    DOC NO.: D-2-01-03-01-03

    PRE-COMMISSIONING FORMATS FOR CIRCUIT BREAKER

    I. GENERAL DETAILS

    DETAILS

    Region: Eastern Sub-Station: 400/220kV

    Feeder Name:425 52 CB

    LOA No. :

    Make:Areva T&D india Ltd

    Year of Manufacture:2010

    Sr. No.: 160418 Type:GL316

    Rating:3150A Rated Breaking Capacity(kA): 50

    Operating Voltage: 420KV Control Voltage (DC) :220V

    Date of Receipt at site: Date of Erection:

    Date of energisation:

    II. PRE-COMMISSIONING CHECKS:

    SL

    .NO DESCRIPTION

    STATUS

    REMARKSYES NO

    1 Equipment is free from dirt/dust foreign materials etc.YES

    2 Equipment is free from all visible defects on physical inspection YES

    3Support structures, marshalling box has been provided with doubleearth

    YES

    4 All nuts and bolts are tightened correctly as per specified torque YES

    5

    Equipment erection is complete in all respect & erection completioncertificate along with list of outstanding activities reviewed

    (attach remaining activities, if any)

    YES

    6 Permanent pole leveling and identification is done YES

    7 Leveling and alignment of structure and base frame is checkedYES

    8 Control box / marshalling kiosk is free from any physical defectsYES

    9 Tightness of nuts bolts of terminal connectors are checkedYES

    10

    Auxiliary contacts and relays have been cleaned and free

    from rust / damage

    YES

    11

    All spare wires to be kept with ferrules but not terminated

    at the terminal blocks

    YES

    12

    Check all the valves in the sf6 pipe line are tightened,

    DILO coupling are tightened.

    YES

    13Slow and power closing operation and opening done (whereverapplicable)

    YES

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker

    Page 1 of15

  • 7/27/2019 28 Circuit Breaker

    2/15

    DOC NO.: D-2-01-03-01-03

    III. OPERATING SYSTEM

    Closing Opening

    Hydraulic Hydraulic

    Pneumatic Pneumatic

    Spring yes Spring YesOthers Others

    i. Hydraulic system

    a) Accumulator

    b) Pump details

    c) Details of relays/contactors used

    Schematic drawing no______________________

    CIRCUIT REFERENCE MAKE SERIAL NO. TYPE NO+NC

    Oil Pressure Monitor NA NA NA NA

    Closing Lockout NA NA NA NA

    Auto Reclosing Lockout NA NA NA NA

    General Lockout NA NA NA NA

    Anti Pumping ContactorNA NA NA NA

    Pole Discrepancy Timer NA NA NA NA

    Auxiliary NA NA NA NA

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker

    Page 2 of15

    R Y B

    Make NA NA NA

    Serial number NA NA NA

    Type NA NA NA

    Year of manufacture NA NA NA

    Make NA Volt NA

    Serial number

    NA

    Amperes

    NA

    Type NA Hp/ kW NA

    Year of manufacturer

    NA O/L setting(Thermal Over

    load)

    NA

  • 7/27/2019 28 Circuit Breaker

    3/15

    DOC NO.: D-2-01-03-01-03

    Power Contactor NA NA NA NA

    Others NA NA NA NA

    d) Operation checks

    Date of Hydraulic Oil filling_____________________

    Type of Hydraulic Oil _____________________

    1. Venting of Hydraulic system

    SL .NO ITEM DESCRIPTIONSTATUS

    REMARKSYES NO

    Pump NA NA NA

    Pilot Valve NA NA NA

    Accumulator NA NA NA

    Hydraulic Mechanism NA NA NA

    2. Pressurising hydraulic system

    SL.NO DESCRIPTIONFACTORY

    TEST VALUESITE TEST

    VALUE

    REMARK RECORDDEFICIENCIES,IF

    ANY

    1 Pre-filling pressure of N2 in accumulator ( bar /deg. C)

    NA NA

    2 Pump running time for charging hydraulicsystem from initial pressure to working pressure

    NA NA

    3 Checking safety valve (open/close) NA NA

    4 Hydraulic pressure drop for 1 hr NA NA

    Breaker on position NA NA

    Breaker off position NA NA

    5 Oil pressure monitor NA NA

    Pump on / off bar NA NA

    Pump running time NA NA

    6 Auto reclosing lockout (oil) Pressure contact

    _____________ make/break

    NA NA

    7 Closing lockout (oil) pressure Contact__________make/break

    NA NA

    8 General lockout (oil) Pressure contact__________ make/break

    NA NA

    9 Checking anti pumping contactor Pressurecontact __________make/break

    NA NA

    10 Checking loss of nitrogen Pressure contact__________make/break

    NA NA

    Factory test report ref no: ________________________________

    3. Oil pressure drop during operations and pump running time in seconds

    SL.NO DESCRIPTIONFACTORY TEST

    VALUESITE TEST VALUE

    (i) Pressure before operation(Bar)NA NA

    Pressure after closing operation(Bar)NA NA

    Pump running time(Sec)NA NA

    (ii) Pressure before operation(Bar)NA NA

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker

    Page 3 of15

  • 7/27/2019 28 Circuit Breaker

    4/15

    DOC NO.: D-2-01-03-01-03

    Pressure after opening operation(Bar)NA NA

    Pump running time(Sec)NA NA

    (iii) Pressure before operation(Bar)NA NA

    Pressure after close/open operation (Bar)NA NA

    Pump running time in secNA NA

    (iv) Pressure before operation(Bar) NA NA

    Pressure after open-close-open operation(Bar)NA NA

    Pump running time(Sec)NA NA

    Factory test report ref no: ________________________________ii. Pneumatic System

    a) Operating system detailsR - Y - B Remarks

    Air receiver no NA NA NA

    Control block no NA NA NA

    Pneumatic drive no NA NA NAMagnetic ventil no NA NA NA

    b) Motor details

    c) ICU Details

    d) Details of Relays / Contactors used

    Schematic drawing no______________________

    CIRCUIT REFERENCE MAKE SERIAL NO. TYPE NO+NC

    Air Pressure Monitor NA NA NA NA

    Closing Lockout NA NA NA NA

    Auto Reclosing Lockout NA NA NA NA

    General Lockout NA NA NA NA

    Pole Discrepancy Timer NA NA NA NA

    Auxiliary NA NA NA NA

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker

    Page 4 of15

    Make NA Volt NA

    Serial number NA Amperes NA

    Type NA Hp/ kW NA

    Year of manufacturer NA O/L setting (Thermal Over load) NA

    Make NA

    Serial number NA

    Type NA

    Discharge NA

    Capacity NA

    Year of manufacturer NA

  • 7/27/2019 28 Circuit Breaker

    5/15

    DOC NO.: D-2-01-03-01-03

    Power Contactor in ICU NA NA NA NA

    Others NA NA NA NA

    e) Pressure Switch setting

    CIRCUIT REFERENCE

    FACTORY SETTING

    VALUE

    SITE SETTING VALUE

    MAKE

    REMARKS

    BLOCK DEBLOCK BLOCK DEBLOCK

    Operation lockout -1 NA NA NA NA NA

    Operation lockout -2 NA NA NA NA NA

    Closing lockout NA NA NA NA NA

    Auto reclosing ckt NA NA NA NA NA

    Low/high pressure NA NA NA NA NA

    Alarm circuit NA NA NA NA NA

    ICU auto setting NA NA NA NA NA

    ICU safety valve NA NA NA NA NA

    OperationsNA NA NA NA NA

    Factory test report ref no: ________________________________

    f) Pressure drop during operation : ( in kg/ sq.cm -bar )

    SL NO DESCRIPTIONFACTORY SETTING

    VALUESITE SETTING

    VALUE

    A Tripping through TC-I NA NA

    B Tripping through TC- II NA NA

    C

    Closing circuit

    NA NA

    D Close-open operation NA NA

    E Open - close - open

    NA NA

    Factory test report ref no: ________________________________

    g) Number of operation from local

    Tank pressure ___________ kg/sq.cm or bar

    BREAKER INITIALLY CLOSE :

    FACTORY TEST : O-C-

    NA

    PLEASE KEEP INLET PNEUMATIC VALVE

    CLOSED IN THESE OPERATION

    SITE TEST : O-C-

    NA

    BREAKER INITIALLY OPEN :

    FACTORY TEST : C-O-

    NA

    PLEASE KEEP INLET PNEUMATIC VALVE

    CLOSED IN THESE OPERATION

    SITE TEST : C-O-

    NA

    h) Air pressure drop in 24 hrs

    DROP IN PRESSURE IN

    KG/SQ.CM OR BAR

    BREAKERONNA

    BREAKEROFFNA

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker

    Page 5 of15

  • 7/27/2019 28 Circuit Breaker

    6/15

    DOC NO.: D-2-01-03-01-03

    iii. SPRING OPERATING SYSTEMa) Motor details

    MakeNA

    VoltNA

    Sl noNA

    AmperesNA

    TypeNA

    Hp/kwNA

    Year of ManufactureNA

    Setting (thermal overload)NA

    Dc current taken by motor for

    charging the spring ( amp)

    NA

    b) Details of relays/contactors used : schematic drawing no

    c) Spring operating time

    DETAILS

    R-PHASE Y-PHASE B-PHASE

    FACTORY SITE FACTORY SITE FACTORY SITE

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker

    Page 6 of15

    CIRCUIT REFERENCE MAKE SERIAL NO. TYPE NO+NC

    Closing lockoutNA NA NA NA

    Auto reclosing lockoutNA NA NA NA

    General lockoutNA NA NA NA

    Pole descrepancy timerNA NA NA NA

    AuxillaryNA NA NA NA

    Power contactorNA NA NA NA

    OthersNA NA NA NA

  • 7/27/2019 28 Circuit Breaker

    7/15

    DOC NO.: D-2-01-03-01-03

    CHARGING TIME 3.5s 3.6s 4.25s 4.0s 3.6s 3.9s

    Factory test report ref no

    IV. SF6 DENSITY MONITOR DETAILS

    i.

    R-PHASE Y-PHASE B-PHASE

    Make WIKAI WIKAI WIKAI

    Model - - -

    Sl.no 280HNYI 280HNYH 280HNY

    Year of manufacture

    Quantity of SF6 gas filled actual 7.8bar 7.8bar 7.8bar

    As per Specification

    ii . SF6 density monitor settings

    PHASE

    DETAILS

    BLOCKING DEBLOCKING

    FACTORY SITE FACTORY SITE

    R PHASE REFILL ALARM OPERATION BLOCK 6.4 6.4 6.7 6.7

    Y PHASE REFILL ALARM OPERATION BLOCK 6.4 6.4 6.7 6.7

    B PHASE REFILL ALARM OPERATION BLOCK 6.4 6.4 6.7 6.7

    Factory test report ref no :iii. Measurement of dew point of sf6 gas

    SL. NOMEASURED

    VALUE PERMISSIBLE LIMITS TO BE DECIDED AS PER GRAPH

    Rph -38C

    Yph -37C

    Bph -38C

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker

    Page 7 of15

  • 7/27/2019 28 Circuit Breaker

    8/15

    DOC NO.: D-2-01-03-01-03

    NOTE: Dew point measurement of SF6 gas needs to be done pole wise in close loop method without any wastageof SF6 gas

    iv. Leakage check

    SL.NO INTERVALS UNIT

    A

    Initial filling of sf6 gas at ____deg c

    (As per temp. Correction chart ) BAR 7.8

    B Drop in sf6 gas pressure in 24 hrs : BAR 7.8

    C

    Final sf6 pressure at __24______deg. C

    After all testing BAR 7.8

    D

    Additional leakage test by covering

    individual joint with polythene

    YES NO

    V. COIL RESISTANCE MEASUREMENT

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker

    Page 8 of15

  • 7/27/2019 28 Circuit Breaker

    9/15

    DOC NO.: D-2-01-03-01-03

    SL NO

    PHASE

    COILUNIT

    MEASUREDVALUE

    SERIESRESISTOR TOTAL

    A R

    TRIP COIL - I 145 NA 145

    TRIP COIL - II 144 NA 144

    CLOSE COIL 145 NA 145

    BY

    TRIP COIL - I 144 NA 144

    TRIP COIL - II 145 NA 145

    CLOSE COIL 144 NA 144

    CB

    TRIP COIL - I 146 NA 146

    TRIP COIL - II 145 NA 145

    CLOSE COIL 145 NA 145

    VI. CIRCUITRY / OPERATIONAL CHECKS

    SL NO CIRCUIT REFERENCECIRCUITARY CHECK OPERATIONAL CHECK

    LOCAL REMOTE LOCAL REMOTE

    A TRIPPING THROUGH TC-I OK OK OK OK

    B TRIPPING THROUGH TC-II OK OK OK OK

    C CLOSING CIRCUIT OK OK OK OK

    D ANTI-HUNTING FEATUREOK

    OK

    OK

    OK

    OK

    OK

    OK

    OK(CLOSE OPEN OPERATION )

    E POLE DISCREPANCY FEATURE OK OK OK OK

    F BREAKER POSITION INDICATION OK OK OK OK

    G HEATER IN SWITCH CUBICLE OK OK OK OK

    H HEATER IN CONTROL CUBICLE OK OK OK OK

    I ILLUM. IN SWITCH CUBICLE OK OK OK OK

    J ILLUM. IN CONTROL CUBICLE OK OK OK OK

    Note: In case wiring for remote operation is not ready, please indicate terminal number along with wire ferrulenumber in switch cubicle where remote cables shall be terminated. Remote operation can be checked from these

    terminals

    VII. OPERATING TIME ( IN MILLI-SECONDS )

    PHASE

    BREAK

    CLOSE(Max 150

    ms)

    T R I P (Max 25ms 400kV,35 ms

    220kV, 40 ms 132kV)

    CLOSE TRIP (Min. 35 ms)

    TRIP - I TRIP - II TRIP I TRIP - II

    R - ph main contactBREAK 1

    106.3 22.6 22.5 50.3 50.5

    R - PH PIR ( 12 4 ms)

    Auxiliary contact 118.0 16.5 16.4 156.9 157.4

    R - ph main contactBREAK 2

    106.3 22.6 22.5 50.3 50.5

    R - PH PIR ( 12 4 ms)

    Auxiliary contact 118.0 16.5 16.4 156.9 157.4

    Y - ph main contactBREAK 1

    106.1 21.8 21.8 48.5 49.5

    Y - PH PIR ( 12 4 ms)

    Auxiliary contact 116.5 16.2 16.3 155.8 155.8

    Y - ph main contactBREAK 2

    106.1 21.7 21.8 48.5 49.5

    Y - PH PIR ( 12 4 ms) Auxiliary contact 116.5 16.2 16.3 155.8 157.2

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker

    Page 9 of15

  • 7/27/2019 28 Circuit Breaker

    10/15

    DOC NO.: D-2-01-03-01-03

    B - ph main contactBREAK 1

    104.9 21.5 21.5 49.0 48..9

    B - PH PIR ( 12 4 ms)

    Auxiliary contact 114.5 16.4 16.3 156.6 156.9

    B - ph main contact BREAK 2 104.9 21.5 21.5 49.0 48..9

    B - PH PIR ( 12 4 ms)

    Auxiliary contact 114.5 16.4 16.3 156.6 156.8

    NOTE: for 765 kV, take measurements for four breaks

    VIII. IR VALUE OF CONTROL CIRCUIT(USING 500 VOLT MEGGER)

    COIL DETAILSUNIT MEASUREMENT VALUE

    R PHASE TRIP COIL - I M >1000

    R PHASE TRIP COIL - IIM >1000

    R PHASE CLOSE COILM >1000

    Y PHASE TRIP COIL - IM

    >1000Y PHASE TRIP COIL - II

    M >1000

    Y PHASE CLOSE COILM >1000

    B PHASE TRIP COIL - IM >1000

    B PHASE TRIP COIL - IIM >1000

    B PHASE CLOSE COILM >1000

    CAUTION: Isolate necessary dc for trip coil i and trip coil ii ,closing coil before meggaring .

    MINIMUM VALUE 2 MOHM

    IX. IR VALUE WITH BREAKER OPEN(USING 5000 VOLT MEGGER)

    ACROSS OPEN CONTACT UNIT MEASUREMENT VALUE

    R - PHASE BREAK 1G 436

    R - PHASE BREAK-2G 486

    Y - PHASE BREAK 1G 500

    Y - PHASE BREAK-2G 550

    B - PHASE BREAK 1G 475

    B - PHASE BREAK-2G 450

    MINIMUM VALUE 2 MOHMX. IR VALUE WITH RESPECT TO EARTH WITH BREAKER CLOSED, EARTH SWITCHAND ISOLATOR OPEN

    BETWEEN UNIT MEASUREMENT VALUE

    R PHASE AND EARTHG 436

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker

    Page 10 of15

  • 7/27/2019 28 Circuit Breaker

    11/15

    DOC NO.: D-2-01-03-01-03

    Y PHASE AND EARTHG 500

    B PHASE AND EARTHG 450

    XI. MINIMUM PICKUP VOLTAGE OF COILS

    COIL DETAILSUNIT MEASUREMENT VALUE

    R PHASE TRIP COIL - I V 109

    R PHASE TRIP COIL - IIV 113

    R PHASE CLOSE COILV 101

    Y PHASE TRIP COIL - IV 105

    Y PHASE TRIP COIL - IIV 103

    Y PHASE CLOSE COILV 106

    B PHASE TRIP COIL - IV 109

    B PHASE TRIP COIL - IIV 108

    B PHASE CLOSE COILV 103

    XII. GRADING CAPACITOR - NAi. DETAILS

    DETAILSINTERRUPTER 1 INTERRUPTER 2

    R Y B R Y B

    MAKE NA NA NA NA NA NA

    SERIAL NO. NA NA NA NA NA NA

    CAPACITANCE VALUE NA NA NA NA NA NA

    FACTORY VALUE NA NA NA NA NA NA

    YEAR OF MANUFAC. NA NA NA NA NA NA

    ii. CAPACITANCE AND TAN DELTA MEASUREMENT (TO BE DONE IN UST MODE)

    CAPACITANCEINTERRUPTER 1 INTERRUPTER 2

    R Y B R Y B

    SITE NA NA NA NA NA NA

    -FACTORY NA NA NA NA NA NA

    % DEVIATION NA NA NA NA NA NA

    TAN DELTA NA NA NA NA NA NA

    SITE NA NA NA NA NA NA

    -FACTORY NA NA NA NA NA NA

    % DEVIATION NA NA NA NA NA NA

    Permissible Limits

    a) Tan delta of grading capacitors 0.007 (max.)

    b) Rate of rise in Tan Delta 0.001 per year (max)

    c) Capacitance of grading capacitors within 5% of the rated value

    Note:

    a) Since temperature correction factor for Tan-Delta depends on make, type and also aging conditions, the correction

    factors for different types / makes are different. Hence, no standard temperature correction factors can be applied.

    b) In case of violation of Tan-Delta the test results with temperature are to be referred to CC/OS

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker

    Page 11 of15

  • 7/27/2019 28 Circuit Breaker

    12/15

    DOC NO.: D-2-01-03-01-03

    XIII. CONTACT RESISTANCE MEASUREMENTEqipment detail:- CRM 100 &Sr No:-2300.06X60Calib date 29/12/2011All Values In Micro-Ohm

    SL.NO

    PHASE

    ACROSS EACH POLE ACROSS INTERRUPTR 1 ACROSS INTERRUPTR 2

    FACTORY SITE FACTORY SITE FACTORY SITE

    A R-PHASE 75.1 82 NA 38 NA 39

    B Y-PHASE 73.5 81 NA 39 NA 40

    C B-PHASE 73.8 80 NA 38 NA 40

    a)Contact Resistance of CB (in Micro-Ohm)* 75 (Micro-Ohm) per breakb)Contact Resistance of CB terminal connector 10 Micro-Ohm per connectorFactory test report ref no :______________________

    XIV. BREAKER OPERATION COUNTER READING

    XV. CHECK FOR ANNUNCIATION IN CONTROL ROOM AS PER THE FOLLOWINGFORMATS AND RECORD THE READING

    SLNO

    DESCRIPTIONOF TEST

    SOURCE OFINITIATION

    WINDOW

    DESCRIPTION

    RESULT REMARKOK NOTOK

    A

    Switch off the dc switch in Control

    cubicle

    Control cubicledc

    Switch on/off

    Source I/II dc

    fail / ac failB Switch off the ac Switch in control Control cubicle Source I/II dc

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker

    Page 12 of15

    400kV 220kV 132kV

    150 * 100 100

    COUNTER TYPE PUT MARK

    ELECTRICAL

    MECHANICAL

    SL.NO PHASE READING DATE

    A R-PHASE 183 04/12/12

    B Y-PHASE 226 04/12/12

    C B-PHASE 213 04/12/12

  • 7/27/2019 28 Circuit Breaker

    13/15

    DOC NO.: D-2-01-03-01-03

    Cubicle

    ac

    Switch on/off fail / ac fail

    C

    Short the alarm contacts of sf6 Gas

    density monitor (R-phase) Density monitor

    Sf6 gas density

    low

    D

    Short the alarm contacts of sf6 Gas

    density monitor (Y-phase) Density monitor

    Sf6 gas density

    low

    EShort the alarm contacts of sf6 Gasdensity monitor (B-phase) Density monitor

    Sf6 gas densitylow

    F

    Remove the cable connected to

    density monitor (R-phase)

    Density monitor

    Operation/closi

    ng lockout

    G

    Remove the cable connected todensity monitor (Y-phase)

    Density monitor

    Operation/closi

    ng lockout

    H

    Remove the cable connected to

    density monitor (B-phase)Density monitor

    Operation/closing lock out

    I

    Give tripping command to R-ph only

    and check the operation of polediscrepancy relay

    Pole discrepancyrelay at breaker

    Cubicle Breaker polediscrepancy

    J

    Give tripping command to Y-phOnly and check the operation of pole

    discrepancy relay

    Pole discrepancy

    relay at breakerCubicle

    Breaker polediscrepancy

    K

    Give tripping Command to B-ph onlyand check the

    operation of polediscrepancy relay

    polediscrepancy

    relay at breakercubicle

    Breaker polediscrepancy

    L

    Check other alarms as per plantCircuit diagram

    M

    Close the breaker and trip throughProtection which are applicable

    protection relayas per scheme

    Breaker autotrip

    NOTE : The tripping details are to be checked as per the Scheme approved byengineering.

    XVI. DYNAMIC CONTACT RESISTANCE & TRAVEL MEASUREMENT

    PHASE FACTORY SITE REMARKSAPPROVAL FROM

    CC/OS OBTAINED

    R

    Y

    Enclosed

    B

    XVII. OPERATION TIME MEASUREMENT OF POLE DISCREPANCY RELAY

    Close/Trip time pole discrepancy at ratedoperating pressure Permissible Limits

    a) Phase to Phase (Max) - close operation5.0ms

    b) Phase to Phase (Max) - open operation 3.33ms

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker

    Page 13 of15

  • 7/27/2019 28 Circuit Breaker

    14/15

    DOC NO.: D-2-01-03-01-03

    c) Break to Break (Max) of same pole 2.5 ms

    Note- 2.5 Sec for CBs with Auto Reclose Function & 0.5 Sec for CBs without Auto Reclose Function.

    XVIII. MECHANICAL CLOSE INTERLOCK CHECKED

    (WHEREVER APPLICABLE)

    XIX. FINAL DOCUMENTATION REVIEW

    i. Factory test results are available

    ii. Final documents of Pre- Commissioning checks reviewed and approved

    iii. Document regarding spares equipment, O&M manuals etc available at sit

    for O&M purpose

    iv. After modification, if any, As built Drawings are available at site

    v. CC-OS approved dcrm signatures available

    Signature:

    Name:

    Designation:

    Organization:(SupplierRepresentative)(WhereverApplicable)

    Signature:

    Name:

    Designation:

    (Erection Agency)

    Signature:

    Name:

    Designation:

    (POWERGRID SiteI/C)

    Signature:

    Name:

    Designation:

    (POWERGRIDCommissioning. Team)Members:1.2.

    3.4.

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker

    Page 14 of15

    Yes No

    Yes

    Yes No

    Yes

    Yes No

    Yes

    Yes No

    Yes

    Yes No

    Yes

    Yes No

    Yes

  • 7/27/2019 28 Circuit Breaker

    15/15

    DOC NO.: D-2-01-03-01-03

    Format No.: No. CF/CB/03/ R-3 DATED 01/04/2011 Circuit Breaker