    esserbus-PLusmaximumsecurity, minimum costs

    www.novar.de

  • 8/3/2019 797821

    2/6

    The innovation

    The latest in ringbus

    technology:

    The esserbus-PLus supplies

    data, signals and power,

    too, for the direct operation

    of alarm devices on only

    2 wiresVdS certified.

    l For the first time in Germany, thanks to the esserbus-PLus, the certified and

    approved operation of addressable, loop-powered alarm devices on the ringbus

    together with fire detectors and other devices is possible. The esserbus-PLus

    enables alarm devices to be powered directly, tolerant of short circuits and wire

    breaks, from the 2-wire analog loop. In other words, all participants, including

    alarm devices, are connected directly to the bus. In an alarm situation, the ring

    loop increases the voltage to 42 volts and thus provides them with the necessary

    power. An alarm can therefore be signalled using completely new (wiring) paths:reliably, economically and in conformity with the relevant standards.

    An additional and unique quality characteristic of the esserbus-PLus is the syn-

    chronous alarm signalling function. All sweep and intermittent tones are therefore

    no longer distorted unrecognisably by the irregular emission of several tones in the

    fire compartment.

    For a building sector affected by fire esserbus-PLus means the alarm signal is not

    compromised until the device itself is destroyed by fire. Thanks to the loop technol-

    ogy, the warning devices in the unaffected fire compartments remain functional,

    even without fireproof wiring.

  • 8/3/2019 797821

    3/6

    l At present all internal alarm devices must be activated in conformity with various

    installation standards through monitored circuits. In addition, wiring that bridges

    more than one fire section, must satisfy the requirements for fire resilience. With

    conventional resources, this can only be achieved by the costly installation of a

    separate power unit for each fire compartment.

    The only exception: the wiring system is realised with powered loop technology and

    the alarm devices are short circuit and open circuit-tolerant. In this way it is possi-ble to deliver sustained operation in a fire situation.

    The status quo

    Ringbus technology has

    been used in modern alarm

    systems for a long time.

    However, separate power

    sources must be provided

    for high-current devices,

    such as alarm sounders.

    This means unnecessary

    costs are incurred for add-

    itional wiring, power supply

    units and longer installation

    times.

  • 8/3/2019 797821

    4/6

    The esserbus-PLus enables versatile new

    system components to be used. A base

    sounder with an integrated fire detector

    base and a system sounder are available as

    alarm devices in conformity with EN 54-3.

    Both have 4 programmable and approved

    sounds.

    The advantages

    The esserbus-PLus offers numerous advantages in terms of security and

    cost-effectiveness.

    l Maximum planning reliability

    l Permanent monitoring of the alarm device

    l No detailed consideration of fire sections for alarm devicesand their wiring paths is needed

    l Measures to ensure continued functionality of wiring

    systems with alarm devices can be dispensed with in

    most cases

    l Maximum security in cases of alarm

    l Savings due to lower material costs and shorter

    installation time

    l No separate power supply units for fire compartments

    l Synchronous alarm signalling

  • 8/3/2019 797821

    5/6

    System components

    The addressable base sounderhas two functions. It serves as a fully functional

    alarm device, which generates a uniform 360 sound pressure, and also as a mount-

    ing base for Series 9200 fire detectors. Like the base sounder, the addressable

    system sounderin red and white contains an isolator. Both the base sounder and

    the system sounder are fully integrated bus devices.

    Technical datacommon features:

    s 4 different tones, which can be programmed using the customer data editors Warning tone to DIN 33404 Part 3

    Technical database sounder:

    s Conforms to DIN EN 54-3, VdS approval G 202046

    s Sound pressure 93 dB (A)/1 m

    s Current: < 6 mA at ring voltage, 22 mA at battery voltage

    s Flush-mount kit available for false ceilings

    s Up to 48 signal bases can be accommodated on one ring loop

    Technical datasystem sounder:

    s Conforms to DIN EN 54-3, VdS approval 202049

    s Sound pressure 97 dB (A)/1 m

    s Current: < 10 mA at ring voltage, 55 mA at battery voltage

    s The sound level in the warning device is adjustable

    s Up to 16 warning devices can be accommodated on one ring loop

  • 8/3/2019 797821

    6/6

    Novar GmbH

    Dieselstrae 2

    D-41469 Neuss

    Tel.: +49 (0)2137 171

    Fax: +49 (0)2137 17286

    Johannes-Mauthe-Strae 14

    D-72458 Albstadt

    Tel.: +49 (0)7431 8010

    Fax: +49 (0)7431 8011220

    Internet:

    www.novar.de

    E-mail:

    [email protected]

    p

    lenums

    toll&fischbachCommunicationGmbH,Dsseldorf

    Art.No.797821/10.2003