LPC Rules for automatic
sprinkler installations
variations to
BS EN 12845: 2009TB229.1 INTRODUCTION
This Technical Bulletin introduces variations from BS EN 12845 to make the specification
suitable for use. The Technical Bulletin includes LPC Rules amendments which have
been drawn up by the Active Steering Group of RISCAuthority, either as modifications to
the CEN 2009 amendments or as changes to the content of BS EN 12845.
TB229.2 GENERAL
A brief description of the change is given under each heading.
Revised or new text is shown in italic bold underlined font.
To aid understanding of some changes, deleted text has been depicted using
strikethrough text.
Where changes have been introduced by this Technical Bulletin to the proposed
amendments, the details of the change and, where appropriate, reasons for the change
have been given.
Table notes have the status of recommendations whilst Table footnotes are
requirements.
TB229.3 VARIATIONS TO BS EN 12845: 2009
TB229.3.1 BS EN Table 2
Description of changes:
Renumber Note 3 to Note 2, column 4, row 2 and row 8;
Change Note 2 to footnotea, rows 2, 3, 4, 5, 7 and 8;
Insertion of Note 2 as footnote a.
Table TB229.T1 Limitations and protection requirements for different storage configurations BS EN Table 2
(amended)
Storage
configurationLayout limitations
Protection in addition to sprinklers
at ceiling or roof
Applicable table
notes:
ST1Storage shall be confined to blocks
not exceeding 150m2 in plan area for
C III and IV
None (2, a)
-
7/30/2019 00000937
2/9
Table TB229.T1 Limitations and protection requirements for different storage configurations BS EN Table 2
(amended)
Storage
configurationLayout limitations
Protection in addition to sprinklers
at ceiling or roof
Applicable table
notes:
ST2Aisles between rows shall be not
less than 2,4m wideNone (a)
ST3Storage shall be confined to blocks
not exceeding 150m2 in plan areaNone (a)
ST4
Aisles separating rows are equal or
greater than 1,2m wide
Intermediate sprinklers are
recommended(1, a)
Aisles separating rows are less than
1,2m wide Intermediate sprinklers are required(1)
ST5
Either the aisles separating rows
shall be no less than 1,2m wide, or
storage blocks shall be no more than
150m in plan area
Intermediate sprinklers are
recommended(1, a)
ST6
Either the aisles separating rows
shall be no less than 1,2m wide, or
storage blocks shall be no more than150m in plan area
Intermediate sprinklers are required
or, if this is impossible, continuous
full height vertical bulkheads with
Euroclass A1 or A2 or an equivalent
in existing national classification
systems shall be fitted longitudinally
and transversely within each shelf
(1, a)
Note 1: When the ceiling is more than 4m above the highest level of stored goods, intermediate levels of in-rack
sprinklers should be used.
Note 2:Storage blocks should be separated by aisles no less than 2,4m wide.
Note 3: Note 2: Storage should be confined to blocks not exceeding 150m2 in plan area for C I and C II.
a Storage blocksshallbe separated by aisles no less than 2,4m wide.
TB229.3.2 BS EN Table 4
Description of change:
Amend Note 2 to delete and alternate.
LPC Rules requirements change table note to footnote (b) and insert footnote (a)
concerning alternate systems.
Table TB229.T2 Design criteria for HHS with roof or ceiling protection only (Replacing BS EN Table 4)
-
7/30/2019 00000937
3/9
Storage
configuration
Maximum permitted storage height(1)
m Design
density
mm/min
Area of
operation (wet
or pre-action
system(2, a, b))
mCategory I Category II Category III Category IV
ST1 Free
standing or
block stacking
5,3
6,5
7,6
4,1
5,0
5,9
6,7
7,5
2,9
3,5
4,1
4,7
5,2
1,6
2,0
2,3
2,7
3,0
7,5
10,0
12,5
15,0
17,5
260
5,7
6,3
6,7
7,2
3,3
3,6
3,8
4,1
4,4
20,0
22,5
25,0
27,5
30,0
300
ST2 Post pallets
in single rows
ST4 Palletized
racks
4,7
5,7
6,8
3,4
4,2
5,0
5,6
6,0
2,2
2,6
3,2
3,7
4,1
1,6
2,0
2,3
2,7
3,0
7,5
10,0
12,5
15,0
17,5
260
4,4
4,8
5,3
5,66,0
3,3
3,6
3,8
4,14,4
20,0
22,5
25,0
27,530,0
300
ST3 Post pallets
in multiple rows
ST5 and ST6
Solid or slatted
shelves
4,7
5,7
3,4
4,2
5,0
2,2
2,6
3,2
1,6
2,0
2,3
2,7
3,0
7,5
10,0
12,5
15,0
17,5
260
Note 1: The vertical distance from the floor to the sprinkler deflectors, minus 1m, or the highest value shown in the
table, whichever is the lower.
Note 2: Dry and alternate systems should be avoided on High Hazard storage especially with the more combustible
products (the higher categories) and the higher storage.aLPC Rules requirements Alternate systems are no longer permitted. bLPC Rules requirements Should it nonetheless be necessary to install a dry system, the area of operation
should be increased by 25%.
TB229.3.3 BS EN Table 5
Description of change:
Amend Note 2 to delete and alternate.
LPC Rules requirement change part of table note 2 to table footnote.
-
7/30/2019 00000937
4/9
Table TB229.T3 Design criteria for roof or ceiling sprinklers with in-rack sprinklers
(Replacing BS EN Table 5)
Storage
configuration
Maximum permitted storage height above the top level of
in-rack protection(1)
mDesign
densitymm/min
Area of
operation (wet
or pre-actionsystem(2))
mCategory I Category II Category III Category IV
ST4 Palletized
racks3,5 3,4
2,2
2,6
3,2
3,5
1,6
2,0
2,3
2,7
7,5
10,0
12,5
15,0
260
ST5 and ST6
Solid or slattedshelves
3,5 3,4
2,2
2,63,2
1,6
2,0
2,3
2,7
7,5
10,0
12,5
15,0
260
Note 1: The vertical distance from the highest level of in-rack sprinklers to the top of the storage.
Note 2: Dry and alternate systems should be avoided on High Hazard storage especially with the more combustible
products (the higher categories) and the higher storage.aLPC Rules requirement Should it nonetheless be necessary to install a dry system, the area of operation
shall be increased by 25%.
TB229.3.4 BS EN Clause 8.5.2Description of changes:
Insertion of LPC Rules requirement as fourth paragraph.
BS EN Clause 8.5.2 At water supplies
Additional LPC Rules requirement: Where a permanent flow test facility is not
provided which returns the test flow to a water storage tank (cistern) or
alternatively to a permanent drain, temporary measures shall be provided to safely
dispose of the waste water.
TB229.3.5 BS EN Table 11
Description of change:
Insertion of LPC Rule requirement, column 2, row 7;
Insertion of and LPC Rules requirement as footnote, row 8;
Insertion of LPC Rules commentary and recommendation, row 9.
Table TB229.T4 Minimum effective capacity of reduced capacity tanks (Replacing BS EN Table 11 )
Hazard classMinimum effective capacity(a)
m3
LH Wet or pre-action 5
-
7/30/2019 00000937
5/9
Table TB229.T4 Minimum effective capacity of reduced capacity tanks (Replacing BS EN Table 11 )
Hazard classMinimum effective capacity(a)
m3
OH1 Wet or pre-action 10
OH1 Dry or alternate
OH2 Wet or pre-action20
OH2 Dry or alternate
OH3 Wet or pre-action30
OH3 Dry or alternate
OH4 Wet or pre-action50
HHP and HHS
70
but in no case less than 10% of the full capacity
LPC Rules Requirement:
2/3 of the value specified in BS EN Table 10 or
BS EN 9.3.2.3
or
the value specified in BS EN Table 10 or BS EN
9.3.2.3 less the infill flow rate, in l/min, multiplied by
0,09, whichever is the greater
See footnote(a)
Additional LPC Rules requirement:a When determining the minimum effective capacity of a reduced capacity tank, a maximum of 80% of an
adjusted infill flow rate, verified by test, shall be used. The adjusted infill flow rate shall take into account any
reductions in flow due to static head and friction between the test point and the tank infill at a period of
maximum demand.
LPC Rules commentary and recommendation:
The water supplier should be consulted before using town mains as infill for reduced capacity tanks. It is
essential to establish that the performance of the town main will not depreciate over the life of the sprinkler
system water supply.
TB229.3.6 BS EN Clause 9.6.4
Description of change:
LPC Rules requirement replacing BS EN Clause 9.6.4.
BS EN Clause 9.6.4 Combined water supplies
Combined water supplies shall be superior single or duplicate water supplies designed to
supply more than one fixed fire fighting system, as for example in the case of combined
hydrant, hose and sprinkler installations.
Note: Some countries may not allow sprinkler systems to be fed from a combinedsupply.
Combined supplies shall fulfil the following conditions:
-
7/30/2019 00000937
6/9
a) the systems shall be fully calculated;
b) the supply shall be capable of supplying the sum of the simultaneous maximum
calculated flows from each system. The flows shall be corrected up to the
pressure required by the most demanding system;
c) the duration of the supply shall be no less than that required for the most
demanding system;
d) duplicate pipe connections shall be installed between the water supplies and the
systems.
TB229.3.6 Combined water supplies (Replacing BS EN 9.6.4)
The sprinkler system pumps and water source shall be separate from any hydrant
system pumps and water source.
TB229.3.7 BS EN Table 17
Description of change:
LPC Rules requirement replacing BS EN Table 17.
Table TB229.T5 Maximum size of wet pipe and pre-action installations (Replacing BS EN Table 17)
Hazard classMaximum size of protection per control valve set
m2
LH 10 000m2
OH, including any LH sprinklers12 000m2
except as allowed in annexes D and F
HH excluding in-rack sprinkler protection,
including any OH or LH sprinklers,9 000m2
HH in-rack sprinkler protection
Categories I and II
Categories III and IV
9000m2
1 000 sprinklers
2 000 sprinklers
TB229.3.8 BS EN Clause 13.4.4
Description of change:
LPC Rule requirement, amendment of fourth bullet point.
TB229.3.8 Minimum sprinkler discharge pressure
(Replacing BS EN Clause 13.4.4)
The pressure at the hydraulically most unfavourably situated sprinkler, when all the
sprinklers in the area of operation are in operation, shall be not less than that required to
achieve the density specified in 13.4.1 or the following, whichever is the higher:
0,70 bar in LH;
0,35 bar in OH;
-
7/30/2019 00000937
7/9
0,50 bar in HHP and HHS except for in-rack sprinklers;
2,00 bar for K80 in-rack sprinklers;
1,00 bar for K115 in-rack sprinklers.
TB229.3.9 BS EN Clause 9.3.5Description of change:
Clarification of Figure 4
Note. The drawings show the pipe end with a vortex inhibitor. Where a vortex inhibitor is
fitted depth measurements are taken from the underside of the upper flange. Horizontal
separation, from the wall is measured from the periphery of the vortex inhibitor to the
wall. When there is no vortex inhibitor depth measurements are taken from the lowest
edge of the pipe and horizontal separation from the wall is measured from the nearest
point on the pipe surface at the pipe end to the wall.
BS EN Clause 9.6.4, Figure 4, drawing 1 without sump.
-
7/30/2019 00000937
8/9
BS EN Clause 9.6.4 Figure 4, drawing 2 with sump
Where:
A - Minimum dimension from the suction pipe to the low water level
B - Minimum dimension from the suction pipe to the bottom of the sump
d - Nominal diameter of the suction pipe.
N - Normal water level
X Low water level
effective capacity
-
7/30/2019 00000937
9/9
TB229.3.10 BS EN Clause G.8.5
Description of change:
Re-instatement of minimum duration of foam additive
G.8.5 Foam additive
A suitable film forming foam, used in accordance with the supplier's
recommendation, shall be added to thesprinkler water.
NOTE In full scale fire tests, AFFF (aqueous film forming foam) has been shown to
be effective.
TB229.3.10 Minimum duration of foam additive supply.
(Replacing BS EN Annex G.8.5)
Aqueous film-forming foam (AFFF) shall be added to the sprinkler water in
accordance with the manufacturers recommendations. The duration of supply of
AFFF should not be less than 10min for a flow equivalent to 0.5Qmax