PARAMETER LIST
Compact Genset Controller, CGC 400 Alarm list Parameter list
Document no.: 4189340789ASW version:
1. General information1.1. Warnings, legal information and safety..................................................................................................4
1.1.1. Warnings and notes ......................................................................................................................41.1.2. Legal information and disclaimer ..................................................................................................41.1.3. Safety issues ................................................................................................................................41.1.4. Electrostatic discharge awareness ...............................................................................................41.1.5. Factory settings ............................................................................................................................5
1.2. About the Parameter List........................................................................................................................51.2.1. General purpose of the Parameter List..........................................................................................51.2.2. Intended users...............................................................................................................................51.2.3. Contents and overall structure ......................................................................................................5
2. Alarm list2.1. General information about the alarm list................................................................................................6
2.1.1. Alarm list features and options .....................................................................................................62.2. Protection parameters............................................................................................................................8
2.2.1. Reverse power and overcurrent protection....................................................................................82.2.2. Voltage protections......................................................................................................................122.2.3. Frequency protections.................................................................................................................142.2.4. Busbar voltage protections..........................................................................................................172.2.5. Busbar frequency protections......................................................................................................192.2.6. Overload protections....................................................................................................................212.2.7. Undervoltage and reactive power low..........................................................................................23
2.3. Breaker control parameters..................................................................................................................252.3.1. Breaker alarms............................................................................................................................25
2.4. Input/output parameters, binary input setup.........................................................................................282.4.1. Digital input 10-15 and 56-57 setup.............................................................................................282.4.2. Digital input 6-8 setup..................................................................................................................292.4.3. Emergency stop...........................................................................................................................302.4.4. M-Logic alarm 1-5 setup .............................................................................................................31
2.5. Analogue input setup............................................................................................................................322.5.1. Multi-input no. 6...........................................................................................................................322.5.2. Multi-input no. 7 ..........................................................................................................................372.5.3. Multi-input no. 8...........................................................................................................................422.5.4. Speed and running feedback setup.............................................................................................472.5.5. Differential measurement.............................................................................................................502.5.6. Aux. supply setup........................................................................................................................532.5.7. Multi-input no. 58.........................................................................................................................542.5.8. Multi-input no. 59.........................................................................................................................59
2.6. System parameters, general setup......................................................................................................642.6.1. Engine heater failure....................................................................................................................642.6.2. Max. ventilation............................................................................................................................652.6.3. Switchboard error - Block and Stop.............................................................................................662.6.4. Switchboard error - Not in auto....................................................................................................672.6.5. Avg U BB.....................................................................................................................................68
2.7. System parameters, communication....................................................................................................692.7.1. External communication error......................................................................................................692.7.2. Engine interface communication alarms......................................................................................70
3. Parameter list3.1. General information about the parameter list.......................................................................................74
3.1.1. Parameter list settings.................................................................................................................743.2. Control parameter, regulation...............................................................................................................75
3.2.1. Regulation....................................................................................................................................753.3. Control parameters, output setup.........................................................................................................76
3.3.1. Digital output setup......................................................................................................................763.4. System parameters..............................................................................................................................773.5. System parameters, general setup......................................................................................................78
CGC 400 parameter list 4189340789 UK
DEIF A/S Page 2 of 98
3.5.1. General setup..............................................................................................................................783.5.2. Counters and timers....................................................................................................................813.5.3. Alarm horn...................................................................................................................................823.5.4. Run coil setup..............................................................................................................................823.5.5. Running, start and stop................................................................................................................833.5.6. Breaker control............................................................................................................................853.5.7. Idle start.......................................................................................................................................853.5.8. Engine heater..............................................................................................................................863.5.9. Cooling ventilation.......................................................................................................................863.5.10. Summer/winter time...................................................................................................................863.5.11. Fuel transfer pump logic............................................................................................................873.5.12. Alarm jump.................................................................................................................................873.5.13. Command timers.......................................................................................................................88
3.6. System parameters, mains setup.........................................................................................................893.6.1. Test..............................................................................................................................................893.6.2. Mains failure................................................................................................................................90
3.7. System parameters, external communication......................................................................................913.7.1. External communication..............................................................................................................91
3.8. System parameters, engine interface communication.........................................................................923.8.1. Engine interface communication..................................................................................................92
3.9. System parameters, setup menu.........................................................................................................933.9.1. Password config. ........................................................................................................................933.9.2. AC config.....................................................................................................................................933.9.3. Display control ............................................................................................................................93
3.10. System parameters, RMI inputs.........................................................................................................943.10.1. RMI 6.........................................................................................................................................943.10.2. RMI 7.........................................................................................................................................953.10.3. RMI 8.........................................................................................................................................953.10.4. RMI 58.......................................................................................................................................963.10.5. RMI 59.......................................................................................................................................963.10.6. Multi-input selections.................................................................................................................973.10.7. Analogue unit input scaling........................................................................................................98
CGC 400 parameter list 4189340789 UK
DEIF A/S Page 3 of 98
1. General information1.1 Warnings, legal information and safety1.1.1 Warnings and notesThroughout this document, a number of warnings and notes with helpful user information will be presented.To ensure that these are noticed, they will be highlighted as follows in order to separate them from the gener-al text.
Warnings
Warnings indicate a potentially dangerous situation, which could result in death, personal in-jury or damaged equipment, if certain guidelines are not followed.
Notes
Notes provide general information, which will be helpful for the reader to bear in mind.
1.1.2 Legal information and disclaimerDEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about howto install or operate the engine/generator controlled by the unit, the company responsible for the installation orthe operation of the set must be contacted.
The unit is not to be opened by unauthorised personnel. If opened anyway, the warranty will belost.
DisclaimerDEIF A/S reserves the right to change any of the contents of this document without prior notice.
1.1.3 Safety issuesInstalling and operating the unit may imply work with dangerous currents and voltages. Therefore, the instal-lation should only be carried out by authorised personnel who understand the risks involved in working withlive electrical equipment.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in-puts as this could lead to injury or death.
DEIF do not recommend to use the USB as the primary power supply for the unit.
1.1.4 Electrostatic discharge awarenessSufficient care must be taken to protect the terminal against static discharges during the installation. Once theunit is installed and connected, these precautions are no longer necessary.
CGC 400 parameter list 4189340789 UK General information
DEIF A/S Page 4 of 98
1.1.5 Factory settingsThe unit is delivered from factory with certain factory settings. These are based on average values and arenot necessarily the correct settings for matching the engine/generator set in question. Precautions must betaken to check the settings before running the engine/generator set.
1.2 About the Parameter List1.2.1 General purpose of the Parameter ListThis document is a complete parameter list including all parameters, which means that some of the optionparameters included may not be accessible in the system in question.
The document includes a complete standard alarm list and a complete standard parameter list for setup.Therefore, this document is to be used for reference, when information about specific alarms and parametersis needed.
Please make sure to read this document before starting to work with the unit and the genset tobe controlled. Failure to do this could result in human injury or damage to the equipment.
1.2.2 Intended usersThis Parameter List is mainly intended for the person responsible for the unit parameter setup. In most cases,this would be a panel builder designer. Naturally, other users might also find useful information here.
1.2.3 Contents and overall structureThis document is divided into chapters, and in order to make the structure simple and easy to use, eachchapter will begin from the top of a new page.
CGC 400 parameter list 4189340789 UK General information
DEIF A/S Page 5 of 98
2. Alarm list2.1 General information about the alarm list2.1.1 Alarm list features and options
In the following, these abbreviations are used:G: GeneratorGB: Generator breakerMB: Mains breakerN/A: Not available
This chapter includes a complete alarm list, including all possible options. Therefore, this chapter is to beused for reference when specific information about the individual parameters is needed for the unit setup.
The table consists of the following possible adjustments:
Set point: The alarm set point is adjusted in the set point menu. The setting is a percentage ofthe nominal values.
Delay: The timer setting is the time that must expire from the alarm level is reached until thealarm occurs.
Relay output A: A relay can be activated by output A.
Relay output B: A relay can be activated by output B.
Enable: The alarm can be activated or deactivated. ON means always activated, RUN meansthat the alarm has run status. This means it is activated when the running signal ispresent.
Fail class: When the alarm occurs the unit will react depending on the selected fail class.
Fail classes are:
Fail class DG (diesel generator) Mains unitF1 Block BlockF2 Warning WarningF3 Trip GB Trip TBF4 Trip + Stop Trip MBF5 Shutdown N/AF6 Trip MB N/AF7 Safety stop N/AF8 Trip MB/GB N/A
Small differences due to the character of the parameters may exist between the individual ta-bles.
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 6 of 98
It is also possible to configure the param-eters by using the PC utility software. Itwill be possible to make the same config-urations as described above.
By using the PC utility software, extrafunctionality is available. For all the pro-tections it is possible to make an auto-matic acknowledgement of the alarm.
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 7 of 98
2.2 Protection parameters2.2.1 Reverse power and overcurrent protection
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1000 Reverse power 11001 P> 1 Set
point-200.0 %0.0 %
-5.0 % DesignersReferenceHandbook
The alarm and fail class are ac-tivated when the reverse powerhas been continuously abovethe programmed value duringthe programmed delay.
1002 P> 1 Timer 0.1 s100.0 s
10.0 s
1003 P> 1 RelayoutputA
Not usedOption-depend-ent
Not used
1004 P> 1 RelayoutputB
Not usedOption-depend-ent
Not used
1005 P> 1 Enable OFFON
ON
1006 P> 1 Failclass
F1F8 Trip GB(F3)
1010 Reverse power 21011 P> 2 Set
point-200.0 %0.0 %
-5.0 % DesignersReferenceHandbook
The alarm and fail class are ac-tivated when the reverse powerhas been continuously abovethe programmed value duringthe programmed delay.
1012 P> 2 Timer 0.1 s100.0 s
10.0 s
1013 P> 2 RelayoutputA
Not usedOption-depend-ent
Not used
1014 P> 2 RelayoutputB
Not usedOption-depend-ent
Not used
1015 P> 2 Enable OFFON
ON
1016 P> 2 Failclass
F1F8 Trip GB(F3)
1030 Overcurrent 1
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 8 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1031 I> 1 Setpoint
50.0 %200.0 %
115.0 % DesignersReferenceHandbook
The alarm and fail class are ac-tivated when the current hasbeen continuously above theprogrammed value during theprogrammed delay.
1032 I> 1 Timer 0.1 s3200.0 s
10.0 s
1033 I> 1 RelayoutputA
Not usedOption-depend-ent
Not used
1034 I> 1 RelayoutputB
Not usedOption-depend-ent
Not used
1035 I> 1 Enable OFFON
ON
1036 I> 1 Failclass
F1F8 Warn-ing(F2)
1040 Overcurrent 21041 I> 2 Set
point50.0 %200.0 %
120.0 % DesignersReferenceHandbook
The alarm and fail class are ac-tivated when the current hasbeen continuously above theprogrammed value during theprogrammed delay.
1042 I> 2 Timer 0.1 s3200.0 s
5.0 s
1043 I> 2 RelayoutputA
Not usedOption-depend-ent
Not used
1044 I> 2 RelayoutputB
Not usedOption-depend-ent
Not used
1045 I> 2 Enable OFFON
ON
1046 I> 2 Failclass
F1F8 Trip GB(F3)
1050 Overcurrent 31051 I> 3 Set
point50.0 %200.0 %
115.0 % DesignersReferenceHandbook
The alarm and fail class are ac-tivated when the current hasbeen continuously above theprogrammed value during theprogrammed delay.
1052 I> 3 Timer 0.1 s3200.0 s
10.0 s
1053 I> 3 RelayoutputA
Not usedOption-depend-ent
Not used
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 9 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1054 I> 3 RelayoutputB
Not usedOption-depend-ent
Not used
1055 I> 3 Enable OFFON
ON
1056 I> 3 Failclass
F1F8 Trip GB(F3)
1060 Overcurrent 41061 I> 4 Set
point50.0 %200.0 %
120.0 % DesignersReferenceHandbook
The alarm and fail class are ac-tivated when the current hasbeen continuously above theprogrammed value during theprogrammed delay.
1062 I> 4 Timer 0.1 s3200.0 s
5.0 s
1063 I> 4 RelayoutputA
Not usedOption-depend-ent
Not used
1064 I> 4 RelayoutputB
Not usedOption-depend-ent
Not used
1065 I> 4 Enable OFFON
ON
1066 I> 4 Failclass
F1F8 Trip GB(F3)
1080 I> inverse1081 I> in-
verseType
Setpoint
IEC In-verseCustom
IEC In-verse
DesignersReferenceHandbook
Type selections are:IEC InverseIEC Very InverseIEC Extremely Inv.IEEE Moderately Inv.IEEE Very InverseIEEE Extremely Inv.Custom
Output B is only available in theutility software.
1082 I> in-verseLimit
Setpoint
50 %200 %
110.0 %
1083 I> in-verseTMS
Setpoint
0.1100.0
1.0
1084 I> in-verse k
Setpoint
0.001 s32.000 s
0.140 s
1085 I> in-verse c
Setpoint
0.000 s32.000 s
0.000 s
1086 I> in-verse a
Setpoint
0.00132.000
0.020
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 10 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1087 I> in-verse
RelayoutputA
Not usedOption-depend-ent
Not used
1088 I> in-verse
Enable OFFON
ON
1089 I> in-verse
Failclass
F1F8 Trip GB(F3)
1130 Fast overcurrent 11131 I>> 1 Set
point150.0 %350.0 %
150.0 % DesignersReferenceHandbook
The alarm settings relate to thenominal current setting. Thealarm and fail class are activa-ted when the current has beencontinuously above the pro-grammed value during the pro-grammed delay.
1132 I>> 1 Timer 0.0 s100.0 s
2.0 s
1133 I>> 1 RelayoutputA
Not usedOption-depend-ent
Not used
1134 I>> 1 RelayoutputB
Not usedOption-depend-ent
Not used
1135 I>> 1 Enable OFFON
OFF
1136 I>> 1 Failclass
F1...F8 Trip GB(F3)
1140 Fast overcurrent 21141 I>> 2 Set
point150.0 %350.0 %
200 % DesignersReferenceHandbook
The alarm and fail class are ac-tivated when the current hasbeen continuously above theprogrammed value during theprogrammed delay
1142 I>> 2 Delay 0.0 s100.0 s
0.5 s
1143 I>> 2 RelayoutputA
Not usedOption-depend-ent
Not used
1144 I>> 2 RelayoutputB
Not usedOption-depend-ent
Not used
1145 I>> 2 Enable OFFON
OFF
1146 I>> 2 Failclass
F1...F8 Trip GB(F3)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 11 of 98
2.2.2 Voltage protectionsNo. Setting Min.
Max.Factorysetting
Notes Ref. Description
1150 G overvoltage 11151 G U>
1Setpoint
100.0 %120.0 %
103.0 % DesignersReferenceHandbook
The alarm and fail class are acti-vated when the voltage has beencontinuously above the program-med value during the program-med delay.
1152 G U>1
Timer 0.1 s100.0 s
10.0 s
1153 G U>1
RelayoutputA
Not usedOption-dep.
Notused
1154 G U>1
RelayoutputB
Not usedOption-dep.
Notused
1155 G U>1
Enable OFFON
OFF
1156 G U>1
Failclass
F1F8 Warning(F2)
1160 G overvoltage 21161 G U>
2Setpoint
100.0 %120.0 %
105.0 % DesignersReferenceHandbook
The alarm and fail class are acti-vated when the voltage has beencontinuously above the program-med value during the program-med delay.
1162 G U>2
Timer 0.1 s100.0 s
5.0 s
1163 G U>2
RelayoutputA
Not usedOption-dep.
Notused
1164 G U>2
RelayoutputB
Not usedOption-dep.
Notused
1165 G U>2
Enable OFFON
OFF
1166 G U>2
Failclass
F1F8 Warning(F2)
1170 G undervoltage 11171 G U3
Failclass
F1F8 Warning(F2)
1240 G underfrequency 11241 G f
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1254 G f
2.2.4 Busbar voltage protections
Voltage settings relate to the nominal voltage setting.
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1270 Busbar overvoltage 11271 BB
U> 1Setpoint
100.0 %120.0 %
103.0 % DesignersReferenceHandbook
The alarm and fail class are acti-vated when the voltage has beencontinuously above the program-med value during the program-med delay.
1272 BBU> 1
Timer 0.00 s99.99 s
10.00 s
1273 BBU> 1
RelayoutputA
Not usedOption-depend-ent
Notused
1274 BBU> 1
RelayoutputB
Not usedOption-depend-ent
Notused
1275 BBU> 1
Enable OFFON
OFF
1276 BBU> 1
Failclass
F1F8 Warning(F2)
1280 Busbar overvoltage 21281 BB
U> 2Setpoint
100.0 %120.0 %
105.0 % DesignersReferenceHandbook
The alarm and fail class are acti-vated when the voltage has beencontinuously above the program-med value during the program-med delay.
1282 BBU> 2
Timer 0.00 s99.99 s
10.00 s
1283 BBU> 2
RelayoutputA
Not usedOption-depend-ent
Notused
1284 BBU> 2
RelayoutputB
Not usedOption-depend-ent
Notused
1285 BBU> 2
Enable OFFON
OFF
1286 BBU> 2
Failclass
F1F8 Warning(F2)
1300 Busbar undervoltage 1
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 17 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1301 BBU< 1
Setpoint
40.0 %100.0 %
97.0 % DesignersReferenceHandbook
The alarm and fail class are acti-vated when the voltage has beencontinuously under the program-med value during the program-med delay.
1302 BBU< 1
Timer 0.00 s99.99 s
10.00 s
1303 BBU< 1
RelayoutputA
Not usedOption-depend-ent
Notused
1304 BBU< 1
RelayoutputB
Not usedOption-depend-ent
Notused
1305 BBU< 1
Enable OFFON
OFF
1306 BBU< 1
Failclass
F1F8 Warning(F2)
1310 Busbar undervoltage 21311 BB
U< 2Setpoint
40.0 %100.0 %
95.0 % DesignersReferenceHandbook
The alarm and fail class are acti-vated when the voltage has beencontinuously under the program-med value during the program-med delay.
1312 BBU< 2
Timer 0.00 s99.99 s
5.00 s
1313 BBU< 2
RelayoutputA
Not usedOption-depend-ent
Notused
1314 BBU< 2
RelayoutputB
Not usedOption-depend-ent
Notused
1315 BBU< 2
Enable OFFON
OFF
1316 BBU< 2
Failclass
F1F8 Warning(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 18 of 98
2.2.5 Busbar frequency protections
Frequency settings relate to the nominal frequency setting.
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1350 Busbar overfrequency 11351 BB f>
1Setpoint
100.0 %120.0 %
103.0 % DesignersReferenceHandbook
The alarm and fail class are acti-vated when the frequency hasbeen continuously above the pro-grammed value during the pro-grammed delay.
1352 BB f>1
Timer 0.00 s99.99 s
10.00 s
1353 BB f>1
RelayoutputA
Not usedOption-dep.
Notused
1354 BB f>1
RelayoutputB
Not usedOption-dep.
Notused
1355 BB f>1
Enable OFFON
OFF
1356 BB f>1
Failclass
F1F8 Warning(F2)
1360 Busbar overfrequency 21361 BB f>
2Setpoint
100.0 %120.0 %
105.0 % DesignersReferenceHandbook
The alarm and fail class are acti-vated when the frequency hasbeen continuously above the pro-grammed value during the pro-grammed delay.
1362 BB f>2
Timer 0.00 s99.99 s
5.00 s
1363 BB f>2
RelayoutputA
Not usedOption-dep.
Notused
1364 BB f>2
RelayoutputB
Not usedOption-dep.
Notused
1365 BB f>2
Enable OFFON
OFF
1366 BB f>2
Failclass
F1F8 Warning(F2)
1380 Busbar underfrequency 11381 BB f 2 Failclass
F1F8 Trip GB(F3)
1470 Overload 31471 P> 3 Set
point-200.0 %200.0 %
100.0 % DesignersReferenceHandbook
The alarm and fail class are activa-ted when the power has been con-tinuously above the programmedvalue during the programmed de-lay.
1472 P> 3 Timer 0.1 s3200.0 s
10.0 s
1473 P> 3 RelayoutputA
Not usedOption-dep.
Notused
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 21 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1474 P> 3 RelayoutputB
Not usedOption-dep.
Notused
1475 P> 3 Enable OFFON
OFF
1476 P> 3 Failclass
F1F8 Trilp GB(F3)
1480 Overload 41481 P> 4 Set
point-200.0 %200.0 %
110.0 % DesignersReferenceHandbook
The alarm and fail class are activa-ted when the power has been con-tinuously above the programmedvalue during the programmed de-lay.
1482 P> 4 Timer 0.1 s3200.0 s
5.0 s
1483 P> 4 RelayoutputA
Not usedOption-dep.
Notused
1484 P> 4 RelayoutputB
Not usedOption-dep.
Notused
1485 P> 4 Enable OFFON
OFF
1486 P> 4 Failclass
F1F8 Trip GB(F3)
1490 Overload 51491 P> 5 Set
point-200.0 %200.0 %
100.0 % DesignersReferenceHandbook
The alarm and fail class are activa-ted when the power has been con-tinuously above the programmedvalue during the programmed de-lay.
1492 P> 5 Timer 0.1 s3200.0 s
10.0 s
1493 P> 5 RelayoutputA
Not usedOption-dep.
Notused
1494 P> 5 RelayoutputB
Not usedOption-dep.
Notused
1495 P> 5 Enable OFFON
OFF
1496 P> 5 Failclass
F1...F8 Trip GB(F3)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 22 of 98
2.2.7 Undervoltage and reactive power lowNo. Setting Min.
Max.Factorysetting
Notes Ref. Description
1960 U and Q < 11961 U and
Q < 1Setpoint
40.0 %100.0 %
85.0 % Option A1 The setting relates to the genera-tor nominal voltage.The condition for trip is that the ac-tual voltage drops below the set-ting value and the reactive poweris 0 kVAr.
1962 U andQ < 1
Timer 0.1 s3200.0 s
0.5 s
1963 U andQ < 1
RelayoutputA
Option-dep.
Notused
1964 U andQ < 1
RelayoutputB
Option-dep.
Notused
1965 U andQ < 1
Enable OFFON
OFF
1966 U andQ < 1
Failclass
F1F8 Warning(F2)
1970 U and Q < 21971 U and
Q < 2Setpoint
40.0 %100.0 %
85.0 % Option A1 The setting relates to the genera-tor nominal voltage.The condition for trip is that the ac-tual voltage drops below the set-ting value and the reactive poweris 0 kVAr.
1972 U andQ < 2
Timer 0.1 s3200.0 s
0.5 s
1973 U andQ < 2
RelayoutputA
Option-dep.
Notused
1974 U andQ < 2
RelayoutputB
Option-dep.
Notused
1975 U andQ < 2
Enable OFFON
OFF
1976 U andQ < 2
Failclass
F1F8 Warning(F2)
1980 GB/MB external trip1981 GB ext.
tripEnable OFF
ONON Design-
er's Refer-enceHandbook
The generator breaker or themains breaker has been tripped byan external device.1982 GB ext.
tripFailclass
F1...F8 Warning(F2)
1983 MB ext.trip
Enable OFFON
ON
1984 MB ext.trip
Failclass
F1...F8 Warning(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 23 of 98
Minimum current and minimum Phi angle
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
1990 U and Q< 11991 I Min. 1 Set
point0 %20 %
0 % OptionA1
Settings relate to U and Q< parameters1960 and 1970.Condition for "U and Q
2.3 Breaker control parameters2.3.1 Breaker alarms
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
2110 Sync. blackout2111 Sync.
blackoutdfMax. 0.0 Hz
5.0 Hz3.0 Hz Designers
ReferenceHandbook
Settings are accepted limits forclosing of the breaker, refer-ring to nominal frequency andvoltage.
2112 Sync.blackout
dUMax. 2 %10 %
5 %
2150 Phase sequence error2151 Phase
seq er-ror
Relayoutput A
Not usedOption-dep.
Not used DesignersReferenceHandbook
Prior to closing a breaker, theunit checks that the phase se-quence is correct, dependingon the chosen phase directionin parameter 2154: Phase ro-tation. If it is incorrect (re-versed), an alarm will be is-sued and the breaker in ques-tion will not be closed.
2152 Phaseseq er-ror
Relayoutput B
Not usedOption-dep.
Not used
2153 Phaseseq er-ror
Failclass
F1F8 Block(F1)
2154 Phaserotation
Set point L1L2L3L1L3L2
L1L2L3
2160 GB open failure2161 GB
open failTimer 1.0 s
10.0 s2.0 s Designers
ReferenceHandbook
The breaker open failure willoccur if the unit has transmit-ted a breaker open signal andthe breaker feedback has notchanged position from ON toOFF within the time delay.
2162 GBopen fail
Relayoutput A
Not usedOption-dep.
Not used
2163 GBopen fail
Relayoutput B
Not usedOption-dep.
Not used
2164 GBopen fail
Enable OFFON
ON
2165 GBopen fail
Failclass
F1F8 Warning(F2)
2170 GB breaker close failure2171 GB
closefail
Timer 1.0 s5.0 s
2.0 s DesignersReferenceHandbook
The breaker close failure willoccur if the unit has transmit-ted a breaker close signal andthe breaker feedback has notchanged position from OFF toON within the time delay.
2172 GBclosefail
Relayoutput A
Not usedOption-dep.
Not used
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 25 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
2173 GBclosefail
Relayoutput B
Not usedOption-dep.
Not used
2174 GBclosefail
Enable OFFON
ON
2175 GBclosefail
Failclass
F1F8 Warning(F2)
2180 GB breaker position failure2181 GB pos
failTimer 1.0 s
5.0 s1.0 s Designers
ReferenceHandbook
This alarm will occur if thebreaker feedbacks for ON andOFF are both missing or activefor more than the time delay.
2182 GB posfail
Relayoutput A
Not usedOption-dep.
Not used
2183 GB posfail
Relayoutput B
Not usedOption-dep.
Not used
2184 GB posfail
Enable OFFON
ON
2185 GB posfail
Failclass
F1F8 Warning(F2)
2200 MB open failure2201 MB
open failTimer 1.0 s
10.0 s2.0 s Designers
ReferenceHandbook
The breaker open failure willoccur if the unit has transmit-ted a breaker open signal andthe breaker feedback has notchanged position from ON toOFF within the time delay.
2202 MBopen fail
Relayoutput A
Not usedOption-dep.
Not used
2203 MBopen fail
Relayoutput B
Not usedOption-dep.
Not used
2204 MBopen fail
Enable OFFON
ON
2205 MBopen fail
Failclass
F1F8 Warning(F2)
2210 MB close failure2211 MB
closefail
Timer 1.0 s5.0 s
2.0 s DesignersReferenceHandbook
The breaker close failure willoccur if the unit has transmit-ted a breaker close signal andthe breaker feedback has notchanged position from OFF toON within the time delay.
2212 MBclosefail
Relayoutput A
Not usedOption-dep.
Not used
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 26 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
2213 MBclosefail
Relayoutput B
Not usedOption-dep.
Not used
2214 MBclosefail
Enable OFFON
ON
2215 MBclosefail
Failclass
F1F8 Warning(F2)
2220 MB position failure2221 MB pos
failTimer 1.0 s
5.0 s1.0 s Designers
ReferenceHandbook
This alarm will occur if thebreaker feedbacks for ON andOFF are both missing or activefor more than the time delay.
2222 MB posfail
Relayoutput A
Not usedOption-dep.
Not used
2223 MB posfail
Relayoutput B
Not usedOption-dep.
Not used
2224 MB posfail
Enable OFFON
ON
2225 MB posfail
Failclass
F1F8 Warning(F2)
No. Setting Min. setting Max. setting Factory setting2770 EIC control2771 EIC control Droop 0.0 % 25.0 % 0.0 %2772 EIC control Scania rpm User
1500 rpm1800 rpmLow Idle
User
2773 EIC control Cummins gain 0.00 10.00 5.002790 EIC speed demand switch2791 EIC speed demand
switchLocal normal sw. Analogue CAN
UpDown ECUUpDown CANAnalogue ECUAnalogue ECU relativeFrequency
Analogue CAN
2792 EIC speed demandswitch
Local emergency sw.
2793 EIC speed demandswitch
Remote normal sw.
2794 EIC speed demandswitch
Remote emergency sw.
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 27 of 98
2.4 Input/output parameters, binary input setup2.4.1 Digital input 10-15 and 56-57 setup
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
3000 Digital input 103001 Dig. in-
put 10Timer 0.0 s
100.0 s10.0 s Designers
ReferenceHandbook
The input is configurableand can have differentfunctions in different units.3002 Dig. in-
put 10Relayoutput A
Not usedOption-dep.
Not used
3003 Dig. in-put 10
Relayoutput B
Not usedOption-dep.
Not used
3004 Dig. in-put 10
Enable OFFON
OFF
3005 Dig. in-put 10
Fail class F1F8 Warning(F2)
3006 Dig. in-put 10
HighAlarm
OFFON
ON
The same settings apply to inputs 11-15 and 56-57, menus 3010 to 3070.
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 28 of 98
2.4.2 Digital input 6-8 setupNo. Setting Min.
Max.Facto-ry set-
ting
Notes Ref. Description
3400 Digital input 63401 Wire
fail 6Enable OFF OFF Designers
ReferenceHandbook
The input is configurable and canhave different functions in differentunits.(Only available if multi-input 6 isconfigured to "binary" in menu10980).
3402 Dig. in-put 6
Timer 0.0 s100.0 s
10.0 s
3403 Dig. in-put 6
RelayoutputA
NotusedOption-dep.
Notused
3404 Dig. in-put 6
RelayoutputB
NotusedOption-dep.
Notused
3405 Dig. in-put 6
Enable OFFON
OFF
3406 Dig. in-put 6
Failclass
F1F8 Warn-ing(F2)
3410 Digital input 73411 Wire
fail 7Enable OFF OFF Designers
ReferenceHandbook
The input is configurable and canhave different functions in differentunits.(Only available if multi-input 7 isconfigured to "binary" in menu10990).
3412 Dig. in-put 7
Timer 0.0 s100.0 s
10.0 s
3413 Dig. in-put 7
RelayoutputA
NotusedOption-dep.
Notused
3414 Dig. in-put 7
RelayoutputB
NotusedOption-dep.
Notused
3415 Dig. in-put 7
Enable OFFON
OFF
3416 Dig. in-put 7
Failclass
F1F8 Warn-ing(F2)
3420 Digital input 8
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 29 of 98
No. Setting Min.Max.
Facto-ry set-
ting
Notes Ref. Description
3421 Wirefail 8
Enable OFF OFF DesignersReferenceHandbook
The input is configurable and canhave different functions in differentunits.(Only available if multi-input 8 isconfigured to "binary" in menu11000).
3422 Dig. in-put 8
Timer 0.0 s100.0 s
10.0 s
3423 Dig. in-put 8
RelayoutputA
NotusedOption-dep.
Notused
3424 Dig. in-put 8
RelayoutputB
NotusedOption-dep.
Notused
3425 Dig. in-put 8
Enable OFFON
OFF
3426 Dig. in-put 8
Failclass
F1F8 Warn-ing(F2)
2.4.3 Emergency stopNo. Setting Min.
Max.Factorysetting
Notes Ref. Description
3490 Emergency stop3491 Emer.
stopTimer 0.0 s
60.0 s0.0 s Designers
ReferenceHandbook
Emergency stop input isintended for a normallyclosed contact.3492 Emer.
stopRelayoutput A
Not usedOption-dependent
Not used
3493 Emer.stop
Relayoutput B
Not usedOption-de-pendent
Not used
3494 Emer.stop
Enable OFFON
ON
3495 Emer.stop
Fail class F1F8 Shut-down(F5)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 30 of 98
2.4.4 M-Logic alarm 1-5 setupNo. Setting Min.
Max.Factorysetting
Notes Ref. Description
3570 Mlogic alarm 13570 Mlogic alarm 1 Timer 0.0 s
100.0 s10.0 s The input is configura-
ble.3571 Mlogic alarm 1 Relay output
ANot usedOption-dep.
Not used
3572 Mlogic alarm 1 Relay outputB
Not usedOption-dep.
Not used
3573 Mlogic alarm 1 Enable OFFON
OFF
3574 Mlogic alarm 1 Fail class F1F8 Warning(F2)
3575 Mlogic alarm 1 High alarm OFFON
ON
The same settings apply to alarm inputs 2-5, menus 3580 to 3610.
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 31 of 98
2.5 Analogue input setup2.5.1 Multi-input no. 6
The available menus for multi-input no. 6 depend on the input type configured in the PC utilitysoftware (menu 10980).
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4120 4-20 mA 6.14121 4-20
mA 6.1Setpoint
4 mA20 mA
10 mA DesignersReferenceHandbook
The multi-input 6 has beenconfigured as 4-20 mA.
4122 4-20mA 6.1
Timer 0.0 s999.0 s
120.0 s
4123 4-20mA 6.1
Relayoutput A
Not usedOption-dep.
Notused
4124 4-20mA 6.1
Relayoutput B
Not usedOption-dep.
Notused
4125 4-20mA 6.1
Enable OFFON
OFF
4126 4-20mA 6.1
Failclass
F1F8 Warning(F2)
4130 4-20 mA 6.24131 4-20
mA 6.2Setpoint
4 mA20 mA
10 mA DesignersReferenceHandbook
The multi-input 6 has beenconfigured as 4-20 mA.
4132 4-20mA 6.2
Timer 0.0 s999.0 s
120.0 s
4133 4-20mA 6.2
Relayoutput A
Not usedOption-dep.
Notused
4134 4-20mA 6.2
Relayoutput B
Not usedOption-dep.
Notused
4135 4-20mA 6.2
Enable OFFON
OFF
4136 4-20mA 6.2
Failclass
F1F8 Warning(F2)
4160 Pt100/Pt1000 6.14161 PT 6.1 Set
point-49482
80 DesignersReferenceHandbook
The multi-input 6 has beenconfigured as Pt100 orPt1000.4162 PT 6.1 Timer 0.0 s
999.0 s5.0 s
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 32 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4163 Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).
PT 6.1 Relayoutput A
Not usedOption-dep.
Notused
4164 PT 6.1 Relayoutput B
Not usedOption-dep.
Notused
4165 PT 6.1 Enable OFFON
OFF
4166 PT 6.1 Failclass
F1F8 Warning(F2)
4167 PT 6.1 Offset 0.0 Ohm5.0 Ohm
0.0 Ohm
4170 Pt100/Pt1000 6.24171 PT 6.2 Set
point-49482
80 DesignersReferenceHandbook
The multi-input 6 has beenconfigured as Pt100 orPt1000.Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).
4172 PT 6.2 Timer 0.0 s999.0 s
10.0 s
4173 PT 6.2 Relayoutput A
Not usedOption-dep.
Notused
4174 PT 6.2 Relayoutput B
Not usedOption-dep.
Notused
4175 PT 6.2 Enable OFFON
OFF
4176 PT 6.2 Failclass
F1...F8 Warning(F2)
4180 Resistance measurement input, oil pressure 6.14181 RMI oil
6.1Setpoint
0.0145.0
2.0 DesignersReferenceHandbook
The multi-input 6 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).
4182 RMI oil6.1
Timer 0.0 s999.0 s
5.0 s
4183 RMI oil6.1
Relayoutput A
Not usedOption-dep.
Notused
4184 RMI oil6.1
Relayoutput B
Not usedOption-dep.
Notused
4185 RMI oil6.1
Enable OFFON
OFF
4186 RMI oil6.1
Failclass
F1F8 Warning(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 33 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4190 Resistance measurement input, oil pressure 6.24191 RMI oil
6.2Setpoint
0.0145.0
1.0 DesignersReferenceHandbook
The multi-input 6 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).
4192 RMI oil6.2
Timer 0.0 s999.0 s
5.0 s
4193 RMI oil6.2
Relayoutput A
Not usedOption-dep.
Notused
4194 RMI oil6.2
Relayoutput B
Not usedOption-dep.
Notused
4195 RMI oil6.2
Enable OFFON
OFF
4196 RMI oil6.2
Failclass
F1F8 Shut-down(F5)
4200 Resistance measurement input, water temperature 6.14201 RMI
water6.1
Setpoint
-49482
100 DesignersReferenceHandbook
The multi-input 6 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection(menu 10970).
4202 RMIwater6.1
Timer 0.0 s999.0 s
5.0 s
4203 RMIwater6.1
Relayoutput A
Not usedOption-dep.
Notused
4204 RMIwater6.1
Relayoutput B
Not usedOption-dep.
Notused
4205 RMIwater6.1
Enable OFFON
OFF
4206 RMIwater6.1
Failclass
F1F8 Warning(F2)
4210 Resistance measurement input, water temperature 6.24211 RMI
water6.2
Setpoint
-49482
110 DesignersReferenceHandbook
The multi-input 6 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection(menu 10970).
4212 RMIwater6.2
Timer 0.0 s999.0 s
5.0 s
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 34 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4213 RMIwater6.2
Relayoutput A
Not usedOption-dep.
Notused
4214 RMIwater6.2
Relayoutput B
Not usedOption-dep.
Notused
4215 RMIwater6.2
Enable OFFON
OFF
4216 RMIwater6.2
Failclass
F1F8 Trip +Stop(F4)
4220 Resistance measurement input, fuel level 6.14221 RMI
fuel 6.1Setpoint
0 %100 %
10 % DesignersReferenceHandbook
The multi-input 6 has beenconfigured as RMI fuel level.
4222 RMIfuel 6.1
Timer 0.0 s999.0 s
10.0 s
4223 RMIfuel 6.1
Relayoutput A
Not usedOption-dep.
Notused
4224 RMIfuel 6.1
Relayoutput B
Not usedOption-dep.
Notused
4225 RMIfuel 6.1
Enable OFFON
OFF
4226 RMIfuel 6.1
Failclass
F1F8 Warning(F2)
4230 Resistance measurement input, fuel level 6.24231 RMI
fuel 6.2Setpoint
0 %100 %
5 % DesignersReferenceHandbook
The multi-input 6 has beenconfigured as RMI fuel level.
4232 RMIfuel 6.2
Timer 0.0 s999.0 s
10.0 s
4233 RMIfuel 6.2
Relayoutput A
Not usedOption-dep.
Notused
4234 RMIfuel 6.2
Relayoutput B
Not usedOption-dep.
Notused
4235 RMIfuel 6.2
Enable OFFON
OFF
4236 RMIfuel 6.2
Failclass
F1F8 Warning(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 35 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4240 Wire fail 64241 W. fail
6Relayoutput A
Not usedOption-dep.
Notused
DesignersReferenceHandbook
The wire break fault detectionis activated.
4242 W. fail6
Relayoutput B
Not usedOption-dep.
Notused
4243 W. fail6
Enable OFFON
OFF
4244 W. fail6
Failclass
F1F8 Warning(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 36 of 98
2.5.2 Multi-input no. 7The available menus for multi-input no. 7 depend on the input type configured in the PC utilitysoftware (menu 10990).
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4250 4-20 mA 7.14251 4-20
mA 7.1Setpoint
4 mA20 mA
10 mA DesignersReferenceHandbook
The multi-input 7 has beenconfigured as 4-20 mA.
4252 4-20mA 7.1
Timer 0.0 s999.0 s
120.0 s
4253 4-20mA 7.1
Relayoutput A
Not usedOption-dep.
Notused
4254 4-20mA 7.1
Relayoutput B
Not usedOption-dep.
Notused
4255 4-20mA 7.1
Enable OFFON
OFF
4256 4-20mA 7.1
Failclass
F1F8 Warning(F2)
4260 4-20 mA 7.24261 4-20
mA 7.2Setpoint
4 mA20 mA
10 mA DesignersReferenceHandbook
The multi-input 7 has beenconfigured as 4-20 mA.
4262 4-20mA 7.2
Timer 0.0 s999.0 s
120.0 s
4263 4-20mA 7.2
Relayoutput A
Not usedOption-dep.
Notused
4264 4-20mA 7.2
Relayoutput B
Not usedOption-dep.
Notused
4265 4-20mA 7.2
Enable OFFON
OFF
4266 4-20mA 7.2
Failclass
F1F8 Warning(F2)
4290 Pt100/Pt1000 7.14291 PT 7.1 Set
point-49482
80 DesignersReferenceHandbook
The multi-input 7 has beenconfigured as Pt100 orPt1000.4292 PT 7.1 Timer 0.0 s
999.0 s5.0 s
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 37 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4293 PT 7.1 Relayoutput A
Not usedOption-dep.
Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).
Notused
4294 PT 7.1 Relayoutput B
Not usedOption-dep.
Notused
4295 PT 7.1 Enable OFFON
OFF
4296 PT 7.1 Failclass
F1F8 Warning(F2)
4297 PT 7.1 Offset 0.0 Ohm5.0 Ohm
0.0 Ohm
4300 Pt100/Pt1000 7.24301 PT 7.2 Set
point-49482
80 DesignersReferenceHandbook
The multi-input 7 has beenconfigured as Pt100 orPt1000.Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).
4302 PT 7.2 Timer 0.0 s999.0 s
10.0 s
4303 PT 7.2 Relayoutput A
Not usedOption-dep.
Notused
4304 PT 7.2 Relayoutput B
Not usedOption-dep.
Notused
4305 PT 7.2 Enable OFFON
OFF
4306 PT 7.2 Failclass
F1...F8 Warning(F2)
4310 Resistance measurement input, oil pressure 7.14311 RMI oil
7.1Setpoint
0.0145.0
2.0 DesignersReferenceHandbook
The multi-input 7 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).
4312 RMI oil7.1
Timer 0.0 s999.0 s
5.0 s
4313 RMI oil7.1
Relayoutput A
Not usedOption-dep.
Notused
4314 RMI oil7.1
Relayoutput B
Not usedOption-dep.
Notused
4315 RMI oil7.1
Enable OFFON
OFF
4316 RMI oil7.1
Failclass
F1F8 Warning(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 38 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4320 Resistance measurement input, oil pressure 7.24321 RMI oil
7.2Setpoint
0.0145.0
1.0 DesignersReferenceHandbook
The multi-input 7 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).
4322 RMI oil7.2
Timer 0.0 s999.0 s
5.0 s
4323 RMI oil7.2
Relayoutput A
Not usedOption-dep.
Notused
4324 RMI oil7.2
Relayoutput B
Not usedOption-dep.
Notused
4325 RMI oil7.2
Enable OFFON
OFF
4326 RMI oil7.2
Failclass
F1F8 Shut-down(F5)
4330 Resistance measurement input, water temperature 7.14331 RMI
water7.1
Setpoint
-49482
100 DesignersReferenceHandbook
The multi-input 7 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection(menu 10970).
4332 RMIwater7.1
Timer 0.0 s999.0 s
5.0 s
4333 RMIwater7.1
Relayoutput A
Not usedOption-dep.
Notused
4334 RMIwater7.1
Relayoutput B
Not usedOption-dep.
Notused
4335 RMIwater7.1
Enable OFFON
OFF
4336 RMIwater7.1
Failclass
F1F8 Warning(F2)
4340 Resistance measurement input, water temperature 7.24341 RMI
water7.2
Setpoint
-49482
110 DesignersReferenceHandbook
The multi-input 7 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection(menu 10970).
4342 RMIwater7.2
Timer 0.0 s999.0 s
5.0 s
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 39 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4343 RMIwater7.2
Relayoutput A
Not usedOption-dep.
Notused
4344 RMIwater7.2
Relayoutput B
Not usedOption-dep.
Notused
4345 RMIwater7.2
Enable OFFON
OFF
4346 RMIwater7.2
Failclass
F1F8 Trip +Stop(F4)
4350 Resistance measurement input, fuel level 7.14351 RMI
fuel 7.1Setpoint
0 %100 %
10 % DesignersReferenceHandbook
The multi-input 7 has beenconfigured as RMI fuel level.
4352 RMIfuel 7.1
Timer 0.0 s999.0 s
10.0 s
4353 RMIfuel 7.1
Relayoutput A
Not usedOption-dep.
Notused
4354 RMIfuel 7.1
Relayoutput B
Not usedOption-dep.
Notused
4555 RMIfuel 7.1
Enable OFFON
OFF
4356 RMIfuel 7.1
Failclass
F1F8 Warning(F2)
4360 Resistance measurement input, fuel level 7.24361 RMI
fuel 7.2Setpoint
0 %100 %
5 % DesignersReferenceHandbook
The multi-input 7 has beenconfigured as RMI fuel level.
4362 RMIfuel 7.2
Timer 0.0 s999.0 s
10.0 s
4363 RMIfuel 7.2
Relayoutput A
Not usedOption-dep.
Notused
4364 RMIfuel 7.2
Relayoutput B
Not usedOption-dep.
Notused
4365 RMIfuel 7.2
Enable OFFON
OFF
4366 RMIfuel 7.2
Failclass
F1F8 Warning(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 40 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4370 Wire fail 74371 W. fail
7Relayoutput A
Not usedOption-dep.
Notused
DesignersReferenceHandbook
The wire break fault detectionis activated.
4372 W. fail7
Relayoutput B
Not usedOption-dep.
Notused
4373 W. fail7
Enable OFFON
OFF
4374 W. fail7
Failclass
F1F8 Warning(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 41 of 98
2.5.3 Multi-input no. 8The available menus for multi-input no. 8 depend on the input type configured in the PC utilitysoftware (menu 11000).
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4380 4-20 mA 8.14381 4-20
mA 8.1Setpoint
4 mA20 mA
10 mA DesignersReferenceHandbook
The multi-input 8 has beenconfigured as 4-20 mA.
4382 4-20mA 8.1
Timer 0.0 s999.0 s
120.0 s
4383 4-20mA 8.1
Relayoutput A
Not usedOption-dep.
Notused
4384 4-20mA 8.1
Relayoutput B
Not usedOption-dep.
Notused
4385 4-20mA 8.1
Enable OFFON
OFF
4386 4-20mA 8.1
Failclass
F1F8 Warning(F2)
4390 4-20 mA 8.24391 4-20
mA 8.2Setpoint
4 mA20 mA
10 mA DesignersReferenceHandbook
The multi-input 8 has beenconfigured as 4-20 mA.
4392 4-20mA 8.2
Timer 0.0 s999.0 s
120.0 s
4393 4-20mA 8.2
Relayoutput A
Not usedOption-dep.
Notused
4394 4-20mA 8.2
Relayoutput B
Not usedOption-dep.
Notused
4395 4-20mA 8.2
Enable OFFON
OFF
4396 4-20mA 8.2
Failclass
F1F8 Warning(F2)
4420 Pt100/Pt1000 8.14421 PT 8.1 Set
point-49482
80 DesignersReferenceHandbook
The multi-input 8 has beenconfigured as Pt100 orPt1000.4422 PT 8.1 Timer 0.0 s
999.0 s5.0 s
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 42 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4423 PT 8.1 Relayoutput A
Not usedOption-dep.
Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).
Notused
4424 PT 8.1 Relayoutput B
Not usedOption-dep.
Notused
4425 PT 8.1 Enable OFFON
OFF
4426 PT 8.1 Failclass
F1F8 Warning(F2)
4427 PT 8.1 Offset 0.0 Ohm5.0 Ohm
0.0 Ohm
4430 Pt100/Pt1000 8.24431 PT 8.2 Set
point-49482
80 DesignersReferenceHandbook
The multi-input 8 has beenconfigured as Pt100 orPt1000.Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).
4432 PT 8.2 Timer 0.0 s999.0 s
10.0 s
4433 PT 8.2 Relayoutput A
Not usedOption-dep.
Notused
4434 PT 8.2 Relayoutput B
Not usedOption-dep.
Notused
4435 PT 8.2 Enable OFFON
OFF
4436 PT 8.2 Failclass
F1...F8 Warning(F2)
4440 Resistance measurement input, oil pressure 8.14441 RMI oil
8.1Setpoint
0.0145.0
2.0 DesignersReferenceHandbook
The multi-input 8 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).
4442 RMI oil8.1
Timer 0.0 s999.0 s
5.0 s
4443 RMI oil8.1
Relayoutput A
Not usedOption-dep.
Notused
4444 RMI oil8.1
Relayoutput B
Not usedOption-dep.
Notused
4445 RMI oil8.1
Enable OFFON
OFF
4446 RMI oil8.1
Failclass
F1F8 Warning(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 43 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4450 Resistance measurement input, oil pressure 8.24451 RMI oil
8.2Setpoint
0.0145.0
1.0 DesignersReferenceHandbook
The multi-input 8 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).
4452 RMI oil8.2
Timer 0.0 s999.0 s
5.0 s
4453 RMI oil8.2
Relayoutput A
Not usedOption-dep.
Notused
4454 RMI oil8.2
Relayoutput B
Not usedOption-dep.
Notused
4455 RMI oil8.2
Enable OFFON
OFF
4456 RMI oil8.2
Failclass
F1F8 Shut-down(F5)
4460 Resistance measurement input, water temperature 8.14461 RMI
water8.1
Setpoint
-49482
100 DesignersReferenceHandbook
The multi-input 8 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection(menu 10970).
4462 RMIwater8.1
Timer 0.0 s999.0 s
5.0 s
4463 RMIwater8.1
Relayoutput A
Not usedOption-dep.
Notused
4464 RMIwater8.1
Relayoutput B
Not usedOption-dep.
Notused
4465 RMIwater8.1
Enable OFFON
OFF
4466 RMIwater8.1
Failclass
F1F8 Warning(F2)
4470 Resistance measurement input, water temperature 8.24471 RMI
water8.2
Setpoint
-49482
110 DesignersReferenceHandbook
The multi-input 8 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection(menu 10970).
4472 RMIwater8.2
Timer 0.0 s999.0 s
5.0 s
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 44 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4473 RMIwater8.2
Relayoutput A
Not usedOption-dep.
Notused
4474 RMIwater8.2
Relayoutput B
Not usedOption-dep.
Notused
4475 RMIwater8.2
Enable OFFON
OFF
4476 RMIwater8.2
Failclass
F1F8 Trip +Stop(F4)
4480 Resistance measurement input, fuel level 8.14481 RMI
fuel 8.1Setpoint
0 %100 %
10 % DesignersReferenceHandbook
The multi-input 8 has beenconfigured as RMI fuel level.
4482 RMIfuel 8.1
Timer 0.0 s999.0 s
10.0 s
4483 RMIfuel 8.1
Relayoutput A
Not usedOption-dep.
Notused
4484 RMIfuel 8.1
Relayoutput B
Not usedOption-dep.
Notused
4485 RMIfuel 8.1
Enable OFFON
OFF
4486 RMIfuel 8.1
Failclass
F1F8 Warning(F2)
4490 Resistance measurement input, fuel level 8.24491 RMI
fuel 8.2Setpoint
0 %100 %
5 % DesignersReferenceHandbook
The multi-input 8 has beenconfigured as RMI fuel level.
4492 RMIfuel 8.2
Timer 0.0 s999.0 s
10.0 s
4493 RMIfuel 8.2
Relayoutput A
Not usedOption-dep.
Notused
4494 RMIfuel 8.2
Relayoutput B
Not usedOption-dep.
Notused
4495 RMIfuel 8.2
Enable OFFON
OFF
4496 RMIfuel 8.2
Failclass
F1F8 Warning(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 45 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4500 Wire fail 84501 W. fail
8Relayoutput A
Not usedOption-dep.
Notused
DesignersReferenceHandbook
The wire break fault detectionis activated.
4502 W. fail8
Relayoutput B
Not usedOption-dep.
Notused
4503 W. fail8
Enable OFFON
OFF
4504 W. fail8
Failclass
F1F8 Warning(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 46 of 98
2.5.4 Speed and running feedback setupNo. Setting Min.
Max.Factorysetting
Notes Ref. Description
4510 Overspeed 14511 Over-
speed 1Setpoint
100.0 %150.0 %
110.0 % DesignersReferenceHandbook
The set point in percentagerelates to nominal RPM.
4512 Over-speed 1
Timer 0.0 s100.0 s
5.0 s
4513 Over-speed 1
RelayoutputA
Not usedOption-dep.
Notused
4514 Over-speed 1
RelayoutputB
Not usedOption-dep.
Notused
4515 Over-speed 1
Enable OFFON
OFF
4516 Over-speed 1
Failclass
F1F8 Warn-ing(F2)
4520 Overspeed 24521 Over-
speed 2Setpoint
100.0 %150.0 %
120.0 % DesignersReferenceHandbook
The set point in percentagerelates to nominal RPM.
4522 Over-speed 2
Timer 0.0 s100.0 s
1.0 s
4523 Over-speed 2
RelayoutputA
Not usedOption-dep.
Notused
4524 Over-speed 2
RelayoutputB
Not usedOption-dep.
Notused
4525 Over-speed 2
Enable OFFON
OFF
4526 Over-speed 2
Failclass
F1F8 Shut-down(F5)
4530 Crank failure4531 Crank
failureSetpoint
1 RPM400 RPM
50 RPM DesignersReferenceHandbook
If MPU is chosen as the pri-mary running feedback, thisalarm will be raised if thespecified RPM is not reachedbefore the delay has expired.
4532 Crankfailure
Timer 0.0 s20.0 s
2.0 s
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 47 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4533 Crankfailure
RelayoutputA
Not usedOption-dep.
Notused
4534 Crankfailure
RelayoutputB
Not usedOption-dep.
Notused
4535 Crankfailure
Enable OFFON
OFF
4536 Crankfailure
Failclass
F1F8 Warn-ing(F2)
4540 Running feedback failure4541 Run
feedb.fail
Timer 0.0 s20.0 s
2.0 s DesignersReferenceHandbook
If running is detected on thefrequency (secondary), butthe primary running feedback,e.g. digital input, has not de-tected running, this alarm willbe raised after the adjusteddelay time.
4542 Runfeedb.fail
RelayoutputA
Not usedOption-dep.
Notused
4543 Runfeedb.fail
RelayoutputB
Not usedOption-dep.
Notused
4544 Runfeedb.fail
Enable OFFON
ON
4545 Runfeedb.fail
Failclass
F1...F8 Warn-ing(F2)
4560 Hz/voltage failure4561 Hz/V fail-
ureTimer 1.0 s
99.0 s30.0 s Designers
ReferenceHandbook
If the frequency and voltageare not within the limits afterthe running feedback is re-ceived, this alarm will beraised when the delay timehas expired. Limits are placedin menu 2110 (Sync. black-out).
4562 Hz/V fail-ure
RelayoutputA
Not usedOption-dep.
Notused
4563 Hz/V fail-ure
RelayoutputB
Not usedOption-dep.
Notused
4564 Hz/V fail-ure
Enable OFFON
ON
4565 Hz/V fail-ure
Failclass
F1...F8 Shut-down(F5)
4570 Start failure
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 48 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4571 Start fail-ure
RelayoutputA
Not usedOption-dep.
Notused
DesignersReferenceHandbook
The start failure alarm occursif the genset has not startedafter the number of start at-tempts.4572 Start fail-
ureRelayoutputB
Not usedOption-dep.
Notused
4573 Start fail-ure
Failclass
F1F8 Block(F1)
4580 Stop failure4581 Stop fail-
ureTimer 10.0 s
120.0 s30.0 s Designers
ReferenceHandbook
A stop failure alarm will ap-pear if the primary runningfeedback or the generatorvoltage and frequency are stillpresent after the delay timehas expired.
4582 Stop fail-ure
RelayoutputA
Not usedOption-dep.
Notused
4583 Stop fail-ure
RelayoutputB
Not usedOption-dep.
Notused
4584 Stop fail-ure
Enable OFFON
ON
4585 Stop fail-ure
Failclass
F1F8 Shut-down(F5)
4590 Underspeed 14591 Under-
speedSetpoint
50.0 %100.0 %
90.0 % DesignersReferenceHandbook
The set point in percentagerelates to nominal RPM.
4592 Under-speed
Timer 0.0 s100.0 s
5.0 s
4593 Under-speed
RelayoutputA
Not usedOption-dep.
Notused
4594 Under-speed
RelayoutputB
Not usedOption-dep.
Notused
4595 Under-speed
Enable OFFON
OFF
4596 Under-speed
Failclass
F1F8 Warn-ing(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 49 of 98
2.5.5 Differential measurementNo. Setting Min.
Max.Factorysetting
Notes Ref. Description
4600 Delta ana 1/2/3 Inp4601 Delta
ana1 InpASet point Multi-input
6EIC
Multi-in-put 6
Designers Ref-erence Hand-book
Delta analogue Inp1/2/3 setting.Choose betweenmulti-inputs, externalanalogue inputs andEIC values
4602 Deltaana1 InpB
Set point Multi-input6EIC
Multi-in-put 6
4603 Deltaana2 InpA
Set point Multi-input6EIC
Multi-in-put 6
4604 Deltaana2 InpB
Set point Multi-input6EIC
Multi-in-put 6
4605 Deltaana3 InpA
Set point Multi-input6EIC
Multi-in-put 6
4606 Deltaana3 InpB
Set point Multi-input6EIC
Multi-in-put 6
4610 Delta ana1 14611 Delta
ana1 1Set point -9999
999910 Designers Ref-
erence Hand-book
Delta analogue alarmsetting 1.1
4612 Deltaana1 1
Timer 0.0 s999.0 s
5.0 s
4613 Deltaana1 1
Relayoutput A
Not usedOption-dep.
Not used
4614 Deltaana1 1
Relayoutput B
Not usedOption-dep.
Not used
4615 Deltaana1 1
Enable OFFON
OFF
4616 Deltaana1 1
Failclass
F1F8 Warning(F2)
4620 Delta ana1 24621 Delta
ana1 2Set point -9999
999910 Designers Ref-
erence Hand-book
Delta analogue alarmsetting 1.2
4622 Deltaana1 2
Timer 0.0 s999.0 s
5.0 s
4623 Deltaana1 2
Relayoutput A
Not usedOption-dep.
Not used
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 50 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4624 Deltaana1 2
Relayoutput B
Not usedOption-dep.
Not used
4625 Deltaana1 2
Enable OFFON
OFF
4626 Deltaana1 2
Failclass
F1F8 Warning(F2)
4630 Delta ana2 14631 Delta
ana2 1Set point -9999
999910 Designers Ref-
erence Hand-book
Delta analogue alarmsetting 2.1
4632 Deltaana2 1
Timer 0.0 s999.0 s
5.0 s
4633 Deltaana2 1
Relayoutput A
Not usedOption-dep.
Not used
4634 Deltaana2 1
Relayoutput B
Not usedOption-dep.
Not used
4635 Deltaana2 1
Enable OFFON
OFF
4636 Deltaana2 1
Failclass
F1F8 Warning(F2)
4640 Delta ana2 24641 Delta
ana2 2Set point -9999
99910 Designers Ref-
erence Hand-book
Delta analogue alarmsetting 2.2
4642 Deltaana2 2
Timer 0.0 s999.0 s
5.0 s
4643 Deltaana2 2
Relayoutput A
Not usedOption-dep.
Not used
4644 Deltaana2 2
Relayoutput B
Not usedOption-dep.
Not used
4645 Deltaana2 2
Enable OFFON
OFF
4646 Deltaana2 2
Failclass
F1...F8 Warning(F2)
4650 Delta ana3 14651 Delta
ana3 1Set point -9999
999910 Designers Ref-
erence Hand-book
Delta analogue alarmsetting 3.1
4652 Deltaana3 1
Timer 0.0 s999.0 s
5.0 s
4653 Deltaana3 1
Relayoutput A
Not usedOption-dep.
Not used
4654 Deltaana3 1
Relayoutput B
Not usedOption-dep.
Not used
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 51 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4655 Deltaana3 1
Enable OFFON
OFF
4656 Deltaana3 1
Failclass
F1...F8 Warning(F2)
4660 Delta ana3 24661 Delta
ana3 2Set point -9999
999910 Designers Ref-
erence Hand-book
Delta analogue alarmsetting 3.2
4662 Deltaana3 2
Timer 0.0 s999.0 s
5.0 s
4663 Deltaana3 2
Relayoutput A
Not usedOption-dep.
Not used
4664 Deltaana3 2
Relayoutput B
Not usedOption-dep.
Not used
4665 Deltaana3 2
Enable OFFON
OFF
4666 Deltaana3 2
Failclass
F1...F8 Warning(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 52 of 98
2.5.6 Aux. supply setupNo. Setting Min.
Max.Factorysetting
Notes Ref. Description
4960 U< auxiliary power supply terminal 14961 U< aux.
term. 1Setpoint
8.0 Vdc32.0 Vdc
18.0 Vdc DesignersReferenceHandbook
The power supply on terminal1 and 2 has been continu-ously below the adjusted setpoint during the programmeddelay.
4962 U< aux.term. 1
Timer 10.0 s999.0 s
10.0 s
4963 U< aux.term. 1
Relayoutput A
Not usedOption-dep.
Not used
4964 U< aux.term. 1
Relayoutput B
Not usedOption-dep.
Not used
4965 U< aux.term. 1
Enable OFFON
ON
4966 U< aux.term. 1
Failclass
F1F8 Warning(F2)
4970 U> auxiliary power supply terminal 14971 U> aux.
term. 1Setpoint
12.0 Vdc36.0 Vdc
30.0 Vdc DesignersReferenceHandbook
The power supply on terminal1 and 2 has been continu-ously above the adjusted setpoint during the programmeddelay.
4972 U> aux.term. 1
Timer 10.0 s999.0 s
10.0 s
4973 U> aux.term. 1
Relayoutput A
Not usedOption-dep.
Not used
4974 U> aux.term. 1
Relayoutput B
Not usedOption-dep.
Not used
4975 U> aux.term. 1
Enable OFFON
ON
4976 U> aux.term. 1
Failclass
F1F8 Warning(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 53 of 98
2.5.7 Multi-input no. 58The available menus for multi-input no. 58 depend on the input type configured in the PC utilitysoftware (menu 11300).
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4740 Digital input 584741 Dig. in-
put 58Enable OFF
ONOFF Designers
ReferenceHandbook
The input is configurable andcan have different functions indifferent units.The multi-input 58 has beenconfigured as Binary.
4742 Dig. in-put 58
Timer 0.0 s999.0 s
10.0 s
4743 Dig. in-put 58
RelayoutputA
Not usedOption-dep.
Notused
4744 Dig. in-put 58
RelayoutputB
Not usedOption-dep.
Notused
4745 Dig. in-put 58
Enable OFFON
OFF
4746 Dig. in-put 58
Failclass
F1F8 Warning(F2)
4740 4-20 mA 58.14741 4-20
mA58.1
Setpoint
4 mA20 mA
10 mA DesignersReferenceHandbook
The multi-input 58 has beenconfigured as 4-20 mA.
4742 4-20mA58.1
Timer 0.0 s999.0 s
120.0 s
4743 4-20mA58.1
RelayoutputA
Not usedOption-dep.
Notused
4744 4-20mA58.1
RelayoutputB
Not usedOption-dep.
Notused
4745 4-20mA58.1
Enable OFFON
OFF
4746 4-20mA58.1
Failclass
F1F8 Warning(F2)
4750 4-20 mA 58.2
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 54 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4751 4-20mA58.2
Setpoint
4 mA20 mA
10 mA DesignersReferenceHandbook
The multi-input 58 has beenconfigured as 4-20 mA.
4752 4-20mA58.2
Timer 0.0 s999.0 s
120.0 s
4753 4-20mA58.2
RelayoutputA
Not usedOption-dep.
Notused
4754 4-20mA58.2
RelayoutputB
Not usedOption-dep.
Notused
4755 4-20mA58.2
Enable OFFON
OFF
4756 4-20mA58.2
Failclass
F1F8 Warning(F2)
4740 Pt100/Pt1000 58.14741 PT
58.1Setpoint
-49482
80 DesignersReferenceHandbook
The multi-input 58 has beenconfigured as Pt100 orPt1000.Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).
4742 PT58.1
Timer 0.0 s999.0 s
5.0 s
4743 PT58.1
RelayoutputA
Not usedOption-dep.
Notused
4744 PT58.1
RelayoutputB
Not usedOption-dep.
Notused
4745 PT58.1
Enable OFFON
OFF
4746 PT58.1
Failclass
F1F8 Warning(F2)
4750 Pt100/Pt1000 58.24751 PT
58.2Setpoint
-49482
80 DesignersReferenceHandbook
The multi-input 58 has beenconfigured as Pt100 orPt1000.Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).
4752 PT58.2
Timer 0.0 s999.0 s
10.0 s
4753 PT58.2
RelayoutputA
Not usedOption-dep.
Notused
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 55 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4754 PT58.2
RelayoutputB
Not usedOption-dep.
Notused
4755 PT58.2
Enable OFFON
OFF
4756 PT58.2
Failclass
F1...F8 Warning(F2)
4740 Resistance measurement input, oil pressure 58.14741 RMI oil
58.1Setpoint
0.0145.0
2.0 DesignersReferenceHandbook
The multi-input 58 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).
4742 RMI oil58.1
Timer 0.0 s999.0 s
5.0 s
4743 RMI oil58.1
RelayoutputA
Not usedOption-dep.
Notused
4744 RMI oil58.1
RelayoutputB
Not usedOption-dep.
Notused
4745 RMI oil58.1
Enable OFFON
OFF
4746 RMI oil58.1
Failclass
F1F8 Warning(F2)
4750 Resistance measurement input, oil pressure 58.24751 RMI oil
58.2Setpoint
0.0145.0
1.0 DesignersReferenceHandbook
The multi-input 58 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).
4752 RMI oil58.2
Timer 0.0 s999.0 s
5.0 s
4753 RMI oil58.2
RelayoutputA
Not usedOption-dep.
Notused
4754 RMI oil58.2
RelayoutputB
Not usedOption-dep.
Notused
4755 RMI oil58.2
Enable OFFON
OFF
4756 RMI oil58.2
Failclass
F1F8 Shut-down(F5)
4740 Resistance measurement input, water temperature 58.14741 RMI
water58.1
Setpoint
-49482
100 DesignersReferenceHandbook
The multi-input 58 has beenconfigured as RMI water tem-perature.
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 56 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4742 Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection (menu10970).
RMIwater58.1
Timer 0.0 s999.0 s
5.0 s
4743 RMIwater58.1
RelayoutputA
Not usedOption-dep.
Notused
4744 RMIwater58.1
RelayoutputB
Not usedOption-dep.
Notused
4745 RMIwater58.1
Enable OFFON
OFF
4746 RMIwater58.1
Failclass
F1F8 Warning(F2)
4750 Resistance measurement input, water temperature 58.24751 RMI
water58.2
Setpoint
-49482
110 DesignersReferenceHandbook
The multi-input 58 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection (menu10970).
4752 RMIwater58.2
Timer 0.0 s999.0 s
5.0 s
4753 RMIwater58.2
RelayoutputA
Not usedOption-dep.
Notused
4754 RMIwater58.2
RelayoutputB
Not usedOption-dep.
Notused
4755 RMIwater58.2
Enable OFFON
OFF
4756 RMIwater58.2
Failclass
F1F8 Trip +Stop(F4)
4740 Resistance measurement input, fuel level 58.14741 RMI
fuel58.1
Setpoint
0 %100 %
10 % DesignersReferenceHandbook
The multi-input 58 has beenconfigured as RMI fuel level.
4742 RMIfuel58.1
Timer 0.0 s999.0 s
10.0 s
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 57 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4743 RMIfuel58.1
RelayoutputA
Not usedOption-dep.
Notused
4744 RMIfuel58.1
RelayoutputB
Not usedOption-dep.
Notused
4745 RMIfuel58.1
Enable OFFON
OFF
4746 RMIfuel58.1
Failclass
F1F8 Warning(F2)
4750 Resistance measurement input, fuel level 58.24751 RMI
fuel58.2
Setpoint
0 %100 %
5 % DesignersReferenceHandbook
The multi-input 58 has beenconfigured as RMI fuel level.
4752 RMIfuel58.2
Timer 0.0 s999.0 s
10.0 s
4753 RMIfuel58.2
RelayoutputA
Not usedOption-dep.
Notused
4754 RMIfuel58.2
RelayoutputB
Not usedOption-dep.
Notused
4755 RMIfuel58.2
Enable OFFON
OFF
4756 RMIfuel58.2
Failclass
F1F8 Warning(F2)
4760 Wire fail 584761 W. fail
58RelayoutputA
Not usedOption-dep.
Notused
DesignersReferenceHandbook
The wire break fault detectionis activated.
4762 W. fail58
RelayoutputB
Not usedOption-dep.
Notused
4763 W. fail58
Enable OFFON
OFF
4764 W. fail58
Failclass
F1F8 Warning(F2)
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 58 of 98
2.5.8 Multi-input no. 59The available menus for multi-input no. 59 depend on the input type configured in the PC utilitysoftware (menu 11310).
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4770 Digital input 594771 Dig. in-
put 59Enable OFF
ONOFF Designers
ReferenceHandbook
The input is configurable andcan have different functions indifferent units.The multi-input 59 has beenconfigured as Binary.
4772 Dig. in-put 59
Timer 0.0 s999.0 s
10.0 s
4773 Dig. in-put 59
RelayoutputA
Not usedOption-dep.
Notused
4774 Dig. in-put 59
RelayoutputB
Not usedOption-dep.
Notused
4775 Dig. in-put 59
Enable OFFON
OFF
4776 Dig. in-put 59
Failclass
F1F8 Warning(F2)
4770 4-20 mA 59.14771 4-20
mA59.1
Setpoint
4 mA20 mA
10 mA DesignersReferenceHandbook
The multi-input 59 has beenconfigured as 4-20 mA.
4772 4-20mA59.1
Timer 0.0 s999.0 s
120.0 s
4773 4-20mA59.1
RelayoutputA
Not usedOption-dep.
Notused
4774 4-20mA59.1
RelayoutputB
Not usedOption-dep.
Notused
4775 4-20mA59.1
Enable OFFON
OFF
4776 4-20mA59.1
Failclass
F1F8 Warning(F2)
4780 4-20 mA 59.2
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 59 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4781 4-20mA59.2
Setpoint
4 mA20 mA
10 mA DesignersReferenceHandbook
The multi-input 59 has beenconfigured as 4-20 mA.
4782 4-20mA59.2
Timer 0.0 s999.0 s
120.0 s
4783 4-20mA59.2
RelayoutputA
Not usedOption-dep.
Notused
4784 4-20mA59.2
RelayoutputB
Not usedOption-dep.
Notused
4785 4-20mA59.2
Enable OFFON
OFF
4786 4-20mA59.2
Failclass
F1F8 Warning(F2)
4770 Pt100/Pt1000 59.14771 PT
59.1Setpoint
-49482
80 DesignersReferenceHandbook
The multi-input 59 has beenconfigured as Pt100 orPt1000.Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).
4772 PT59.1
Timer 0.0 s999.0 s
5.0 s
4773 PT59.1
RelayoutputA
Not usedOption-dep.
Notused
4774 PT59.1
RelayoutputB
Not usedOption-dep.
Notused
4775 PT59.1
Enable OFFON
OFF
4776 PT59.1
Failclass
F1F8 Warning(F2)
4780 Pt100/Pt1000 59.24781 PT
59.2Setpoint
-49482
80 DesignersReferenceHandbook
The multi-input 59 has beenconfigured as Pt100 orPt1000.Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).
4782 PT59.2
Timer 0.0 s999.0 s
10.0 s
4783 PT59.2
RelayoutputA
Not usedOption-dep.
Notused
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 60 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4784 PT59.2
RelayoutputB
Not usedOption-dep.
Notused
4785 PT59.2
Enable OFFON
OFF
4786 PT59.2
Failclass
F1...F8 Warning(F2)
4770 Resistance measurement input, oil pressure 59.14771 RMI oil
59.1Setpoint
0.0145.0
2.0 DesignersReferenceHandbook
The multi-input 59 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).
4772 RMI oil59.1
Timer 0.0 s999.0 s
5.0 s
4773 RMI oil59.1
RelayoutputA
Not usedOption-dep.
Notused
4774 RMI oil59.1
RelayoutputB
Not usedOption-dep.
Notused
4775 RMI oil59.1
Enable OFFON
OFF
4776 RMI oil59.1
Failclass
F1F8 Warning(F2)
4780 Resistance measurement input, oil pressure 59.24781 RMI oil
59.2Setpoint
0.0145.0
1.0 DesignersReferenceHandbook
The multi-input 59 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).
4782 RMI oil59.2
Timer 0.0 s999.0 s
5.0 s
4783 RMI oil59.2
RelayoutputA
Not usedOption-dep.
Notused
4784 RMI oil59.2
RelayoutputB
Not usedOption-dep.
Notused
4785 RMI oil59.2
Enable OFFON
OFF
4786 RMI oil59.2
Failclass
F1F8 Shut-down(F5)
4770 Resistance measurement input, water temperature 59.14771 RMI
water59.1
Setpoint
-49482
100 DesignersReferenceHandbook
The multi-input 59 has beenconfigured as RMI water tem-perature.
CGC 400 parameter list 4189340789 UK Alarm list
DEIF A/S Page 61 of 98
No. Setting Min.Max.
Factorysetting
Notes Ref. Description
4772 Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection (menu10970).
RMIwater59.1
Timer 0.0 s999.0 s
5.0 s
4773 RMIwater59.1
RelayoutputA
Not usedOption-dep.
Notused
4774 RMIwater59.1
RelayoutputB
Not usedOption-dep.
Notused
4775 RMIwater59.1
Enable OFFON
OFF
4776 RMIwater59.1
Failclass
F1F8 Warning(F2)
4780 Resistance measurement input, water temperature 59.24781 RMI
water59.2
Setpoint
-49482
110 DesignersReferenceHandbook
The multi-input 59 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection (menu10970).
4782 RMIwater59.2
Timer 0.0 s999.0 s
5.0 s
4783 RMIwater59.2
RelayoutputA
Not usedOption-dep.
Notused
4784 RMIwater59.2
RelayoutputB
Not usedOption-dep.