Spectronic Air Circuit Breaker Operating Instructions RMS10, RMS12 RMS7 S800 - 2500 / S3200 - 4000

Transcript of Spectronic Air Circuit Breaker Operating Instructions · Spectronic Air Circuit Breaker - Operating...

Spectronic Air Circuit Breaker Operating Instructions

ProtectionRMS7 Trip• If the circuit breaker is to be reset in local mode,it must be reset manually after an overcurrentcondition by pushing in fully the local trip pushbutton 13.

Description :Powered by the current transformers, lmax = 4000, the RMS7 unitperforms all the necessary current protections with true rms value sensing:• overload protection (LT)• short-circuit protection (ST and I)• ground fault protection (GF) (The 4th (neutral) current transformer must be of the same rating as those of the three phases).

RMS7 : OptionsThe following options are field fittable

Distinct Fault Signalling (LT, ST, I, GF)• Local indication by LED display. this option is power supplied by an internal battery.• Lead sealing.

Setting Ranges Setting Points

LT (x ln) 0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.00

LTD (s) 5, 10, 15, 20, 25, 30, 35, 40 delay at 7.2 lr

ST (x ln) 1.5, 2, 3, 4, 5, 7, 9, 10, 12, 14

Delay (ms) 30, 60, 90, 120, 150, 180, 210, 240, 270, 300

I (x ln) 1.5, 2, 3, 5, 7, 10, 15, OFF

GF (x ln) 0.20, 0.30, 0.40, 0.50, 0.60, 0.70, 0.80 for 800 to 2000A

0.20, 0.30, 0.35, 0.45, 0.55, 0.60, 0.70 2500A

0.20, 0.30, 0.35, 0.45 for 3200 to 4000A

Delay (ms) 100, 200, 300

lr = k x ln

X = In (Nominal rating or

value of rating plug indications reproduced on the calibrator

S = Sensor rating

12

RMS 7: Protection Unit

���

RMS10, RMS12 RMS7 S800 - 2500 / S3200 - 4000

Spectronic Air Circuit Breaker - Operating Instructions

201

Table of contentsRECEIPT OF EQUIPMENT S800-2500A / S3200-4000A

- Arrival ........................................................................................................................................................................................................................ 3- Storage ..................................................................................................................................................................................................................... 3- Unpacking ............................................................................................................................................................................................................... 3

IDENTIFICATION- S800-2500-3200-4000 ..................................................................................................................................................................................... 4 - 5

INSTALLATION- Fixed Breaker S800-2500 ................................................................................................................................................................................ 6- Withdrawable Breaker S800-2500 ............................................................................................................................................................. 7- Fixed Breaker S3200-4000 .............................................................................................................................................................................. 8- Withdrawable Breaker S3200-4000 ........................................................................................................................................................... 9

COMMISSIONING-OPERATION- Circuit Breaker S-800-2500 / 3200-4000 ................................................................................................................................................ 10 - 11- Protection ............................................................................................................................................................................................................ 11- RMS7 : Protection Unit ....................................................................................................................................................................................... 12- RMS7 : Settings ..................................................................................................................................................................................................... 12 - 13- RMS7 : Distinct Fault Signalling Option ..................................................................................................................................................... 14- RMS7 : Time - Current Characteristics ....................................................................................................................................................... 15 - 16- RMS10, RMS12 : Protection and Measurement Unit ............................................ .............................................................................. 17- RMS10, RMS12 : Time - Current Characteristics ................................................................................................................................... 18 - 19- Cabling Diagram .................................................................................................................................................................................................. 20- LMZ7 : Protection Unit ....................................................................................................................................................................................... 21- RMS7 : Time - Current Characteristics ....................................................................................................................................................... 21- Voltmetric Releases ............................................................................................................................................................................................. 22- Inhibited Closing ................................................................................................................................................................................................... 22- Auxiliary Contacts ............................................................................................................................................................................................... 22- Faults Signalling Contacts and Indicator ................................................................................................................................................. 23- Interlocking ............................................................................................................................................................................................................ 24

MAINTENANCE - LUBRICATION .................................................................................................................................................................................................. 25

CHECKING - REPLACEMENT - ADAPTATION1A - Adjusting and Checking ....................................................................................................................................................... 262A - Arc Chute S800-2500 ........................................................................................................................................................... 263A - Spark Arresters S800-2500 ............................................................................................................................................... 264A - Arc Barrier S800-2500 ......................................................................................................................................................... 261C - Adjusting and Checking ....................................................................................................................................................... 272C - Arc Chute S3200-4000 ........................................................................................................................................................ 273C - Spark Arresters S3200-4000 ............................................................................................................................................. 275A - Current Transformers S800-2500 .................................................................................................................................. 286A - Pole Tightening ........................................................................................................................................................................ 285B - Current Transformers S3200-4000 ................................................................................................................................ 29

Protections Releases7 - Overcurrent Releases RMS7-RMS10, RMS12 ............................................................................................................. 308 - Trip Coil EX ................................................................................................................................................................................. 31 - 329A - Verification of Resetting S800-2500 .............................................................................................................................. 33 - 359B - Verification of Resetting S3200-4000 ........................................................................................................................... 33 - 3510 - Lead Sealing of RMS7 ........................................................................................................................................................... 36

Accessories11 - Voltmetric Releases ............................................................................................................................................................... 3712 - Auxiliary Contacts (Replacement) ................................................................................................................................... 38

Electrical Control13 - Motor (Replacement) ............................................................................................................................................................. 3914 - Resetting Limit Switch (Replacement) S3200-4000 ............................................................................................... 4015A - Resetting Spring Contact (Replacement) S800-2500 ............................................................................................ 4115B - Resetting Spring Contact (Replacement) S3200-4000 .......................................................................................... 41 - 42

Spectronic Air Circuit Breaker - Operating Instructions

3

01

Table of contentsRECEIPT OF EQUIPMENT S800-2500A / S3200-4000A

- Arrival ................................................................................................................................................................................................... ..................... 3

- Storage ..................................................................................................................................................................................................................... 3

- Unpacking ............................................................................................................................................................................................................... 3

IDENTIFICATION

- S800-2500-3200-4000 ..................................................................................................................................................................................... 4 - 5

INSTALLATION

- Fixed Breaker S800-2500 ................................................................................................................................................................................ 6

- Withdrawable Breaker S800-2500 ............................................................................................................................................................. 7

- Fixed Breaker S3200-4000 .............................................................................................................................................................................. 8

- Withdrawable Breaker S3200-4000 ........................................................................................................................................................... 9

COMMISSIONING-OPERATION

- Circuit Breaker S-800-2500 / 3200-4000 ................................................................................................................................................ 10 - 11

- Protection ............................................................................................................................................................................................................ 11

- RMS7 : Protection Unit ....................................................................................................................................................................................... 12

- RMS7 : Settings ..................................................................................................................................................................................................... 12 - 13

- RMS7 : Distinct Fault Signalling Option ..................................................................................................................................................... 14

- RMS7 : Time - Current Characteristics ....................................................................................................................................................... 15 - 16

- RMS9D : Protection and Measurement Unit ........................................................................................................................................... 17

- RMS9D : Time - Current Characteristics .................................................................................................................................................... 18 - 19

- Cabling Diagram .................................................................................................................................................................................................. 20

- LMZ7 : Protection Unit ....................................................................................................................................................................................... 21

- RMS7 : Time - Current Characteristics ....................................................................................................................................................... 21

- Voltmetric Releases ............................................................................................................................................................................................. 22

- Inhibited Closing ................................................................................................................................................................................................... 22

- Auxiliary Contacts ............................................................................................................................................................................................... 22

- Faults Signalling Contacts and Indicator ................................................................................................................................................. 23

- Interlocking .............................................................................................................................................................................................. .............. 24

MAINTENANCE - LUBRICATION .................................................................................................................................................................................................. 25

CHECKING - REPLACEMENT - ADAPTATION

1A - Adjusting and Checking ....................................................................................................................................................... 26

2A - Arc Chute S800-2500 ........................................................................................................................................................... 26

3A - Spark Arresters S800-2500 ............................................................................................................................................... 26

4A - Arc Barrier S800-2500 ......................................................................................................................................................... 26

1C - Adjusting and Checking ....................................................................................................................................................... 27

2C - Arc Chute S3200-4000 ........................................................................................................................................................ 27

3C - Spark Arresters S3200-4000 ............................................................................................................................................. 27

5A - Current Transformers S800-2500 .................................................................................................................................. 28

6A - Pole Tightening ........................................................................................................................................................................ 28

5B - Current Transformers S3200-4000 ................................................................................................................................ 29

Protections Releases

7 - Overcurrent Releases RMS7-RMS9D ............................................................................................................................. 30

8 - Trip Coil EX ................................................................................................................................................................................. 31 - 32

9A - Verification of Resetting S800-2500 .............................................................................................................................. 33 - 35

9B - Verification of Resetting S3200-4000 ........................................................................................................................... 33 - 35

10 - Lead Sealing of RMS7 ........................................................................................................................................................... 36

Accessories

11 - Voltmetric Releases ............................................................................................................................................................... 37

12 - Auxiliary Contacts (Replacement) ................................................................................................................................... 38

Electrical Control

13 - Motor (Replacement) ............................................................................................................................................................. 39

14 - Resetting Limit Switch (Replacement) S3200-4000 ............................................................................................... 40

15A - Resetting Spring Contact (Replacement) S800-2500 ............................................................................................ 41

15B - Resetting Spring Contact (Replacement) S3200-4000 .......................................................................................... 41 - 42

02

16A - Resetting Spring Contact (Adaptation) S800-2500 ................................................................................................ 42

16B - Resetting Spring Contact (Adaptation) S3200-4000 .............................................................................................. 43

17A - Closing Prevention Device (Replacement) S800-2500 .......................................................................................... 44

17B - Closing Prevention Device (Replacement) S3200-4000 ....................................................................................... 44 - 45

18A - Closing Coil (Replacement) S800-2500 ........................................................................................................................ 45

18B - Closing Coil (Replacement) S3200-4000 ..................................................................................................................... 46

19A - Insertion Contact (Replacement) S800-2500 ............................................................................................................ 46

19B - Insertion Contact (Replacement) S3200-4000 .......................................................................................................... 46

20A - Economy Resistor (Replacement) S800-2500 ........................................................................................................... 47

20B - Economy Resistor (Replacement) S3200-4000 ........................................................................................................ 47

Safety Shutters

21A - Safety Shutters S800-2500 ............................................................................................................................................... 48 - 49

21B - Safety Shutters S3200-4000 ............................................................................................................................................. 50 - 51

Interlocking

22 - “Tripped” position by Padlock (optional) ..................................................................................................................... 52

23 - “Tripped” position by Padlock and GE ACB / RONIS (optional) ......................................................................... 53 - 54

24 - “Tripped” position by GE ACB / RONIS lock (optional) ........................................................................................... 55 - 56

25 - “Tripped” position by SINGLE LETTER CASTELL LOCK (optional) ...................................................................... 57 - 58

26 - “Tripped” position by DOUBLE LETTER CASTELL LOCK or SINGLE LETTER CASTELL LOCK + GE ACB / RONIS LOCK (optional) ............................................................... 59 - 61

27 - “Withdrawn” / “Connected” position by GE ACB / RONIS LOCK & Padlock (optional) .......................... 62

Fault Signalling Contact

28A - Fault Signalling Contact (Replacement) S800-2500 .............................................................................................. 63

28B - Fault Signalling Contact (Replacement) S3200-4000 ............................................................................................ 64 - 65

Secondary Disconnects

29 - Secondary Disconnects ....................................................................................................................................................... 66 - 67

Earth Connector

30 - Earth Connector ...................................................................................................................................................................... 68 - 69

Signalling Contacts on Cradle

31 - Signalling Contacts on Cradle .......................................................................................................................................... 70

32 - 33 - Coupled Contact with Signalling Contact ................................................................................................................... 71

REPLACEMENTS PARTS ................................................................................................................................................................................................................... 72 - 73

SCHEMATIC / WIRING DIAGRAMS ............................................................................................................................................................................................. 74 - 77

Spectronic Air Circuit Breaker - Operating Instructions

403

Receipt of equipment S800-2500 / S3200-4000

1 - Arrival

When packages arrive, check that they are inperfect condition. If otherwise, proceed with theusual notifications.Do not hesitate to proceed with unpacking in thepresence of an authorized agent representing thedelivery firm.

2 - Storage

If the equipment is not installed immediately, itmust be stored in a premises where it is protectedfrom dust and splashing by water. To avoid anydeterioration, it is recommended that equipmentbe left in its protective covering or provided witha waterproof covering.

3 - UnpackingS800-2500 / S3200-4000

Withdrawable* breaker with cradle• Remove the 2 supports (A) securing the

circuit-breaker onto its fixed section on

either sides

• Remove the 4 brackets (B) securing the fixed

section onto the base of the packing case.

• Remove the 2 brackets (C) protecting the

front box (cradle).

* Fixed breaker : remove the 4 attachment

screws at the base of the breaker fixed to

the woden pallete.

Withdrawable* breaker withoutcradleThe handles on the upper section of the sideflanges may be used to lift the equipment.Never carry the circuit-breaker by its cut-offclamps. Rest it on a flat surface, either on itslower section or on its side flanges. Keep thebase of the packing case for use as a palette.

* Fixed breaker : follow the same instructions asthat of withdrawable breaker.

C

B

A

Spectronic Air Circuit Breaker - Operating Instructions

504

Identification S800-2500 and S3200-4000

1 - information label2 - supply voltage for auxiliary equipment3 - trip and local reset push-button (BPDL)4 - “On” push-button (BPEL)

5 - front cover6 - carrying handle7 - identification plate8 - spring charging handle9 - front facia

24 - voltmetric releases25 - reset spring contact

21 - connection terminal box (fixed breaker)22 - earth connector (fixed breaker)23 - current transformers

16 - arc chute17 - electrical operation motor18 - releases LMZ7/RMS7/RMS10/12

10 - local controls padlocking11 - spring charge status indicator

• white : spring discharged• red : spring charged

12 - mechanical fault• white (I>) : fault• black : normal

13 - interlocking in tripped position (single figure castell lock / GE ACB or Ronis lock)14 - padlocking in tripped position15 - circuit-breaker status indicator:

• red : closed• green : open

16 - locking catch for local controls padlocking

ed noitneverp gnisolc - 02srotcatnoc yrailixua - 91 vice

20

19

16

18

17

22

21

23 2524

5 1 2 6

4 7

3

15

10

9

13

8

14

11 12

16

Spectronic Air Circuit Breaker - Operating Instructions

6

05

26 - safety shutters

27 - name plate

28 - secondary disconnectors - fixed

29 - wiper-type earth connector

30 - “withdrawn” position indicating contact

31 - “connected” position indicating contact

32 - contact coupled with “plug-in” control

33 - interlocking in “Withdrawn” / “Connceted” position by GE ACB / Ronis lock34 - interlocking in“Withdrawn” position by padlock

37 - rating error prevention plug / device

26

28

27

31

30

29

32 34 33

37

Spectronic Air Circuit Breaker - Operating Instructions

7

Installation

S800 - 2500 Spectronic “Withdrawable”

Connections

Panel cut-out for gasket fittings Legend

Circuit breaker

Nr. of poles A B C D E F H I

S 800-1000 1250-1600

3 399 98 101.5 77.5 217.5 87 46.5 22.5

4 487 98 96.5 72.5 217.5 87 90.5 66.5

S20003 487 130 113.5 89.5 207.5 107 90.5 66.5

4 621 130 115.5 91.5 207.5 107 157.5 133.5

S25003 555 150 127.5 103.5 197.5 127 124.5 100.5

4 701 150 125.5 101.5 197.5 127 197.5 173.5

Connection TerminalsF.T.R.V.T.

R.H.T. S800-1600 S2000 S2500F.T.: Front TerminalsR.V.T.: Rear Vertical TerminalsR.H.T.: Rear Horizontal Terminals

S1600 S2000 S2500S800-1600 S2000 S2500

H1 = minimum clearance above the arc chutes

Ue≤500V Ue≤690V

Insulated screen 150 mm 150 mm

Metallic screen 150 mm 200 mm

Spectronic Air Circuit Breaker - Operating Instructions

8

Installation

S3200 - 4000 Spectronic “Fixed”

Panel cut-out for gasket fitting

Legend

Rear horizontal terminal

S3200A / S4000A

Circuit breaker

Number poles Weight A B C D

S3200A / S4000A 3 116 628 250.3 132 233.8

S3200A / S4000A 4 146 826 448.3 130 431.8

H1 = minimum clearance above the arc chutes

Ue ≤ 500V Ue ≤ 690V

Insulated Screen 200 mm 200 mm

Metallic Screen 200 mm 200 mm

F G

S3200 15 (2X5) 127

S4000 25 (3X5) 121.5

Spectronic Air Circuit Breaker - Operating Instructions

9

Installation

S3200 - 4000 Spectronic “Withdrawable”

Panel cut-out for gasket fitting Front or rear horizontal connection terminals

Legend

F G

S3200A 15 (2X5) 266.5

S4000A 25 (3X5) 216.5

Circuit breaker Numberpoles A B C D

S3200 / S40003 711 246.8 130.5 230.3

4 909 444.8 129.5 428.8

H1 = minimum clearance above the arc chutes

Ue ≤ 500V Ue ≤ 690V

Insulated Screen 200 mm 200 mm

Metallic Screen 200 mm 200 mm

Spectronic Air Circuit Breaker - Operating Instructions

10

Installation

S3200 - 4000 Spectronic “Fixed”

Hole details of earthing for 800A - 2500A (backside of the breaker)

Earthing Position for S3200-S4000

Hole details of earthing for 3200A - 4000A (backside of the breaker)

Rear terminal mould cavity dimension S800-S2000

RATING A

1600A 73

2000A 109

Spectronic Air Circuit Breaker - Operating Instructions

11

• “WITHDRAWN”Turn the crank as far as it will go in theanticlockwise direction with the indicatorstopping at the “withdrawn” position mark. Inthis position both main and auxiliary circuits areisolated.

• “TEST”Turn the crank, with indicator stopping at the“test” mark. In this position the main circuit iso-lated and auxiliary circuits connected.

Circuit breaker position• “CONNECTED”Turn the crank as far as it will go in the clock-wise direction. Here the indicator will stop at“connected” position mark. In this position themain and auxiliary circuits are connected.

• “EXTRACTED MAINTENANCE (COMPLETELY WITHDRAWN) POSITION”Pull the retractable rails to fully extend themand pull the breaker as far as it will go.

Fitting the breaker :

• Turn the plug-in crank as far as it will go in

anti-clockwise direction.

• Pull the retractable rails out to the fully

extended position.

• Pull the breaker out on the rails using the

pulling handles.

• Push the breaker back and then the rails

fully home.

Electrically operated circuit breaker :• Press the “On” and “Off” push buttons in turnto release the energy stored in the spring.

Position-indicating contacts• “connected position” - 1 or 2 contacts actuated when circuit-breaker is fully plugged-in (32).• “withdrawn position” - 1 or 2 contacts actuated when circuit-breaker is fully removed (31).• 1 contact actuated on fitting and removing the crank (33).

33

32 31

33

32

31 S 800/2500AS 3200/4000A

Fitting the breaker :

• Push the knob to insert the plug-in crank.

10

Commissioning - Operation S800-2500 / S3200-4000

Spectronic Air Circuit Breaker - Operating Instructions

12

Circuit Breakera - Manual Operation• reset the release- press the trip (OFF)push button (13) (BPDL) fullyin• resetting- operate the handle (11) to compress the spring(stored energy required for closing)- press the ON push-button (15)• closing- presence of voltage required on UV or UVRD iffitted on breaker.• opening- in local mode by trip push button (BPDL) (13)- in remote mode by voltmetric releases

b - Electrical OperationElectrical operation with stored energy : thestored energy is reset automatically once thebreaker has been closed.The trip push button (BPDL) (13) resets theovercurrent release except if the circuit-breakeris reset automatically, with or without indicationwith memory.• opening- in local mode, using the red trip (OFF) pushbutton (13)- in remote mode, using the voltmetric releases- if closing the breaker is provided by acontinuous command, the closing commandmust be momentarily interupted after trippingin order to obtain resetting• closing- in local mode, using the green ON push-button(15)- in remote mode by closing coil.

ProtectionRelease• If the circuit-breaker is to be reset in local mode,it must be reset manually after overload andshort-circuit operation by pressing the local trippush button BPDL (13) fully in.

Each protected pole of the circuit-breaker isequipped with current transformers (CT) whichsupply input to the releases RMS7 / RMS9D /LMZ7.

15

11

15

11

13

13

11

Spectronic Air Circuit Breaker - Operating Instructions

13

ProtectionRMS7 Trip• If the circuit breaker is to be reset in local mode,it must be reset manually after an overcurrentcondition by pushing in fully the local trip pushbutton 13.

Description :Powered by the current transformers, lmax = 4000, the RMS7 unitperforms all the necessary current protections with true rms value sensing:• overload protection (LT)• short-circuit protection (ST and I)• ground fault protection (GF) (The 4th (neutral) current transformer must be of the same rating as those of the three phases).

RMS7 : OptionsThe following options are field fittable

Distinct Fault Signalling (LT, ST, I, GF)• Local indication by LED display. this option is power supplied by an internal battery.• Lead sealing.

Setting Ranges Setting Points

LT (x ln) 0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.00

LTD (s) 5, 10, 15, 20, 25, 30, 35, 40 delay at 7.2 lr

ST (x ln) 1.5, 2, 3, 4, 5, 7, 9, 10, 12, 14

Delay (ms) 30, 60, 90, 120, 150, 180, 210, 240, 270, 300

I (x ln) 1.5, 2, 3, 5, 7, 10, 15, OFF

GF (x ln) 0.20, 0.30, 0.40, 0.50, 0.60, 0.70, 0.80 for 800 to 2000A

0.20, 0.30, 0.35, 0.45, 0.55, 0.60, 0.70 2500A

0.20, 0.30, 0.35, 0.45 for 3200 to 4000A

Delay (ms) 100, 200, 300

lr = k x ln

X = In (Nominal rating or

value of rating plug indications reproduced on the calibrator

S = Sensor rating

12

RMS 7: Protection Unit

���

Spectronic Air Circuit Breaker - Operating Instructions

14

2 3

3435

3637

3839

37

3839

RMS 7

RMS 7

1Current

transformers

White

Yellow

yellow

whiteyellow

whiteyellow

whiteyellow

whiteyellow

4950

3435

36

N 1 2 3

S1 whiteyellow

whiteyellow

white

Total cut-out time at ST : selected time delay + 90 ms

Tolerance for ST operating thresholds : ± 15 %

PH 2+PH 2-

PH 3+PH 3-

PHN +PHN -

PH 1+PH 1-

PH 1+PH 1-

PH 2+PH 2-

PH 3+PH 3-

Threshold

GF in A (±15%)

Threshold

Threshold

GF in A (±15%)

Threshold

Overload threshold LT in A according to the index position

(Tolerances :1.05 -1.30 of setting current according to IEC 60947-2)

Rating

plug

(A)

Currenttransformer

(A)

Circuit

breaker

type

0,4In 0,5In 0,6In 0,7In 0,75In 0,8In 0,85In 0,9In 0,95In 1,0In 0,20 In 0,80 In

S800 800 400 160 200 240 280 300 320 340 360 380 400 80 320

600 240 300 360 420 450 480 510 540 570 600 120 480

800 320 400 480 560 600 640 680 720 760 800 160 640

S1000 1000 800 320 400 480 560 600 640 680 720 760 800 160 640

1000 400 500 600 700 750 800 850 900 950 1000 200 800

S1250 1250 500 625 750 875 937 1000 1063 1125 1188 1250 250 1000

S1600 1600 800 320 400 480 560 600 640 680 720 760 800 160 640

1200 480 600 720 840 900 960 1020 1080 1140 1200 240 960

1600 640 800 960 1120 1200 1280 1360 1440 1520 1600 320 1280

S2500 2500 1600 640 800 960 1120 1200 1280 1360 1440 1520 1600 320 1280

2500 1000 1250 1500 1750 1875 2000 2125 2250 2375 2500 500 2000

S3200 3200 1600 640 800 960 1120 1200 1280 1360 1440 1520 1600 320 1280

3200 1280 1600 1920 2240 2400 2560 2720 2880 3040 3200 640 2560

S4000 4000 2500 1000 1250 1500 1750 1875 2000 2125 2250 2375 2500 500 2000

4000 1600 2000 2400 2800 3000 3200 3400 3600 3800 4000 800 3200

Neutral CT Mounting Instructions :While using 3P ACBs in 3Phase 4WireSystem,

a) If the supply connections are madeto the top terminals, P2 of theNeutral CT shall face the supply side.

b) If the supply connections are madeto the bottom terminals, P1 of theNeutral CT shall face the supply side.

3 Phase 4 Wire System

3 Phase 3 Wire System

S2

S1

S2

S1

S2

S1

S2

S1

S2

S1

S2

S1

S2

13

Setting and operating current values

RMS10,RMS12

RMS10,RMS12

Spectronic Air Circuit Breaker - Operating Instructions

15

ProtectionRMS7 Trip• If the circuit breaker is to be reset in local mode,it must be reset manually after an overcurrentcondition by pushing in fully the local trip pushbutton 13.

Description :Powered by the current transformers, lmax = 4000, the RMS7 unitperforms all the necessary current protections with true rms value sensing:• overload protection (LT)• short-circuit protection (ST and I)• ground fault protection (GF) (The 4th (neutral) current transformer must be of the same rating as those of the three phases).

RMS7 : OptionsThe following options are field fittable

Distinct Fault Signalling (LT, ST, I, GF)• Local indication by LED display. this option is power supplied by an internal battery.• Lead sealing.

Setting Ranges Setting Points

LT (x ln) 0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.00

LTD (s) 5, 10, 15, 20, 25, 30, 35, 40 delay at 7.2 lr

ST (x ln) 1.5, 2, 3, 4, 5, 7, 9, 10, 12, 14

Delay (ms) 30, 60, 90, 120, 150, 180, 210, 240, 270, 300

I (x ln) 1.5, 2, 3, 5, 7, 10, 15, OFF

GF (x ln) 0.20, 0.30, 0.40, 0.50, 0.60, 0.70, 0.80 for 800 to 2000A

0.20, 0.30, 0.35, 0.45, 0.55, 0.60, 0.70 2500A

0.20, 0.30, 0.35, 0.45 for 3200 to 4000A

Delay (ms) 100, 200, 300

lr = k x ln

X = In (Nominal rating or

value of rating plug indications reproduced on the calibrator

S = Sensor rating

12

RMS 7: Protection Unit

���

VIEW Button

- Indicates the battery status (battery ok when the “BAT” led is powered).

- Indicates the origin of fault (LTPU - GF - OVL - SHORT).

RESET Button

- Reset the fault indicator.

Trip Unit Healthiness : press and hold the view button for more than 5

seconds. If the LTPU LED blinks slowly, it indicates the healthiness of the tripunit.

CAUTION

- The battery can be replaced only by Panasonic CR1616 or Duracell DC1616B.

- Use of others battery can present a risk of fire, explosion or can damage the product.

- Check the polarity of the battery.

Fault Signal

LT : LED OVL : Tripping on overload condition

ST - I : LED SHORT : Tripping on short circuit condition

GF : LED GF : Tripping on ground fault condition

LTPU : LED Pre-alarm LT

The LTPU led blinks slowly when the LT threshold is below 100%.

The LTPU led blinks rapidly when the LT threshold is above 100% and indicatesan imminent tripping on overload condition.

Replacement

The “CLIC” sound at the end of installation operation indicates that the ratingplug is correctly installed on the unit.

ATTENTION

� The (S) rating indicated on the rating plug must be identical to the

nominal current indicated on the RMS7 unit.

�In 800A

In 800A

14

Distinct fault signalling option

Spectronic Air Circuit Breaker - Operating Instructions

16

Spectronic Air Circuit Breaker - Operating Instructions

17

T. S

EC

ON

DS

MULTIPLES OF NOMINAL CURRENT In (CT CURRENT)

AIR CIRCUIT BREAKERS : S800 to 4000A

GF Threshold0.2 to 0.8 (800 to 2000A)0.2 to 0.7 (2500A)0.2 to 0.45 (3200 to 6400A)times the value X In

GF Time Delay0.1 - 0.2 - 0.3s

16

RMS7 Time - Current Characteristics

Spectronic Air Circuit Breaker - Operating Instructions

18

RMS10, RMS12 : Protection & Measurement Unit

Standard Protection RMS10, RMS12 :• overload protection (LT)• short-circuit protection (ST and I)• ground fault protection (GF)••

thermal memoryRELT

Description :Powered by the current trans-former,Imax = 4000A, the RMS10, RMS12 unitperforms all the necessary currentprotections as well as measuring(RMS) all the para-meters.In addition to the above functions, theRMS10, RMS12 can also perform remoteevent measurement and recording.

Mic

ropr

oces

sor

RMS1

0, R

MS1

2

Conv

erte

r A

/DB

Keyboard

Current Transformers

N

A

C

LCD display

Relay

Auxiliary PowerSupply 24V DC

Actuator

Communication

Voltage Conditioner

PROTECTION

MEASUREMENT

Each function can be time delayedwith a range of 1 to 15s (+ OFFposition).

Distinct fault signatisationBy local display with the RMS10, RMS12unit in “STATUS” mode the conditionof the breaker is indicated. Also thetime and number of releases underfault :- LT, ST, I, GF- undervoltage, overvoltage, ......, reversal power.

RMS1 0 , R M S 1 2 : Protection andMeasurement Unit“High Precision” MeasurementsWithout Voltage Monditioner- Current on each phase (A, KA)With Voltage Conditioner- Power supply voltage of conditioner 230/380/415V- Current on each phase (A, KA)- Voltage between phase and neutral (V)- Energy (KWh, MWh)- Active power per phase (1) (KW)- Total active power (KW, MW)- Total power per phase (1) (KVA, MVA)- Total power (KVA, MVA)- Average power demand (KW, MW)- Maximum power demand (KW, MW)- Voltage range RMS10, RMS12 from 120 to 600V AC- Frequency (Hz)

-

(1) if the neutral is connected

For all voltage / power parameters and communication / relaying protection supplingof 24 V DC is required.

lr = K x ln

NoteIf the GF function is selected, the 4thtransformer (Neutral CT) must have thesame rating as the one of the phases.

Function Range (%) Step

< V 50 - 90 1

> V 110 - 150 1

V 10 - 50 1

I 10 - 50 1Pi 10 to 990KW 10KW

Setting points

LT (x In) 0.5 - 1 (steps of 0.05)

LTD (S) 0.5 - 30@6Ir

ST (x Ir) 1.5 - 9 (steps of 0.5)

Time Delay (ms) 90 to 400

I (x In) 2 - 15 - OFF (steps of 0.5) RMS 9D/2000A2 - 13 - OFF (steps of 0.5) RMS 9D/3200A2 - 9 - OFF (steps of 0.5) RMS 9D/4000A

GF (x In) 0.2 - 0.6 (steps of 0.01) /2000A*0.2 - 0.48 (steps of 0.01) /2500A0.2 - 0.37 (steps of 0.01) /3200A0.2 - 0.3 (steps of 0.01) /4000A

Time Delay

RELT1

(ms) 60 to 390

Setting ranges

Sam

pler

Additional Programmable FunctionsAll or part of the programmable function in RMS12 can be selected- current unbalance - under voltage - over voltage - voltage unbalance - reverse power - reverse power - load shedding- GFA- RELT- 2 way communication with RS485 port in-built

1.5 In to 15 In-settable throughcommunication / 24v DC/AC throughwiring input

*For 1250A, please refer attachment in annexure 1 page --1RELT needs to be factory enabled. Once RELT is enabled, the input and output contact available are dedicated to this features and no other options for input / output will available for use.

Spectronic Air Circuit Breaker - Operating Instructions

19

1.5 2 2.5 3 4 302015975 20070 00500105 3001

2 302075 20070 00500105 3001 10

S800 to S4000A

Inst. Threshold (I) 1.5 to 15 timesthe LT value (Ir)(in steps of 0.5)

ST Time Delay0.1 - 0.21 - 0.35s

ST Threshold1.5 to 9 times the LT value

(Ir)

LT Time delay3 - 6 - 12 - 25s at 6Ir

LT Threshold in Kxln 0.5 to 1

1.05Operating Limits IEC 60947-2

0.8

100

200

0.8

50

10

20

30

1

5

34

50000

20000

30000

2000

3000

5000

10000

1000

500

300

2

0.1

0.2

0.3

0.5

0.05

0.01

0.02

0.03

I2t OUT I2t IN

T. S

ECO

ND

S

MULTIPLES OF CURRENT SETTING

3

1.3 }

}

}

}

18

RMS10, RMS12 Time - Current Characteristics

09.08

Low-Voltage Circuit Breakers

EntelliGuard TU Trip Unit for PowerBreak, PowerBreak II, AKR and WavePro Circuit Breakers UL489 and UL1066 Stored EnergyMechanism Circuit Breakers

Long-Time CB Characteristics

Curves apply at 60 Hertz and from -20°C to 55°C circuit breaker ambient temperature.

DES-095Frames 800-5000A AKR & WaveProFrames 800-4000A PowerBreak & PowerBreak II

All Voltages: 600 Vac and below

Pickup Range0.5X-1.0X Trip Rating Plug

TIM

E IN

SEC

ON

DS

DES

-095

DES

-095

10

20

30

40

50

60708090

100

200

300

400

500

600

700800900

1000

9876

5

4

3

2

.9

.8

.7

.6

.5

.4

.3

.2

.1

.09

.08

.07

.06

.05

.04

.03

.02

.01

1

.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090

100

200

300

400

500

600

7008009001000

2000

3000

4000

5000

6000

70008000900010000

.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90

100

200

300

400

500

600700800900

1000

2000

3000

4000

5000

6000

700080009000

10000

MULTIPLE OF LONG-TIME PICKUP

MULTIPLE OF LONG-TIME PICKUP

TIM

E IN

SEC

ON

DS

200

300

400

500

600700800900

1000

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91

2

3

4

5

6

789

10

20

30

40

50

60708090

100

Nominal Clearing and Commit Times for X Multipliers of Nominal Pickup.

X = 1.5 1.5 6 6 7.2 7.2 10 10Curve Commit Clear Commit Clear Commit Clear Commit Clear

Min CB 4.25 8.04 0.20 0.33 0.14 0.24 0.072 0.137

C-2 12.7 24.1 0.60 0.94 0.42 0.66 0.21 0.35

C-3 25.5 48.1 1.21 1.84 0.83 1.28 0.43 0.67

C-4 34.0 64.1 1.61 2.45 1.11 1.70 0.57 0.89

C-5 51.0 96.2 2.41 3.66 1.67 2.53 0.86 1.32

C-6 67.9 128 3.21 4.87 2.22 3.37 1.15 1.75

C-7 84.9 160 4.02 6.08 2.78 4.20 1.43 2.18

C-8 101.9 192 4.82 7.29 3.33 5.03 1.72 2.61

C-9 118.9 224 5.62 8.49 3.89 5.87 2.01 3.03

C-10 135.9 256 6.43 9.70 4.44 6.70 2.29 3.46

C-11 152.9 289 7.23 10.9 5.00 7.54 2.58 3.89

C-12 169.8 321 8.04 12.1 5.56 8.37 2.87 4.32

C-13 203.8 385 9.64 14.5 6.67 10.0 3.44 5.18

C-14 237.8 449 11.2 17.0 7.78 11.7 4.01 6.04

C-15 271.7 513 12.9 19.4 8.89 13.4 4.59 6.90

C-16 305.7 577 14.5 21.8 10.0 15.0 5.16 7.76

C-17 339.7 641 16.1 24.2 11.1 16.7 5.73 8.61

C-18 373.6 705 17.7 26.6 12.2 18.4 6.30 9.47

Max CB 407.6 769 19.3 29.1 13.3 20.0 6.88 10.3

Algorithm will not commit below 1.5 cycles, clearing time will not be less than 0.088 seconds.

Actual Long-Time Pickup is 112% of Nominal Pickup.

Transition to Short-Time Pickup, Short- Time Delay Band or Instantaneous

Determines End of Curve Minimum CB

Maximum CB

C-3

C-6

C-13

Spectronic Air Circuit Breaker - Operating Instructions

20

09.08

Low-Voltage Circuit Breakers

EntelliGuard TU Trip Unit for PowerBreak, PowerBreak II, AKR and WavePro Circuit Breakers UL489 and UL1066 Stored EnergyMechanism Circuit Breakers

Long-Time Fuse Like Characteristics

Curves apply at 60 Hertz and from -20°C to 55°C circuit breaker ambient temperature.

DES-096Frames 800-5000A AKR & WaveProFrames 800-4000A PowerBreak & PowerBreak II

All Voltages: 600 Vac and below

Long Time Pickup Range0.5X-1.0X Trip Rating Plug

TIM

E IN

SEC

ON

DS

DES

-096

DES

-096

10

20

30

40

50

60708090

100

200

300

400

500

600

700800900

1000

9876

5

4

3

2

.9

.8

.7

.6

.5

.4

.3

.2

.1

.09

.08

.07

.06

.05

.04

.03

.02

.01

1

.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090

100

200

300

400

500

600

7008009001000

2000

3000

4000

5000

6000

70008000900010000

.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90

100

200

300

400

500

600700800900

1000

2000

3000

4000

5000

6000

700080009000

10000

MULTIPLE OF LONG-TIME PICKUP

MULTIPLE OF LONG-TIME PICKUP

TIM

E IN

SEC

ON

DS

200

300

400

500

600700800900

1000

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91

2

3

4

5

6

789

10

20

30

40

50

60708090

100

Nominal Clearing and Commit Times for X Multipliers of Nominal Pickup.

X = 1.5 1.5 6 6 7.2 7.2 10 10Curve Commit Clear Commit Clear Commit Clear Commit Clear

Min F 0.67 1.54 0.025 0.085 0.025 0.085 0.025 0.085

F-2 2.0 4.40 0.025 0.085 0.025 0.085 0.025 0.085

F-3 3.6 7.98 0.025 0.085 0.025 0.085 0.025 0.085

F-4 5.6 12.5 0.025 0.085 0.025 0.085 0.025 0.085

F-5 8.1 18.0 0.032 0.100 0.025 0.085 0.025 0.085

F-6 11.2 25.0 0.044 0.13 0.025 0.085 0.025 0.085

F-7 15.1 33.8 0.059 0.16 0.028 0.094 0.025 0.085

F-8 20.0 44.7 0.078 0.20 0.038 0.114 0.025 0.085

F-9 26.1 58.4 0.10 0.26 0.049 0.14 0.025 0.085

F-10 33.8 75.4 0.13 0.32 0.064 0.17 0.025 0.085

F-11 43.3 96.8 0.17 0.41 0.082 0.21 0.025 0.085

F-12 55.3 123 0.22 0.51 0.104 0.26 0.028 0.092

F-13 70.2 157 0.27 0.64 0.13 0.33 0.036 0.109

F-14 88.9 198 0.35 0.81 0.17 0.40 0.045 0.13

F-15 112 251 0.44 1.01 0.21 0.50 0.057 0.16

F-16 141 316 0.55 1.26 0.27 0.62 0.072 0.19

F-17 178 397 0.69 1.58 0.34 0.78 0.090 0.23

F-18 224 499 0.87 1.98 0.42 0.97 0.113 0.28

Max-F 280 626 1.10 2.48 0.53 1.21 0.142 0.35

Algorithm will not commit below 1.5 cycles, clearing time will not be less than 0.088 seconds.

Actual Long-Time Pickup is 112% of Nominal Pickup.

Transition to Short-Time Pickup, Short- Time Delay Band or Instantaneous

Determines End of Curve

Minimum F

Maximum F

F-5

F-13

Spectronic Air Circuit Breaker - Operating Instructions

21

09.08

DES-098Low-Voltage Circuit Breakers

EntelliGuard TU Trip Unit for PowerBreak, PowerBreak II, AKR and WavePro Circuit Breakers UL489 and UL1066 Stored EnergyMechanism Circuit Breakers

Ground Fault

Curves apply at 60 Hertz and from -20°C to 55°C circuit breaker ambient temperature.

Pickup RangeMinimum 0.2X Sensor

Maximum up to 0.6x Sensor

Not to exceed 1200A

Frames 800-5000A AKR & WaveProFrames 800-4000A PowerBreak & PowerBreak II

All Voltages: 600 Vac and below

TIM

E IN

SEC

ON

DS

DES

-098

DES

-098

10

20

30

40

50

60708090

100

200

300

400

500

600

700800900

1000

9876

5

4

3

2

.9

.8

.7

.6

.5

.4

.3

.2

.1

.09

.08

.07

.06

.05

.04

.03

.02

.01

1

.8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090

100

.8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90

100

.8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090

100

.8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90

100

MULTIPLE OF SENSOR

MULTIPLE OF SENSOR

TIM

E IN

SEC

ON

DS

200

300

400

500

600700800900

1000

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91

2

3

4

5

6

789

10

20

30

40

50

60708090

100

Maximum GF Pickup based on sensor.

Sensor Maximum

≤ 2000 0.6X

2500 0.48X

3000 0.4X

3200 0.37X

4000 0.3X

5000 0.24X

7

1312

1110

98

65

4

32

1

Maximum

Minimum

1

14t slope SGF slope

12t slope

16mS additional at minimum possible GF pick up, (20% sensor)

TGF delay band additional time may be calculated via the following formula;Additional t = 21.25 –18x%Sensor 1000Up to 119% sensor

0mS additional at 119% sensor

Spectronic Air Circuit Breaker - Operating Instructions

22

09.08

Low-Voltage Circuit Breakers

EntelliGuard TU Trip Unit for PowerBreak, PowerBreak II, AKR & Wavepro Circuit BreakersUL489 and UL1066 Stored EnergyMechanism Circuit Breakers

Short-Time Pickup and Delay Bands

Curves apply at 60 Hertz and from -20°C to 55°C circuit breaker ambient temperature.

DES-097Frames 800-5000A AKR & WavePro PowerBreak & Frames 800-4000A PowerBreak II

All Voltages: 600 Vac and below

Pickup Range1.5X - 9X up to 4000A Frames

1.5X - 7X 5000A AKR and WavePro

TIM

E IN

SEC

ON

DS

DES

-097

DES

-097

10

20

30

40

50

60708090

100

200

300

400

500

600

700800900

1000

9876

5

4

3

2

.9

.8

.7

.6

.5

.4

.3

.2

.1

.09

.08

.07

.06

.05

.04

.03

.02

.01

1

2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090

100

1

1

2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90

100

2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090

100

1

1

2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90

100

2

MULTIPLE OF LONG-TIME PICKUP

MULTIPLE OF LONG-TIME PICKUP

TIM

E IN

SEC

ON

DS

200

300

400

500

600700800900

1000

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91

2

3

4

5

6

789

10

20

30

40

50

60708090

100

Transition to Instantaneous, Override or Application

Determines End of Curve

Transition to Instantaneous, Override or Application

Determines End of Curve

1011

87

9

65

43

21

10X STPU MaximumSlope Calculation

Min.

Int.

Max.

.1

.09

.08

.07

.06

.05

.04

.03

.02

.01

.2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7

.2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7

16mS additional at minimum possible ST pick up (Minimum Trip Rating Plug X Minimum Long Time pickup X Minimum Short Time pickup. (28% sensor)

Additional clearing time required for very low pickup settings under self power

Time band additional time may be calculated via the following formula;Additional t = 21.25 –18x%Sensor 1000Up to 119% sensor

0mS additional at 119% sensor

Spectronic Air Circuit Breaker - Operating Instructions

23

Spectronic Air Circuit Breaker - Operating Instructions

24

stnioP gnitteSsegnaR gnitteS

Over Load (LT) k (xln) 0.5,0.6,0.7,0.8,0.9,1

Short Time Pickup (ST) >> (xlr) 3,4,5,6,8,9

ST Delay (sec.) t >> (sec) Inst, 0.2, 0.3,0.4

Ground Fault (GF) lo (xln) 0.2,0.3,0.4,0.5,0.6,0.7

Earth Fault Delay (sec) t>>+0.2

lr = kxln

Optional Fault Indicator in LMZ7

21

LMZ 7 : PROTECTION UNIT

Spectronic Air Circuit Breaker - Operating Instructions

25

Voltmetric ReleasesThe equipment can be equipped with 2 releasesof types EA (Shunt), UV or UVRD (Delayed UV).They are reset by the breaker’s main shaft at theend of the opening operation.

Inhibited ClosingClosing is prevented by Closing-PreventionDevice FE operating at minimum voltage and isindependent of UV release.

Auxiliary Contacts• Between 5 and 8 contacts operate at thebeginning of closing of poles.• Between 1 and 4 contacts operate at the sametime as the main poles.

S 800/2500A

S 800/2500A

S 800/2500A S 3200/4000A

S 3200/4000A

S 3200/4000A

22222222

Spectronic Air Circuit Breaker - Operating Instructions

26

• common mechanical fault indicator for“overload” and “short-circuit” (A)Black : NormalWhite (I>) : Fault

• electrically-operated circuit breaker (withautomatic resetting).

The fault is cleared by operating the local trippush button.

• breaker with manual control (with localresetting).

Contacts and Fault Indicator• common “overload” and “short-circuit” faultindication: Possibility of 2 contacts withcommon point (CD) actuated by means of therelease.- contacts with local resetting by means of push-button.- momentarily actuated contacts for electrically-operated circuit-breaker (on request).

98

96

08

06

05

95CD

CD

The fault must be cleared on push-button BPED.Fault indication does not inhibit reclosing of thecircuit-breaker.

K14 1

3K1

CDBPED

H1

A

• Operate of Voltmetric Releases UV,UVRD, EAContacts with common point with fleeting action.- C41 actuated by UV or UVRD- C31 actuated by EA

• Voltage Presence on VoltmetricRelease UV or UVRDfactory fitted.Possibility of 1 contact with common point (C43),directly actuated by coil.

23

InterlockingA - Fixed and Withdrawable Breakers

(1) Interlocking of local control buttons bypadlock

press & hold the “Off” push button, turn the lock-ing catch at 90°, slide the push button windowcovers in and padlock them

- for electrically - operated breaker

(2) Interlocking in “tripped” position byGE ACB / Ronis lock

- press the trip push button (BPDL) fully in to turnthe key

(3) interlocking in “tripped” position by padlock

- press the trip push button (BPDL) fully in to pullthe padlocking tab

(5) Interlocking in “Withdrawn”/”Connected”Position by Padlockstandard on the basic breaker• place the breaker in the “Withdrawn”/”Connected” position• remove the crank• push the padlocking tab to the left and thenpull

B - Withdrawable Breakers(4) Padlocking of safety shutters

4

(6) Interlocking in “Withdrawn” / “Connected”Position by Padlock

1

2

3

24

Spectronic Air Circuit Breaker - Operating Instructions

27

InterlockingA - Fixed and Withdrawable Breakers

(1) Interlocking of local control buttons bypadlock

press & hold the “Off” push button, turn the lock-ing catch at 90°, slide the push button windowcovers in and padlock them

- for electrically - operated breaker

(2) Interlocking in “tripped” position byGE ACB / Ronis lock

- press the trip push button (BPDL) fully in to turnthe key

(3) interlocking in “tripped” position by padlock

- press the trip push button (BPDL) fully in to pullthe padlocking tab

(5) Interlocking in “Withdrawn”/”Connected”Position by Padlockstandard on the basic breaker• place the breaker in the “Withdrawn”/”Connected” position• remove the crank• push the padlocking tab to the left and thenpull

B - Withdrawable Breakers(4) Padlocking of safety shutters

4

(6) Interlocking in “Withdrawn” / “Connected”Position by Padlock

1

2

3

24

Spectronic Air Circuit Breaker - Operating Instructions

28

2 - RevisionInspection is to be performed every 3000operations or 3 years (we recommend theintervention of the specialists in the service andverification for this revision).

A - Arc Chute• wipe the insulating cover

B - Poles

• Fixed and Withdrawable Breakers- remove dust from isolating parts- check the gap on arcing contacts with thecircuit-breaker closed.• repeat the adjustment of fixed arcing contactsif the gap is greater than 1,5 mm.

1 - MaintenanceThe arc chutes and arcing contacts ensure :• 1500 closing cut-out operations at In*• 3 closing/cut-out operations at maximumshort-circuit current*• 10 closing cut-out operations at 10 In*All other components are designed to last as longas the breaker ’s normal service life (20,000operations for the electrically-operated ormanual operated breaker).* In one of these cases : Remove the arc chutesand change the arcing contacts.Visual monitoring (every year) :• cleanliness of the circuit breaker.• cleanliness of grease (if the apparatus isexposed to dust)

3 - LubricationA - Components to be Lubricated• all metal/metal friction surfaces must be kept greased.• wipe off excess grease.• grease characteristics : High Speed Grease 475HS mfd. by OKS Industries, Bangalore, India.B - Components not to be lubricated• current-threshold and voltmetric release.

C - Disconnection of SecondaryWiringClean the fixed and movable contacts with acloth slightly dampened with carbontetrachloride.Check for contact pressure.Grease lightly.

D - Overcurrent and VoltmetricReleaseNo maintenance.In case of failure, replace the release.

• replace the arc barriers and the spark arrestersif they are worn by more than 1 mm• clean the surfaces of main contacts with fine-grain emery paper and wipe carefully.

• Removable BreakersClean the following parts with a cloth slightlydampened with carbon tetrachloride :- the cluster contacts- the studs for the cradleGrease lightly

Poles Tightening :The set of poles is maintained under pressure bysix rams located on each flange of the circuit-breaker. Check the tightening torque.

25

Maintenance - Lubrication

Spectronic Air Circuit Breaker - Operating Instructions

2926

Checking - Replacement - Adaptation

2A - 1• release the locking pins (1)• remove the arc chute by lifting upwards.• refiting : engage the chamber on the arcinghorns.• reinstall the locking pins (1)

3A - Arcing Contacts S800 - 2500A• replacement maximum wear limit : 1.5 mm

3A - 1 fixed arcing contact breaker in “open”position• loosen the screw (1)• slide the arcing contact forwards

3A - 2 moving arcing contact / breaker in “closed”position• loosen the screws (2) by about 1.5 mm• free the locator and pull the arcing contact• tightening torque : 3 Nm

3A - 3 gap adjustment breaker in “closed” position• move the fixed arcing contact in order to obtaina dimension of 0.9 ± 0.1 between the end arcingcontacts.• tightening torque : 8 Nm

1A - Adjustment and CheckingAdjustment and checking operations arenormally carried out on equipment before itleaves the factory. It is, however, necessary toverify these points during maintenanceoperations. A maximum wear limit is specifiedfor each paragraph in order to facilitate thisprocedure. When satisfactory adjustment is nolonger possible, the part concerned must bereplaced.

1

2

4A - Arc Barrier• Replacement

4A - 1 Extract the staples (1) with a screwdriver• refit by carrying out operations in the reverseorder.• install new staples.

1

0.9±0.1

1

0.9±0.1

2A - Arc Chute S800 - 2500AReplacement

Spectronic Air Circuit Breaker - Operating Instructions

30

1C - Adjustment and CheckingAdjustment and checking operations arenormally carried out on equipment before itleaves the factory. It is, however, necessary toverfiy these points during maintenanceoperations. A maximum wear limit is specifiedfor each paragraph in order to facilitate thisprocedure. When satisfactory adjustment is nolonger possible, the part concerned must bereplaced.

3C - 2 After removing the arc chutes and circuitbreaker position “open” :• undo the bolts (1)• slide the arcing contacts forward

2C - Arc Chute S3200 - 4000AReplacement

3C - 4 Setting the gap for “closed” position circuitbreaker• adjust the arcing contact to obtain a dimension0.9 ± 0.1• tightening torque : 8 Nm

Replace the Arc Chute• unscrew the knurled button

3C - 1 Arcing Contacts S3200 - 4000A• replacement wear limit : 1.5 mm

3C - 3 Circuit breaker position “closed”• remove the 2 nuts (2)• slide the arcing contacts by pushing towardsthe front after opening of the circuit breaker.

2

1

0.9±0.1

27

Checking - Replacement - Adaptation

Spectronic Air Circuit Breaker - Operating Instructions

31

5A - 1 Disconnect the wiring 5A - 2 Extract pin (2) after removing the two rings(1)

5A - 3 Take out the two screws (3) to remove thecluster contacts (withdrawable 800 to 2500)Rating 2500A maintain the clamps underpressure until they are refitted.

5A - 7 Refit by performing the operation in thereverse order (do not forget the insulating sleevesaround the studs). The screws (3) and (4) are tobe tightened after fitting the assembly pin (2).Tightening torque for screws (3) : 4 Nm.

5A - Current Transformer S800- 2500A• replacement

12

3

5A - 4 Remove the 4 screws (4) (nuts for rating2000), withdraw the pillars (5) with the clamps(removable 2000A) or connection fittings (fixedbreaker).

5A - 5 Remove the transformers

5A - 6 Setting of wire of the transformer ofreplacement using the preinsulated sleevedelivered with the current transformer’s

6A - Pole Tightening• check on tightening- close the breaker. Check the tightening torqueon rams (V) 4 Nm on each flange.

V

5

4

2500A

28

Spectronic Air Circuit Breaker - Operating Instructions

32

5B - 1 Circuit breaker “open”• Remove the arc chute• Disconnect the wiring

5B - 2 Remove the 4 bolts and remove theprimary jaw

5B - 3 Remove the 4 bolts (2). 5B - 4 Lift the fixed contact assembly to removethe transformer.

5B - 5 Reassemble in the reverse sequencepaying attention to the assembly position of theprimary jaw.

5B - 7 Check the arcing contacts gap

5B - Current TransformerS3200 - 4000A• Replacement

2

5B - 6 Setting of wire of the transformer ofreplacement using the preinsulated sleevedelivered with the current transformers.

29

Spectronic Air Circuit Breaker - Operating Instructions

33

7 - 3 To remove the RMS7 / 9D Unit from its mechanical support, push the lever (4) to the top and pull it . 7 - 4 Disconnect the connector (5).Replacement : plug in the connector (5) on thetrip unit and filt the unit on its support in the sameway as the dismounting operation.

7 - 5 Attach the front panel (12) with four 5Øscrews (2). Tilt the operating handle forwards tofacilitate installation.

7 - 6 Refit the front cover (10) with four 4Ø screws(1).Inspection : check electrical operation with thetest set (checking instructions inside the test box).

7 - 2 Remove the front panel (12), by taking outthe four 5 Ø screws (2)• tilt the operating handle forward to facilitateremoval

7 - 1 Breaker in “open” position• remove the front cover (10), by taking out thefour 4Ø screws (1)

7 - RMS7 and RMS10, RMS12• Replacement

4 5

12 2

2

1

10

1

12

2

2

4

1

10

1

RMS7 and RMS10, RMS12

Spectronic Air Circuit Breaker - Operating Instructions

34

8 EX (Trip Coil) EX RMS• Replacement

8 - 7 Remove the 6Ø attaching nuts (14) fromthe EX support plate with a 10mm wrench.

8 - 6 Remove the hook-up by taking out the two6Ø screws (13), using a 10mm wrench.

8 - 5 Uncouple rod (6) from the crank (7) of tripswitch EX, removing ring (8) and pin (9).

8 - 1 Breaker in “open” position• remove the front cover (10) by taking out thefour 4Ø screws (1)

8 - 2 Remove the front panel (12), by taking outthe four 5Ø screws (2)• tilt the operating handle forward to facilitateremoval

8 - 3 To remove the RMS7, RMS10, RMS12 Unit from its mechanical support,push the lever (4) to the top and pull it .

8 - 4 Disconnect the connector (5).Replacement : plug in the connector (5) on thetrip unit and fit the unit on its support in the sameway as the dismounting operation.

7

6

98

13

14

4

12 2

2

1

10

1

4

5

Spectronic Air Circuit Breaker - Operating Instructions

35

8 - 8 Remove the support plate from EX by takingout one 5Ø screw (15).

8 - 11 Refit the fixed section of the new connector(4)

8 - 12 Refit by carrying out the same operationin reverse order. Connect up the connectors.

8 - 9 Remove the fixed section of connector (4). 8 - 10 Refit the new EX on the support plate withone 5Ø screw (15).

8 - 14 Refit the front cover (10) with four 4Øscrews (1).

8 - 13 Refit the front panel (12) with by four 5Øscrews (2). Tilt the operating handle tofascilitate installation.

1

1

10

12

2

15

15

4

42

32

Spectronic Air Circuit Breaker - Operating Instructions

36

Overcurrent release RMS S800 - 2500A

A - Breaker with no memory type tripping indication (local-reset circuit-breaker)

9A - 2 Breaker in “open” position, with trip releaseand crank (11) against stop (10)• adjust the link rod (9) to obtain 1 ± 0,5

9A - 3 Push trip button BPDL (12) fully in on thefront panel• adjust the screw (14) so as to latch the release• loosen the screw by one turn to obtain therequired resetting safety margin.

9A - 1 Resetting• breaker without memory-type trippingindication (local-reset circuit-breaker)

9A - 5 Check that there is a minimum play of 0,2mm between the armature (13) and the adjustingscrew (14)• press trip push button BPDL (12) fully in andcheck that there is a minimum play of 0,2 mmbetween the spigot (5) on the latch (4) and thebottom of the recess.(A) latched.

9A - Verification of Resetting

9A - 4 Operate trip push button BPDL (12) andcheck that there is a latching safety margin of0.5 mm : return of release crank on latching.

33

Reset checking

Spectronic Air Circuit Breaker - Operating Instructions

37

Overcurrent release RMS S3200 - 4000A

A - Breaker with no memory-type tripping indication (local-reset circuit-breaker)

9B - 2 Check the play by holding the crank (11)on its stop (10), the rod (12) on the axis (13),evaluate the distance/clearance by alternatelydisplacing the rod.

9B - 3 Push down on the local reset and trip pushbutton (14) situated on the panel.• adjust the screw (15) to achieve a trip.• unscrew one turn to obtain reset clearance.• a very distinct trigger signal is made on themoment of tripping.

9B - 1 Circuit breaker “open” position, tripreleased, crank (11) pushing on its stop (10) therod (12) at the bottom of the slot on the axis (13),set the rod (9) to obtain the dimension 1 ± 0.5mm.

9B - 5 Push fully on the local reset and trip pushbutton (14) and check for a minimum play of 0.2mm between the pin (5) of the lock (4) and thebottom of the slot (see sketches9-3 and 9-4).

9B - Verification of Resetting

9B - 4 Circuit breaker position “open” push the local trip and reset button (14) and check a safetylinkage clearance of 0.5 mm: trip crank returns on engagement.• Push button at rest, rod on its stop.• Check for a minimum play of 0.2 mm between the plate (16) and the adjustment screw (15).

34

Reset Checking

Spectronic Air Circuit Breaker - Operating Instructions

38

35

B - Breaker equipped with memory-type indication of tripping due to overload and short-circuit (automatic reset circuit-breaker)

9 - 6 Breaker in “open” position• adjust the screw (1) so as to obtain latching ofthe release• screw in 3/4 of a turn in order to obtain therequired resetting safety margin.Note : a very distinc sound can be heard whenlatching occurs.

C - Breaker with no trip device (Switch) 9 - 8 Breaker in “open” position• check that there is a minimum play of 0.5 mmbetween the actuating part (11) operated ontripping and the spigot (12) on the latch (13) inthe rest position.• check that there is a minimum play of 2 mmbetween the reset screw (16) and the actuatingpart (11)

9 - 7 Checking• breaker in “open” position• check that there is a latching safety margin of1.5 mm :return of release crank on latchingWEAR LIMIT : failure to latch.(A) latched (R) reset

9 - 9 Tripping with RMS• check that there is a minimum play of 2mmbetween the reset screw (16) and the trippingbreaker in “open” position• reset adjusting screw (1) fully unscrewed.

9 - 11 Checking• breaker in “closed” position.• check that there is a minimum play of 0,5 mmbetween the actuating part (6) operated ontripping and the spigot (5) on the latch (4) in thereset position.WEAR LIMIT : 0.1• connect up the TEST box and test the variousfunctions in accordance with the instructionsgiven in the test box• check that the breaker trips normally on eachtest .

9 - 10 With the release latched, adjust thelink rod (7) to obtain a dimension of 1 ± 0,5between the actuating part (6) operated ontripping and the spigot (5) on the latch (4) inthe rest position.

Resetting

S800/2500A S3200/4000A

Spectronic Air Circuit Breaker - Operating Instructions

39

Options for protection units RMS7, RMS10, RMS12

Affix the lead (4).Feed through the lead wire (3).

Set the lead (lead + wire not supplied). End of operation.

Fit this sub-assembly on the unit.Fit (2) onto the sealable cover (1).10 - LEAD SEALING THE RMSSETTINGSInstallation - Replacement

1

2

2 1

3

34

Spectronic Air Circuit Breaker - Operating Instructions

40

37

11 - Voltage-threshold tripdevices• Replacement

11 - 2 Remove the ring (1) to un-couple the linkrod

11 - Disconnect the wiring

11 - 3 Take out the two screws (2) and removethe release

11 - 5 Checking• tripping with breaker in “open” position• resetting adjusting screw (item (7) in figurebelow) fully loosened

11 - 4 Refit by carrying out the same operationsin reverse order

11 - 6 With the release latched, adjust the linkrod (1) to obtain a dimension of 1 ± 0.5 betweenthe lever (2) and the spigot (3) on the latch (4) inthe reset position.• breaker in “closed” position• hold the striker (6) with a hook (C) in order toavoid acting against opening when resetting therelease, and free the release latch mechanism.Free the latch slowly to check that the breakertrips.

11 - 1 Disconnect the wiring

11 - 7 Resetting with breaker in the “open”position• adjust the screw (7) to position the striker (6)fully home.• unscrew by half a turn• check that there is a safety margin minimumresetting of 2 mmWEAR LIMIT : failure to resetNB : If the breaker is equipped with two voltmetricreleases, check that both releases operatecorrectly after adjustment.

1

S-800 - 2500A S3200 - 4000A

2

6

Spectronic Air Circuit Breaker - Operating Instructions

41

12 - 2 Disconnect the wiring

12 - 5 Refit by carrying out the same operationsin reverse order

12 -1 After removal of the protective plate fromthe front panel and protection RMS :• breaker in the “open” position : access to contacts (1, 2, 3, 4)• breaker in the “closed” position : access to contacts (5, 6, 7, 8)

12 - Auxiliary• Replacement

12 - 3 Loosen the screw (1) and remove thecontact

12 - 4 Remove the contact from its support (2)

1

38

Spectronic Air Circuit Breaker - Operating Instructions

42

13 - Electrical Operator - Motor• Replacement

13 - 2 Disconnect the wiring from the terminals13 - 1 After removing the front cover

13 - 6 Refit by carrying out the same operationsin reverse order, checking that there is workingplay between the pinion and the gear wheel• reconnect the wiring

13 - 3 Loosen the 2 screws (1)• remove the motor

13 - 4 Following removal of the cover• disconnect the wire terminals

1

S800 - 2500A

S 800 - 2500A

S3200 - 4000A S3200 - 4000A

13 - 5 Loosen the 2 screws (2)• remove the motor

2

39

Spectronic Air Circuit Breaker - Operating Instructions

43

14A - Reset limit switchS800-2500A• Replacement

14A - 1 After removing the front cover, unscrewthe nuts• remove the contact

14A - 2 Disconnect the wiring14A - 3 Reconnect the wiring onto the newcontact• refit by carrying out the same operations inreverse order, checking that the spacers are stillin place on the attachment screws.

14B - Reset limit switchS3200-4000A• Replacement

14B - 4 Reconnect the wires on the new contact• reassemble in the reverse order, making surethat the spacers remain in position on the fixationbolts.

14B - 1 Unscrew the nut (6), 10 mm spanner.

6

14B - 2 Remove the plate support handle

14B - 3 Unscrew the 2 nuts (7) (8mm spanner)• remove the contact• disconnect the wire

7

40

Spectronic Air Circuit Breaker - Operating Instructions

44

Note : Unused parts are to be discarded

15A - 4 Reconnect the wiring onto the newcontact and refit by carrying out the sameoperations in reverse order

15A - 3 Disconnect the wiring and mark thepositioning of the wires

15A - Resetting spring contactS800-2500A• Replacement

15A - 1 Lay down the circuit-breaker of the leftpanel

15A - 2 Loosen the screw (1) and take out thecontact/support assembly (using two 10 mmwrenches)

15B - Resetting Spring ContactS3200-4000A• Replacement

15B - 1 Undo the 3 Ø5 screws (5) and lift out theplate support assembly and RMS trip release.

15B - 2 Disconnect the wire marking the positionof the wires

1

5

5

41

Spectronic Air Circuit Breaker - Operating Instructions

45

16A - 3 Swing the link rod (4) forwards to fit thescrews (3) and plate (1), 5.5 mm wrench

16A - 4 Fit the contact as described in theprevious section

16A - 1 Unhook the spring (3) and note itsdirection of installation for refittng

16A - Resetting spring contactS800-2500A• adaptation (1) plate

(2) contact (3) screws

15B - 4 Take out the contact support assembly15B - 3 Undo the screws(3)

15B - 5 Reconnect the wire on the new contactsupport assembly and assemble in the reverseorderNote : The parts provided which are not usedare to be discarded.

1

2 3

3

16A - 2 Remove the screws (1) using two10mm wrenches

1

4

3

3

4

42

Spectronic Air Circuit Breaker - Operating Instructions

46

43

16B - 2 Gently incline the handle forwards toallow the installation of the bolt (3)

16B - 1 Undo the 3 Ø5 bolts (5) and remove theplate support assembly and RMS trip release.

16B - Resetting spring contact3200-4000A• adaptation(1) plate(2) contact(3) screws

16B - 3 Install the contact support assembly (2)paying attention to the positioning of themoving plate of the contact

16B - 4 Tighten the assembly bolts, washer, nut(3)

16B -5 Reassemble in the reverse orderNote : The parts provided which are not usedare to be discarded.

5

2

3

3

5

Spectronic Air Circuit Breaker - Operating Instructions

47

44

17A - 1 Disconnect the wiring after removing thefront cover, the front panel and protection RMS.

17A - Closing PreventionDevice S800-2500A• Replacement

17A - 2 Remove the two attachment screws• refit the new closing prevention device bycarrying out the same oepration in reverse order.

17B - 1 After removing the front cover, disconnectthe wire• Remove the closing prevention device

17B - Closing PreventionDevice S3200-4000A• Replacement

17B - 2 Reassemble the new closing preventiondevice in the reverse order.

17A - 3 Adjustment• breaker energizedwith parts (57, 58 and 59) resting on their stops,adjust the elbowed lever (60) to obtain a play of0.6 ± 0.4• checking :- check that there is a minimum play of0.2 mm

17A - 4 Wear limit : 0.1 mm• in this position, the device allows engagementof the mechanism.• with the device de-energized and lever (59)resting at its stop, check that there is a minimumplay of 0.1 mm between level (58) and the pin(61)• the device does not allow engagement in thisposition.

Spectronic Air Circuit Breaker - Operating Instructions

48

45

17B - 3 Setting• Circuit Breaker “open”(1) set the gap to 0.5mm between the trip lever(1) and the axis (3) by turning the cam (4), tightenup the lock nut.

17B - 4 Setting• electrical-supply(1)set the play to 0.5 mm between the pin 2and the axis of the crank 5 by adjusting thenut 6 of the reset and trip push button,tighten the lock nut.(2) set the play to 0.5 mm between the pin 2and the axis of the crank 7 by tightening orslackening the latter, tighten the lock nut.

18A - 2 Remove the pin (1)18A - 1 Disconnect the wiring after removing thefront cover, the front panel and protection RMS.

18A - Closing Coil S800-2500A• Replacement

18A - 3 Take out the four screws (2)• remove the closing coil• refit by carrying out the same operations inreverse order

2

1

Spectronic Air Circuit Breaker - Operating Instructions

49

46

19A - 1 After removing the front cover, disconnectthe wiring, Remove the cut-out chambers foreasier access to the terminal.

19A - 2 Loosen the 2 screws (1)• remove the contact• refit by carrying out the same operations inreverse

19A - Insertion Contact S800-2500A(Direct Current)• Replacement

18B - 1 After removal of the front cover,disconnect the wire• remove the 4 bolts (2)

18B - 2 Remove the axis pin (1)• remove the closing electro magnet• reassemble in the reverse order

18B - Closing Coil S3200-4000A• Replacement

19B - 1 After removal of the front cover,disconnect the wire, lift out the arc chutes tofacilitate access to the terminals.

19B - 2 Unscrew the 2 bolts (1)• remove the contact• reassemble in the reverse order

19B - Insertion Contact S3200-4000A(Direct Current)• Replacement

1

2

1

1

Spectronic Air Circuit Breaker - Operating Instructions

50

47

20A - Economy Resistor S800-2500A(Direct Current)• Replacement

20A - 1 After removing the front cover, disconnectthe wiring. Remove the cut-out chambers foreasier access to the terminal.

20A - 2 Loosen the 2 screws (1)• remove the contact• refit by carrying out the same operations inreverse order

20B - Economy Resistor S3200-4000A(Direct Current)• Replacement

20B - 1 After removal of the front cover,disconnect the wire, lift out the arc chutes tofacilitate access to the terminals.

20B - 2 Unscrew the 2 bolts (1)• remove the resistor• reassemble in the reverse order

1

1

Spectronic Air Circuit Breaker - Operating Instructions

51

48

21A - Isolating Shutters S800 -2500A• Installation

21A - 1 Identification

21A - 3 Fit the parts (8), (9), (10) and (11) on thepins (7)

21A - 2 Install the padlocking system (14) withattachment hardware (15)

21A - 4 Secure the right-hand mechanism (4) onthe right-hand flange with 2 screws and washers(5)

21A - 5 Engage the upper spigot on the pin (7) inthe hole (C)• slide the pin for part (10) into the fork (A)

21A - 6 Engage the lower spigot on the pin (7)into the bracket (13) and secure it withattachment hardware (12).

21A - 7 Engage the link rod (B) on the pin for part(11)

3 5 6

12

5

8

9

16

13 1817

13

12

10

11

5

4562

7

1

7

1415

11

10

77

8

9

C

A

10

B11

713

12

Spectronic Air Circuit Breaker - Operating Instructions

52

49

21A - 8 Fit the ring (6) 21A - 9 Carry out the same operation on the left-hand side and then install the shutters (1) withattachment hardware (2).

21A - 10 Fit the spacers (18) on the guide plates(16) and (17) with attachmenthardware.

21A - 11 Fit the right and left-hand assembly ontothe circuit-breaker.

6

Spectronic Air Circuit Breaker - Operating Instructions

53

50

21B - Isolating Shutters S3200 -4000A• Installation

21B - 1 Identification

21B - 3 Remove the 3 nuts, lock washers and flatwashers. On reassembly do not re-use the flatwashers.

21B - 2 Install the padlock mechanism (14) withthe aid of the bolt set (15).

10

824

5

17 187 25

26

9

11

7

18

2

16 14

1

1322

21

4

15

11

7 7

89

10

22

Spectronic Air Circuit Breaker - Operating Instructions

54

51

21B - 5 Fix the right mechanism (4) on the rightflask and the mechanism (24) on the left flask withthe aid of the 2 bolts and washers (25).

21B - 4 To engage the rod (B) on the axis ofmechanisms (9 right and 8 left) to put rings (6)after having positioned the sets (11-4 right and10-24 left) enters square (13) and top of cradle.

21B - 8 Check the operation of the shutters andinter-locks.

21B - 6 With all parts being correctly assembled,complete by tightening up the nuts and checkingthe operation.

B

21B - 7 Install the upper screen (1) with the boltset (2) and the lower screen (21) with the bolt set(26).

21B - 9 Install the spacers (18) on the guide plate(16) and (17) with the aid of the bolt sets.

21B - 10 Mount the left and right assembly onthe circuit breaker.

8/9

10/11 4/24

13

25

Spectronic Air Circuit Breaker - Operating Instructions

5552

Fixed or Withdrawable Breaker - Interlocking in "tripped" position

22 - 2 Remove the front panel (2) by taking outthe four 5Ø screws.Tilt the operating handle forward to facilitateremoval.

22 - 1 With the breaker open, remove the frontcover (1) by taking out the four 4Øscrews.

22 - With Padlock Fitting• Fitting

22 - 6 Tighten the guide plates (5) and (7) withrecovered screws (8) and screws supplied in thebag (9).

22 - 3 Break through the imprint (3) to allowinsertion of the padlock tab (4).

22 - 5 Engage the link rod (6) by raising thepadlock tab (4).

22 - 7 Hook up the spring (10). 22 - 8 Refit the front panel (2) with four 5Ø screws,and refit the front cover (1) with four 4Ø screws.

4

3

21

6

22 - 4 Remove the guide plate (5) and recover 2screws (8).

10

21

4

6

9

7

9 10

4

9

75

8

5

8

Spectronic Air Circuit Breaker - Operating Instructions

5653

Fixed or withdrawable breaker - Interlocking in "tripped" position

23 - 1 With the breaker open, remove the frontcover (1) by taking out the four 4Ø screws.

23 - 2 Remove the front panel (2) by taking outthe four 5Ø screws.Tilt the operating handle forward to facilitateremoval.

23 - With Padlock and GE ACB / RONISlockRONIS Lock Type 1104, 1/4 turn left-handopening or PROFALUX lock, type KS 5B 20 G4Y(not supplied).

23 - 3 Break through the imprint (11) to allowinsertion of the lock (12) in the front panel (2).

23 - 4 Break through the imprint (3) to allowinsertion of the padlock tab (4).

23 - 5 Remove the guide plate (5) and recover 2screws (8).

23 - 6 Fit the GE ACB / RONIS lock or PROFALUXlock (12) with collar, with the key imprint facingdownwards.

23 - 7 Fit the corresponding cam (A or B) for thelock : A = RONIS B = GE ACB or Profalux. Lock thenut. Take care to install the cam the right wayround so that the key is removed in lockedposition.

23 - 8 Fit the padlock tab (4).

1212

2

4

A

3

4

1

6 A B

7 9

10

4

12

2

11 5

8

Spectronic Air Circuit Breaker - Operating Instructions

57

54

23 - 9 Engage the link rod (6) by raising thepadlock tab (4).

23 - 11 Hook up the spring (10).23 - 10 Tighten the guide plates (5) and (7) withrecovered screws (8) and screws in the bagsupplied (9).

6

10

4

23 - 12 Refit the front panel (2) with four 5Øscrews.

23 - 13 Refit the front cover (1) with four 4Øscrews.

2 1

8

5

9

7

Spectronic Air Circuit Breaker - Operating Instructions

5855

Fixed or withdrawable breaker - Interlocking in "tripped" position

24 - With GE ACB / Ronis locktype 1104 1/4 turn left-hand openingor PROFALUX lock type KS 5B 20 G4Y (notsupplied)

24 - 1 With the breaker open, remove the frontcover (1) by taking out the four 4Ø screws.

24 - 2 Remove the front panel (2) by taking outthe four 5Ø screws.Tilt the operating handle forward to facilitateremoval.

24 - 3 Break through the imprint (11) to allowinsertion of the lock (12) in the front panel (2).

24 - 7 Engage the link rod (6).

24 - 5 Fit the GE ACB / Ronis lock or PROFALUXlock (12) with collar, with the key imprint facingdownwards.

24 - 6 Fit the cam (A or B) for the lock : A = RONISB = GE ACB or Profalux. Lock the nut . Take careto install the cam the right way round, so thatthe key is removed in the locked position.

24 - 8 Tighten the guide plates (5) and (7) withrecovered screws (8) and screws in the bagsupplied (9).

10

A

6

12

24 - 4 Remove the guide plate (5) and recover 2screws (8).

12

21

A B

7 9

12

5

8

11

2

8

5

9

7

6

Spectronic Air Circuit Breaker - Operating Instructions

59

56

24 - 10 Refit the front panel (2) with four 5Øscrews.

24 - 9 Hook up the spring (10). 24 - 11 Refit the front cover (1) with four 4Øscrews.

10

2

1

Spectronic Air Circuit Breaker - Operating Instructions

6057

Fixed or withdrawable breaker - Interlocking in "tripped" position

25 - 1 With breaker open, remove the front cover(1) by taking out the four 4Ø screws.

25 - 2 Remove the front panel (2) by taking outthe four 5Ø screws.Tilt the operating handle forward to facilitateremoval.

1

25 - 4 Remove the guide plate (5) and recover 2screws (8)

25 - With Single Letter CastellLock

25 - 5 Fit the Castell Lock (12) with collar, withthe key imprint facing downwards

25 - 6 Fit the cam on Lock (12) with nut andwasher. Take care to install the cam right wayround, so that the key is removed in the lockedposition.

2

12

25- 3 Break through the imprint (11) to allowinsertion of the lock (12) in the front panel (2).

1216

25 - 7 Engage the link rod (6). 25 - 8 Tighten the guide plates (5) and (7) withrecovered screws (8) and screws in the bagsupplied (9).

12

6

10

5

16

8 9

7

6

2

11 5

8

8

5

9

7

Spectronic Air Circuit Breaker - Operating Instructions

61

58

25 - 10 Refit the front panel (2) with four 5Øscrews.

25 - 9 Hook up the spring (10). 25 - 11 Refit the front cover (1) with four 4Øscrews.

10

2

1

Spectronic Air Circuit Breaker - Operating Instructions

6259

Fixed or withdrawable breaker - Interlocking in "tripped" position

26 - CASTELL LOCK 2 LETTER or CASTELL LOCK 1 LETTER + GE ACB / RONIS LOCK

26 - 3 Machine the front panel (2) in accordance with this drawing for insertion of castell lock 2 letter or castell lock 1 letter (37mm dia).

Place the drilling templateSGS 6100096 as shown &drill hole Ø37 ± 0.2 (Removethe template after comple-ting the drilling operation).

CASTELL LOCK KEY

M6 NUT (15)

M6 STAR WASHER (15)

SCREWS (13)

SPRING (10)

PUSH BUTTON BASE

SELF TAPPING SCREWS(9)

SPACER (11)

SUPPORT (4)

LINK ROD (6)

26 - 3 Break through the imprint (11) to allowinsertion of GE ACB / Ronis lock in the front panel(2).

GE ACB / Ronis Lock

CASTELL LOCK(12)

26 - 1 With breaker open, remove the front cover(1) by taking out the four 4Ø screws.

26 - 2 Remove the front panel (2) by taking outthe four 5Ø screws.

2

1

2

11

Spectronic Air Circuit Breaker - Operating Instructions

63

60

26 - 5 Engage the spacer (17) on the lock (12)above the cam (16)

26 - 4 Fit the cam (16) on the lock (12) Take careto install the right way round: so that the key isremoved in the locked position

26 - 6 Position the screws (13) on the lock (12)and spacers(11)

26 - 8 Attach the lock with the contact washers(19) and nuts (15) using a 10 mm wrench

26 - 7 Fit the lock (12), assembled as describedabove, on the support (18)

26 - 10 Engage the link rod (6)26 - 11 Install the support / lock assembly alongwith the recovered screws (8) and the screwssupplied in the bag (9), making sure that the cam(16) is positioned under the link rod (6) and behindthe spigot

1312

1117

12

16

12

16

18 12

15

19

19

15

26 - 9 Remove the guide plate (5) and recover 2screws (8).

5

8

6

89

Spectronic Air Circuit Breaker - Operating Instructions

64

61

26 - 13 Refit the front panel (2) with four 5Øscrews.

26 - 14 Refit the front cover (1) with four 4Øscrews. (front facia with double letter or singleletter (37mm dia) castell lock )

26 - 12 Hook up the spring (10)

10

26 - 15 to fix the GE ACB / Ronis lock follow thesteps decribed in 24-3 to 24-6.

26 - 16 front facia with single letter castell lock(37mm dia) and GE ACB / Ronis lock. This singleletter castell lock (37 mm dia) is different fromthe stand alone single figure castell lock whichis fixed in the position of GE ACB / Ronis lock.

2

1

Spectronic Air Circuit Breaker - Operating Instructions

6562

Withdrawable breaker - Interlocking in "Withdrawn" / "Connected" position

27 - With GE ACB / RONIS locktype 1104 1/4 turn right-hand openingor PROFALUX lock, type KS 5B 20 D4Y (notsupplied).

27- 3 Remove the front box mould (20) from thebreaker's cradle by taking out the two 5Ø screws.

27 - 6 Fit the corresponding cam for the lockchosen and secure it by locking the nutfor GE ACB / RONIS lock : cam (13) and nut (3)for PROFALUX lock : cam (14) and nut (30)Take care to install the cam the right way roundso that the key is removed in the locked position.

27 - 1 The lock is attached onto the front box (20)on the breaker's cradle.

27 - 2 Remove the sleeve (5) by removing the3Ø screw

27 - 4 Break through the imprint to fit thelock

27 - 5 Position the lock (12) and collar withthe corresponding nut: GE ACB / RONIS lockwith nut (3) / PROFALUX with nut (30). Thekey imprint must be facing downwards.

20

27 - 7 Refit the front box mould (20) on the cradlewith the horizontal captive key. Stick on the label(32) as shown above. Refit the sleeve (5).

27 - 8 Cradle with 2 locks, GE ACB / Ronis Lockand Padlock

Note: The maximum number of interlockingdevices that can be installed on a cradle is one‘’connected’’ / ‘’withdrawn’’ position GE ACB /Ronis lock and one ‘’withdrawn’’ / ‘’connected’’position Padlock.

5

205

3

14

12

13

30

32

13

20

3

12

Spectronic Air Circuit Breaker - Operating Instructions

66

63

28A - Fault Signalling ContactS800-2500A

• Replacement

28A - 1 Bag containing 1 contact

28A - 2 Packets of 2 contacts 28A - 3 Location on the equipment. Rest thebreaker on the left-hand flange and lockunderneath, at the cross-member, zone A.

28A - 6 Disconnect the wiring and mark thelocations of the wires :- 1st contact : 95 - 96 - 98- 2nd contact : 05 - 06 - 08Discard the support-contact assembly, screws.

28A - 7 Place the new support in position andreconnect the wiring on the contact.Taking care to comply with the markings.

28A - 8 Position the support/contactassembly and secure it with the attach-ment hardware supplied : two screws 5x16,two 5 Ø DE washers, and two 5 Ø nuts, usingan 8 mm wrench.

28A - 9 Check the position of the crank (3) withrespect to the armature for the contact or contacts.Check for correct operation with the breakeropen and the fault contact actuated.NOTE : Unused parts and wires are to bediscarded.

28A - 5 Swing the support/contact assembly(1 or 2) towards you (2).

28A - 4 Loosen the two screws (1) 5Ø x 16, with a8 mm wrench.

A

12

3

Spectronic Air Circuit Breaker - Operating Instructions

67

64

28B - Fault signalling contactS3200-4000A

• Replacement

28B - 1 Bag containing 1 contact

28B - 2 Bag containing 2 contacts 28B - 3 Unscrew the 3 5Ø screws (5) and lift outthe plate support assembly and RMS trip release.

28B - 6 Undo the 2 nuts (1), 8mm spanner.

28B - 7 Unscrew the plate and slide to the left(facing the circuit breaker).

28B - 8 Swing the support assembly and contacttowards yourself (2).

28B - 9 Disconnect the wire whilst marking theposition of the wires.- 1st contact : 95 - 96 -98- 2nd contact : 05 - 06 - 08Throw away the contact support assembly.

28B - 5 Undo the fixation nuts 6Ø (14), 10 mmspanner, of the EX plate support.

28B - 4 Uncouple the arm (6) of the crank (7) of theEX trip release by removing the clips (8).

6

7

8

141

5

2

5

Spectronic Air Circuit Breaker - Operating Instructions

68

65

28B - 10 Present the new support and reconnectthe wire to the contact.Pay attention to the marking.

28B - 11 Position the contact support assemblyand fix with the nut and bolt set provided (two5Øx16 bolts + two 5Ø washers + two 5Ø nuts), 8mm spanner.

28B - 12 Check the position of the crank (3)relative to the contacts plate. Check the operationwith the circuit breaker "open" and fault contactactivated.Note : The parts and wires not used should bediscarded.

3

Spectronic Air Circuit Breaker - Operating Instructions

69

Spectronic Air Circuit Breaker - Operating Instructions

70

67

29 - 10 Fixed sectionNOTE : If the craddle is fitted with a spacer, attachthe cut-off block onto that spacer.

29 - 11 Secure the fixed block onto the cradle,to the right or left-hand side, according to themovable section, using the attachment hardwaresupplied (zone B of the craddle flange).

29- 16 Fixed sectionAttention : The 3rd block is never factory-installedon the fixed section.NOTE : If the 2nd block is fitted with a spacer, the3rd block must imperatively be fitted with thespacer supplied.

29 - 14 Secure the movable block to the right-hand or left-hand flange of the circuit-breakerusing the attachment hardware supplied (zone Cof the flange).

29 - 15 Connect the Wiring29 - 13 Adaptation third block• Movable section

29 -17 Removing the attaching plate used duringtransportation and secure the 3rd block (zone Cof the right or left-hand flange of the cradle)according to the movable section of the circuit-breaker, using the attachment hardware supplied.

29 - 18 Remove the cover to connect up thewiring, Refit the cover.NOTE : Customer connection by clips 6.35 x 0.8.

29 - 12 Connect up the Wiring

C

B

C

Spectronic Air Circuit Breaker - Operating Instructions

7168

Withdrawable breaker - Earth connector 25 KA 0.5 S

30 - 2 Movable section (2)30 - 1 Contents of bag

30 - 4 Place the connector (2) in position on the

right-hand flange and insert the threaded studsand screw (1) in the corresponding holes.

30 - 5 Fit the three 6 Ø contact washers (3) and

the three 6 Ø nuts (4). Lock the assembly with a 10mm wrench.

30 - Fitting

30 - 3 Fit the screw (1) 6 Ø x 16, in the hole in the

movable connector (2).

1

2

2

1

3

4

S800 - 2500A

S3200 - 4000A

3

2

4

1

12

156 7 1

2

4

3

4

13

10 115

Spectronic Air Circuit Breaker - Operating Instructions

72

69

30 - 6 Fixed section (14) 30 - 7 Take the small columns (5) and assemble

them as shown above with renforcement piece(6) and the connecting component (15) on theside with the longest thread.

30 - 8 Fit the two 8 Ø plain washers (7) and the

two 8Ø nuts (9).Lock the assembly with a 13 mm wrench.

30 - 9 Place the assembly in position fitted in

the craddle to the bottom right-hand side of zoneB at the back.

30 - 10 With the two studs fitted in the

corresponding holes, fit the two 8 Ø DE washers(10) and the two 8Ø nuts (11). Lock them witha 13 mm wrench.

30 - 11 Position the label (12) in between the

two "CUSTOMER EARTH" connecting screws asdesired, as shown above.

NOTE : The two bigger columns (13) suppliedin the bag are to be used in place of thetwo smaller columns (5) for Spectronic circuit-breakers 3200 and 4000A.Discard the unused parts.

7 - 9

10 - 1112

B

15

5

6

9

6

13 12 15

1110

5

7

Spectronic Air Circuit Breaker - Operating Instructions

7370

31 - Signalling contacts on cradle

• Adaptation

31 - 1 Attach the assembly onto the two studsprovided on the cradle, with two washers andnuts.Connect up the wiring. A grommet is providedfor the wiring feed-through.

31 - 2 Indicating contacts on cradle• Replacement

31 - 3 After disconnecting the wiring, remove theassembly with the support in order to facilitatereplacement of the faulty contact.

31 - 5 Extract the mounting pins (2)· Remove the contact

31 - 4 Remove the rings (1)

2

1

S800 - 2500A S3200 - 4000A

Spectronic Air Circuit Breaker - Operating Instructions

74

71

32 - 1 Screw the support/contact assembly ontothe craddle.

32 - Coupled Contact With plug-in Control

• Adaptation

32 - 2 Connect up the wiring, a grommetis provided for the

33 - Coupled Contact With plug-in Control

• Adaptation

33 - 1 Screw the support/contact assembly onto

the craddle.

33 - 2 Connect up the wiring, a grommetis provided for the wiring feed-through.

S800 - 2500A

S3200 - 4000A

Spectronic Air Circuit Breaker - Operating Instructions

75

Replacement PartsgnitaR eloP ot gnidroccA rebmuNnoitpircseD

S 800 1000 1250 1600 2000 2500111111stcatnoc gnicra dexiF543333stcatnoc gnicra eliboM222222sreirrab crA444444tnemhcatta reirrab crA

Arc chute 500V 1 1 1 1 1 1690V 1 1 1 1 1 1

111111SMR esaeler rof liocpirTNumber According to Pole Rating

S 3200 400064stcatnoc gnicra dexiF64stcatnoc gnicra eliboM

Arc chute 1 111SMR esaeler rof liocpirT

Number Per BreakerRating RMS7 800 1000 1250 1600 2000 2500 3200 4000

In 400A 1In 600A 1In 800A 1In 800A 1In 1000A 1

1A0521 nIIn 800A 1In 1200A 1In 1600A 1In 1200A 1In 2000A 1In 1600A 1In 2500A 1In 1600A 1In 3200A 1In 2500A 1In 4000A 1

)xam( rekaerB reP rebmuNnoitpircseDRMS7 1

Release RMS7 EX RMS 1Options RMS7 1RMS9D 2000 3P 1

Release RMS10/RMS12 RMS9D 2000 4P 1RMS9D 3200 3P 1RMS9D 3200 4P 1RMS9D 4000 3P 1RMS9D 4000 4P 1

Voltmetric ReleasesEA 50 Hz 110V 2

220V 2415V 2

EA DC 24V 2110V 2220V 2

UV 50Hz 220V 2415V 2

UV DC 24V 2110V 2

UVRD 50Hz 220V 2250 ms

To seenotes

RMS10/RMS12EX is built in

EX is built in

Spectronic Air Circuit Breaker - Operating Instructions

76

73

Description Number Per Breaker (max)

8CN1 + ON1 stcatnoc yrailixuAResetting motor for electrical operation S800-2500 S3200-4000

11V011zH0511V02211V42CD11V011

Closing coil for electrical operation S800-2500 S3200-400011V011zH0511V02211V42CD11V011

Economy resistor for DC closing coil24V R 11 1 1110V R 330 1 1

Insertion contact of 1 1economy resistor for closing coilClosing prevention device S800-2500 S3200-4000

11V011zH0511V02211

Spectronic Air Circuit Breaker - Operating Instructions

7774

Schematic DiagramRMS 7 : protection and monitoring unitDiagram showing de-energised circuits, open circuit breaker, connected, reset, handles not inserted.

Legend

Overcurrent releasesBA Overload and short-circuit fault contact

K1 Fault signalling relay

R1 Booster voltage for 220V

S1 Fault cancelling push-button

GF Ground fault indicator lamp

ST-I Instantaneous or short circuittripping indicator lamp

LT Long time trip (overload) tripping indicator lamp

Voltmetric releasesC41 Trip contact UVR-UVRD

C43 Undervoltage contact UVR-UVRD

C31 Trip contact EA

Ra-R6 Booster resistor for direct current voltages

S1 Optional disconnecting switch UVR-UVRD(break out of service)

Operation with energy storageM Motor

FCA Resetting limit switchManual setting

CA 1-8 Auxiliary contacts

EE Closing coil

EA Shunt Trip

S2 Remote tripping control

S5 Remote closing control

S3 Remote closing and tripping controlchangeover switch

C22 Reset contact of the spring

C20 Contact coupled with local reset tripping push-button

FE Closing prevention device

WithdrawableC51.52 Contacts ‘connected’ position

C61.62 Contacts ‘withdrawn’ position

C71 Pre-trip contact coupled with insertion control

Spectronic Air Circuit Breaker - Operating Instructions

7875

Schematic Diagram

End user connections

Withdrawable Circuit BreakerConnection by terminals 6.3 x 0.8For electrical operation of EA, BA1, BA2, UVR, UVRD, RMS7, LMZ7use the allocated numbers.Other accessories : numbers are increasing in the directionshown (use reserved terminals if they are available).

LT Disconnects

Spectronic Air Circuit Breaker - Operating Instructions

7976

Schematic DiagramRMS10, RMS12 : protection and monitoring unitDiagram showing de-energised circuits, open circuit breaker, connected, reset, crank not inserted.

Stored Energy ControlM Motor

FCA Resetting limit switch

Manual reset

AS 1-8 Auxiliary switches

Ra Economy resistor for selected voltages in directcurrent

EE Closing coil

EA Shunt Trip

S2 Remote trip push-button

S5 Remote closing push-button

S3 Remote closing and tripping changeover switch

C22 Spring reset contact

C20 Contact coupled with local resetting push-button

FE Closing prevention device

LegendAmmetricBA Overload and short-circuit fault contact

K1 Fault signalling relay

S1 Fault cancelling push-button

GF Ground fault display

ST-I Instanatneous or short-circuit tripping indicator lamp

LT Long time (overload) tripping display

Voltmetric ReleasesC41 Trip contact UVR-UVRD

C43 Undervoltage contact UVR-UVRD

C31 Trip contact EA

RQ-R6 Economy resistor for direct current voltages

S4 Optional disconnecting switch UVR-UVRD(circuit breaker disconnected)

WithdrawableC51.52 “Connected” position contact

C61.62 “Withdrawn” position contact

C71 Pre-tripping contact associated with plug-in controldevice

RMS10,RMS12

Spectronic Air Circuit Breaker - Operating Instructions

8077

Schematic Diagram

End user connections

Withdrawable circuit breakerConnection by terminals 6.3 x 0.8For electrical operation of EA, BA1, BA2, UVR, UVRD, RMS9D use the allocated numbers.Other accessories : numbers are increasing in the direction shown (use reserved terminals ifthey are available).

Spectronic Air Circuit Breaker - Operating Instructions

81

Ground fault Pickup setting to be done on 1250A Spectronic ACB GF Fault Threshold value of current corresponding

to the steps in adjoining tableGF Pickup to be set

Amps xX(steps in display of release)325 0.2

337.5 0.21350 0.22

362.5 0.23375 0.23

387.5 0.24400 0.25

412.5 0.26425 0.26

437.5 0.27450 0.28

462.5 0.29475 0.29

487.5 0.3500 0.31

512.5 0.32525 0.33

537.5 0.33550 0.34

562.5 0.35575 0.36

587.5 0.36600 0.37

612.5 0.38625 0.39

637.5 0.4650 0.4

662.5 0.41675 0.42

687.5 0.43700 0.44

712.5 0.44725 0.45

737.5 0.46750 0.47

762.5 0.48775 0.48

787.5 0.49800 0.5

812.5 0.51825 0.51

837.5 0.52850 0.53

862.5 0.54875 0.55

887.5 0.55900 0.56

912.5 0.57925 0.58

937.5 0.58950 0.59

962.5 0.6