Concept Design Review (CoDR)
Shore StationDC Breaker Cable modelTransient AnalysisComponents
![Page 2: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/2.jpg)
NEPTUNE
Explorer Plate
Pacific Plate
Gorda Plate
Juan de Fuca Ridge
North American Plate
Nedonna Beach
Junction Box
Cable
study area
Plate
Juan de Fuca
![Page 3: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/3.jpg)
Shore Station
![Page 4: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/4.jpg)
Configuration of Shore Station
![Page 5: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/5.jpg)
SHORE STATION…Power supply Selection
Off-the-shelf Buck regulator. General ratings:
Output Voltage = 10 kV DC Output Range = 9 – 15 kV Voltage tolerance within 2%. Output Power = 200 kW Current Limiting Capability = twice the rated
current = 20 A. Local and remote control functions Self diagnostics capabilities
![Page 6: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/6.jpg)
SHORE STATION…Power supply Selection
Potential vendor for shore stations
Manufacturer: Diversified TechModel: Custom made.Specifications: Input: 3 phase 13.8 kW service. Output: 10kV / 200kW using the
HV buck regulator technology. Over current protection: Above
40A. Solid state system will act as current limiter.
Dimensions: 40” by 36” by 42” estimated.
![Page 7: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/7.jpg)
SHORE STATION…Surge Protection
Spark gap arresters Metal oxide varistor (MOV)
ceramic, polymer or silicon rubber insulator Surge arresters are selected based on
several ratings Energy absorption capability (or energy
withstand capability) Maximum continuous operating voltage
(MCOV) Temperature rise.
![Page 8: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/8.jpg)
SHORE STATION…Vacuum Switches (Breaker)
Types: Air Air-blast Magnetic quencher Oil Sulfur hexafluoride gas (SF6) Vacuum Solid-state
![Page 9: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/9.jpg)
SHORE STATION…Vacuum Switches
Vacuum breaker is used for systems under 36 kV. Pollution-free Fast Reliable Compact Light weight Requires small energy to operate.
![Page 10: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/10.jpg)
SHORE STATION…Vacuum Switches
Potential manufacturer: Kilovac or Jennings
Specifications: Contact Arrangement: Normally
Open. Rated Operating Voltage:28kV Max. Current: 40A. Max. Contact Resistance: 0.02 ohm. Release time < 20 ms mechanical lifetime > 2 million
cycles.
![Page 11: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/11.jpg)
DC Circuit Breaker
![Page 12: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/12.jpg)
DC CIRCUIT BREAKER
R1 R2S1
S2 S3
S4
C
![Page 13: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/13.jpg)
S2 S3
R1 R2
S1 S4
C
DC CIRCUIT BREAKER…Stage 1- Normal closure
![Page 14: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/14.jpg)
S2
R1 R2S1
S4
C
S3
DC CIRCUIT BREAKER…Stage 2 - Interruption
Current is routed through C Size of C is selected to prevent restrikes
![Page 15: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/15.jpg)
R1 R2S1
S2 S3
S4
C
DC CIRCUIT BREAKER…Stage 3 – Discharging of Capacitor
Cap is discharged through R2 to set the circuit for next switching
![Page 16: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/16.jpg)
R1 R2S1
S2 S3
C
S4
DC CIRCUIT BREAKER…Stage 4 – Soft Starting
Soft starting resistance R1 reduces the inrush current during energization
![Page 17: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/17.jpg)
S2 S3
R1 R2
S1 S4
C
DC CIRCUIT BREAKER…Stage 5 – Normal closure
![Page 18: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/18.jpg)
Components Selection Vacuum Switches
Voltage Rating Withstanding Voltage > 25kV
Continuous Current Rating 20A or higher
Release time Faster release time means smaller capacitor is
required. Release time < 20 ms Lifespan, measured in cycles of operation
Millions of operations
![Page 19: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/19.jpg)
Components Selection Capacitor
Voltage Rating 15-20kV rating
Capacitance 1-10μF, depending on node location
Size up to 600 cubic inches
Lifespan Measured in hours of operation
![Page 20: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/20.jpg)
Components Selection Resistors
2 Resistors: soft close and capacitor discharge Resistance value: Both are currently specified
at 1kΩ Peak Voltage Rating: 10-20kV Peak Energy Rating
Power dissipation more important in this application than average power, as resistors will be used for brief (less than one second) intervals
![Page 21: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/21.jpg)
Components Selection Diodes
![Page 22: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/22.jpg)
Components Selection Diodes
VRRM (maximum repeat reverse voltage): 20-25kV
Continuous forward current Based on normal operation > 50 A Maximum Transient Current > 300A di/dt ratings > 100A/s
Reverse leakage current ~ A Type: Stacked Hockey Puck
![Page 23: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/23.jpg)
Cable Model
![Page 24: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/24.jpg)
Cable Model…inductance
SteeltubeØ: 2.3 mm
Optical
fibers
Compositeconductor
Steel wiresstrand
Thixotropic
J elly
Insulating sheath Ø 17mm
![Page 25: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/25.jpg)
Cable Model…inductance
flux linkages theory a) the core b) the sheath. c) the insulation.
![Page 26: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/26.jpg)
Cable Model…inductance
Cable Inductance
cable
cable
iL
Where:
cable = Total flux associated with the cable.
cablei = Total cable current.
![Page 27: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/27.jpg)
Cable Model…Resistance
The resistance per unit length of a tubular conductor is given by:
22 abR
condcond
The total cable resistance is thus given by:
custcable RRR ||
![Page 28: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/28.jpg)
Cable Model…Capacitance
The cable capacitance per unit length can be calculated by the formula:
mF
cd
C /ln
2
Where, is the permittivity of the insulator.d is the outer radius of insulator c is the inner radius of insulator.
![Page 29: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/29.jpg)
Cable Model…Seawater
The current return is through the seawater.
In near DC conditions the sea-water resistance and inductance are calculated as:
R = 0.098 m/km.
L = 2.221 mH/km. These values are frequency dependent.
![Page 30: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/30.jpg)
Cable Model…Composite model
For transient simulation, the steel core and copper sheath can be modeled as a composite conductor
comp = 5.1753*10-8 m.
comp = 9.0788
![Page 31: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/31.jpg)
Results …
![Page 32: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/32.jpg)
Transient Simulation
Normal SwitchingFault
![Page 33: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/33.jpg)
TRANSIENT ANALYSIS…ATP
![Page 34: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/34.jpg)
TRANSIENT ANALYSIS…What is ATP?
ATP is a universal program system for digital simulation of transient analysis of transmission systems.
ATP has extensive modeling capabilities including power electronics, control, protection, etc.
![Page 35: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/35.jpg)
Simulation Circuit… Normal Switching
100km
100km
100km
100km
100km
N2 N3 N4N1
LOAD LOAD LOAD LOAD
Node #3
R
R
C
S1
S2S3
S4
Load
VaIa
D1 D2
![Page 36: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/36.jpg)
Simulation Circuit… Switching Timing
0.1 0.4 0.7 1.0
N1
N2
N3
N4
1.2 1.5 1.8 2.1
![Page 37: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/37.jpg)
Current at the input of Node 3
1
2
34
5
![Page 38: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/38.jpg)
Voltage at the input of Node 3
1
23 4
5
![Page 39: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/39.jpg)
Voltage across the left diode in Node 3
3
4
5
![Page 40: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/40.jpg)
Simulation Circuit… Fault Condition
Sf LOAD LOAD LOAD
100 km
100 km
50 km
N2 N3 N1 50 km
V1
![Page 41: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/41.jpg)
Voltage across load in Node 2
1
2
3
![Page 42: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/42.jpg)
Current entering Node 2
1
2
3
![Page 43: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/43.jpg)
Simulation Circuit… Restrike
![Page 44: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/44.jpg)
Simulation Circuit… Restrike
t = (topen-t)
Switch closed
t = topen
Switch open: initial arcing
t =( topen +t)
Capacitor charging
![Page 45: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/45.jpg)
Simulation of Restrikes
topen
VmaxRESTRIKE
Initial Arcing
Time
Voltage
![Page 46: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/46.jpg)
Simulation ResultsMaximum voltage across
switch Release Time Minimum value of
capacitor to prevent restrikes (F)
15 kV 5 ms 2
15 kV 10ms 5
15 kV 18 ms 10
25 kV 15 ms 1
25 kV 18 ms 1
25 kV 20 ms 1
![Page 47: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/47.jpg)
Fault Simulation with restrike
1
2
3
![Page 48: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/48.jpg)
Fault Simulation without restrike
1
2
![Page 49: Concept Design Review (CoDR) Shore Station DC Breaker Cable model Transient Analysis Components.](https://reader038.fdocument.pub/reader038/viewer/2022110205/56649ca85503460f9496acb8/html5/thumbnails/49.jpg)
Fault Simulation without restrike
1
2