AquastreamAir-CooledWater ChillerWith Heat Pump Option

CXAH/CGAH 040-150 (R407C)106~380kW

PKGP-PRC006-EN

Page 2: CGAHCXAH

Features and Benefits

Product Nomenclature

General Data

Unit Dimension

Refrigerant System Diagram

Selection Procedure

Pressure Drop, Correction Factor, Electrical Data

Performance Data

Electrical Wiring Diagram

Notes of Application

4

6

7

8

10

11

12

13

15

39

Contents

3

Page 3: CGAHCXAH

Features andBenefits

4

• The rotating part is made by high-

strength cast iron. It forms a closed

compression chamber, prevents the

deformation and the leakage, ensures

the high performance and prevents the

compressor from the hammering.

• 3-D scroll compressor has been

researched and improved for more than

20 years. The measurements and the

performance of more than 400,000 hours

have proved its high performance and

outstanding quality.

Outstanding and Reliable

Performance

• High part load efficiency, reduce power

consumption and save energy.

• Low sound level, applicable to high

standard requirement buildings.

• Chillers are tested before shipment,

ensure the safety and the reliability.

• Able to operating within 43˚C ambient

temperature.

• Specially designed electrical control

panel and colored cables for easier

connection. An attached strainer can be

installed on site by customers to prevent

the evaporator from clogging. Removable

panels make it easy to install, adjust and

maintain.

• The structure is compact and low in

height. It can be installed with clearance

of 1 meter to wall and chiller design

blends in well with most building

environment.

• Water flow protection system is included

as a standard component thus eliminating

installation of water switches on site.

• The dry contacts are provided by the

chiller to control the chilled water pump.

▲Crankshaft angle(Compared with the reciprocating compressor

the torque of the 3-D scroll compressor is

greatly reduced.)

Tor

que(

%)

scroll

reciprocating

High efficiency 3-D Scroll

Compressor

The compressor of the chiller is 3-D scroll

compressor, which combines the 25

patents of "TRANE" together with

advantages of:

• Compared with the reciprocating

compressor of the same capacity, 3-D

scroll compressor reduced 64%

components, thus decreases frictions

and improves reliability and efficiency.

• The compressor torque variation is 30%

that of the reciprocating compressor with

the same capacity, thus reduces

vibrations and noise.

• The motor is cooled by the suction gas,

thus prolongs the service life, improves

the efficiency.

• Enclosed design, free of maintenance.

Page 4: CGAHCXAH

5

Features andBenefits

Powerful Microprocessor

SMM

• Leaving chilled water temperature

control

A water temperature sensor is fixed at

the outlet of evaporator. With this

temperature information, the SMM

module uses proportional integral

differential (PID) algorithm to predict and

control the on/off combinations of

sequencing compressors, thus controlling

the leaving chilled water temperature.

• Condensing pressure control

The SMMmodule can control the number

of operating condenser fans to achieve

the best of coefficient of performance

(COP), and to avoid the frequent chiller

shut down caused by the high/low

pressure protection.

• Performance optimization

In order to reduce electricity consumption,

the SMMmodule can automatically adjust

the chilled water setpoint in relation to

the outdoor temperature.

• Operator interface

The SMM module inc ludes a

communication interface with a liquid

crystal display. It helps technician to

access chiller operating conditions and

diagnosis information, thus making

operation and maintenance much easier.

• Remote control

The dry contacts and the analog inputs

are provided by the SMM module to

remote control the start/stop of the chiller

and to adjust the chil led water

temperature setpoint.

• Connection to the Building

Management System (BMS)

By option of TCI-S Communication Card

and serial communication cables, the

SMM module can communicate with the

professional BMS and in turn put the

chiller system under BMS group control,

so as to achieve operation and

maintenance convenience.

Environmentally Responsible

R407C Refrigerant

Both Aquastream cooling-only and

reversible chillers have been optimized

for exclusive use of chlorine-free R407C

refrigerant. Aquastream chillers operate

with a refrigerant that has a future and

complies with current and upcoming

environmental regulations.

Value Added Hydraulic

Module (Optional for models

040 to 080)

Only a main power supply & water

connections are necessary, the rest is

in the "box" such as pump, expansion

tank, valves, relief valve, water make-

up system etc which reduces customer's

installation time. TRANE offers this

hassle-free package that also saves

installation, operational and maintenance

costs.

Additional Functions

• Delay protection prevents the

compressors from frequent start/stop.

• Self-start after power off

• Self-balance the operation time of each

compressor

• Control the chilled water pump operation

• Prevent the evaporator from frosting

• Safety and protection operation

Standard Components

• Vibration proof rubber pad

• Y-type water strainer

• Differential pressure type water flow

switch

• Remote on / off switch

Options

• Condenser protecting grille

• Main power disconnect switch

• Compressor sound attenuator

• Factory installed low ambient

temperature kit.

• Integrated hydraulic module (Only for

040, 050, 060, 080 models)

Factory Testing and Quality

Assurance

• All chillers are subject to the strict

performance tests before shipment

• The Quality Management System

applied by "TRANE" factories in China

has been assessed and approved to ISO

9001 by professional organization.

Page 5: CGAHCXAH

C X A H 050 7 B N M R B N A

Digit 1 C=Chiller

Digit 2 G=Cooling only

X=Heat pump

Digit 3 A=Air-cooled

Digit 4 H=Major design sequence

Digit 5,6,7 Nominal capacity code

040 050 060 080 120 150

Digit 8 Power supply

5=380V/50Hz/3Ph

7=415V/50Hz/3Ph

Digit 9 Development sequence

A=First

B=Second

Digit 10 Grille/compressor sound attenuator

N=without condenser protecting grille or compressor sound

attenuator (standard)

J=without condenser protecting grille/with compressor sound

attenuator

L=with condenser protecting grille/without compressor sound

attenuator

K=with condenser protecting grille and compressor sound

attenuator

Digit 11 Main power supply switch configuration

M=without (standard)

G=with (optional)

Digit 12 Available ambient temperature

R=3~43˚C (standard)

L=Low ambient temperature (below 3˚C) (optional)

Digit 13 Refrierant system

A=R22 (optional)

B=R407C (standard)

Digit 14 Hydraulic module

N=without hydraulic module (standard)

W=with hydraulic module (Only for CXAH/CGAH 040, 050, 060,

080)

Digit 15 Service squence

A=First

B=Second

ProductNomenclature

6

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Page 6: CGAHCXAH

1. Cooling capacity is based on 35˚C ambient temperature, 7˚C outlet water temperature and 12˚C inlet water temperature.

2. Heating capacity is based on 7˚C DB/6˚C WB ambient temperature, 45˚C outlet water temperature and 40˚C inlet water temperature.

3. R22 refrigerant is also available for above models upon request.

GeneralData

7

415V-3Ph-50Hz

High efficiency hermetic scroll compressor

CGAH/CXAH040

106

39.8

100/108

36.2

CGAH/CXAH050

132

46.4

125/133

46.4

CGAH/CXAH060

158

54.6

156/159

54.6

CGAH/CXAH080

208

77.8

208/210

76.2

CGAH/CXAH150

380

140

380/410

150

CGAH/CXAH120

300

110

300/310

120

Model

Cooling OnlyUnit

Heat PumpUnit

Cooling capacity

Power input

Cooling/Heating capacity

Power input

kW

kW

kW

kW

Main Power supply

Compressor

Number of circuit A

Number of circuit B

Capacity steps

Minimum capacity

unit

unit

%

Refrigerant

Charge of circuit A

Charge of circuit B

kg

kg

Controller

Air Side Heat Exchanger

Fan type

Fan motor power input

Number of fan

Total air flow

Motor RPM

kW

unit

l/s

rpm

Water Side Heat Exchanger

Water flow

Max operating water pressure(without hydraulic module)

l/s

kPa

Built In Hydraulic Module (optional)

Pump type

Pump motor power input

Number of pump

Discharge head

Capacity of expansion tank

Max operating water pressure(with hydraulic module)

kW

m

l

kPa

in

mm

mm

mm

kg

kg

kg

kg

˚C

˚C

dBA

Water Pipe Diameter

Dimensions

OperatingWeight

ShippingWeight

Width

Length

Height

With hydraulic module

Without hydraulic module

With hydraulic module

Without hydraulic module

Operating temperature range (cooling)

Operating temperature range (heating)

sound pressure @ 1m

1

1

2

50

2

2

4

25

2

2

4

25

2

2

4

25

3

3

4

33.3

3

3

4

33.3

R407C

16.5

16.5

24

24

24

24

24

24

70/85

70/85

65/80

65/80

SMM inteligent control

Copper tube / Aluminium fins

Axial

0.9

4

10552

720

0.9

6

15828

720

0.9

6

15828

720

0.9

6

15828

720

1.3

8

33300

720

1.3

8

33300

720

Brazed Plate Heat Exchanger

4.8 6.35 7.61 10.1 18.314.6

1000

Pump, filter, relief valve, expansion tank, pressure gauge, flow switch, etc. N/A

Single stage centrifugal pump 2900r.p.m

2.2

1

22

24

600

2-1/2

1950

2828

1608

1400

1300

1390.20

1290.20

2.2

1

17

24

600

2-1/2

1950

3160

1850

1640

1535

1630.20

1525.20

3.0

1

22

24

600

2-1/2

1950

3160

1850

1696

1582

1684.00

1570.00

3.0

1

19

24

600

2-1/2

1950

3160

2002

1970

1852

1950.00

1832.00

N/A

N/A

N/A

N/A

N/A

5

2362

4940

2610

N/A

3950

N/A

3918.00

N/A

N/A

N/A

N/A

N/A

5

2362

4940

2610

N/A

3980

N/A

3940.00

15˚C to 43˚C ambient temperature

-10˚C to 24˚C ambient temperature

72 79 80 81 8383

Page 7: CGAHCXAH

8

UnitDimensions

CXAH/CGAH040 Unit: mm

CXAH/CGAH050, 060, 080 Unit: mm

- 3D SCROLL -

L2

A

View 'A'

1527

POWER/功率

风��冷��式��冷��水��机��组AIR�COOLED�WATER�CHILLER

特�灵�空�调�器�有�限�公�司

ELECTRIC�HEATER/电加热量

TELING�AIR�CONDITIONER�CO.,�LTD.

R-22�CHARGE/冷媒充灌量

COOLING�WATER�FLOW/冷却水流量Kw

KgR

- Q

ELECTRICAL�SUPPLY/电源

QTY/数量

CAPACITY

COMPRESSOR/压�缩�机

FAN�MOTOR/风�扇�马�达

MODEL/型�号

COOLING 制�冷�能�力 HEATING

SERIAL/机号

CAPACITY

F

N

B

G

VOLTS O

A

C

AMPS/额定电流

A

S

A

KW

LRA/堵转电流

Hz P

H

D

PHASE

A I

A E

制�热�能�力 J

L/M

Kw

Kw

KW

194

973

Aquastream

装入回水管路中,否则其后果本公安装时务必将随机带的水过滤器

注�意�:

公司一概不负

1606

CXAH3005A1NMRNA

CO.LTD

合格证

TELING�AIR�CONDITIONER

特灵空调器有限公司

0037370********

日���期:

检�验�员:

检验结论:编��号:

型��号:

产品名称: 风冷式冷水机组

1946

1950

2828

2800

2380

20 20

1999

11

25

Remarks

135 698

L2L1

- 397

with hydraulic system

without hydraulic systemL1

water outlet�(ZG2-1/2")

water inlet�(ZG2-1/2")

make-up inlet�(ZG1/2")

wire �entry

electrical �access �panel

进�水�口

出�水�口

补�水�口

AIR CONDITIONING

hanging pore

1850

2002

Hmodel

CXAH080 CGAH080

CXAH050/060 CGAH050/060

628

397

L2(without hydraulic system)

194

L1

205

808

698

L3(with hydraulic system)L2(with hydraulic system)

135

AIR CONDITIONING

L2

wire entry

View 'A'

electrical access panelelectrical box

A

hanging pore

- 3D SCROLL -

Aquastream

20

20

1950

3160

2696

3140

3246

20

974

L1

H

2002

1950

L3

water outlet(ZG2-1/2")

water inlet(ZG2-1/2")

make-up inlet(ZG1/2")

Page 8: CGAHCXAH

UnitDimensions

CXAH/CGAH120,150

9

Unit: mm

195206

232

INLET OUTLET

AIR CONDITIONING

4700

49402362

2610

952.

7

POWER/功率

风 冷 式 冷 水 机 组AIR COOLED WATER CHILLER

特 灵 空 调 器 有 限 公 司

ELECTRIC HEATER/电加热量

TELING AIR CONDITIONER CO., LTD.

R-22 CHARGE/冷媒充灌量

COOLING WATER FLOW/冷却水流量Kw

KgR

- Q

ELECTRICAL SUPPLY/电源

QTY/数量

CAPACITY

COMPRESSOR/压 缩 机

FAN MOTOR/风 扇 马 达

MODEL/型 号

COOLING 制 冷 能 力 HEATING

SERIAL/机号

CAPACITY

F

N

B

G

VOLTS O

A

C

AMPS/额定电流

A

S

A

KW

LRA/堵转电流

Hz P

H

D

PHASE

A I

A E

制 热 能 力 J

L/M

Kw

Kw

KW

1510

CXAH3005A1NMRNA

CO.LTD

合格证

TELING AIR CONDITIONER

特灵空调器有限公司

0037370********

日 期:

检 验 员:

检验结论:编 号:

型 号:

产品名称: 风冷式冷水机组

5"water connection

electrical box

Page 9: CGAHCXAH

Refrigerant SystemDiagram

Cooling mode

Heating mode13

1

16

8 15

6

17

18

18 15

13

13

10

11

12

13

11

2

3

7

9

5

414

1) scroll compressor

2) condenser

3) supercooler

4) brazed plate heat exchanger

5) liquid receiver

6) four-way valve

7) expansion valve (heating)

8) air vent

9) filter dryer

10) expansion valve (cooling)

11) solenoid valve

12) liquid sight glass

13) non return valve

14) solenoid valve

15) safety valve

16) high pressure switch (cooling)

17) high pressure switch (heating)

18) pressure sensor

10

1

16

8 15

6

17

18

18 15

13

13

13

10

11

12

13

11

2

3

7

9

5

414

Page 10: CGAHCXAH

The cooling capacity table in the chapter

of "general data" represents of typical

leaving water temperature under the

following conditions:

• Fouling factor = 0.086m2 • ˚C/kW

• Evaporator entering and leaving water

temperature difference between 4~8˚C.

Take CXAH as an example, the following

design conditions should be determined:

Cooling:

1) System cooling load(kW)

2) Chilled water leaving temperature(˚C)

3) Ambient temperature(˚C)

Heating

1) hot water leaving temperature(˚C)

2) ambient temperature(˚C), dry bulb(DB)

and wet bulb(WB) temperature.

Calculate the water flow rate with the

following formula:

Flowrate(L/s)=0.239xload(kW)/enteringand

leaving water temperature difference (˚C)

Case study for selection procedure

Cooling Conditiong:

Condition:

1) system load: 120 kW

2) chilled water leaving temperature:+7˚C

3) chilled water entering temperature:+12˚C

4) ambient temperature: 35˚C

1. Select model

According to the cooling capacity chart,

model CXAH050 can provide 125 kW

cooling capacity, and 39.5 kW input

power is required.

2. Water flow rate

Flow rate(L/s)=125x0.239/(12-7)=5.97(L/s)

3. Water pressure drop across evaporator

According to the water pressure drop

chart, when the flow rate is 5.97 L/s, the

pressure drop is 50 kPa for CXAH050.

Heating Condition:

Condition:

1) hot water leaving temperature 45˚C

2) ambient temperature: 7˚C(DB), 6˚C(WB)

1. According to the heating capacity

chart, model CXAH050 can provide 133

kW heating capacity, and 43 kW input

power is required.

2. The entering and leaving water

temperature difference can be calculated

by the following formula:

hot water entering and leaving

temperature difference= heating capacity

(133kW)x0.239/ water flow rate(5.97 L/s)

= 5.32˚C.

External water system connection diagram (recommendation)

SelectionProcedure

11

inflow water

outflow water flexible joint

chiller

gate valve (1) gate valve

gate valve (3)

gate valve (4)

three-way valve

three-wayvalve

balancevalve

pressure gauge

water strainer

thermometer

thermometerair vent

pressure gauge

drain valve

drainvalve

flexible joint

Page 11: CGAHCXAH

Pressure Drop,Correction Factor,Electrical Data

12

Correction factor - CXAH/CGAH

Chilled water outflow

temperature (˚C)

12

5

4

0

-4

-8

-12

Ethylene glycol

mass concentration(%)

30

30

10

20

27

33

37

Flow rate

1.11

1.11

1.02

1.05

1.08

1.1

1.12

Pressure drop

1.2

1.24

1.08

1.19

1.29

1.46

1.62

Input power

1.005

1.005

1

1

1

1

1

Cooling capacity

0.98

0.97

1

1

1

1

1

Correction factor

Note: Correction factor should be considered when ethylene glycol is used in the chilled water system. (actual value = original value x correction factor)

Correction for pressure drop (kPa) CXAH/CGAH

Temperature difference betweeninflow and outflow water(˚C)

3

5

7

3

5

7

3

5

7

3

5

7

3

5

7

3

5

7

Chiller model

040

050

060

080

120

479

288

206

597

358

256

745

447

319

994

596

426

1587

952

680

1825

1096

782

Water flow rate(LPM)

Water pressure drop(kPa)

52.6

19.9

10.7

121.9

50.0

23.8

125.9

50.8

24.3

130.2

51.6

24.8

130.0

46.6

23.8

115.0

41.5

21.1

150

Electrical Data

Compressor

Number

Rated Amps

Locked Rotor Amps

Rated Power Input

Number

Rated Amps A

Locked Rotor Amps

Rated Power Input

Parameter

Connections

model

Fan Motor

Power Supply

A

A

kW

A

A

kW

mm2

CGAH/CXAH 040

2

29.5x2

230x2

16.3x2

4

1.7x4

8.5x4

0.9x4

415V/50Hz/3ø

3x16

CGAH/CXAH 050

2+2

23.6x2+13.9x2

175x2+125x2

12.3x2+8.2x2

6

1.7x6

8.5x6

0.9x6

415V/50Hz/3ø

3x25

CGAH/CXAH 060

4

23.6x4

175x4

12.3x4

6

1.7x6

8.5x6

0.9x6

415V/50Hz/3ø

3x35

CGAH/CXAH 080

4

30.8x4

230x4

17.7x4

6

1.7x6

8.5x6

0.9x6

415V/50Hz/3ø

3x50

CGAH/CXAH 120

6

30.8x6

230x6

16.5x6

8

2.7x8

13.5x8

1.30x8

415V/50Hz/3ø

3x95

CGAH/CXAH 150

6

36.1x6

270x6

21.8x6

8

2.7x8

13.5x8

1.30x8

415V/50Hz/3ø

3x95

Page 12: CGAHCXAH

PerformanceData

13

Cooling capacity CXAH/CGAH150

AmbientTemp (˚C)

LWT (˚C)

5

7

9

25

Capacity(kW)

375.63

405.74

437.68

Power Input(kW)

113.11

113.72

114.41

30

Capacity(kW)

359.31

388.34

419.12

Power Input(kW)

125.71

126.43

127.16

35

Capacity(kW)

340.87

380.06

398.18

Power Input(kW)

139.17

140.03

140.88

40

Capacity(kW)

320.58

347.01

375.08

Power Input(kW)

153.82

154.80

155.72

Cooling capacity CXAH/CGAH120

AmbientTemp (˚C)

LWT (˚C)

5

7

9

25

Capacity(kW)

310.31

336.22

363.70

Power Input(kW)

91.21

91.62

92.02

30

Capacity(kW)

293.84

318.59

344.85

Power Input(kW)

99.62

100.11

100.29

35

Capacity(kW)

276.59

300.11

325.08

Power Input(kW)

109.09

109.64

110.19

40

Capacity(kW)

258.63

280.87

298.78

Power Input(kW)

119.85

120.40

121.01

Cooling capacity CXAH/CGAH080

AmbientTemp (˚C)

LWT (˚C)

5

7

9

25

Capacity(kW)

215.54

233.54

252.63

Power Input(kW)

64.66

64.96

65.25

30

Capacity(kW)

204.10

221.29

239.53

Power Input(kW)

70.83

71.19

71.32

35

Capacity(kW)

192.12

208.46

225.80

Power Input(kW)

77.78

78.18

78.58

40

Capacity(kW)

179.64

195.09

207.54

Power Input(kW)

85.66

86.07

86.51

Cooling capacity CXAH/CGAH060

AmbientTemp (˚C)

LWT (˚C)

5

7

9

25

Capacity(kW)

163.48

176.95

191.17

Power Input(kW)

44.86

44.91

44.95

30

Capacity(kW)

155.00

167.90

181.52

Power Input(kW)

49.37

49.46

49.71

35

Capacity(kW)

145.84

158.12

171.11

Power Input(kW)

54.51

54.59

54.65

40

Capacity(kW)

136.03

147.65

160.09

Power Input(kW)

60.35

60.39

60.47

Cooling capacity CXAH/CGAH050

AmbientTemp (˚C)

LWT (˚C)

5

7

9

25

Capacity(kW)

137.62

149.00

161.03

Power Input(kW)

38.24

38.25

38.25

30

Capacity(kW)

130.45

141.36

152.89

Power Input(kW)

42.03

42.05

42.15

35

Capacity(kW)

122.68

133.08

144.08

Power Input(kW)

46.37

46.39

46.40

40

Capacity(kW)

114.30

124.15

134.65

Power Input(kW)

51.38

51.36

51.36

Cooling capacity CXAH/CGAH040

AmbientTemp (˚C)

LWT (˚C)

5

7

9

25

Capacity(kW)

111.87

121.21

131.12

Power Input(kW)

32.63

32.67

32.70

30

Capacity(kW)

105.93

114.86

124.32

Power Input(kW)

35.95

36.01

36.20

35

Capacity(kW)

99.71

108.19

117.20

Power Input(kW)

39.73

39.79

39.84

40

Capacity(kW)

93.24

101.26

107.72

Power Input(kW)

44.02

44.05

44.12

Page 13: CGAHCXAH

PerformanceData

14

Heating Capacity CXAH040

AmbientDry/Wet

Temp (˚C)

LWT (˚C)

40

45

50

15/13

Capacity(kW)

142.60

138.65

134.87

Power Input(kW)

33.67

36.95

40.66

7/6

Capacity(kW)

110.35

108.04

106.00

Power Input(kW)

33.04

36.24

39.89

0/-1

Capacity(kW)

87.91

86.79

86.00

Power Input(kW)

32.54

35.72

39.34

-3/-4

Capacity(kW)

79.73

79.04

Power Input(kW)

32.36

35.54

Heating Capacity CXAH050

AmbientDry/Wet

Temp (˚C)

LWT (˚C)

40

45

50

15/13

Capacity(kW)

175.05

169.85

172.64

Power Input(kW)

42.17

46.43

59.52

7/6

Capacity(kW)

135.83

133.02

130.28

Power Input(kW)

41.94

46.37

51.42

0/-1

Capacity(kW)

108.38

107.06

Power Input(kW)

41.75

46.18

-3/-4

Capacity(kW)

98.34

Power Input(kW)

41.64

Heating Capacity CXAH060

AmbientDry/Wet

Temp (˚C)

LWT (˚C)

40

45

50

15/13

Capacity(kW)

208.86

202.77

212.24

Power Input(kW)

50.10

54.99

77.00

7/6

Capacity(kW)

162.30

158.98

155.74

Power Input(kW)

49.49

54.70

60.58

0/-1

Capacity(kW)

129.64

128.14

Power Input(kW)

49.12

54.30

-3/-4

Capacity(kW)

117.75

Power Input(kW)

48.93

Heating Capacity CXAH080

AmbientDry/Wet

Temp (˚C)

LWT (˚C)

40

45

50

15/13

Capacity(kW)

277.17

269.49

262.15

Power Input(kW)

70.64

77.74

85.79

7/6

Capacity(kW)

214.48

210.00

206.02

Power Input(kW)

69.26

76.21

84.12

0/-1

Capacity(kW)

170.87

168.69

167.15

Power Input(kW)

68.19

75.08

82.94

-3/-4

Capacity(kW)

154.97

153.63

Power Input(kW)

67.80

74.69

Heating Capacity CXAH120

AmbientDry/Wet

Temp (˚C)

LWT (˚C)

40

45

50

15/13

Capacity(kW)

409.29

397.95

387.10

Power Input(kW)

111.35

122.33

134.80

7/6

Capacity(kW)

316.72

310.10

304.23

Power Input(kW)

109.21

119.97

132.22

0/-1

Capacity(kW)

252.32

249.10

246.83

Power Input(kW)

107.56

118.22

130.38

-3/-4

Capacity(kW)

228.83

226.86

Power Input(kW)

106.96

117.61

Heating Capacity CXAH150

AmbientDry/Wet

Temp (˚C)

LWT (˚C)

40

45

50

15/13

Capacity(kW)

534.81

522.75

509.75

Power Input(kW)

139.44

154.14

170.15

7/6

Capacity(kW)

417.26

410.39

403.14

Power Input(kW)

136.09

150.28

165.75

0/-1

Capacity(kW)

335.08

331.84

328.71

Power Input(kW)

133.11

146.73

161.61

-3/-4

Capacity(kW)

304.91

302.95

Power Input(kW)

131.78

145.13

Page 14: CGAHCXAH

Electrical WiringDiagram

15

Page 15: CGAHCXAH

Electrical WiringDiagram

16

Page 16: CGAHCXAH

Electrical WiringDiagram

17

Page 17: CGAHCXAH

Electrical WiringDiagram

18

Page 18: CGAHCXAH

Electrical WiringDiagram

19

Page 19: CGAHCXAH

Electrical WiringDiagram

20

Page 20: CGAHCXAH

Electrical WiringDiagram

21

Page 21: CGAHCXAH

Electrical WiringDiagram

22

Page 22: CGAHCXAH

Electrical WiringDiagram

23

Page 23: CGAHCXAH

Electrical WiringDiagram

24

Page 24: CGAHCXAH

Electrical WiringDiagram

25

Page 25: CGAHCXAH

Electrical WiringDiagram

26

Page 26: CGAHCXAH

Electrical WiringDiagram

27

Page 27: CGAHCXAH

Electrical WiringDiagram

28

Page 28: CGAHCXAH

Electrical WiringDiagram

29

Page 29: CGAHCXAH

Electrical WiringDiagram

30

Page 30: CGAHCXAH

Electrical WiringDiagram

31

Page 31: CGAHCXAH

Electrical WiringDiagram

32

Page 32: CGAHCXAH

Electrical WiringDiagram

33

Page 33: CGAHCXAH

Electrical WiringDiagram

34

Page 34: CGAHCXAH

Electrical WiringDiagram

35

Page 35: CGAHCXAH

Electrical WiringDiagram

36

Page 36: CGAHCXAH

Electrical WiringDiagram

37

Page 37: CGAHCXAH

Electrical WiringDiagram

38

Page 38: CGAHCXAH

Notes ofApplication

CXAH/CGAH chiller safety device

1. High pressure

2. Low pressure

3. Anti-freeze low temperature

4. Water flow rate

5. Air vent

6. Phase Reverse

7. Compressor overcurrent, overload

8. Fan motor overcurrent, overload

Illustration of clearanceNote: minimum top air discharge distance 3000mm.

39

Page 39: CGAHCXAH

TraneA business of American Standard Companieswww.trane.com

For more information, contact your local districtoffice

Literature Order Number

File Number

Supersedes

Stocking location

CG-PRC013-EN (December 2004)

PL-RF-CG-000-PRC013-EN-1204

PKGP-PRC007-EN

Taicang

Trane has a policy of continuous product and data improvement and reserves the right tochange design specifications without notice.