EQTip13

download EQTip13

of 16

Transcript of EQTip13

  • 7/30/2019 EQTip13

    1/16

    Why should Masonry Buildings have simple Structural Configuration?

    EarthquakeTip 13LearningEarthquake DesignandConstruction

    Box Action in Masonry BuildingsBrick masonry buildings have large mass and

    hence attract large horizontal forces during earthquakeshaking. They develop numerous cracks under bothcompressive and tensile forces caused by earthquakeshaking. The focus of earthquake resistant masonrybuilding construction is to ensure that these effects aresustained without major damage or collapse.Appropriate choice of structural configuration canhelp achieve this.

    The structural configuration of masonry buildingsincludes aspects like (a) overall shape and size of thebuilding, and (b) distribution of mass and (horizontal)lateral load resisting elements across the building.Large, tall, long and unsymmetric buildings performpoorly during earthquakes (IITK-BMTPC EarthquakeTip 6). A strategy used in making them earthquake-resistant is developing good box action between all theelements of the building, i.e., between roof, walls andfoundation (Figure 1). Loosely connected roof orunduly slender walls are threats to good seismicbehaviour. For example, a horizontal band introduced

    at the lintel level ties the walls together and helps tomake them behave as a single unit.

    Influence of OpeningsOpenings are functional necessities in buildings.

    However, location and size of openings in wallsassume significance in deciding the performance ofmasonry buildings in earthquakes. To understand this,

    consider a four-wall system of a single storey masonrybuilding (Figure 2). During earthquake shaking, inertiaforces act in the strong direction of some walls and inthe weak direction of others (See IITK-BMTPCEarthquake Tip 12). Walls shaken in the weak directionseek support from the other walls, i.e., walls B1 and B2seek support from walls A1 and A2 for shaking in thedirection shown in Figure 2. To be more specific, wallB1 pulls walls A1 and A2, while wall B2 pushesagainst them. At the next instance, the direction of

    shaking could change to the horizontal directionperpendicular to that shown in Figure 2. Then, walls Aand B change their roles; Walls B1 and B2 become thestrong ones and A1 and A2 weak.

    Thus, walls transfer loads to each other at theirjunctions (and through the lintel bands and roof).Hence, the masonry courses from the walls meeting atcorners must have good interlocking. For this reason,openings near the wall corners are detrimental to goodseismic performance. Openings too close to wallcorners hamper the flow of forces from one wall toanother (Figure 3). Further, large openings weaken

    walls from carrying the inertia forces in their ownplane. Thus, it is best to keep all openings as small aspossible and as far away from the corners as possible.

    Figure 1: Essential requirements to ensure boxactionin a masonry building.

    Goodconnectionbetweenroofand walls

    Walls withsmallopenings

    Roof that stays together as a singleintegral unitduring earthquakes

    Goodconnection

    betweenwalls and

    foundationGood connectionat wall corners

    Stiff Foundation

    LintelBand

    Figure 2: Regions of force transfer from weakwalls to strong walls in a masonry building wall B1 pulls walls A1 and A2, while wall B2pushes walls A1 and A2.

    Inertia forcefrom roof

    A2

    Direction ofearthquake

    shaking

    A1

    B1

    B2

    Regionswhere loa

    transfertakes place

    from one

    wall toanother

    Inertia forcefrom roof

    25

  • 7/30/2019 EQTip13

    2/16

    IITK-BMTPC Earthquake Tip 13

    Why should Masonry Buildings have simple Structural Configuration? page 2

    Earthquake-Resistant FeaturesIndian Standards suggest a number of earthquake-

    resistant measures to develop good box-type action inmasonry buildings and improve their seismicperformance. For instance, it is suggested that abuilding having horizontal projections when seenfrom the top, e.g., like a building with plan shapes L, T,E and Y, be separated into (almost) simple rectangularblocks in plan, each of which has simple and goodearthquake behaviour (IITK-BMTPC Earthquake Tip 6).

    During earthquakes, separated blocks can oscillateindependently and even hammer each other if they aretoo close. Thus, adequate gap is necessary betweenthese different blocks of the building. The IndianStandards suggest minimum seismic separationsbetween blocks of buildings. However, it may not benecessary to provide such separations between blocks,if horizontal projections in buildings are small, say upto ~15-20% of the length of building in that direction.

    Inclined staircase slabs in masonry buildings offeranother concern. An integrally connected staircase slabacts like a cross-brace between floors and transfers

    large horizontal forces at the roof and lower levels(Figure 4a). These are areas of potential damage inmasonry buildings, if not accounted for in staircasedesign and construction. To overcome this, sometimes,staircases are completely separated (Figure 4b) andbuilt on a separate reinforced concrete structure.Adequate gap is provided between the staircase towerand the masonry building to ensure that they do notpound each other during strong earthquake shaking.

    Reading MaterialIS 1905, (1987), Indian Standard Code of Practice for Structural Use of

    Unreinforced Masonry, Bureau of Indian Standards, New DelhiIS 42326, (1993), Indian Standard Code of Practice for Earthquake

    Resistant Design and Construction of Buildings, Bureau of IndianStandards, New Delhi

    IS 13828, (1993), Indian Standard Guidelines for Improving EarthquakeResistance of Low-strength Masonry Buildings, Bureau of IndianStandards, New Delhi

    Tomazevic,M., (1999), Earthquake Resistant Design of MasonryBuildings, Imperial College Press, UK

    Related Earthquake TipTip 5: What are the seismic effects on structures?Tip 6: How architectural features affect buildings during earthquakes?Tip12: How brick masonry houses behave during earthquakes?

    This release is a property of IIT Kanpur and BMTPC NewDelhi. It may be reproduced without changing its contentsand with due acknowledgement. Suggestions/commentsmay be sent to: [email protected]. Visit www.nicee.org orwww.bmtpc.org, to see previous IITK-BMTPC Earthquake Tips.

    Authored by:C.V.R.MurtyIndian Institute of Technology KanpurKanpur, India

    Sponsored by:Building Materials and Technology PromotionCouncil, New Delhi, India

    Figure 3: Openings weaken walls in a masonrybuilding a single closed horizontal band must

    be provided above all of them.

    Largewindowopeningreduces thewall strengthin its strongdirection

    Figure 4: Earthquake-resistant detailing ofstaircase in masonry building must be carefully designed and constructed.

    Inertia force oroof mass

    DamageDiagonal

    bracingeffect

    Damage

    Damage

    (a) Damage in building with rigidly built-in staircase

    Gap

    (b) Building with separated staircase

    Reinforced ConcreteStair Case Tower(or Mumty)

    Tallslenderwall

    Door openingclose to wall cornerweakens the connection between walls

    26

  • 7/30/2019 EQTip13

    3/16

    Why are Horizontal Bands necessary in Masonry Buildings?

    EarthquakeTip 14LearningEarthquake DesignandConstruction

    Role of Horizontal BandsHorizontal bands are the most important

    earthquake-resistant feature in masonry buildings. Thebands are provided to hold a masonry building as asingle unit by tying all the walls together, and aresimilar to a closed belt provided around cardboardboxes. There are four types of bands in a typicalmasonry building, namely gable band, roof band, lintelband and plinth band (Figure 1), named after theirlocation in the building. The lintel band is the most

    important of all, and needs to be provided in almost allbuildings. The gable band is employed only inbuildings with pitched or sloped roofs. In buildingswith flat reinforced concrete or reinforced brick roofs, theroof band is not required, because the roof slab alsoplays the role of a band. However, in buildings with

    flat timber or CGI sheet roof, roof band needs to beprovided. In buildings with pitched or sloped roof, theroof band is very important. Plinth bands areprimarily used when there is concern about unevensettlement of foundation soil.

    The lintel band ties the walls together and createsa support for walls loaded along weak direction fromwalls loaded in strong direction. This band alsoreduces the unsupported height of the walls andthereby improves their stability in the weak direction.

    During the 1993 Latur earthquake (Central India), theintensity of shaking in Killari village was IX on MSKscale. Most masonry houses sustained partial orcomplete collapse (Figure 2a). On the other hand, therewas one masonry building in the village, which had alintel band and it sustained the shaking very well withhardly any damage (Figure 2b).

    Figure 1: Horizontal Bands in masonry building Improve earthquake-resistance.

    Foundation

    Roof

    Masonryabove lintel

    Masonrybelow linte

    Lintel Band

    Wall

    Soil

    Plinth Band

    RoofBand

    (a) Building with Flat Roof

    (b) Two-storey Building with Pitched Roof

    PlinthBand

    LintelBand

    GableBand

    Floor-wallsconnection

    Gable-rooconnection

    Peripheral wallconnection

    Cross wallconnection

    Truss-wallconnection

    Figure 2: The 1993 Latur Earthquake (CentralIndia) - one masonry house in Killari village hadhorizontal lintel band and sustained the shakingwithout damage.

    (a) Building with no horizontal lintel band:collapse of roof and walls

    (b) A building with horizontal lintel band in Killarivillage:no damage

    LintelBand

    27

  • 7/30/2019 EQTip13

    4/16

    IITK-BMTPC Earthquake Tip 14

    Why are Horizontal Bands necessary in Masonry Buildings? page 2

    Design of Lintel BandsDuring earthquake shaking, the lintel band

    undergoes bending and pulling actions (Figure 3). Toresist these actions, the construction of lintel bandrequires special attention. Bands can be made of wood(including bamboo splits) or of reinforced concrete

    (RC) (Figure 4); the RC bands are the best. The straightlengths of the band must be properly connected at thewall corners. This will allow the band to support wallsloaded in their weak direction by walls loaded in theirstrong direction. Small lengths of wood spacers (inwooden bands) or steel links (in RC bands) are used tomake the straight lengths of wood runners or steelbars act together. In wooden bands, proper nailing ofstraight lengths with spacers is important. Likewise, inRC bands, adequate anchoring of steel links with steelbars is necessary.

    Indian StandardsThe Indian Standards IS:4326-1993 and IS:13828

    (1993) provide sizes and details of the bands. When

    wooden bands are used, the cross-section of runners isto be at least 75mm38mm and of spacers at least

    50mm30mm. When RC bands are used, the minimumthickness is 75mm, and at least two bars of 8mmdiameter are required, tied across with steel links of atleast 6mm diameter at a spacing of 150 mm centers.

    Related Earthquake TipTip 5: What are the seismic effects on structures?Tip12: How brick masonry houses behave during earthquakes?Tip13: Why masonry buildings should have simple structural

    configuration?

    Reading MaterialIAEE, (1986), Guidelines for Earthquake Resistant Non-Engineered

    Construction, International Association for EarthquakeEngineering, Tokyo, available on www.nicee.org

    IS 4326, (1993), Indian Standard Code of Practice for Earthquake Resistant

    Design and Construction of Buildings, Bureau of Indian Standards,New Delhi

    IS 13828, (1993), Indian Standard Guidelines for Improving EarthquakeResistance of Low-strength Masonry Buildings, Bureau of IndianStandards, New Delhi

    This release is a property of IIT Kanpur and BMTPC NewDelhi. It may be reproduced without changing its contentsand with due acknowledgement. Suggestions/commentsmay be sent to: [email protected]. Visit www.nicee.org orwww.bmtpc.org, to see previous IITK-BMTPC Earthquake Tips.

    Authored by:C.V.R.MurtyIndian Institute of Technology KanpurKanpur, India

    Sponsored by:Building Materials and Technology Promotion

    Council, New Delhi, India

    Figure 3: Bending and pulling in lintel bands Bands must be capable of resisting these.

    Direction ofInertia Force

    Bending ofLintel Band

    LintelBand

    Pulling ofLintel Band

    Small

    Cross-section ofLintel Bands

    Large

    150mm75 mm

    Direction ofearthquake

    shaking

    Figure 4: Horizontal Bands in masonry buildings

    RC bands are the best.

    (a) Wooden Band

    A

    B

    WooRunners

    Wood Spacers

    Correct

    Practices

    (b) RC Band

    IncorrectPractice

    A

    SteelLinks

    BSteel Bars

    28

  • 7/30/2019 EQTip13

    5/16

    Why is Vertical Reinforcement required in Masonry Buildings?

    EarthquakeTip 15LearningEarthquake DesignandConstruction

    Response of Masonry WallsHorizontal bands are provided in masonry

    buildings to improve their earthquake performance.These bands include plinth band, lintel band and roofband. Even if horizontal bands are provided, masonrybuildings are weakened by the openings in their walls(Figure 1). During earthquake shaking, the masonrywalls get grouped into three sub-units, namelyspandrel masonry, wall pier masonry and sill masonry.

    Consider a hipped roof building with two windowopenings and one door opening in a wall (Figure 2a). Ithas lintel and plinth bands. Since the roof is a hippedone, a roof band is also provided. When the groundshakes, the inertia force causes the small-sizedmasonry wall piers to disconnect from the masonry

    above and below. These masonry sub-units rock backand forth, developing contact only at the oppositediagonals (Figure 2b). The rocking of a masonry piercan crush the masonry at the corners. Rocking ispossible when masonry piers are slender, and whenweight of the structure above is small. Otherwise, thepiers are more likely to develop diagonal (X-type)shear cracking (Figure 2c); this is the most commonfailure type in masonry buildings.

    In un-reinforced masonry buildings (Figure 3), thecross-section area of the masonry wall reduces at theopening. During strong earthquake shaking, the

    building may slidejust under the roof, below the lintelband or at the sill level. Sometimes, the building mayalso slide at the plinth level. The exact location ofsliding depends on numerous factors includingbuilding weight, the earthquake-induced inertia force,the area of openings, and type of doorframes used.

    29

    Figure 1: Sub-units in masonry building wallsbehave as discrete units during earthquakes.

    Foundation

    Roof

    SpandrelMasonry

    SillMasonry

    Soil

    Wall PierMasonry

    SillLevel

    LintelLevel

    PlinthLevel

    Figure 2: Earthquake response of a hipped roofmasonry building no vertical reinforcementis provided in walls.

    (b) Rocking of Masonry Piers

    Rockingof Pier

    Uplifting ofmasonry

    Crushing

    LintelBand

    Soil

    RoofBand

    DoorOpening

    WindowOpening

    Roof

    Foundation

    PlinthBand

    X-Crackingof Masonry

    Piers

    Soil

    (c) X-Cracking of Masonry Piers

    Foundation

    MasonryPier(a) Building Components

    Figure 3: Horizontal sliding at sill level in amasonry building no vertical reinforcement.

    Foundation

    RoofEarthquake-induced inertiaforce

    Sliding

  • 7/30/2019 EQTip13

    6/16

    IITK-BMTPC Earthquake Tip 15

    Why is Vertical Reinforcement required in Masonry Buildings? page 2

    How Vertical Reinforcement HelpsEmbedding vertical reinforcement bars in the

    edges of the wall piers and anchoring them in thefoundation at the bottom and in the roof band at thetop (Figure 4), forces the slender masonry piers toundergo bending instead of rocking. In wider wall piers,

    the vertical bars enhance their capability to resisthorizontal earthquake forces and delay the X-cracking.Adequate cross-sectional area of these vertical barsprevents the bar from yielding in tension. Further, thevertical bars also help protect the wall from sliding aswell as from collapsing in the weak direction.

    Protection of Openings in WallsSliding failure mentioned above is rare, even in

    unconfined masonry buildings. However, the mostcommon damage, observed after an earthquake, isdiagonal X-cracking of wall piers, and also inclinedcracks at the corners of door and window openings.When a wall with an opening deforms duringearthquake shaking, the shape of the opening distortsand becomes more like a rhombus - two oppositecorners move away and the other two come closer.Under this type of deformation, the corners that comecloser develop cracks (Figure 5a). The cracks are bigger

    when the opening sizes are larger. Steel bars providedin the wall masonry all around the openings restrictthese cracks at the corners (Figure 5b). In summary,lintel and sill bands above and below openings, andvertical reinforcement adjacent to vertical edges,provide protection against this type of damage.

    Related - Earthquake TipTip 5: What are the seismic effects on structures?Tip12: How brick masonry houses behave during earthquakes?Tip13: Why masonry buildings should have simple structural

    configuration?Tip14: Why horizontal bands are required in masonry buildings?

    Reading MaterialAmrose,J., (1991), Simplified Design of Masonry Structures, John Wiley

    & Sons, Inc., USABMTPC, (2000), Guidelines: Improving Earthquake Resistance of

    Housing, Building Materials and Technology Promotion Council,New Delhi

    IS 4326, (1993), Indian Standard Code of Practice for Earthquake ResistantDesign and Construction of Buildings, Bureau of Indian Standards,New Delhi

    IS 13828, (1993), Indian Standard Guidelines for Improving EarthquakeResistance of Low-strength Masonry Buildings, Bureau of IndianStandards, New Delhi

    This release is a property of IIT Kanpur and BMTPC NewDelhi. It may be reproduced without changing its contentsand with due acknowledgement. Suggestions/commentsmay be sent to: [email protected]. Visit www.nicee.org orwww.bmtpc.org, to see previous IITK-BMTPC Earthquake Tips.

    Authored by:C.V.R.MurtyIndian Institute of Technology KanpurKanpur, India

    Sponsored by:Building Materials and Technology Promotion

    Council, New Delhi, India

    Figure 5: Cracks at corners of openings in amasonry building reinforcement around themhelps.

    (b) No cracks in buildingwithvertical reinforcement

    Earthquake-induced inertia force

    Cracking

    (a) Cracking in building withnocorner reinforcement

    ReinforcementBars

    (a) Vertical reinforcement causes bending ofmasonry piers in place of rocking (See Figure 2).

    Bendingof Pier

    Vertical steel bars anchored infoundation and roof band

    Figure 4: Vertical reinforcement in masonry walls wall behaviour is modified.

    (b) Vertical reinforcement prevents sliding in walls(See Figure 3).

    Lintel Band

    Sill Band(Similar toLintel Band,but discontinuedat door openings)

    30

  • 7/30/2019 EQTip13

    7/16

    How to make Stone Masonry Buildings Earthquake-Resistant?

    EarthquakeTip 16LearningEarthquake DesignandConstruction

    Behaviour during Past India EarthquakesStone has been used in building construction in

    India since ancient times since it is durable and locallyavailable. There are huge numbers of stone buildingsin the country, ranging from rural houses to royalpalaces and temples. In a typical rural stone house,there are thick stone masonry walls (thickness rangesfrom 600 to 1200 mm) built using rounded stones fromriverbeds bound with mud mortar. These walls areconstructed with stones placed in a random manner,

    and hence do not have the usual layers (or courses)seen in brick walls. These uncoursed walls have twoexterior vertical layers (called wythes) of large stones,filled in between with loose stone rubble and mudmortar. A typical uncoursed random (UCR) stonemasonry wall is illustrated in Figure 1. In many cases,these walls support heavy roofs (for example, timberroof with thick mud overlay).

    Laypersons may consider such stone masonrybuildings robust due to the large wall thickness androbust appearance of stone construction. But, thesebuildings are one of the most deficient buildingsystems from earthquake-resistance point of view. Themain deficiencies include excessive wall thickness,absence of any connection between the two wythes ofthe wall, and use of round stones (instead of shaped

    ones). Such dwellings have shown very poorperformance during past earthquakes in India andother countries (e.g., Greece, Iran, Turkey, formerYugoslavia). In the 1993 Killari (Maharashtra)earthquake alone, over 8,000 people died, most ofthem buried under the rubble of traditional stone

    masonry dwellings. Likewise, a majority of the over13,800 deaths during 2001 Bhuj (Gujarat) earthquake isattributed to the collapse of this type of construction.

    The main patterns of earthquake damage include:(a) bulging/separation of walls in the horizontaldirection into two distinct wythes (Figure 2a), (b)separation of walls at corners and T-junctions (Figure2b), (c) separation of poorly constructed roof fromwalls, and eventual collapse of roof, and (d)disintegration of walls and eventual collapse of the

    whole dwelling.

    Earthquake Resistant FeaturesLow strength stone masonry buildings are weak

    against earthquakes, and should be avoided in highseismic zones. The Indian Standard IS:13828-1993states that inclusion of special earthquake-resistantdesign and construction features may raise theearthquake resistance of these buildings and reducethe loss of life. However, in spite of the seismicfeatures these buildings may not become totally free

    from heavy damage and even collapse in case of amajor earthquake. The contribution of the each ofthese features is difficult to quantify, but qualitativelythese features have been observed to improve theperformance of stone masonry dwellings during pastearthquakes. These features include:

    Figure 1: Schematic of the wall section of atraditional stone house thick walls withoutstones that go across split into 2 vertical layers.

    Outward bulgingof vertical walllayer

    Half-dressedoblong stones

    Vertically splitlayer of wall

    Mud mortar

    (b) Separation of unconnected adjacent walls atjunctions

    Figure 2: Major concerns in a traditional stone

    house deficiencies in walls, roof and in theirconnections have been prime causes for failure.

    Vertically split layerof wall

    Vertical gap(a) Separation of a thick wall into two layers

    31

  • 7/30/2019 EQTip13

    8/16

    IITK-BMTPC Earthquake Tip 16

    How to make Stone Masonry Buildings Earthquake-Resistant? page 2(a)Ensure proper wall construction The wall thickness

    should not exceed 450mm. Round stone bouldersshould not be used in the construction! Instead, thestones should be shaped using chisels andhammers.Use of mud mortar should be avoided inhigher seismic zones. Instead, cement-sand mortar

    should be 1:6 (or richer) and lime-sand mortar 1:3 (orricher) should be used.

    (b)Ensure proper bond in masonry courses: The masonrywalls should be built in construction lifts notexceeding 600mm. Through-stones (each extendingover full thickness of wall) or a pair of overlapping

    bond-stones (each extending over at least thsthickness of wall) must be used at every 600mmalong the height and at a maximum spacing of 1.2malong the length (Figure 3).

    (c)Provide horizontal reinforcing elements: The stonemasonry dwellings must have horizontal bands(See IITK-BMTPC Earthquake Tip 14 forplinth, lintel,

    roof and gable bands). These bands can beconstructed out of wood or reinforced concrete, andchosen based on economy. It is important toprovide at least one band (either lintel band or roofband) in stone masonry construction (Figure 4).

    (d)Control on overall dimensions and heights: Theunsupported length of walls between cross-wallsshould be limited to 5m; for longer walls, crosssupports raised from the ground level calledbuttresses should be provided at spacing not morethan 4m. The height of each storey should notexceed 3.0m. In general, stone masonry buildings

    should not be taller than 2 storeys when built incement mortar, and 1 storey when built in lime ormud mortar. The wall should have a thickness of atleast one-sixth its height.

    Although, this type of stone masonry constructionpractice is deficient with regards to earthquake

    resistance, its extensive use is likely to continue due totradition and low cost. But, to protect human lives andproperty in future earthquakes, it is necessary tofollow proper stone masonry construction as describedabove (especially features (a) and (b) in seismic zonesIII and higher). Also, the use of seismic bands is highly

    recommended (as described in feature (c) above and inIITK-BMTPC Earthquake Tip 14).

    Related - Earthquake TipTip14: Why horizontal bands are required in masonry buildings?

    Reading MaterialBrzev,S., Greene,M. and Sinha,R. (2001), Rubble stone masonry

    walls with timber walls and timber roof, World HousingEncyclopedia (www.world-housing.net), India/Report 18,published by EERI and IAEE

    IAEE, (1986), Guidelines for Earthquake Resistant Non-EngineeredConstruction, The ACC Limited, Thane, 2001 (See www.niceee.org).

    IS 13828, (1993), Indian Standard Guidelines - Improving EarthquakeResistance of Low-Strength Masonry Buildings, Bureau of IndianStandards, New Delhi

    Publications of Building Materials and Technology Promotion Council,New Delhi (www.bmtpc.org):(a) Retrofitting of Stone Houses in Marathwada Area of Maharashtra(b) Guidelines For Improving Earthquake Resistance of Housing(c) Manual for Repair and Reconstruction of Houses Damaged in

    Earthquake in October 1991 in the Garhwal Region of UP

  • 7/30/2019 EQTip13

    9/16

    How do Earthquakes affect Reinforced Concrete Buildings?

    EarthquakeTip 17LearningEarthquake DesignandConstruction

    Reinforced Concrete BuildingsIn recent times, reinforced concrete buildings have

    become common in India, particularly in towns andcities. Reinforced concrete (or simply RC) consists oftwo primary materials, namely concrete with reinforcingsteel bars. Concrete is made of sand, crushed stone (calledaggregates) and cement, all mixed with pre-determinedamount of water. Concrete can be molded into anydesired shape, and steel bars can be bent into manyshapes. Thus, structures of complex shapes are

    possible with RC.A typical RC building is made of horizontal

    members (beams and slabs) and vertical members(columns and walls), and supported by foundations thatrest on ground. The system comprising of RC columnsand connecting beams is called a RC Frame. The RCframe participates in resisting the earthquake forces.Earthquake shaking generates inertia forces in thebuilding, which are proportional to the building mass.Since most of the building mass is present at floorlevels, earthquake-induced inertia forces primarilydevelop at the floor levels. These forces travel

    downwards - through slab and beams to columns andwalls, and then to the foundations from where they aredispersed to the ground. As inertia forces accumulatedownwards from the top of the building, the columnsand walls at lower storeys experience higherearthquake-induced forces (Figure 1) and are thereforedesigned to be stronger than those in storeys above.

    Roles of Floor Slabs and Masonry WallsFloor slabs are horizontal plate-like elements,

    which facilitate functional use of buildings. Usually,beams and slabs at one storey level are cast together.

    In residential multi-storey buildings, thickness of slabsis only about 110-150mm. When beams bend in thevertical direction during earthquakes, these thin slabsbend along with them (Figure 2a). And, when beamsmove with columns in the horizontal direction, theslab usually forces the beams to move together with it.

    In most buildings, the geometric distortion of the slabis negligible in the horizontal plane; this behaviour isknown as the rigid diaphragm action (Figure 2b).Structural engineers must consider this during design.

    After columns and floors in a RC building are castand the concrete hardens, vertical spaces betweencolumns and floors are usually filled-in with masonrywalls to demarcate a floor area into functional spaces(rooms). Normally, these masonry walls, also calledinfill walls, are not connected to surrounding RCcolumns and beams. When columns receive horizontalforces at floor levels, they try to move in the horizontal

    direction, but masonry walls tend to resist thismovement. Due to their heavy weight and thickness,these walls attract rather large horizontal forces(Figure 3). However, since masonry is a brittlematerial, these walls develop cracks once their abilityto carry horizontal load is exceeded. Thus, infill wallsact like sacrificial fuses in buildings; they developcracks under severe ground shaking but help share theload of the beams and columns until cracking.Earthquake performance of infill walls is enhanced bymortars of good strength, making proper masonrycourses, and proper packing of gaps between RC

    frame and masonry infill walls. However, an infill wallthat is unduly tall or long in comparison to itsthickness can fall out-of-plane (i.e., along its thindirection), which can be life threatening. Also, placinginfills irregularly in the building causes ill effects likeshort-column effect and torsion (these will be discussedin subsequent IITK-BMTPC Earthquake Tips).

    Figure 1: Total horizontal earthquake force in abuilding increases downwards along its height.

    Total Force

    FloorL

    evel

    5

    4

    3

    2

    1

    Figure 3: Infill walls move together with thecolumns under earthquake shaking.

    Compression

    Cracks

    Figure 2: Floor bends with the beam but movesall columns at that level together.

    Gap

    (a) Out-of-planeVertical Movement

    (b) In-plane Horizontal Movement

    33

  • 7/30/2019 EQTip13

    10/16

    IITK-BMTPC Earthquake Tip 17

    How do Earthquakes affect Reinforced Concrete Buildings? page 2

    Horizontal Earthquake Effects are DifferentGravity loading (due to self weight and contents) on

    buildings causes RC frames to bend resulting instretching and shortening at various locations. Tensionis generated at surfaces that stretch and compressionat those that shorten (Figure 4b). Under gravity loads,

    tension in the beams is at the bottom surface of thebeam in the central location and is at the top surface atthe ends. On the other hand, earthquake loading causestension on beam and column faces at locationsdifferent from those under gravity loading (Figure 4c);the relative levels of this tension (in technical terms,bending moment) generated in members are shown inFigure 4d. The level of bending moment due toearthquake loading depends on severity of shakingand can exceed that due to gravity loading. Thus,under strong earthquake shaking, the beam ends candevelop tension on either of the top and bottom faces.

    Since concrete cannot carry this tension, steel bars arerequired on both faces of beams to resist reversals ofbending moment. Similarly, steel bars are required onall faces of columns too.

    Strength HierarchyFor a building to remain safe during earthquake

    shaking, columns (which receive forces from beams)should be stronger than beams, and foundations

    (which receive forces from columns) should bestronger than columns. Further, connections betweenbeams & columns and columns & foundations shouldnot fail so that beams can safely transfer forces tocolumns and columns to foundations.

    When this strategy is adopted in design, damage is

    likely to occur first in beams (Figure 5a). When beamsare detailed properly to have large ductility, thebuilding as a whole can deform by large amountsdespite progressive damage caused due to consequentyielding of beams. In contrast, if columns are madeweaker, they suffer severe local damage, at the top andbottom of a particular storey (Figure 5b). This localizeddamage can lead to collapse of a building, althoughcolumns at storeys above remain almost undamaged.

    Relevant Indian StandardsThe Bureau of Indian Standards, New Delhi,

    published the following Indian standards pertaining todesign of RC frame buildings: (a) Indian Seismic Code(IS 1893 (Part 1), 2002) for calculating earthquake forces,(b) Indian Concrete Code (IS 456, 2000) for design ofRC members, and (c) Ductile Detailing Code for RCStructures (IS 13920, 1993) for detailing requirements inseismic regions.

    Related - Earthquake Tip

    Tip 5: What are the seismic effects on structures?

    Reading MaterialEnglekirk,R.E.,(2003), Seismic Design of Reinforced and Precast

    Concrete Buildings, John Wiley & Sons, Inc., USAPenelis,G.G., and Kappos,A.J., (1997), Earthquake Resistant Concrete

    Structures, E&FN SPON, UK

    This release is a property of IIT Kanpur and BMTPC NewDelhi. It may be reproduced without changing its contentsand with due acknowledgement. Suggestions/commentsmay be sent to: [email protected] Visit www.nicee.org orwww.bmtpc.org, to see previous IITK-BMTPC Earthquake Tips.

    Authored by:C.V.R.MurtyIndian Institute of Technology KanpurKanpur, India

    Sponsored by:

    Building Materials and Technology PromotionCouncil, New Delhi, India

    Figure 5: Two distinct designs of buildings thatresult in different earthquake performances columns should be stronger than beams.

    Smalldisplacementat collapse

    All damagein onestorey

    Weak Columns,Strong Beams

    Damagedistributedin allstoreys

    Largedisplacementat collapse

    Strong Columns,Weak Beams

    (a) (b)

    Figure 4: Earthquake shaking reverses tensionand compression in members reinforcement isrequired on both faces of members.

    Stretching of memberand locations of tension

    Amount otension

    (b)

    (d)

    (a)

    (c)

    Damage

    GravityLoad

    EarthquakeLoad

    Tension

    Tension

    34

  • 7/30/2019 EQTip13

    11/16

    How do Beams in RC Buildings resist Earthquakes?

    EarthquakeTip 18LearningEarthquake DesignandConstruction

    Reinforcement and Seismic DamageIn RC buildings, the vertical and horizontal

    members (i.e., the columns and beams) are builtintegrally with each other. Thus, under the action ofloads, they act together as a frame transferring forcesfrom one to another. This Tip is meant for beams thatare part of a building frame and carry earthquake-induced forces.

    Beams in RC buildings have two sets of steelreinforcement, namely: (a) long straight bars (called

    longitudinal bars) placed along its length, and (b) closedloops of small diameter steel bars (called stirrups)placed vertically at regular intervals along its fulllength (Figure 1).

    Beams sustain two basic types of failures, namely:(a)Flexural (or Bending) Failure: As the beam sags under

    increased loading, it can fail in two possible ways.If relatively more steel is present on the tensionface, concrete crushes in compression; this is a brittlefailure and is therefore undesirable. If relativelyless steel is present on the tension face, the steelyields first (it keeps elongating but does not snap, assteel has ability to stretch large amounts before itsnaps; see IITK-BMTPC Earthquake Tip 9) andredistribution occurs in the beam until eventually

    the concrete crushes in compression; this is a ductilefailure and hence is desirable. Thus, more steel ontension face is not necessarily desirable! The ductilefailure is characterized with many vertical cracksstarting from the stretched beam face, and goingtowards its mid-depth (Figure 2a).

    (b)Shear Failure: A beam may also fail due to shearing

    action. A shear crack is inclined at 45 to thehorizontal; it develops at mid-depth near thesupport and grows towards the top and bottomfaces (Figure 2b). Closed loop stirrups are providedto avoid such shearing action. Shear damage occurswhen the area of these stirrups is insufficient.

    Shear failure is brittle, and therefore, shear failuremust be avoided in the design of RC beams.

    Design Strategy

    Designing a beam involves the selection of itsmaterial properties (i.e, grades of steel bars and concrete)and shape and size; these are usually selected as a partof an overall design strategy of the whole building.And, the amount and distribution of steel to be providedin the beam must be determined by performing designcalculations as per is:456-2000 and IS13920-1993.

    Longitudinal bars are provided to resist flexuralcracking on the side of the beam that stretches. Sinceboth top and bottom faces stretch during strongearthquake shaking (IITK-BMTPC Earthquake Tip 17),longitudinal steel bars are required on both faces at theends and on the bottom face at mid-length (Figure 3).

    The Indian Ductile Detailing Code IS13920-1993prescribes that:(a) At least two bars go through the full length of the

    beam at the top as well as the bottom of the beam.(b) At the ends of beams, the amount of steel provided

    at the bottom is at least half that at top.

    Figure 1: Steel reinforcement in beams - stirrupsprevent longitudinal bars from bending outwards.

    Figure 2: Two types of damage in a beam:flexure damage is preferred. Longitudinal barsresist the tension forces due to bending whilevertical stirrups resist shear forces.

    Inclined crackFlexure Failure

    Shear Failure(b)

    (a)

    Bottom face stretches in tensionand vertical cracks develop

    LongitudinalBarLarger diameter steel bars thatgo through the full length of thebeam

    Vertical StirrupSmaller diameter steelbars that are made intoclosed loops and areplaced at regularintervals along the fulllength of the beam

    45

    Beam

    ColumnColumn

    Column

    Beam

    Beam

    35

  • 7/30/2019 EQTip13

    12/16

    IITK-BMTPC Earthquake Tip 18

    How do Beams in RC Buildings resist Earthquakes? page 2

    Stirrups in RC beams help in three ways, namely(i) they carry the vertical shear force and thereby resistdiagonal shear cracks (Figure 2b), (ii) they protect theconcrete from bulging outwards due to flexure, and(iii) they prevent the buckling of the compressedlongitudinal bars due to flexure. In moderate to severeseismic zones, the Indian Standard IS13920-1993prescribes the following requirements related tostirrups in reinforced concrete beams:(a)The diameter of stirrup must be at least 6mm; in

    beams more than 5m long, it must be at least 8mm.(b)Both ends of the vertical stirrups should be bent

    into a 135 hook (Figure 4) and extendedsufficiently beyond this hook to ensure that thestirrup does not open out in an earthquake.

    (b) The spacing of vertical stirrups in any portion ofthe beam should be determined from calculations

    (c) The maximum spacing of stirrups is less than halfthe depth of the beam (Figure 5).(d) For a length of twice the depth of the beam from

    the face of the column, an even more stringentspacing of stirrups is specified, namely half thespacing mentioned in (c) above (Figure 5).

    Steel reinforcement bars are available usually inlengths of 12-14m. Thus, it becomes necessary tooverlap bars when beams of longer lengths are to bemade. At the location of the lap, the bars transfer largeforces from one to another. Thus, the Indian StandardIS:13920-1993 prescribes that such laps of longitudinal

    bars are (a) made away from the face of the column,and (b) not made at locations where they are likely tostretch by large amounts and yield (e.g., bottom bars atmid-length of the beam). Moreover, at the locations oflaps, vertical stirrups should be provided at a closerspacing (Figure 6).

    Related - Earthquake TipTip 9: How to Make Buildings Ductile for Good Seismic

    Performance?Tip 17: How do Earthquakes Affect Reinforced Concrete Buildings?

    Reading MaterialIS 13920, (1993), Indian Standard Code of Practice for Ductile Detailing

    of Reinforced Concrete Structures Subjected to Seismic Forces, Bureauof Indian Standards, New Delhi

    Paulay,T., and Priestley,M.J.N., (1997), Seismic Design of Masonryand Reinforced Concrete Buildings, John Wiley & Sons, USA

    McGregor,J.M., (1997), Reinforced Concrete Mechanics and Design,Third Edition, Prentice Hall, USA

    Authored by:C.V.R.MurtyIndian Institute of Technology KanpurKanpur, India

    Sponsored by:Building Materials and Technology Promotion

    Council, New Delhi, India

    Figure 3: Location and amount of longitudinalsteel bars in beams these resist tension due toflexure.

    At least2 bars should gofull length of beam

    Figure 6: Details of lapping steel reinforcementin seismic beams as per IS13920-1993.

    Lapping prohibited inregions where

    longitudinal bars can

    yield in tension

    Lapping of longitudinal bars

    Spacing of stirrupsas per calculations(but not more than

    d/2)d

    Spacing of stirrupsas calculated

    (but not more thand/4and8 times beam bar

    diameter)

    2d 2d

    2d 2d

    Figure 5: Location and amount of vertical stirrups

    in beams IS:13920-1993 limit on maximumspacing ensures good earthquake behaviour.

    Spacing of stirrupsnot more than150mm

    Figure 4: Steel reinforcement in seismic beams

    - stirrups with 135hooks at ends required as perIS:13920-1993.

    The ends of stirrups

    are bent at 135.Such stirrupsdo notopen during strongearthquake shaking.

    10 timesdiameter ofstirru

    135

    135

    HorizontalSpacing

    Total amount of steelfrom calculation

    Bottom steel at supportsat leasthalf of that at top

    Beam

    Column Column

    Column Column

    Beam

    Spacing of stirrupsas calculated

    (but not more thand/4and8 times beam bar

    diameter)

    Column

    Beam

    Column

    Preferred:135hooks inadjacentstirrups onalternate sides

    36

  • 7/30/2019 EQTip13

    13/16

    How do Beam-Column Joints in RC Buildings resist Earthquakes?

    EarthquakeTip 20LearningEarthquake DesignandConstruction

    Why Beam-Column Joints are SpecialIn RC buildings, portions of columns that are

    common to beams at their intersections are called beam-column joints (Figure 1). Since their constituentmaterials have limited strengths, the joints have limitedforce carrying capacity. When forces larger than theseare applied during earthquakes, joints are severelydamaged. Repairing damaged joints is difficult, and sodamage must be avoided. Thus, beam-column jointsmust be designed to resist earthquake effects.

    Earthquake Behaviour of JointsUnder earthquake shaking, the beams adjoining a

    joint are subjected to moments in the same (clockwiseor counter-clockwise) direction (Figure 1). Under thesemoments, the top bars in the beam-column joint arepulled in one direction and the bottom ones in theopposite direction (Figure 2a). These forces arebalanced by bond stress developed between concreteand steel in the joint region. If the column is not wideenough or if the strength of concrete in the joint is low,there is insufficient grip of concrete on the steel bars.

    In such circumstances, the bar slips inside the jointregion, and beams loose their capacity to carry load.

    Further, under the action of the above pull-pushforces at top and bottom ends, joints undergogeometric distortion; one diagonal length of the jointelongates and the other compresses (Figure 2b). If thecolumn cross-sectional size is insufficient, the concretein the joint develops diagonal cracks.

    Reinforcing the Beam-Column JointDiagonal cracking & crushing of concrete in joint

    region should be prevented to ensure good earthquakeperformance of RC frame buildings. Using large column

    sizes is the most effective way of achieving this. Inaddition, closely spaced closed-loop steel ties are requiredaround column bars (Figure 3) to hold togetherconcrete in joint region and to resist shear forces.Intermediate column bars also are effective in confiningthe joint concrete and resisting horizontal shear forces.

    Providing closed-loop ties in the joint requiressome extra effort. Indian Standard IS:13920-1993recommends continuing the transverse loops aroundthe column bars through the joint region. In practice,this is achieved by preparing the cage of the

    reinforcement (both longitudinal bars and stirrups) of allbeams at a floor level to be prepared on top of thebeam formwork of that level and lowered into the cage(Figures 4a and 4b). However, this may not always bepossible particularly when the beams are long and theentire reinforcement cage becomes heavy.

    Anchoring Beam BarsThe gripping of beam bars in the joint region is

    improved first by using columns of reasonably largecross-sectional size. As explained in Earthquake Tip 19,the Indian Standard IS:13920-1993 requires buildingcolumns in seismic zones III, IV and V to be at least

    300mm wide in each direction of the cross-sectionwhen they support beams that are longer than 5m orwhen these columns are taller than 4m between floors(or beams). The American Concrete Instituterecommends a column width of at least 20 times thediameter of largest longitudinal bar used in adjoining beam.

    Figure 1: Beam-Column Joints are critical partsof a building they need to be designed.

    Beam-Column JointOverlap volume

    common to beamsand columns

    (a) (b)

    Figure 2: Pull-push forces on joints cause twoproblems these result in irreparable damage injoints under strong seismic shaking.

    Gripping ofbar insideoint region

    Compression

    Tension

    Loss of grip on beam barsin joint region:

    Large column width and goodconcrete help in holding thebeam bars

    Distortion of joint:causes diagonal

    cracking and crushingof concrete

    Figure 3: Closed loop steel ties in beam-column

    jointssuch ties with 135hooks resist the illeffects of distortion of joints.

    Closed tiesBeam

    Column

    10 timesdiameter of tie

    135

    39

    IntermediateColumn Bars

  • 7/30/2019 EQTip13

    14/16

    IITK-BMTPC Earthquake Tip 20

    How do Beam-Column Joints in RC Buildings resist Earthquakes? page 2

    In exterior joints where beams terminate atcolumns (Figure 5), longitudinal beam bars need to beanchored into the column to ensure proper gripping ofbar in joint. The length of anchorage for a bar of gradeFe415 (characteristic tensile strength of 415MPa) isabout 50 times its diameter. This length is measuredfrom the face of the column to the end of the baranchored in the column. In columns of small widthsand when beam bars are of large diameter (Figure 5a),a portion of beam top bar is embedded in the column

    that is cast up to the soffit of the beam, and a part of itoverhangs. It is difficult to hold such an overhanging

    beam top bar in position while casting the column upto the soffit of the beam. Moreover, the verticaldistance beyond the 90 bend in beam bars is not veryeffective in providing anchorage. On the other hand, ifcolumn width is large, beam bars may not extendbelow soffit of the beam (Figure 5b). Thus, it is

    preferable to have columns with sufficient width. Suchan approach is used in many codes [e.g., ACI318, 2005].

    In interior joints, the beam bars (both top andbottom) need to go through the joint without any cutin the joint region. Also, these bars must be placedwithin the column bars and with no bends (Figure 6).

    Related - Earthquake TipTip17: How do Earthquakes Affect Reinforced Concrete Buildings?Tip18: How do Beams in RC Buildings Resist Earthquakes?Tip19: How do Columns in RC Buildings Resist Earthquakes?

    Reading MaterialACI 318, (2005), Building Code Requirements for Structural Concrete

    and Commentary, American Concrete Institute, USAIS 13920, (1993), Indian Standard Code of Practice for Ductile Detailing

    of Reinforced Concrete Structures Subjected to Seismic Forces, Bureauof Indian Standards, New Delhi

    SP 123, (1991), Design of Beam-Column Joints for Seismic Resistance,Special Publication, American Concrete Institute, USA

    This release is a property of IIT Kanpur and BMTPC NewDelhi. It may be reproduced without changing its contentsand with due acknowledgement. Suggestions/comments

    may be sent to: [email protected] Visit www.nicee.org orwww.bmtpc.org, to see previous IITK-BMTPC Earthquake Tips.

    Authored by:C.V.R.MurtyIndian Institute of Technology KanpurKanpur, India

    Sponsored by:Building Materials and Technology PromotionCouncil, New Delhi, India

    Figure 6: Anchorage of beam bars in interiorjoints diagrams (a) and (b) show cross-sectional views in plan of joint region.

    (a) Poor Practice

    Beam bars bent in joint region overstressthe core concrete adjoining the bends

    Beam bars are within columnbars and also straight

    (b) Good Practice

    Figure 5: Anchorage of beam bars in exteriorjoints diagrams show elevation of joint region.

    (a) Poor (b) Good

    Wide ColumnNarrow Column

    ACI 318-2005Practice

    L-shapedbar ends

    Portion of top beambar below soffit of thebeam

    Portion of columnalready cast

    Approximately50timesbardiameter

    (c)

    Shear failure of RCbeam-column jointduring the 1985Mexico CityEarthquake,when beam barsare passed outsidethe column cross-section

    Photofrom:TheEERIAnnotatedSlideCD,

    98-2,

    EERI,Oakland,

    CA,

    USA

    Beam bars are within columnbars and also straight

    Beam

    Column

    Column

    Beam

    (a)Stage I :Beam top bars are notplaced, but horizontalties in the joint regionare stacked up.

    (c)Stage III :Ties in the joint region areraised to their final locations,tied with binding wire, andcolumn ties are continued

    (b)

    Figure 4: Providing horizontal ties in the joints

    three-stage procedure is required.

    Stage II :Top bars of the beam

    are inserted in thebeam stirrups, and

    beam reinforcementcage is lowered into

    the formwork

    Temporaryprop

    40

  • 7/30/2019 EQTip13

    15/16

    How to reduce Earthquake Effects on Buildings?

    EarthquakeTip 24LearningEarthquake DesignandConstruction

    Why Earthquake Effects are to be ReducedConventional seismic design attempts to make

    buildings that do not collapse under strong earthquakeshaking, but may sustain damage to non-structuralelements (like glass facades) and to some structuralmembers in the building. This may render the buildingnon-functional after the earthquake, which may beproblematic in some structures, like hospitals, whichneed to remain functional in the aftermath of theearthquake. Special techniques are required to design

    buildings such that they remain practicallyundamaged even in a severe earthquake. Buildingswith such improved seismic performance usually costmore than normal buildings do. However, this cost isjustified through improved earthquake performance.

    Two basic technologies are used to protectbuildings from damaging earthquake effects. These areBase Isolation Devices and Seismic Dampers. The ideabehind base isolation is to detach (isolate) the buildingfrom the ground in such a way that earthquakemotions are not transmitted up through the building,or at least greatly reduced. Seismic dampers are special

    devices introduced in the building to absorb theenergy provided by the ground motion to the building(much like the way shock absorbers in motor vehiclesabsorb the impacts due to undulations of the road).

    Base IsolationThe concept of base isolation is explained through

    an example building resting on frictionless rollers(Figure 1a). When the ground shakes, the rollers freelyroll, but the building above does not move. Thus, noforce is transferred to the building due to shaking ofthe ground; simply, the building does not experience theearthquake. Now, if the same building is rested on

    flexible pads that offer resistance against lateralmovements (Figure 1b), then some effect of the groundshaking will be transferred to the building above. Ifthe flexible pads are properly chosen, the forcesinduced by ground shaking can be a few times smallerthan that experienced by the building built directly onground, namely afixed base building (Figure 1c).

    The flexible pads are called base-isolators, whereasthe structures protected by means of these devices arecalled base-isolated buildings. The main feature of thebase isolation technology is that it introducesflexibility in the structure. As a result, a robust

    medium-rise masonry or reinforced concrete buildingbecomes extremely flexible. The isolators are oftendesigned to absorb energy and thus add damping tothe system. This helps in further reducing the seismicresponse of the building. Several commercial brands ofbase isolators are available in the market, and many of

    them look like large rubber pads, although there areother types that are based on sliding of one part of thebuilding relative to the other. A careful study isrequired to identify the most suitable type of devicefor a particular building. Also, base isolation is notsuitable for all buildings. Most suitable candidates forbase-isolation are low to medium-rise buildings restedon hard soil underneath; high-rise buildings orbuildings rested on soft soil are not suitable for baseisolation.

    47

    Figure 1: Building on flexible supports shakeslesser this technique is calledBase Isolation.

    Building on rollers without any friction building will not move with ground

    Building on flexible pads connected to buildingand foundation building will shake less

    Building resting directly on ground building will shakeviolently

    Base IsolatedBuilding

    If the gap between thebuilding and vertical wall ofthe foundation pit is small,the vertical wall of the pitmay hit the building, whenthe ground moves underthe building.

    Flexible pads

    Rollers

    Fixed-Base

    Building

    HypotheticalBuilding

    (a)

    (b)

    (c)

    Forces induced can be up to5-6 times smaller than those

    in a regular building restingdirectly on ground.

    Forces induced are large.

    Smallmovement

    of building

    Largemovementof building

    Largemovementin isolators

    Isolator during Earthquake

    OriginalIsolator

    Stainless

    steel lates

    FlexibleMaterial

    Lead plug

  • 7/30/2019 EQTip13

    16/16

    IITK-BMTPC Earthquake Tip 24

    How to reduce Earthquake Effects on Buildings? page 2

    Base Isolation in Real BuildingsSeismic isolation is a relatively recent and evolving

    technology. It has been in increased use since the1980s, and has been well evaluated and reviewedinternationally. Base isolation has now been used innumerous buildings in countries like Italy, Japan, New

    Zealand, and USA. Base isolation is also useful forretrofitting important buildings (like hospitals andhistoric buildings). By now, over 1000 buildings acrossthe world have been equipped with seismic baseisolation. In India, base isolation technique was firstdemonstrated after the 1993 Killari (Maharashtra)Earthquake [EERI, 1999]. Two single storey buildings(one school building and another shopping complexbuilding) in newly relocated Killari town were builtwith rubber base isolators resting on hard ground. Bothwere brick masonry buildings with concrete roof. After the2001 Bhuj (Gujarat) earthquake, the four-storey Bhuj

    Hospital building was built with base isolationtechnique (Figure 2).

    Seismic DampersAnother approach for controlling seismic damage

    in buildings and improving their seismic performance

    is by installing seismic dampers in place of structuralelements, such as diagonal braces. These dampers actlike the hydraulic shock absorbers in cars much ofthe sudden jerks are absorbed in the hydraulic fluidsand only little is transmitted above to the chassis of thecar. When seismic energy is transmitted through them,dampers absorb part of it, and thus damp the motion ofthe building. Dampers were used since 1960s toprotect tall buildings against wind effects. However, itwas only since 1990s, that they were used to protectbuildings against earthquake effects. Commonly usedtypes of seismic dampers include viscous dampers

    (energy is absorbed by silicone-based fluid passingbetween piston-cylinder arrangement), friction dampers(energy is absorbed by surfaces with friction betweenthem rubbing against each other), and yielding dampers(energy is absorbed by metallic components that yield)

    provided in a 18-storey RC frame structure in Gurgaon(See http://www.palldynamics.com/main.htm).

    Related - Earthquake TipTip 5: What are the Seismic Effects on Structures?Tip 8: What is the Seismic Design Philosophy for Buildings?

    Reading MaterialEERI, (1999), Lessons Learnt Over Time Learning from Earthquakes

    Series: Volume II Innovative Recovery in India, EarthquakeEngineering Research Institute, Oakland (CA), USA; alsoavailable at http://www.nicee.org/readings/EERI_Report.htm.

    Hanson,R.D., and Soong,T.T., (2001), Seismic Design withSupplemental Energy Dissipation Devices, Earthquake EngineeringResearch Institute, Oakland (CA), USA

    Skinner,R.I., Robinson,W.H., and McVerry,G.H., (1999), AnIntroduction to Seismic Isolation,John Wiley & Sons, USA

    This release is a property of IIT Kanpur and BMTPC NewDelhi. It may be reproduced without changing its contentsand with due acknowledgement. Suggestions/commentsmay be sent to: [email protected] Visit www.nicee.org or

    Authored by:C.V.R.MurtyIndian Institute of Technology KanpurKanpur, India

    Sponsored by:

    Building Materials and Technology PromotionCouncil, New Delhi, India

    Figure 2: View of Basement in Bhuj Hospitalbuilding built with base isolators after theoriginal District Hospital building at Bhujcollapsed during the 2001 Bhuj earthquake.

    Basement columnssupporting base isolators

    Base Isolator

    Figure 3: Seismic Energy Dissipation Devices each device is suitable for a certain building.

    (c) Yielding Dampers

    Yield locationof metal

    ViscousFluid

    Piston

    (a) Viscous Damper

    (b) Friction Damper

    SteelPlate

    Bolt

    Photo Courtesy:Marjorie Greene, EERI, USA