPa
Design for a pier with 300 x 300 mm,
B[mm] D[mm] s[mm] e[mm] Df [mm]300 300 1200 200 300
@ Strength moment, M*= qLs x [ h/2 + e] = 0.841 x 1.8 x 1.2 x (1.8/2 + 0.2) = 2.00kNm
For the pier size 300 x 300 with 1R10 OR 1L10 (2.12 kNm) Ok!!! 7.65
@ Overturn moment, M*= qLs [h/2+e+Df]= 0.841 x 1.8 x 1.2x(1.8/2+ 0.2+0.3)= 2.54kNm
For resisting of overturn moment is needed to provide a pad footing with 700 SQ pad footing x 300 deep ~ (2.71kNm).
SCREEN WALL TYPE -2 (PAD FOOTING)
from end of wall
If < 3.6 m from end
If > 7.2 m from end
Corner
<"2c
N1
Screenwall calculation series1 22/08/15 [email protected]
-‐ 1 -‐
@ Structure Geometry:Length, b= 5.00mHeight, c= 1.50m
End Restraint 2
Pier located 1b/c= 3.33c/h= 1.00
Values of Cp,n:1.22
If > 3 m and < 6 m from end 1.200.60
Cp,n = 1.22Solidity ratio, δ = 1.00
Kp = 1.00Cfig = Cp,n x kp = 1.22
Wind Class 2 0.91
@ Pressure, [p]=1.2x0.5x(41x0.91)^2x1.22 <=> [pz] = 1.019kPa
Design for a pier with 1000 x 190 mm,B [mm] D [mm] sRight [mm] sLeft [mm] Df [mm] E+Df [mm]
340 350 2000 2300 300 1243Soil Data
Efooting[mm] F.O.S K Surcharge so [mm] t [mm]943 1.5 0.33 2.5 1000 190
@ Strength moment for a pier & 190 wall for retaining , M* 2490 14158.91kNm
2490mm 1415mm
For the pier size 340 x 350 with 4R10 OR 2L10 (9.01 kNm) Ok!!! 11.793870
2.01kNm
For the wall size 1150 x 190 with 2R10 OR 1L10 (2.7 kNm) Ok!!! 11.755643
6.73kNm
For resisting of overturn moment is needed to provide a strip footing with 800 wide strip footing x 300 deep ~ (7.44kNm).
If > 6 m from end
SCREEN WALL WITH RETAINING, V8spec, Jspec (STRIP FOOTING)
from end of wall
If < 3 m from end
Corner
<"2c
N2
Mstrength for a retaining Wall =1.5K.γE3
6max 1
2sright,
12sleft
!
"#$
%&+1.5K.γE 2
2max 1
2sright,
12sleft
!
"#$
%&=
Mstrength for a pier = pz × s1 ×Hpier"# $%×
Hpier
2+Efooting
"
#&
$
%'+1.5KaγEfooting
3
6s2 +
1.5KaγEfooting2
2s2 =
s1 = 0.5× sright +Bpier + 0.5× sleft( ) = ∴ s2 = 0.25× sright +Bpier + 0.25× sleft( ) =
Moverturning = pz × s0 ×Hpier"# $%×
Hpier
2+Efooting +Df
"
#&
$
%'+1.5Kaγ Efooting +Df( )
3
6s0 +
1.5Kaγ Efooting +Df( )2
2s0 =
Screenwall calculation series1 22/08/15 [email protected]
-‐ 1 -‐
Screenwall calculation series1 22/08/15 [email protected]
-‐ 1 -‐
Screenwall calculation series1 22/08/15 [email protected]
-‐ 1 -‐
End Restraint:Free End 1 2 3 4Corner 2 0.990 0.910 0.830 0.750Pier Location: 3 0.990 0.910 0.830 0.750< 2c 4 1.020 0.910 0.830 0.750> 2c & < 4c 5 1.050 0.910 0.830 0.750> 4c 6 1.064 0.928 0.830 0.750N1 7 1.078 0.946 0.830 0.750N2 8 1.092 0.964 0.830 0.750
9 1.106 0.982 0.830 0.75010 1.120 1.000 0.830 0.750
b/c c/h Cp,n e0.2 to 5 0.2 to 1 1.1955 0
> 5 1.2001 0all < 0.2 1.6134 0
b/c c/h Cp,n e
0.2 to 1 1.1955 0< 0.2 1.6134 0
b/c c/hDist from windward
Cp,n
0 to 2c 3.002c to 4c 1.50
> 4c 0.750 to 2h 2.40
2h to 4h 1.20> 4h 0.60
0 to 2h 1.80
b/c c/h Cp,n e
0.2 to 5 0.2 to 1 1.2110 0> 5 1.2001 0all < 0.2 1.5669 0
0.2 to 5
Corners
> 5
≤ 0.7
> 0.7
Terrain CategoryHeight (z) m
Screenwall calculation series1 22/08/15 [email protected]
-‐ 1 -‐
b/c c/h Cp,n e0.2 to 5 0.2 to 1 1.2029 0
> 5 1.2001 0all < 0.2 1.5914 0
b/c c/h Cp,n e0.2 to 5 0.2 to 1 1.2177 0
> 5 1.2001 0all < 0.2 1.5469 0