Spectronic Air Circuit Breaker Operating Instructions
ProtectionRMS7 Trip• If the circuit breaker is to be reset in local mode,it must be reset manually after an overcurrentcondition by pushing in fully the local trip pushbutton 13.
Description :Powered by the current transformers, lmax = 4000, the RMS7 unitperforms all the necessary current protections with true rms value sensing:• overload protection (LT)• short-circuit protection (ST and I)• ground fault protection (GF) (The 4th (neutral) current transformer must be of the same rating as those of the three phases).
RMS7 : OptionsThe following options are field fittable
Distinct Fault Signalling (LT, ST, I, GF)• Local indication by LED display. this option is power supplied by an internal battery.• Lead sealing.
Setting Ranges Setting Points
LT (x ln) 0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.00
LTD (s) 5, 10, 15, 20, 25, 30, 35, 40 delay at 7.2 lr
ST (x ln) 1.5, 2, 3, 4, 5, 7, 9, 10, 12, 14
Delay (ms) 30, 60, 90, 120, 150, 180, 210, 240, 270, 300
I (x ln) 1.5, 2, 3, 5, 7, 10, 15, OFF
GF (x ln) 0.20, 0.30, 0.40, 0.50, 0.60, 0.70, 0.80 for 800 to 2000A
0.20, 0.30, 0.35, 0.45, 0.55, 0.60, 0.70 2500A
0.20, 0.30, 0.35, 0.45 for 3200 to 4000A
Delay (ms) 100, 200, 300
lr = k x ln
X = In (Nominal rating or
value of rating plug indications reproduced on the calibrator
S = Sensor rating
12
RMS 7: Protection Unit
���
RMS10, RMS12 RMS7 S800 - 2500 / S3200 - 4000
Spectronic Air Circuit Breaker - Operating Instructions
201
Table of contentsRECEIPT OF EQUIPMENT S800-2500A / S3200-4000A
- Arrival ........................................................................................................................................................................................................................ 3- Storage ..................................................................................................................................................................................................................... 3- Unpacking ............................................................................................................................................................................................................... 3
IDENTIFICATION- S800-2500-3200-4000 ..................................................................................................................................................................................... 4 - 5
INSTALLATION- Fixed Breaker S800-2500 ................................................................................................................................................................................ 6- Withdrawable Breaker S800-2500 ............................................................................................................................................................. 7- Fixed Breaker S3200-4000 .............................................................................................................................................................................. 8- Withdrawable Breaker S3200-4000 ........................................................................................................................................................... 9
COMMISSIONING-OPERATION- Circuit Breaker S-800-2500 / 3200-4000 ................................................................................................................................................ 10 - 11- Protection ............................................................................................................................................................................................................ 11- RMS7 : Protection Unit ....................................................................................................................................................................................... 12- RMS7 : Settings ..................................................................................................................................................................................................... 12 - 13- RMS7 : Distinct Fault Signalling Option ..................................................................................................................................................... 14- RMS7 : Time - Current Characteristics ....................................................................................................................................................... 15 - 16- RMS10, RMS12 : Protection and Measurement Unit ............................................ .............................................................................. 17- RMS10, RMS12 : Time - Current Characteristics ................................................................................................................................... 18 - 19- Cabling Diagram .................................................................................................................................................................................................. 20- LMZ7 : Protection Unit ....................................................................................................................................................................................... 21- RMS7 : Time - Current Characteristics ....................................................................................................................................................... 21- Voltmetric Releases ............................................................................................................................................................................................. 22- Inhibited Closing ................................................................................................................................................................................................... 22- Auxiliary Contacts ............................................................................................................................................................................................... 22- Faults Signalling Contacts and Indicator ................................................................................................................................................. 23- Interlocking ............................................................................................................................................................................................................ 24
MAINTENANCE - LUBRICATION .................................................................................................................................................................................................. 25
CHECKING - REPLACEMENT - ADAPTATION1A - Adjusting and Checking ....................................................................................................................................................... 262A - Arc Chute S800-2500 ........................................................................................................................................................... 263A - Spark Arresters S800-2500 ............................................................................................................................................... 264A - Arc Barrier S800-2500 ......................................................................................................................................................... 261C - Adjusting and Checking ....................................................................................................................................................... 272C - Arc Chute S3200-4000 ........................................................................................................................................................ 273C - Spark Arresters S3200-4000 ............................................................................................................................................. 275A - Current Transformers S800-2500 .................................................................................................................................. 286A - Pole Tightening ........................................................................................................................................................................ 285B - Current Transformers S3200-4000 ................................................................................................................................ 29
Protections Releases7 - Overcurrent Releases RMS7-RMS10, RMS12 ............................................................................................................. 308 - Trip Coil EX ................................................................................................................................................................................. 31 - 329A - Verification of Resetting S800-2500 .............................................................................................................................. 33 - 359B - Verification of Resetting S3200-4000 ........................................................................................................................... 33 - 3510 - Lead Sealing of RMS7 ........................................................................................................................................................... 36
Accessories11 - Voltmetric Releases ............................................................................................................................................................... 3712 - Auxiliary Contacts (Replacement) ................................................................................................................................... 38
Electrical Control13 - Motor (Replacement) ............................................................................................................................................................. 3914 - Resetting Limit Switch (Replacement) S3200-4000 ............................................................................................... 4015A - Resetting Spring Contact (Replacement) S800-2500 ............................................................................................ 4115B - Resetting Spring Contact (Replacement) S3200-4000 .......................................................................................... 41 - 42
Spectronic Air Circuit Breaker - Operating Instructions
3
01
Table of contentsRECEIPT OF EQUIPMENT S800-2500A / S3200-4000A
- Arrival ................................................................................................................................................................................................... ..................... 3
- Storage ..................................................................................................................................................................................................................... 3
- Unpacking ............................................................................................................................................................................................................... 3
IDENTIFICATION
- S800-2500-3200-4000 ..................................................................................................................................................................................... 4 - 5
INSTALLATION
- Fixed Breaker S800-2500 ................................................................................................................................................................................ 6
- Withdrawable Breaker S800-2500 ............................................................................................................................................................. 7
- Fixed Breaker S3200-4000 .............................................................................................................................................................................. 8
- Withdrawable Breaker S3200-4000 ........................................................................................................................................................... 9
COMMISSIONING-OPERATION
- Circuit Breaker S-800-2500 / 3200-4000 ................................................................................................................................................ 10 - 11
- Protection ............................................................................................................................................................................................................ 11
- RMS7 : Protection Unit ....................................................................................................................................................................................... 12
- RMS7 : Settings ..................................................................................................................................................................................................... 12 - 13
- RMS7 : Distinct Fault Signalling Option ..................................................................................................................................................... 14
- RMS7 : Time - Current Characteristics ....................................................................................................................................................... 15 - 16
- RMS9D : Protection and Measurement Unit ........................................................................................................................................... 17
- RMS9D : Time - Current Characteristics .................................................................................................................................................... 18 - 19
- Cabling Diagram .................................................................................................................................................................................................. 20
- LMZ7 : Protection Unit ....................................................................................................................................................................................... 21
- RMS7 : Time - Current Characteristics ....................................................................................................................................................... 21
- Voltmetric Releases ............................................................................................................................................................................................. 22
- Inhibited Closing ................................................................................................................................................................................................... 22
- Auxiliary Contacts ............................................................................................................................................................................................... 22
- Faults Signalling Contacts and Indicator ................................................................................................................................................. 23
- Interlocking .............................................................................................................................................................................................. .............. 24
MAINTENANCE - LUBRICATION .................................................................................................................................................................................................. 25
CHECKING - REPLACEMENT - ADAPTATION
1A - Adjusting and Checking ....................................................................................................................................................... 26
2A - Arc Chute S800-2500 ........................................................................................................................................................... 26
3A - Spark Arresters S800-2500 ............................................................................................................................................... 26
4A - Arc Barrier S800-2500 ......................................................................................................................................................... 26
1C - Adjusting and Checking ....................................................................................................................................................... 27
2C - Arc Chute S3200-4000 ........................................................................................................................................................ 27
3C - Spark Arresters S3200-4000 ............................................................................................................................................. 27
5A - Current Transformers S800-2500 .................................................................................................................................. 28
6A - Pole Tightening ........................................................................................................................................................................ 28
5B - Current Transformers S3200-4000 ................................................................................................................................ 29
Protections Releases
7 - Overcurrent Releases RMS7-RMS9D ............................................................................................................................. 30
8 - Trip Coil EX ................................................................................................................................................................................. 31 - 32
9A - Verification of Resetting S800-2500 .............................................................................................................................. 33 - 35
9B - Verification of Resetting S3200-4000 ........................................................................................................................... 33 - 35
10 - Lead Sealing of RMS7 ........................................................................................................................................................... 36
Accessories
11 - Voltmetric Releases ............................................................................................................................................................... 37
12 - Auxiliary Contacts (Replacement) ................................................................................................................................... 38
Electrical Control
13 - Motor (Replacement) ............................................................................................................................................................. 39
14 - Resetting Limit Switch (Replacement) S3200-4000 ............................................................................................... 40
15A - Resetting Spring Contact (Replacement) S800-2500 ............................................................................................ 41
15B - Resetting Spring Contact (Replacement) S3200-4000 .......................................................................................... 41 - 42
02
16A - Resetting Spring Contact (Adaptation) S800-2500 ................................................................................................ 42
16B - Resetting Spring Contact (Adaptation) S3200-4000 .............................................................................................. 43
17A - Closing Prevention Device (Replacement) S800-2500 .......................................................................................... 44
17B - Closing Prevention Device (Replacement) S3200-4000 ....................................................................................... 44 - 45
18A - Closing Coil (Replacement) S800-2500 ........................................................................................................................ 45
18B - Closing Coil (Replacement) S3200-4000 ..................................................................................................................... 46
19A - Insertion Contact (Replacement) S800-2500 ............................................................................................................ 46
19B - Insertion Contact (Replacement) S3200-4000 .......................................................................................................... 46
20A - Economy Resistor (Replacement) S800-2500 ........................................................................................................... 47
20B - Economy Resistor (Replacement) S3200-4000 ........................................................................................................ 47
Safety Shutters
21A - Safety Shutters S800-2500 ............................................................................................................................................... 48 - 49
21B - Safety Shutters S3200-4000 ............................................................................................................................................. 50 - 51
Interlocking
22 - “Tripped” position by Padlock (optional) ..................................................................................................................... 52
23 - “Tripped” position by Padlock and GE ACB / RONIS (optional) ......................................................................... 53 - 54
24 - “Tripped” position by GE ACB / RONIS lock (optional) ........................................................................................... 55 - 56
25 - “Tripped” position by SINGLE LETTER CASTELL LOCK (optional) ...................................................................... 57 - 58
26 - “Tripped” position by DOUBLE LETTER CASTELL LOCK or SINGLE LETTER CASTELL LOCK + GE ACB / RONIS LOCK (optional) ............................................................... 59 - 61
27 - “Withdrawn” / “Connected” position by GE ACB / RONIS LOCK & Padlock (optional) .......................... 62
Fault Signalling Contact
28A - Fault Signalling Contact (Replacement) S800-2500 .............................................................................................. 63
28B - Fault Signalling Contact (Replacement) S3200-4000 ............................................................................................ 64 - 65
Secondary Disconnects
29 - Secondary Disconnects ....................................................................................................................................................... 66 - 67
Earth Connector
30 - Earth Connector ...................................................................................................................................................................... 68 - 69
Signalling Contacts on Cradle
31 - Signalling Contacts on Cradle .......................................................................................................................................... 70
32 - 33 - Coupled Contact with Signalling Contact ................................................................................................................... 71
REPLACEMENTS PARTS ................................................................................................................................................................................................................... 72 - 73
SCHEMATIC / WIRING DIAGRAMS ............................................................................................................................................................................................. 74 - 77
Spectronic Air Circuit Breaker - Operating Instructions
403
Receipt of equipment S800-2500 / S3200-4000
1 - Arrival
When packages arrive, check that they are inperfect condition. If otherwise, proceed with theusual notifications.Do not hesitate to proceed with unpacking in thepresence of an authorized agent representing thedelivery firm.
2 - Storage
If the equipment is not installed immediately, itmust be stored in a premises where it is protectedfrom dust and splashing by water. To avoid anydeterioration, it is recommended that equipmentbe left in its protective covering or provided witha waterproof covering.
3 - UnpackingS800-2500 / S3200-4000
Withdrawable* breaker with cradle• Remove the 2 supports (A) securing the
circuit-breaker onto its fixed section on
either sides
• Remove the 4 brackets (B) securing the fixed
section onto the base of the packing case.
• Remove the 2 brackets (C) protecting the
front box (cradle).
* Fixed breaker : remove the 4 attachment
screws at the base of the breaker fixed to
the woden pallete.
Withdrawable* breaker withoutcradleThe handles on the upper section of the sideflanges may be used to lift the equipment.Never carry the circuit-breaker by its cut-offclamps. Rest it on a flat surface, either on itslower section or on its side flanges. Keep thebase of the packing case for use as a palette.
* Fixed breaker : follow the same instructions asthat of withdrawable breaker.
C
B
A
Spectronic Air Circuit Breaker - Operating Instructions
504
Identification S800-2500 and S3200-4000
1 - information label2 - supply voltage for auxiliary equipment3 - trip and local reset push-button (BPDL)4 - “On” push-button (BPEL)
5 - front cover6 - carrying handle7 - identification plate8 - spring charging handle9 - front facia
24 - voltmetric releases25 - reset spring contact
21 - connection terminal box (fixed breaker)22 - earth connector (fixed breaker)23 - current transformers
16 - arc chute17 - electrical operation motor18 - releases LMZ7/RMS7/RMS10/12
10 - local controls padlocking11 - spring charge status indicator
• white : spring discharged• red : spring charged
12 - mechanical fault• white (I>) : fault• black : normal
13 - interlocking in tripped position (single figure castell lock / GE ACB or Ronis lock)14 - padlocking in tripped position15 - circuit-breaker status indicator:
• red : closed• green : open
16 - locking catch for local controls padlocking
ed noitneverp gnisolc - 02srotcatnoc yrailixua - 91 vice
20
19
16
18
17
22
21
23 2524
5 1 2 6
4 7
3
15
10
9
13
8
14
11 12
16
Spectronic Air Circuit Breaker - Operating Instructions
6
05
26 - safety shutters
27 - name plate
28 - secondary disconnectors - fixed
29 - wiper-type earth connector
30 - “withdrawn” position indicating contact
31 - “connected” position indicating contact
32 - contact coupled with “plug-in” control
33 - interlocking in “Withdrawn” / “Connceted” position by GE ACB / Ronis lock34 - interlocking in“Withdrawn” position by padlock
37 - rating error prevention plug / device
26
28
27
31
30
29
32 34 33
37
Spectronic Air Circuit Breaker - Operating Instructions
7
Installation
S800 - 2500 Spectronic “Withdrawable”
Connections
Panel cut-out for gasket fittings Legend
Circuit breaker
Nr. of poles A B C D E F H I
S 800-1000 1250-1600
3 399 98 101.5 77.5 217.5 87 46.5 22.5
4 487 98 96.5 72.5 217.5 87 90.5 66.5
S20003 487 130 113.5 89.5 207.5 107 90.5 66.5
4 621 130 115.5 91.5 207.5 107 157.5 133.5
S25003 555 150 127.5 103.5 197.5 127 124.5 100.5
4 701 150 125.5 101.5 197.5 127 197.5 173.5
Connection TerminalsF.T.R.V.T.
R.H.T. S800-1600 S2000 S2500F.T.: Front TerminalsR.V.T.: Rear Vertical TerminalsR.H.T.: Rear Horizontal Terminals
S1600 S2000 S2500S800-1600 S2000 S2500
H1 = minimum clearance above the arc chutes
Ue≤500V Ue≤690V
Insulated screen 150 mm 150 mm
Metallic screen 150 mm 200 mm
Spectronic Air Circuit Breaker - Operating Instructions
8
Installation
S3200 - 4000 Spectronic “Fixed”
Panel cut-out for gasket fitting
Legend
Rear horizontal terminal
S3200A / S4000A
Circuit breaker
Number poles Weight A B C D
S3200A / S4000A 3 116 628 250.3 132 233.8
S3200A / S4000A 4 146 826 448.3 130 431.8
H1 = minimum clearance above the arc chutes
Ue ≤ 500V Ue ≤ 690V
Insulated Screen 200 mm 200 mm
Metallic Screen 200 mm 200 mm
F G
S3200 15 (2X5) 127
S4000 25 (3X5) 121.5
Spectronic Air Circuit Breaker - Operating Instructions
9
Installation
S3200 - 4000 Spectronic “Withdrawable”
Panel cut-out for gasket fitting Front or rear horizontal connection terminals
Legend
F G
S3200A 15 (2X5) 266.5
S4000A 25 (3X5) 216.5
Circuit breaker Numberpoles A B C D
S3200 / S40003 711 246.8 130.5 230.3
4 909 444.8 129.5 428.8
H1 = minimum clearance above the arc chutes
Ue ≤ 500V Ue ≤ 690V
Insulated Screen 200 mm 200 mm
Metallic Screen 200 mm 200 mm
Spectronic Air Circuit Breaker - Operating Instructions
10
Installation
S3200 - 4000 Spectronic “Fixed”
Hole details of earthing for 800A - 2500A (backside of the breaker)
Earthing Position for S3200-S4000
Hole details of earthing for 3200A - 4000A (backside of the breaker)
Rear terminal mould cavity dimension S800-S2000
RATING A
1600A 73
2000A 109
Spectronic Air Circuit Breaker - Operating Instructions
11
• “WITHDRAWN”Turn the crank as far as it will go in theanticlockwise direction with the indicatorstopping at the “withdrawn” position mark. Inthis position both main and auxiliary circuits areisolated.
• “TEST”Turn the crank, with indicator stopping at the“test” mark. In this position the main circuit iso-lated and auxiliary circuits connected.
Circuit breaker position• “CONNECTED”Turn the crank as far as it will go in the clock-wise direction. Here the indicator will stop at“connected” position mark. In this position themain and auxiliary circuits are connected.
• “EXTRACTED MAINTENANCE (COMPLETELY WITHDRAWN) POSITION”Pull the retractable rails to fully extend themand pull the breaker as far as it will go.
Fitting the breaker :
• Turn the plug-in crank as far as it will go in
anti-clockwise direction.
• Pull the retractable rails out to the fully
extended position.
• Pull the breaker out on the rails using the
pulling handles.
• Push the breaker back and then the rails
fully home.
Electrically operated circuit breaker :• Press the “On” and “Off” push buttons in turnto release the energy stored in the spring.
Position-indicating contacts• “connected position” - 1 or 2 contacts actuated when circuit-breaker is fully plugged-in (32).• “withdrawn position” - 1 or 2 contacts actuated when circuit-breaker is fully removed (31).• 1 contact actuated on fitting and removing the crank (33).
33
32 31
33
32
31 S 800/2500AS 3200/4000A
Fitting the breaker :
• Push the knob to insert the plug-in crank.
10
Commissioning - Operation S800-2500 / S3200-4000
Spectronic Air Circuit Breaker - Operating Instructions
12
Circuit Breakera - Manual Operation• reset the release- press the trip (OFF)push button (13) (BPDL) fullyin• resetting- operate the handle (11) to compress the spring(stored energy required for closing)- press the ON push-button (15)• closing- presence of voltage required on UV or UVRD iffitted on breaker.• opening- in local mode by trip push button (BPDL) (13)- in remote mode by voltmetric releases
b - Electrical OperationElectrical operation with stored energy : thestored energy is reset automatically once thebreaker has been closed.The trip push button (BPDL) (13) resets theovercurrent release except if the circuit-breakeris reset automatically, with or without indicationwith memory.• opening- in local mode, using the red trip (OFF) pushbutton (13)- in remote mode, using the voltmetric releases- if closing the breaker is provided by acontinuous command, the closing commandmust be momentarily interupted after trippingin order to obtain resetting• closing- in local mode, using the green ON push-button(15)- in remote mode by closing coil.
ProtectionRelease• If the circuit-breaker is to be reset in local mode,it must be reset manually after overload andshort-circuit operation by pressing the local trippush button BPDL (13) fully in.
Each protected pole of the circuit-breaker isequipped with current transformers (CT) whichsupply input to the releases RMS7 / RMS9D /LMZ7.
15
11
15
11
13
13
11
Spectronic Air Circuit Breaker - Operating Instructions
13
ProtectionRMS7 Trip• If the circuit breaker is to be reset in local mode,it must be reset manually after an overcurrentcondition by pushing in fully the local trip pushbutton 13.
Description :Powered by the current transformers, lmax = 4000, the RMS7 unitperforms all the necessary current protections with true rms value sensing:• overload protection (LT)• short-circuit protection (ST and I)• ground fault protection (GF) (The 4th (neutral) current transformer must be of the same rating as those of the three phases).
RMS7 : OptionsThe following options are field fittable
Distinct Fault Signalling (LT, ST, I, GF)• Local indication by LED display. this option is power supplied by an internal battery.• Lead sealing.
Setting Ranges Setting Points
LT (x ln) 0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.00
LTD (s) 5, 10, 15, 20, 25, 30, 35, 40 delay at 7.2 lr
ST (x ln) 1.5, 2, 3, 4, 5, 7, 9, 10, 12, 14
Delay (ms) 30, 60, 90, 120, 150, 180, 210, 240, 270, 300
I (x ln) 1.5, 2, 3, 5, 7, 10, 15, OFF
GF (x ln) 0.20, 0.30, 0.40, 0.50, 0.60, 0.70, 0.80 for 800 to 2000A
0.20, 0.30, 0.35, 0.45, 0.55, 0.60, 0.70 2500A
0.20, 0.30, 0.35, 0.45 for 3200 to 4000A
Delay (ms) 100, 200, 300
lr = k x ln
X = In (Nominal rating or
value of rating plug indications reproduced on the calibrator
S = Sensor rating
12
RMS 7: Protection Unit
���
Spectronic Air Circuit Breaker - Operating Instructions
14
2 3
3435
3637
3839
37
3839
RMS 7
RMS 7
1Current
transformers
White
Yellow
yellow
whiteyellow
whiteyellow
whiteyellow
whiteyellow
4950
3435
36
N 1 2 3
S1 whiteyellow
whiteyellow
white
Total cut-out time at ST : selected time delay + 90 ms
Tolerance for ST operating thresholds : ± 15 %
PH 2+PH 2-
PH 3+PH 3-
PHN +PHN -
PH 1+PH 1-
PH 1+PH 1-
PH 2+PH 2-
PH 3+PH 3-
Threshold
GF in A (±15%)
Threshold
Threshold
GF in A (±15%)
Threshold
Overload threshold LT in A according to the index position
(Tolerances :1.05 -1.30 of setting current according to IEC 60947-2)
Rating
plug
(A)
Currenttransformer
(A)
Circuit
breaker
type
0,4In 0,5In 0,6In 0,7In 0,75In 0,8In 0,85In 0,9In 0,95In 1,0In 0,20 In 0,80 In
S800 800 400 160 200 240 280 300 320 340 360 380 400 80 320
600 240 300 360 420 450 480 510 540 570 600 120 480
800 320 400 480 560 600 640 680 720 760 800 160 640
S1000 1000 800 320 400 480 560 600 640 680 720 760 800 160 640
1000 400 500 600 700 750 800 850 900 950 1000 200 800
S1250 1250 500 625 750 875 937 1000 1063 1125 1188 1250 250 1000
S1600 1600 800 320 400 480 560 600 640 680 720 760 800 160 640
1200 480 600 720 840 900 960 1020 1080 1140 1200 240 960
1600 640 800 960 1120 1200 1280 1360 1440 1520 1600 320 1280
S2500 2500 1600 640 800 960 1120 1200 1280 1360 1440 1520 1600 320 1280
2500 1000 1250 1500 1750 1875 2000 2125 2250 2375 2500 500 2000
S3200 3200 1600 640 800 960 1120 1200 1280 1360 1440 1520 1600 320 1280
3200 1280 1600 1920 2240 2400 2560 2720 2880 3040 3200 640 2560
S4000 4000 2500 1000 1250 1500 1750 1875 2000 2125 2250 2375 2500 500 2000
4000 1600 2000 2400 2800 3000 3200 3400 3600 3800 4000 800 3200
Neutral CT Mounting Instructions :While using 3P ACBs in 3Phase 4WireSystem,
a) If the supply connections are madeto the top terminals, P2 of theNeutral CT shall face the supply side.
b) If the supply connections are madeto the bottom terminals, P1 of theNeutral CT shall face the supply side.
3 Phase 4 Wire System
3 Phase 3 Wire System
S2
S1
S2
S1
S2
S1
S2
S1
S2
S1
S2
S1
S2
13
Setting and operating current values
RMS10,RMS12
RMS10,RMS12
Spectronic Air Circuit Breaker - Operating Instructions
15
ProtectionRMS7 Trip• If the circuit breaker is to be reset in local mode,it must be reset manually after an overcurrentcondition by pushing in fully the local trip pushbutton 13.
Description :Powered by the current transformers, lmax = 4000, the RMS7 unitperforms all the necessary current protections with true rms value sensing:• overload protection (LT)• short-circuit protection (ST and I)• ground fault protection (GF) (The 4th (neutral) current transformer must be of the same rating as those of the three phases).
RMS7 : OptionsThe following options are field fittable
Distinct Fault Signalling (LT, ST, I, GF)• Local indication by LED display. this option is power supplied by an internal battery.• Lead sealing.
Setting Ranges Setting Points
LT (x ln) 0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.00
LTD (s) 5, 10, 15, 20, 25, 30, 35, 40 delay at 7.2 lr
ST (x ln) 1.5, 2, 3, 4, 5, 7, 9, 10, 12, 14
Delay (ms) 30, 60, 90, 120, 150, 180, 210, 240, 270, 300
I (x ln) 1.5, 2, 3, 5, 7, 10, 15, OFF
GF (x ln) 0.20, 0.30, 0.40, 0.50, 0.60, 0.70, 0.80 for 800 to 2000A
0.20, 0.30, 0.35, 0.45, 0.55, 0.60, 0.70 2500A
0.20, 0.30, 0.35, 0.45 for 3200 to 4000A
Delay (ms) 100, 200, 300
lr = k x ln
X = In (Nominal rating or
value of rating plug indications reproduced on the calibrator
S = Sensor rating
12
RMS 7: Protection Unit
���
VIEW Button
- Indicates the battery status (battery ok when the “BAT” led is powered).
- Indicates the origin of fault (LTPU - GF - OVL - SHORT).
RESET Button
- Reset the fault indicator.
Trip Unit Healthiness : press and hold the view button for more than 5
seconds. If the LTPU LED blinks slowly, it indicates the healthiness of the tripunit.
CAUTION
- The battery can be replaced only by Panasonic CR1616 or Duracell DC1616B.
- Use of others battery can present a risk of fire, explosion or can damage the product.
- Check the polarity of the battery.
Fault Signal
LT : LED OVL : Tripping on overload condition
ST - I : LED SHORT : Tripping on short circuit condition
GF : LED GF : Tripping on ground fault condition
LTPU : LED Pre-alarm LT
The LTPU led blinks slowly when the LT threshold is below 100%.
The LTPU led blinks rapidly when the LT threshold is above 100% and indicatesan imminent tripping on overload condition.
Replacement
The “CLIC” sound at the end of installation operation indicates that the ratingplug is correctly installed on the unit.
ATTENTION
� The (S) rating indicated on the rating plug must be identical to the
nominal current indicated on the RMS7 unit.
�In 800A
In 800A
14
Distinct fault signalling option
Spectronic Air Circuit Breaker - Operating Instructions
17
T. S
EC
ON
DS
MULTIPLES OF NOMINAL CURRENT In (CT CURRENT)
AIR CIRCUIT BREAKERS : S800 to 4000A
GF Threshold0.2 to 0.8 (800 to 2000A)0.2 to 0.7 (2500A)0.2 to 0.45 (3200 to 6400A)times the value X In
GF Time Delay0.1 - 0.2 - 0.3s
16
RMS7 Time - Current Characteristics
Spectronic Air Circuit Breaker - Operating Instructions
18
RMS10, RMS12 : Protection & Measurement Unit
Standard Protection RMS10, RMS12 :• overload protection (LT)• short-circuit protection (ST and I)• ground fault protection (GF)••
thermal memoryRELT
Description :Powered by the current trans-former,Imax = 4000A, the RMS10, RMS12 unitperforms all the necessary currentprotections as well as measuring(RMS) all the para-meters.In addition to the above functions, theRMS10, RMS12 can also perform remoteevent measurement and recording.
Mic
ropr
oces
sor
RMS1
0, R
MS1
2
Conv
erte
r A
/DB
Keyboard
Current Transformers
N
A
C
LCD display
Relay
Auxiliary PowerSupply 24V DC
Actuator
Communication
Voltage Conditioner
PROTECTION
MEASUREMENT
Each function can be time delayedwith a range of 1 to 15s (+ OFFposition).
Distinct fault signatisationBy local display with the RMS10, RMS12unit in “STATUS” mode the conditionof the breaker is indicated. Also thetime and number of releases underfault :- LT, ST, I, GF- undervoltage, overvoltage, ......, reversal power.
RMS1 0 , R M S 1 2 : Protection andMeasurement Unit“High Precision” MeasurementsWithout Voltage Monditioner- Current on each phase (A, KA)With Voltage Conditioner- Power supply voltage of conditioner 230/380/415V- Current on each phase (A, KA)- Voltage between phase and neutral (V)- Energy (KWh, MWh)- Active power per phase (1) (KW)- Total active power (KW, MW)- Total power per phase (1) (KVA, MVA)- Total power (KVA, MVA)- Average power demand (KW, MW)- Maximum power demand (KW, MW)- Voltage range RMS10, RMS12 from 120 to 600V AC- Frequency (Hz)
-
(1) if the neutral is connected
For all voltage / power parameters and communication / relaying protection supplingof 24 V DC is required.
lr = K x ln
NoteIf the GF function is selected, the 4thtransformer (Neutral CT) must have thesame rating as the one of the phases.
Function Range (%) Step
< V 50 - 90 1
> V 110 - 150 1
V 10 - 50 1
I 10 - 50 1Pi 10 to 990KW 10KW
Setting points
LT (x In) 0.5 - 1 (steps of 0.05)
LTD (S) 0.5 - 30@6Ir
ST (x Ir) 1.5 - 9 (steps of 0.5)
Time Delay (ms) 90 to 400
I (x In) 2 - 15 - OFF (steps of 0.5) RMS 9D/2000A2 - 13 - OFF (steps of 0.5) RMS 9D/3200A2 - 9 - OFF (steps of 0.5) RMS 9D/4000A
GF (x In) 0.2 - 0.6 (steps of 0.01) /2000A*0.2 - 0.48 (steps of 0.01) /2500A0.2 - 0.37 (steps of 0.01) /3200A0.2 - 0.3 (steps of 0.01) /4000A
Time Delay
RELT1
(ms) 60 to 390
Setting ranges
Sam
pler
Additional Programmable FunctionsAll or part of the programmable function in RMS12 can be selected- current unbalance - under voltage - over voltage - voltage unbalance - reverse power - reverse power - load shedding- GFA- RELT- 2 way communication with RS485 port in-built
1.5 In to 15 In-settable throughcommunication / 24v DC/AC throughwiring input
*For 1250A, please refer attachment in annexure 1 page --1RELT needs to be factory enabled. Once RELT is enabled, the input and output contact available are dedicated to this features and no other options for input / output will available for use.
Spectronic Air Circuit Breaker - Operating Instructions
19
1.5 2 2.5 3 4 302015975 20070 00500105 3001
2 302075 20070 00500105 3001 10
S800 to S4000A
Inst. Threshold (I) 1.5 to 15 timesthe LT value (Ir)(in steps of 0.5)
ST Time Delay0.1 - 0.21 - 0.35s
ST Threshold1.5 to 9 times the LT value
(Ir)
LT Time delay3 - 6 - 12 - 25s at 6Ir
LT Threshold in Kxln 0.5 to 1
1.05Operating Limits IEC 60947-2
0.8
100
200
0.8
50
10
20
30
1
5
34
50000
20000
30000
2000
3000
5000
10000
1000
500
300
2
0.1
0.2
0.3
0.5
0.05
0.01
0.02
0.03
I2t OUT I2t IN
T. S
ECO
ND
S
MULTIPLES OF CURRENT SETTING
3
1.3 }
}
}
}
18
RMS10, RMS12 Time - Current Characteristics
09.08
Low-Voltage Circuit Breakers
EntelliGuard TU Trip Unit for PowerBreak, PowerBreak II, AKR and WavePro Circuit Breakers UL489 and UL1066 Stored EnergyMechanism Circuit Breakers
Long-Time CB Characteristics
Curves apply at 60 Hertz and from -20°C to 55°C circuit breaker ambient temperature.
DES-095Frames 800-5000A AKR & WaveProFrames 800-4000A PowerBreak & PowerBreak II
All Voltages: 600 Vac and below
Pickup Range0.5X-1.0X Trip Rating Plug
TIM
E IN
SEC
ON
DS
DES
-095
DES
-095
10
20
30
40
50
60708090
100
200
300
400
500
600
700800900
1000
9876
5
4
3
2
.9
.8
.7
.6
.5
.4
.3
.2
.1
.09
.08
.07
.06
.05
.04
.03
.02
.01
1
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090
100
200
300
400
500
600
7008009001000
2000
3000
4000
5000
6000
70008000900010000
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
100
200
300
400
500
600700800900
1000
2000
3000
4000
5000
6000
700080009000
10000
MULTIPLE OF LONG-TIME PICKUP
MULTIPLE OF LONG-TIME PICKUP
TIM
E IN
SEC
ON
DS
200
300
400
500
600700800900
1000
.01
.02
.03
.04
.05
.06
.07
.08
.09
.1
.2
.3
.4
.5
.6
.7
.8
.91
2
3
4
5
6
789
10
20
30
40
50
60708090
100
Nominal Clearing and Commit Times for X Multipliers of Nominal Pickup.
X = 1.5 1.5 6 6 7.2 7.2 10 10Curve Commit Clear Commit Clear Commit Clear Commit Clear
Min CB 4.25 8.04 0.20 0.33 0.14 0.24 0.072 0.137
C-2 12.7 24.1 0.60 0.94 0.42 0.66 0.21 0.35
C-3 25.5 48.1 1.21 1.84 0.83 1.28 0.43 0.67
C-4 34.0 64.1 1.61 2.45 1.11 1.70 0.57 0.89
C-5 51.0 96.2 2.41 3.66 1.67 2.53 0.86 1.32
C-6 67.9 128 3.21 4.87 2.22 3.37 1.15 1.75
C-7 84.9 160 4.02 6.08 2.78 4.20 1.43 2.18
C-8 101.9 192 4.82 7.29 3.33 5.03 1.72 2.61
C-9 118.9 224 5.62 8.49 3.89 5.87 2.01 3.03
C-10 135.9 256 6.43 9.70 4.44 6.70 2.29 3.46
C-11 152.9 289 7.23 10.9 5.00 7.54 2.58 3.89
C-12 169.8 321 8.04 12.1 5.56 8.37 2.87 4.32
C-13 203.8 385 9.64 14.5 6.67 10.0 3.44 5.18
C-14 237.8 449 11.2 17.0 7.78 11.7 4.01 6.04
C-15 271.7 513 12.9 19.4 8.89 13.4 4.59 6.90
C-16 305.7 577 14.5 21.8 10.0 15.0 5.16 7.76
C-17 339.7 641 16.1 24.2 11.1 16.7 5.73 8.61
C-18 373.6 705 17.7 26.6 12.2 18.4 6.30 9.47
Max CB 407.6 769 19.3 29.1 13.3 20.0 6.88 10.3
Algorithm will not commit below 1.5 cycles, clearing time will not be less than 0.088 seconds.
Actual Long-Time Pickup is 112% of Nominal Pickup.
Transition to Short-Time Pickup, Short- Time Delay Band or Instantaneous
Determines End of Curve Minimum CB
Maximum CB
C-3
C-6
C-13
Spectronic Air Circuit Breaker - Operating Instructions
20
09.08
Low-Voltage Circuit Breakers
EntelliGuard TU Trip Unit for PowerBreak, PowerBreak II, AKR and WavePro Circuit Breakers UL489 and UL1066 Stored EnergyMechanism Circuit Breakers
Long-Time Fuse Like Characteristics
Curves apply at 60 Hertz and from -20°C to 55°C circuit breaker ambient temperature.
DES-096Frames 800-5000A AKR & WaveProFrames 800-4000A PowerBreak & PowerBreak II
All Voltages: 600 Vac and below
Long Time Pickup Range0.5X-1.0X Trip Rating Plug
TIM
E IN
SEC
ON
DS
DES
-096
DES
-096
10
20
30
40
50
60708090
100
200
300
400
500
600
700800900
1000
9876
5
4
3
2
.9
.8
.7
.6
.5
.4
.3
.2
.1
.09
.08
.07
.06
.05
.04
.03
.02
.01
1
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090
100
200
300
400
500
600
7008009001000
2000
3000
4000
5000
6000
70008000900010000
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
100
200
300
400
500
600700800900
1000
2000
3000
4000
5000
6000
700080009000
10000
MULTIPLE OF LONG-TIME PICKUP
MULTIPLE OF LONG-TIME PICKUP
TIM
E IN
SEC
ON
DS
200
300
400
500
600700800900
1000
.01
.02
.03
.04
.05
.06
.07
.08
.09
.1
.2
.3
.4
.5
.6
.7
.8
.91
2
3
4
5
6
789
10
20
30
40
50
60708090
100
Nominal Clearing and Commit Times for X Multipliers of Nominal Pickup.
X = 1.5 1.5 6 6 7.2 7.2 10 10Curve Commit Clear Commit Clear Commit Clear Commit Clear
Min F 0.67 1.54 0.025 0.085 0.025 0.085 0.025 0.085
F-2 2.0 4.40 0.025 0.085 0.025 0.085 0.025 0.085
F-3 3.6 7.98 0.025 0.085 0.025 0.085 0.025 0.085
F-4 5.6 12.5 0.025 0.085 0.025 0.085 0.025 0.085
F-5 8.1 18.0 0.032 0.100 0.025 0.085 0.025 0.085
F-6 11.2 25.0 0.044 0.13 0.025 0.085 0.025 0.085
F-7 15.1 33.8 0.059 0.16 0.028 0.094 0.025 0.085
F-8 20.0 44.7 0.078 0.20 0.038 0.114 0.025 0.085
F-9 26.1 58.4 0.10 0.26 0.049 0.14 0.025 0.085
F-10 33.8 75.4 0.13 0.32 0.064 0.17 0.025 0.085
F-11 43.3 96.8 0.17 0.41 0.082 0.21 0.025 0.085
F-12 55.3 123 0.22 0.51 0.104 0.26 0.028 0.092
F-13 70.2 157 0.27 0.64 0.13 0.33 0.036 0.109
F-14 88.9 198 0.35 0.81 0.17 0.40 0.045 0.13
F-15 112 251 0.44 1.01 0.21 0.50 0.057 0.16
F-16 141 316 0.55 1.26 0.27 0.62 0.072 0.19
F-17 178 397 0.69 1.58 0.34 0.78 0.090 0.23
F-18 224 499 0.87 1.98 0.42 0.97 0.113 0.28
Max-F 280 626 1.10 2.48 0.53 1.21 0.142 0.35
Algorithm will not commit below 1.5 cycles, clearing time will not be less than 0.088 seconds.
Actual Long-Time Pickup is 112% of Nominal Pickup.
Transition to Short-Time Pickup, Short- Time Delay Band or Instantaneous
Determines End of Curve
Minimum F
Maximum F
F-5
F-13
Spectronic Air Circuit Breaker - Operating Instructions
21
09.08
DES-098Low-Voltage Circuit Breakers
EntelliGuard TU Trip Unit for PowerBreak, PowerBreak II, AKR and WavePro Circuit Breakers UL489 and UL1066 Stored EnergyMechanism Circuit Breakers
Ground Fault
Curves apply at 60 Hertz and from -20°C to 55°C circuit breaker ambient temperature.
Pickup RangeMinimum 0.2X Sensor
Maximum up to 0.6x Sensor
Not to exceed 1200A
Frames 800-5000A AKR & WaveProFrames 800-4000A PowerBreak & PowerBreak II
All Voltages: 600 Vac and below
TIM
E IN
SEC
ON
DS
DES
-098
DES
-098
10
20
30
40
50
60708090
100
200
300
400
500
600
700800900
1000
9876
5
4
3
2
.9
.8
.7
.6
.5
.4
.3
.2
.1
.09
.08
.07
.06
.05
.04
.03
.02
.01
1
.8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090
100
.8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
100
.8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090
100
.8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
100
MULTIPLE OF SENSOR
MULTIPLE OF SENSOR
TIM
E IN
SEC
ON
DS
200
300
400
500
600700800900
1000
.01
.02
.03
.04
.05
.06
.07
.08
.09
.1
.2
.3
.4
.5
.6
.7
.8
.91
2
3
4
5
6
789
10
20
30
40
50
60708090
100
Maximum GF Pickup based on sensor.
Sensor Maximum
≤ 2000 0.6X
2500 0.48X
3000 0.4X
3200 0.37X
4000 0.3X
5000 0.24X
7
1312
1110
98
65
4
32
1
Maximum
Minimum
1
14t slope SGF slope
12t slope
16mS additional at minimum possible GF pick up, (20% sensor)
TGF delay band additional time may be calculated via the following formula;Additional t = 21.25 –18x%Sensor 1000Up to 119% sensor
0mS additional at 119% sensor
Spectronic Air Circuit Breaker - Operating Instructions
22
09.08
Low-Voltage Circuit Breakers
EntelliGuard TU Trip Unit for PowerBreak, PowerBreak II, AKR & Wavepro Circuit BreakersUL489 and UL1066 Stored EnergyMechanism Circuit Breakers
Short-Time Pickup and Delay Bands
Curves apply at 60 Hertz and from -20°C to 55°C circuit breaker ambient temperature.
DES-097Frames 800-5000A AKR & WavePro PowerBreak & Frames 800-4000A PowerBreak II
All Voltages: 600 Vac and below
Pickup Range1.5X - 9X up to 4000A Frames
1.5X - 7X 5000A AKR and WavePro
TIM
E IN
SEC
ON
DS
DES
-097
DES
-097
10
20
30
40
50
60708090
100
200
300
400
500
600
700800900
1000
9876
5
4
3
2
.9
.8
.7
.6
.5
.4
.3
.2
.1
.09
.08
.07
.06
.05
.04
.03
.02
.01
1
2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090
100
1
1
2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
100
2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090
100
1
1
2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
100
2
MULTIPLE OF LONG-TIME PICKUP
MULTIPLE OF LONG-TIME PICKUP
TIM
E IN
SEC
ON
DS
200
300
400
500
600700800900
1000
.01
.02
.03
.04
.05
.06
.07
.08
.09
.1
.2
.3
.4
.5
.6
.7
.8
.91
2
3
4
5
6
789
10
20
30
40
50
60708090
100
Transition to Instantaneous, Override or Application
Determines End of Curve
Transition to Instantaneous, Override or Application
Determines End of Curve
1011
87
9
65
43
21
10X STPU MaximumSlope Calculation
Min.
Int.
Max.
.1
.09
.08
.07
.06
.05
.04
.03
.02
.01
.2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7
.2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7
16mS additional at minimum possible ST pick up (Minimum Trip Rating Plug X Minimum Long Time pickup X Minimum Short Time pickup. (28% sensor)
Additional clearing time required for very low pickup settings under self power
Time band additional time may be calculated via the following formula;Additional t = 21.25 –18x%Sensor 1000Up to 119% sensor
0mS additional at 119% sensor
Spectronic Air Circuit Breaker - Operating Instructions
24
stnioP gnitteSsegnaR gnitteS
Over Load (LT) k (xln) 0.5,0.6,0.7,0.8,0.9,1
Short Time Pickup (ST) >> (xlr) 3,4,5,6,8,9
ST Delay (sec.) t >> (sec) Inst, 0.2, 0.3,0.4
Ground Fault (GF) lo (xln) 0.2,0.3,0.4,0.5,0.6,0.7
Earth Fault Delay (sec) t>>+0.2
lr = kxln
Optional Fault Indicator in LMZ7
21
LMZ 7 : PROTECTION UNIT
Spectronic Air Circuit Breaker - Operating Instructions
25
Voltmetric ReleasesThe equipment can be equipped with 2 releasesof types EA (Shunt), UV or UVRD (Delayed UV).They are reset by the breaker’s main shaft at theend of the opening operation.
Inhibited ClosingClosing is prevented by Closing-PreventionDevice FE operating at minimum voltage and isindependent of UV release.
Auxiliary Contacts• Between 5 and 8 contacts operate at thebeginning of closing of poles.• Between 1 and 4 contacts operate at the sametime as the main poles.
S 800/2500A
S 800/2500A
S 800/2500A S 3200/4000A
S 3200/4000A
S 3200/4000A
22222222
Spectronic Air Circuit Breaker - Operating Instructions
26
• common mechanical fault indicator for“overload” and “short-circuit” (A)Black : NormalWhite (I>) : Fault
• electrically-operated circuit breaker (withautomatic resetting).
The fault is cleared by operating the local trippush button.
• breaker with manual control (with localresetting).
Contacts and Fault Indicator• common “overload” and “short-circuit” faultindication: Possibility of 2 contacts withcommon point (CD) actuated by means of therelease.- contacts with local resetting by means of push-button.- momentarily actuated contacts for electrically-operated circuit-breaker (on request).
98
96
08
06
05
95CD
CD
The fault must be cleared on push-button BPED.Fault indication does not inhibit reclosing of thecircuit-breaker.
K14 1
3K1
CDBPED
H1
A
• Operate of Voltmetric Releases UV,UVRD, EAContacts with common point with fleeting action.- C41 actuated by UV or UVRD- C31 actuated by EA
• Voltage Presence on VoltmetricRelease UV or UVRDfactory fitted.Possibility of 1 contact with common point (C43),directly actuated by coil.
23
InterlockingA - Fixed and Withdrawable Breakers
(1) Interlocking of local control buttons bypadlock
press & hold the “Off” push button, turn the lock-ing catch at 90°, slide the push button windowcovers in and padlock them
- for electrically - operated breaker
(2) Interlocking in “tripped” position byGE ACB / Ronis lock
- press the trip push button (BPDL) fully in to turnthe key
(3) interlocking in “tripped” position by padlock
- press the trip push button (BPDL) fully in to pullthe padlocking tab
(5) Interlocking in “Withdrawn”/”Connected”Position by Padlockstandard on the basic breaker• place the breaker in the “Withdrawn”/”Connected” position• remove the crank• push the padlocking tab to the left and thenpull
B - Withdrawable Breakers(4) Padlocking of safety shutters
4
(6) Interlocking in “Withdrawn” / “Connected”Position by Padlock
1
2
3
24
Spectronic Air Circuit Breaker - Operating Instructions
27
InterlockingA - Fixed and Withdrawable Breakers
(1) Interlocking of local control buttons bypadlock
press & hold the “Off” push button, turn the lock-ing catch at 90°, slide the push button windowcovers in and padlock them
- for electrically - operated breaker
(2) Interlocking in “tripped” position byGE ACB / Ronis lock
- press the trip push button (BPDL) fully in to turnthe key
(3) interlocking in “tripped” position by padlock
- press the trip push button (BPDL) fully in to pullthe padlocking tab
(5) Interlocking in “Withdrawn”/”Connected”Position by Padlockstandard on the basic breaker• place the breaker in the “Withdrawn”/”Connected” position• remove the crank• push the padlocking tab to the left and thenpull
B - Withdrawable Breakers(4) Padlocking of safety shutters
4
(6) Interlocking in “Withdrawn” / “Connected”Position by Padlock
1
2
3
24
Spectronic Air Circuit Breaker - Operating Instructions
28
2 - RevisionInspection is to be performed every 3000operations or 3 years (we recommend theintervention of the specialists in the service andverification for this revision).
A - Arc Chute• wipe the insulating cover
B - Poles
• Fixed and Withdrawable Breakers- remove dust from isolating parts- check the gap on arcing contacts with thecircuit-breaker closed.• repeat the adjustment of fixed arcing contactsif the gap is greater than 1,5 mm.
1 - MaintenanceThe arc chutes and arcing contacts ensure :• 1500 closing cut-out operations at In*• 3 closing/cut-out operations at maximumshort-circuit current*• 10 closing cut-out operations at 10 In*All other components are designed to last as longas the breaker ’s normal service life (20,000operations for the electrically-operated ormanual operated breaker).* In one of these cases : Remove the arc chutesand change the arcing contacts.Visual monitoring (every year) :• cleanliness of the circuit breaker.• cleanliness of grease (if the apparatus isexposed to dust)
3 - LubricationA - Components to be Lubricated• all metal/metal friction surfaces must be kept greased.• wipe off excess grease.• grease characteristics : High Speed Grease 475HS mfd. by OKS Industries, Bangalore, India.B - Components not to be lubricated• current-threshold and voltmetric release.
C - Disconnection of SecondaryWiringClean the fixed and movable contacts with acloth slightly dampened with carbontetrachloride.Check for contact pressure.Grease lightly.
D - Overcurrent and VoltmetricReleaseNo maintenance.In case of failure, replace the release.
• replace the arc barriers and the spark arrestersif they are worn by more than 1 mm• clean the surfaces of main contacts with fine-grain emery paper and wipe carefully.
• Removable BreakersClean the following parts with a cloth slightlydampened with carbon tetrachloride :- the cluster contacts- the studs for the cradleGrease lightly
Poles Tightening :The set of poles is maintained under pressure bysix rams located on each flange of the circuit-breaker. Check the tightening torque.
25
Maintenance - Lubrication
Spectronic Air Circuit Breaker - Operating Instructions
2926
Checking - Replacement - Adaptation
2A - 1• release the locking pins (1)• remove the arc chute by lifting upwards.• refiting : engage the chamber on the arcinghorns.• reinstall the locking pins (1)
3A - Arcing Contacts S800 - 2500A• replacement maximum wear limit : 1.5 mm
3A - 1 fixed arcing contact breaker in “open”position• loosen the screw (1)• slide the arcing contact forwards
3A - 2 moving arcing contact / breaker in “closed”position• loosen the screws (2) by about 1.5 mm• free the locator and pull the arcing contact• tightening torque : 3 Nm
3A - 3 gap adjustment breaker in “closed” position• move the fixed arcing contact in order to obtaina dimension of 0.9 ± 0.1 between the end arcingcontacts.• tightening torque : 8 Nm
1A - Adjustment and CheckingAdjustment and checking operations arenormally carried out on equipment before itleaves the factory. It is, however, necessary toverify these points during maintenanceoperations. A maximum wear limit is specifiedfor each paragraph in order to facilitate thisprocedure. When satisfactory adjustment is nolonger possible, the part concerned must bereplaced.
1
2
4A - Arc Barrier• Replacement
4A - 1 Extract the staples (1) with a screwdriver• refit by carrying out operations in the reverseorder.• install new staples.
1
0.9±0.1
�
1
0.9±0.1
�
2A - Arc Chute S800 - 2500AReplacement
Spectronic Air Circuit Breaker - Operating Instructions
30
1C - Adjustment and CheckingAdjustment and checking operations arenormally carried out on equipment before itleaves the factory. It is, however, necessary toverfiy these points during maintenanceoperations. A maximum wear limit is specifiedfor each paragraph in order to facilitate thisprocedure. When satisfactory adjustment is nolonger possible, the part concerned must bereplaced.
3C - 2 After removing the arc chutes and circuitbreaker position “open” :• undo the bolts (1)• slide the arcing contacts forward
2C - Arc Chute S3200 - 4000AReplacement
3C - 4 Setting the gap for “closed” position circuitbreaker• adjust the arcing contact to obtain a dimension0.9 ± 0.1• tightening torque : 8 Nm
Replace the Arc Chute• unscrew the knurled button
3C - 1 Arcing Contacts S3200 - 4000A• replacement wear limit : 1.5 mm
3C - 3 Circuit breaker position “closed”• remove the 2 nuts (2)• slide the arcing contacts by pushing towardsthe front after opening of the circuit breaker.
2
1
0.9±0.1
�
27
Checking - Replacement - Adaptation
Spectronic Air Circuit Breaker - Operating Instructions
31
5A - 1 Disconnect the wiring 5A - 2 Extract pin (2) after removing the two rings(1)
5A - 3 Take out the two screws (3) to remove thecluster contacts (withdrawable 800 to 2500)Rating 2500A maintain the clamps underpressure until they are refitted.
5A - 7 Refit by performing the operation in thereverse order (do not forget the insulating sleevesaround the studs). The screws (3) and (4) are tobe tightened after fitting the assembly pin (2).Tightening torque for screws (3) : 4 Nm.
5A - Current Transformer S800- 2500A• replacement
12
3
5A - 4 Remove the 4 screws (4) (nuts for rating2000), withdraw the pillars (5) with the clamps(removable 2000A) or connection fittings (fixedbreaker).
5A - 5 Remove the transformers
5A - 6 Setting of wire of the transformer ofreplacement using the preinsulated sleevedelivered with the current transformer’s
6A - Pole Tightening• check on tightening- close the breaker. Check the tightening torqueon rams (V) 4 Nm on each flange.
V
5
4
2500A
28
Spectronic Air Circuit Breaker - Operating Instructions
32
5B - 1 Circuit breaker “open”• Remove the arc chute• Disconnect the wiring
5B - 2 Remove the 4 bolts and remove theprimary jaw
5B - 3 Remove the 4 bolts (2). 5B - 4 Lift the fixed contact assembly to removethe transformer.
5B - 5 Reassemble in the reverse sequencepaying attention to the assembly position of theprimary jaw.
5B - 7 Check the arcing contacts gap
5B - Current TransformerS3200 - 4000A• Replacement
2
5B - 6 Setting of wire of the transformer ofreplacement using the preinsulated sleevedelivered with the current transformers.
29
Spectronic Air Circuit Breaker - Operating Instructions
33
7 - 3 To remove the RMS7 / 9D Unit from its mechanical support, push the lever (4) to the top and pull it . 7 - 4 Disconnect the connector (5).Replacement : plug in the connector (5) on thetrip unit and filt the unit on its support in the sameway as the dismounting operation.
7 - 5 Attach the front panel (12) with four 5Øscrews (2). Tilt the operating handle forwards tofacilitate installation.
7 - 6 Refit the front cover (10) with four 4Ø screws(1).Inspection : check electrical operation with thetest set (checking instructions inside the test box).
7 - 2 Remove the front panel (12), by taking outthe four 5 Ø screws (2)• tilt the operating handle forward to facilitateremoval
7 - 1 Breaker in “open” position• remove the front cover (10), by taking out thefour 4Ø screws (1)
7 - RMS7 and RMS10, RMS12• Replacement
4 5
12 2
2
1
10
1
12
2
2
4
1
10
1
RMS7 and RMS10, RMS12
Spectronic Air Circuit Breaker - Operating Instructions
34
8 EX (Trip Coil) EX RMS• Replacement
8 - 7 Remove the 6Ø attaching nuts (14) fromthe EX support plate with a 10mm wrench.
8 - 6 Remove the hook-up by taking out the two6Ø screws (13), using a 10mm wrench.
8 - 5 Uncouple rod (6) from the crank (7) of tripswitch EX, removing ring (8) and pin (9).
8 - 1 Breaker in “open” position• remove the front cover (10) by taking out thefour 4Ø screws (1)
8 - 2 Remove the front panel (12), by taking outthe four 5Ø screws (2)• tilt the operating handle forward to facilitateremoval
8 - 3 To remove the RMS7, RMS10, RMS12 Unit from its mechanical support,push the lever (4) to the top and pull it .
8 - 4 Disconnect the connector (5).Replacement : plug in the connector (5) on thetrip unit and fit the unit on its support in the sameway as the dismounting operation.
7
6
98
13
14
4
12 2
2
1
10
1
4
5
Spectronic Air Circuit Breaker - Operating Instructions
35
8 - 8 Remove the support plate from EX by takingout one 5Ø screw (15).
8 - 11 Refit the fixed section of the new connector(4)
8 - 12 Refit by carrying out the same operationin reverse order. Connect up the connectors.
8 - 9 Remove the fixed section of connector (4). 8 - 10 Refit the new EX on the support plate withone 5Ø screw (15).
8 - 14 Refit the front cover (10) with four 4Øscrews (1).
8 - 13 Refit the front panel (12) with by four 5Øscrews (2). Tilt the operating handle tofascilitate installation.
1
1
10
12
2
15
15
4
42
32
Spectronic Air Circuit Breaker - Operating Instructions
36
Overcurrent release RMS S800 - 2500A
A - Breaker with no memory type tripping indication (local-reset circuit-breaker)
9A - 2 Breaker in “open” position, with trip releaseand crank (11) against stop (10)• adjust the link rod (9) to obtain 1 ± 0,5
9A - 3 Push trip button BPDL (12) fully in on thefront panel• adjust the screw (14) so as to latch the release• loosen the screw by one turn to obtain therequired resetting safety margin.
9A - 1 Resetting• breaker without memory-type trippingindication (local-reset circuit-breaker)
9A - 5 Check that there is a minimum play of 0,2mm between the armature (13) and the adjustingscrew (14)• press trip push button BPDL (12) fully in andcheck that there is a minimum play of 0,2 mmbetween the spigot (5) on the latch (4) and thebottom of the recess.(A) latched.
9A - Verification of Resetting
9A - 4 Operate trip push button BPDL (12) andcheck that there is a latching safety margin of0.5 mm : return of release crank on latching.
33
Reset checking
Spectronic Air Circuit Breaker - Operating Instructions
37
Overcurrent release RMS S3200 - 4000A
A - Breaker with no memory-type tripping indication (local-reset circuit-breaker)
9B - 2 Check the play by holding the crank (11)on its stop (10), the rod (12) on the axis (13),evaluate the distance/clearance by alternatelydisplacing the rod.
9B - 3 Push down on the local reset and trip pushbutton (14) situated on the panel.• adjust the screw (15) to achieve a trip.• unscrew one turn to obtain reset clearance.• a very distinct trigger signal is made on themoment of tripping.
9B - 1 Circuit breaker “open” position, tripreleased, crank (11) pushing on its stop (10) therod (12) at the bottom of the slot on the axis (13),set the rod (9) to obtain the dimension 1 ± 0.5mm.
9B - 5 Push fully on the local reset and trip pushbutton (14) and check for a minimum play of 0.2mm between the pin (5) of the lock (4) and thebottom of the slot (see sketches9-3 and 9-4).
9B - Verification of Resetting
9B - 4 Circuit breaker position “open” push the local trip and reset button (14) and check a safetylinkage clearance of 0.5 mm: trip crank returns on engagement.• Push button at rest, rod on its stop.• Check for a minimum play of 0.2 mm between the plate (16) and the adjustment screw (15).
34
Reset Checking
Spectronic Air Circuit Breaker - Operating Instructions
38
35
B - Breaker equipped with memory-type indication of tripping due to overload and short-circuit (automatic reset circuit-breaker)
9 - 6 Breaker in “open” position• adjust the screw (1) so as to obtain latching ofthe release• screw in 3/4 of a turn in order to obtain therequired resetting safety margin.Note : a very distinc sound can be heard whenlatching occurs.
C - Breaker with no trip device (Switch) 9 - 8 Breaker in “open” position• check that there is a minimum play of 0.5 mmbetween the actuating part (11) operated ontripping and the spigot (12) on the latch (13) inthe rest position.• check that there is a minimum play of 2 mmbetween the reset screw (16) and the actuatingpart (11)
9 - 7 Checking• breaker in “open” position• check that there is a latching safety margin of1.5 mm :return of release crank on latchingWEAR LIMIT : failure to latch.(A) latched (R) reset
9 - 9 Tripping with RMS• check that there is a minimum play of 2mmbetween the reset screw (16) and the trippingbreaker in “open” position• reset adjusting screw (1) fully unscrewed.
9 - 11 Checking• breaker in “closed” position.• check that there is a minimum play of 0,5 mmbetween the actuating part (6) operated ontripping and the spigot (5) on the latch (4) in thereset position.WEAR LIMIT : 0.1• connect up the TEST box and test the variousfunctions in accordance with the instructionsgiven in the test box• check that the breaker trips normally on eachtest .
9 - 10 With the release latched, adjust thelink rod (7) to obtain a dimension of 1 ± 0,5between the actuating part (6) operated ontripping and the spigot (5) on the latch (4) inthe rest position.
Resetting
S800/2500A S3200/4000A
Spectronic Air Circuit Breaker - Operating Instructions
39
Options for protection units RMS7, RMS10, RMS12
Affix the lead (4).Feed through the lead wire (3).
Set the lead (lead + wire not supplied). End of operation.
Fit this sub-assembly on the unit.Fit (2) onto the sealable cover (1).10 - LEAD SEALING THE RMSSETTINGSInstallation - Replacement
1
2
2 1
3
34
Spectronic Air Circuit Breaker - Operating Instructions
40
37
11 - Voltage-threshold tripdevices• Replacement
11 - 2 Remove the ring (1) to un-couple the linkrod
11 - Disconnect the wiring
11 - 3 Take out the two screws (2) and removethe release
11 - 5 Checking• tripping with breaker in “open” position• resetting adjusting screw (item (7) in figurebelow) fully loosened
11 - 4 Refit by carrying out the same operationsin reverse order
11 - 6 With the release latched, adjust the linkrod (1) to obtain a dimension of 1 ± 0.5 betweenthe lever (2) and the spigot (3) on the latch (4) inthe reset position.• breaker in “closed” position• hold the striker (6) with a hook (C) in order toavoid acting against opening when resetting therelease, and free the release latch mechanism.Free the latch slowly to check that the breakertrips.
11 - 1 Disconnect the wiring
11 - 7 Resetting with breaker in the “open”position• adjust the screw (7) to position the striker (6)fully home.• unscrew by half a turn• check that there is a safety margin minimumresetting of 2 mmWEAR LIMIT : failure to resetNB : If the breaker is equipped with two voltmetricreleases, check that both releases operatecorrectly after adjustment.
1
S-800 - 2500A S3200 - 4000A
2
6
Spectronic Air Circuit Breaker - Operating Instructions
41
12 - 2 Disconnect the wiring
12 - 5 Refit by carrying out the same operationsin reverse order
12 -1 After removal of the protective plate fromthe front panel and protection RMS :• breaker in the “open” position : access to contacts (1, 2, 3, 4)• breaker in the “closed” position : access to contacts (5, 6, 7, 8)
12 - Auxiliary• Replacement
12 - 3 Loosen the screw (1) and remove thecontact
12 - 4 Remove the contact from its support (2)
1
38
Spectronic Air Circuit Breaker - Operating Instructions
42
13 - Electrical Operator - Motor• Replacement
13 - 2 Disconnect the wiring from the terminals13 - 1 After removing the front cover
13 - 6 Refit by carrying out the same operationsin reverse order, checking that there is workingplay between the pinion and the gear wheel• reconnect the wiring
13 - 3 Loosen the 2 screws (1)• remove the motor
13 - 4 Following removal of the cover• disconnect the wire terminals
1
S800 - 2500A
S 800 - 2500A
S3200 - 4000A S3200 - 4000A
13 - 5 Loosen the 2 screws (2)• remove the motor
2
39
Spectronic Air Circuit Breaker - Operating Instructions
43
14A - Reset limit switchS800-2500A• Replacement
14A - 1 After removing the front cover, unscrewthe nuts• remove the contact
14A - 2 Disconnect the wiring14A - 3 Reconnect the wiring onto the newcontact• refit by carrying out the same operations inreverse order, checking that the spacers are stillin place on the attachment screws.
14B - Reset limit switchS3200-4000A• Replacement
14B - 4 Reconnect the wires on the new contact• reassemble in the reverse order, making surethat the spacers remain in position on the fixationbolts.
14B - 1 Unscrew the nut (6), 10 mm spanner.
6
14B - 2 Remove the plate support handle
14B - 3 Unscrew the 2 nuts (7) (8mm spanner)• remove the contact• disconnect the wire
7
40
Spectronic Air Circuit Breaker - Operating Instructions
44
Note : Unused parts are to be discarded
15A - 4 Reconnect the wiring onto the newcontact and refit by carrying out the sameoperations in reverse order
15A - 3 Disconnect the wiring and mark thepositioning of the wires
15A - Resetting spring contactS800-2500A• Replacement
15A - 1 Lay down the circuit-breaker of the leftpanel
15A - 2 Loosen the screw (1) and take out thecontact/support assembly (using two 10 mmwrenches)
15B - Resetting Spring ContactS3200-4000A• Replacement
15B - 1 Undo the 3 Ø5 screws (5) and lift out theplate support assembly and RMS trip release.
15B - 2 Disconnect the wire marking the positionof the wires
1
5
5
41
Spectronic Air Circuit Breaker - Operating Instructions
45
16A - 3 Swing the link rod (4) forwards to fit thescrews (3) and plate (1), 5.5 mm wrench
16A - 4 Fit the contact as described in theprevious section
16A - 1 Unhook the spring (3) and note itsdirection of installation for refittng
16A - Resetting spring contactS800-2500A• adaptation (1) plate
(2) contact (3) screws
15B - 4 Take out the contact support assembly15B - 3 Undo the screws(3)
15B - 5 Reconnect the wire on the new contactsupport assembly and assemble in the reverseorderNote : The parts provided which are not usedare to be discarded.
1
2 3
3
16A - 2 Remove the screws (1) using two10mm wrenches
1
4
3
3
4
42
Spectronic Air Circuit Breaker - Operating Instructions
46
43
16B - 2 Gently incline the handle forwards toallow the installation of the bolt (3)
16B - 1 Undo the 3 Ø5 bolts (5) and remove theplate support assembly and RMS trip release.
16B - Resetting spring contact3200-4000A• adaptation(1) plate(2) contact(3) screws
16B - 3 Install the contact support assembly (2)paying attention to the positioning of themoving plate of the contact
16B - 4 Tighten the assembly bolts, washer, nut(3)
16B -5 Reassemble in the reverse orderNote : The parts provided which are not usedare to be discarded.
5
2
3
3
5
Spectronic Air Circuit Breaker - Operating Instructions
47
44
17A - 1 Disconnect the wiring after removing thefront cover, the front panel and protection RMS.
17A - Closing PreventionDevice S800-2500A• Replacement
17A - 2 Remove the two attachment screws• refit the new closing prevention device bycarrying out the same oepration in reverse order.
17B - 1 After removing the front cover, disconnectthe wire• Remove the closing prevention device
17B - Closing PreventionDevice S3200-4000A• Replacement
17B - 2 Reassemble the new closing preventiondevice in the reverse order.
17A - 3 Adjustment• breaker energizedwith parts (57, 58 and 59) resting on their stops,adjust the elbowed lever (60) to obtain a play of0.6 ± 0.4• checking :- check that there is a minimum play of0.2 mm
17A - 4 Wear limit : 0.1 mm• in this position, the device allows engagementof the mechanism.• with the device de-energized and lever (59)resting at its stop, check that there is a minimumplay of 0.1 mm between level (58) and the pin(61)• the device does not allow engagement in thisposition.
Spectronic Air Circuit Breaker - Operating Instructions
48
45
17B - 3 Setting• Circuit Breaker “open”(1) set the gap to 0.5mm between the trip lever(1) and the axis (3) by turning the cam (4), tightenup the lock nut.
17B - 4 Setting• electrical-supply(1)set the play to 0.5 mm between the pin 2and the axis of the crank 5 by adjusting thenut 6 of the reset and trip push button,tighten the lock nut.(2) set the play to 0.5 mm between the pin 2and the axis of the crank 7 by tightening orslackening the latter, tighten the lock nut.
18A - 2 Remove the pin (1)18A - 1 Disconnect the wiring after removing thefront cover, the front panel and protection RMS.
18A - Closing Coil S800-2500A• Replacement
18A - 3 Take out the four screws (2)• remove the closing coil• refit by carrying out the same operations inreverse order
2
1
Spectronic Air Circuit Breaker - Operating Instructions
49
46
19A - 1 After removing the front cover, disconnectthe wiring, Remove the cut-out chambers foreasier access to the terminal.
19A - 2 Loosen the 2 screws (1)• remove the contact• refit by carrying out the same operations inreverse
19A - Insertion Contact S800-2500A(Direct Current)• Replacement
18B - 1 After removal of the front cover,disconnect the wire• remove the 4 bolts (2)
18B - 2 Remove the axis pin (1)• remove the closing electro magnet• reassemble in the reverse order
18B - Closing Coil S3200-4000A• Replacement
19B - 1 After removal of the front cover,disconnect the wire, lift out the arc chutes tofacilitate access to the terminals.
19B - 2 Unscrew the 2 bolts (1)• remove the contact• reassemble in the reverse order
19B - Insertion Contact S3200-4000A(Direct Current)• Replacement
1
2
1
1
Spectronic Air Circuit Breaker - Operating Instructions
50
47
20A - Economy Resistor S800-2500A(Direct Current)• Replacement
20A - 1 After removing the front cover, disconnectthe wiring. Remove the cut-out chambers foreasier access to the terminal.
20A - 2 Loosen the 2 screws (1)• remove the contact• refit by carrying out the same operations inreverse order
20B - Economy Resistor S3200-4000A(Direct Current)• Replacement
20B - 1 After removal of the front cover,disconnect the wire, lift out the arc chutes tofacilitate access to the terminals.
20B - 2 Unscrew the 2 bolts (1)• remove the resistor• reassemble in the reverse order
1
1
Spectronic Air Circuit Breaker - Operating Instructions
51
48
21A - Isolating Shutters S800 -2500A• Installation
21A - 1 Identification
21A - 3 Fit the parts (8), (9), (10) and (11) on thepins (7)
21A - 2 Install the padlocking system (14) withattachment hardware (15)
21A - 4 Secure the right-hand mechanism (4) onthe right-hand flange with 2 screws and washers(5)
21A - 5 Engage the upper spigot on the pin (7) inthe hole (C)• slide the pin for part (10) into the fork (A)
21A - 6 Engage the lower spigot on the pin (7)into the bracket (13) and secure it withattachment hardware (12).
21A - 7 Engage the link rod (B) on the pin for part(11)
3 5 6
12
5
8
9
16
13 1817
13
12
10
11
5
4562
7
1
7
1415
11
10
77
8
9
C
A
10
B11
713
12
Spectronic Air Circuit Breaker - Operating Instructions
52
49
21A - 8 Fit the ring (6) 21A - 9 Carry out the same operation on the left-hand side and then install the shutters (1) withattachment hardware (2).
21A - 10 Fit the spacers (18) on the guide plates(16) and (17) with attachmenthardware.
21A - 11 Fit the right and left-hand assembly ontothe circuit-breaker.
6
Spectronic Air Circuit Breaker - Operating Instructions
53
50
21B - Isolating Shutters S3200 -4000A• Installation
21B - 1 Identification
21B - 3 Remove the 3 nuts, lock washers and flatwashers. On reassembly do not re-use the flatwashers.
21B - 2 Install the padlock mechanism (14) withthe aid of the bolt set (15).
10
824
5
17 187 25
26
9
11
7
18
2
16 14
1
1322
21
4
15
11
7 7
89
10
22
Spectronic Air Circuit Breaker - Operating Instructions
54
51
21B - 5 Fix the right mechanism (4) on the rightflask and the mechanism (24) on the left flask withthe aid of the 2 bolts and washers (25).
21B - 4 To engage the rod (B) on the axis ofmechanisms (9 right and 8 left) to put rings (6)after having positioned the sets (11-4 right and10-24 left) enters square (13) and top of cradle.
21B - 8 Check the operation of the shutters andinter-locks.
21B - 6 With all parts being correctly assembled,complete by tightening up the nuts and checkingthe operation.
B
21B - 7 Install the upper screen (1) with the boltset (2) and the lower screen (21) with the bolt set(26).
21B - 9 Install the spacers (18) on the guide plate(16) and (17) with the aid of the bolt sets.
21B - 10 Mount the left and right assembly onthe circuit breaker.
8/9
10/11 4/24
13
25
Spectronic Air Circuit Breaker - Operating Instructions
5552
Fixed or Withdrawable Breaker - Interlocking in "tripped" position
22 - 2 Remove the front panel (2) by taking outthe four 5Ø screws.Tilt the operating handle forward to facilitateremoval.
22 - 1 With the breaker open, remove the frontcover (1) by taking out the four 4Øscrews.
22 - With Padlock Fitting• Fitting
22 - 6 Tighten the guide plates (5) and (7) withrecovered screws (8) and screws supplied in thebag (9).
22 - 3 Break through the imprint (3) to allowinsertion of the padlock tab (4).
22 - 5 Engage the link rod (6) by raising thepadlock tab (4).
22 - 7 Hook up the spring (10). 22 - 8 Refit the front panel (2) with four 5Ø screws,and refit the front cover (1) with four 4Ø screws.
4
3
21
6
22 - 4 Remove the guide plate (5) and recover 2screws (8).
10
21
4
6
9
7
9 10
4
9
75
8
5
8
Spectronic Air Circuit Breaker - Operating Instructions
5653
Fixed or withdrawable breaker - Interlocking in "tripped" position
23 - 1 With the breaker open, remove the frontcover (1) by taking out the four 4Ø screws.
23 - 2 Remove the front panel (2) by taking outthe four 5Ø screws.Tilt the operating handle forward to facilitateremoval.
23 - With Padlock and GE ACB / RONISlockRONIS Lock Type 1104, 1/4 turn left-handopening or PROFALUX lock, type KS 5B 20 G4Y(not supplied).
23 - 3 Break through the imprint (11) to allowinsertion of the lock (12) in the front panel (2).
23 - 4 Break through the imprint (3) to allowinsertion of the padlock tab (4).
23 - 5 Remove the guide plate (5) and recover 2screws (8).
23 - 6 Fit the GE ACB / RONIS lock or PROFALUXlock (12) with collar, with the key imprint facingdownwards.
23 - 7 Fit the corresponding cam (A or B) for thelock : A = RONIS B = GE ACB or Profalux. Lock thenut. Take care to install the cam the right wayround so that the key is removed in lockedposition.
23 - 8 Fit the padlock tab (4).
1212
2
4
A
3
4
1
6 A B
7 9
10
4
12
2
11 5
8
Spectronic Air Circuit Breaker - Operating Instructions
57
54
23 - 9 Engage the link rod (6) by raising thepadlock tab (4).
23 - 11 Hook up the spring (10).23 - 10 Tighten the guide plates (5) and (7) withrecovered screws (8) and screws in the bagsupplied (9).
6
10
4
23 - 12 Refit the front panel (2) with four 5Øscrews.
23 - 13 Refit the front cover (1) with four 4Øscrews.
2 1
8
5
9
7
Spectronic Air Circuit Breaker - Operating Instructions
5855
Fixed or withdrawable breaker - Interlocking in "tripped" position
24 - With GE ACB / Ronis locktype 1104 1/4 turn left-hand openingor PROFALUX lock type KS 5B 20 G4Y (notsupplied)
24 - 1 With the breaker open, remove the frontcover (1) by taking out the four 4Ø screws.
24 - 2 Remove the front panel (2) by taking outthe four 5Ø screws.Tilt the operating handle forward to facilitateremoval.
24 - 3 Break through the imprint (11) to allowinsertion of the lock (12) in the front panel (2).
24 - 7 Engage the link rod (6).
24 - 5 Fit the GE ACB / Ronis lock or PROFALUXlock (12) with collar, with the key imprint facingdownwards.
24 - 6 Fit the cam (A or B) for the lock : A = RONISB = GE ACB or Profalux. Lock the nut . Take careto install the cam the right way round, so thatthe key is removed in the locked position.
24 - 8 Tighten the guide plates (5) and (7) withrecovered screws (8) and screws in the bagsupplied (9).
10
A
6
12
24 - 4 Remove the guide plate (5) and recover 2screws (8).
12
21
A B
7 9
12
5
8
11
2
8
5
9
7
6
Spectronic Air Circuit Breaker - Operating Instructions
59
56
24 - 10 Refit the front panel (2) with four 5Øscrews.
24 - 9 Hook up the spring (10). 24 - 11 Refit the front cover (1) with four 4Øscrews.
10
2
1
Spectronic Air Circuit Breaker - Operating Instructions
6057
Fixed or withdrawable breaker - Interlocking in "tripped" position
25 - 1 With breaker open, remove the front cover(1) by taking out the four 4Ø screws.
25 - 2 Remove the front panel (2) by taking outthe four 5Ø screws.Tilt the operating handle forward to facilitateremoval.
1
25 - 4 Remove the guide plate (5) and recover 2screws (8)
25 - With Single Letter CastellLock
25 - 5 Fit the Castell Lock (12) with collar, withthe key imprint facing downwards
25 - 6 Fit the cam on Lock (12) with nut andwasher. Take care to install the cam right wayround, so that the key is removed in the lockedposition.
2
12
25- 3 Break through the imprint (11) to allowinsertion of the lock (12) in the front panel (2).
1216
25 - 7 Engage the link rod (6). 25 - 8 Tighten the guide plates (5) and (7) withrecovered screws (8) and screws in the bagsupplied (9).
12
6
10
5
16
8 9
7
6
2
11 5
8
8
5
9
7
Spectronic Air Circuit Breaker - Operating Instructions
61
58
25 - 10 Refit the front panel (2) with four 5Øscrews.
25 - 9 Hook up the spring (10). 25 - 11 Refit the front cover (1) with four 4Øscrews.
10
2
1
Spectronic Air Circuit Breaker - Operating Instructions
6259
Fixed or withdrawable breaker - Interlocking in "tripped" position
26 - CASTELL LOCK 2 LETTER or CASTELL LOCK 1 LETTER + GE ACB / RONIS LOCK
26 - 3 Machine the front panel (2) in accordance with this drawing for insertion of castell lock 2 letter or castell lock 1 letter (37mm dia).
Place the drilling templateSGS 6100096 as shown &drill hole Ø37 ± 0.2 (Removethe template after comple-ting the drilling operation).
CASTELL LOCK KEY
M6 NUT (15)
M6 STAR WASHER (15)
SCREWS (13)
SPRING (10)
PUSH BUTTON BASE
SELF TAPPING SCREWS(9)
SPACER (11)
SUPPORT (4)
LINK ROD (6)
26 - 3 Break through the imprint (11) to allowinsertion of GE ACB / Ronis lock in the front panel(2).
GE ACB / Ronis Lock
CASTELL LOCK(12)
26 - 1 With breaker open, remove the front cover(1) by taking out the four 4Ø screws.
26 - 2 Remove the front panel (2) by taking outthe four 5Ø screws.
2
1
2
11
Spectronic Air Circuit Breaker - Operating Instructions
63
60
26 - 5 Engage the spacer (17) on the lock (12)above the cam (16)
26 - 4 Fit the cam (16) on the lock (12) Take careto install the right way round: so that the key isremoved in the locked position
26 - 6 Position the screws (13) on the lock (12)and spacers(11)
26 - 8 Attach the lock with the contact washers(19) and nuts (15) using a 10 mm wrench
26 - 7 Fit the lock (12), assembled as describedabove, on the support (18)
26 - 10 Engage the link rod (6)26 - 11 Install the support / lock assembly alongwith the recovered screws (8) and the screwssupplied in the bag (9), making sure that the cam(16) is positioned under the link rod (6) and behindthe spigot
1312
1117
12
16
12
16
18 12
15
19
19
15
26 - 9 Remove the guide plate (5) and recover 2screws (8).
5
8
6
89
Spectronic Air Circuit Breaker - Operating Instructions
64
61
26 - 13 Refit the front panel (2) with four 5Øscrews.
26 - 14 Refit the front cover (1) with four 4Øscrews. (front facia with double letter or singleletter (37mm dia) castell lock )
26 - 12 Hook up the spring (10)
10
26 - 15 to fix the GE ACB / Ronis lock follow thesteps decribed in 24-3 to 24-6.
26 - 16 front facia with single letter castell lock(37mm dia) and GE ACB / Ronis lock. This singleletter castell lock (37 mm dia) is different fromthe stand alone single figure castell lock whichis fixed in the position of GE ACB / Ronis lock.
2
1
Spectronic Air Circuit Breaker - Operating Instructions
6562
Withdrawable breaker - Interlocking in "Withdrawn" / "Connected" position
27 - With GE ACB / RONIS locktype 1104 1/4 turn right-hand openingor PROFALUX lock, type KS 5B 20 D4Y (notsupplied).
27- 3 Remove the front box mould (20) from thebreaker's cradle by taking out the two 5Ø screws.
27 - 6 Fit the corresponding cam for the lockchosen and secure it by locking the nutfor GE ACB / RONIS lock : cam (13) and nut (3)for PROFALUX lock : cam (14) and nut (30)Take care to install the cam the right way roundso that the key is removed in the locked position.
27 - 1 The lock is attached onto the front box (20)on the breaker's cradle.
27 - 2 Remove the sleeve (5) by removing the3Ø screw
27 - 4 Break through the imprint to fit thelock
27 - 5 Position the lock (12) and collar withthe corresponding nut: GE ACB / RONIS lockwith nut (3) / PROFALUX with nut (30). Thekey imprint must be facing downwards.
20
27 - 7 Refit the front box mould (20) on the cradlewith the horizontal captive key. Stick on the label(32) as shown above. Refit the sleeve (5).
27 - 8 Cradle with 2 locks, GE ACB / Ronis Lockand Padlock
Note: The maximum number of interlockingdevices that can be installed on a cradle is one‘’connected’’ / ‘’withdrawn’’ position GE ACB /Ronis lock and one ‘’withdrawn’’ / ‘’connected’’position Padlock.
5
205
3
14
12
13
30
32
13
20
3
12
Spectronic Air Circuit Breaker - Operating Instructions
66
63
28A - Fault Signalling ContactS800-2500A
• Replacement
28A - 1 Bag containing 1 contact
28A - 2 Packets of 2 contacts 28A - 3 Location on the equipment. Rest thebreaker on the left-hand flange and lockunderneath, at the cross-member, zone A.
28A - 6 Disconnect the wiring and mark thelocations of the wires :- 1st contact : 95 - 96 - 98- 2nd contact : 05 - 06 - 08Discard the support-contact assembly, screws.
28A - 7 Place the new support in position andreconnect the wiring on the contact.Taking care to comply with the markings.
28A - 8 Position the support/contactassembly and secure it with the attach-ment hardware supplied : two screws 5x16,two 5 Ø DE washers, and two 5 Ø nuts, usingan 8 mm wrench.
28A - 9 Check the position of the crank (3) withrespect to the armature for the contact or contacts.Check for correct operation with the breakeropen and the fault contact actuated.NOTE : Unused parts and wires are to bediscarded.
28A - 5 Swing the support/contact assembly(1 or 2) towards you (2).
28A - 4 Loosen the two screws (1) 5Ø x 16, with a8 mm wrench.
A
12
3
Spectronic Air Circuit Breaker - Operating Instructions
67
64
28B - Fault signalling contactS3200-4000A
• Replacement
28B - 1 Bag containing 1 contact
28B - 2 Bag containing 2 contacts 28B - 3 Unscrew the 3 5Ø screws (5) and lift outthe plate support assembly and RMS trip release.
28B - 6 Undo the 2 nuts (1), 8mm spanner.
28B - 7 Unscrew the plate and slide to the left(facing the circuit breaker).
28B - 8 Swing the support assembly and contacttowards yourself (2).
28B - 9 Disconnect the wire whilst marking theposition of the wires.- 1st contact : 95 - 96 -98- 2nd contact : 05 - 06 - 08Throw away the contact support assembly.
28B - 5 Undo the fixation nuts 6Ø (14), 10 mmspanner, of the EX plate support.
28B - 4 Uncouple the arm (6) of the crank (7) of theEX trip release by removing the clips (8).
6
7
8
141
5
2
5
Spectronic Air Circuit Breaker - Operating Instructions
68
65
28B - 10 Present the new support and reconnectthe wire to the contact.Pay attention to the marking.
28B - 11 Position the contact support assemblyand fix with the nut and bolt set provided (two5Øx16 bolts + two 5Ø washers + two 5Ø nuts), 8mm spanner.
28B - 12 Check the position of the crank (3)relative to the contacts plate. Check the operationwith the circuit breaker "open" and fault contactactivated.Note : The parts and wires not used should bediscarded.
3
Spectronic Air Circuit Breaker - Operating Instructions
70
67
29 - 10 Fixed sectionNOTE : If the craddle is fitted with a spacer, attachthe cut-off block onto that spacer.
29 - 11 Secure the fixed block onto the cradle,to the right or left-hand side, according to themovable section, using the attachment hardwaresupplied (zone B of the craddle flange).
29- 16 Fixed sectionAttention : The 3rd block is never factory-installedon the fixed section.NOTE : If the 2nd block is fitted with a spacer, the3rd block must imperatively be fitted with thespacer supplied.
29 - 14 Secure the movable block to the right-hand or left-hand flange of the circuit-breakerusing the attachment hardware supplied (zone Cof the flange).
29 - 15 Connect the Wiring29 - 13 Adaptation third block• Movable section
29 -17 Removing the attaching plate used duringtransportation and secure the 3rd block (zone Cof the right or left-hand flange of the cradle)according to the movable section of the circuit-breaker, using the attachment hardware supplied.
29 - 18 Remove the cover to connect up thewiring, Refit the cover.NOTE : Customer connection by clips 6.35 x 0.8.
29 - 12 Connect up the Wiring
C
B
C
Spectronic Air Circuit Breaker - Operating Instructions
7168
Withdrawable breaker - Earth connector 25 KA 0.5 S
30 - 2 Movable section (2)30 - 1 Contents of bag
30 - 4 Place the connector (2) in position on the
right-hand flange and insert the threaded studsand screw (1) in the corresponding holes.
30 - 5 Fit the three 6 Ø contact washers (3) and
the three 6 Ø nuts (4). Lock the assembly with a 10mm wrench.
30 - Fitting
30 - 3 Fit the screw (1) 6 Ø x 16, in the hole in the
movable connector (2).
1
2
2
1
3
4
S800 - 2500A
S3200 - 4000A
3
2
4
1
12
156 7 1
2
4
3
4
13
10 115
Spectronic Air Circuit Breaker - Operating Instructions
72
69
30 - 6 Fixed section (14) 30 - 7 Take the small columns (5) and assemble
them as shown above with renforcement piece(6) and the connecting component (15) on theside with the longest thread.
30 - 8 Fit the two 8 Ø plain washers (7) and the
two 8Ø nuts (9).Lock the assembly with a 13 mm wrench.
30 - 9 Place the assembly in position fitted in
the craddle to the bottom right-hand side of zoneB at the back.
30 - 10 With the two studs fitted in the
corresponding holes, fit the two 8 Ø DE washers(10) and the two 8Ø nuts (11). Lock them witha 13 mm wrench.
30 - 11 Position the label (12) in between the
two "CUSTOMER EARTH" connecting screws asdesired, as shown above.
NOTE : The two bigger columns (13) suppliedin the bag are to be used in place of thetwo smaller columns (5) for Spectronic circuit-breakers 3200 and 4000A.Discard the unused parts.
7 - 9
10 - 1112
B
15
5
6
9
6
13 12 15
1110
5
7
Spectronic Air Circuit Breaker - Operating Instructions
7370
31 - Signalling contacts on cradle
• Adaptation
31 - 1 Attach the assembly onto the two studsprovided on the cradle, with two washers andnuts.Connect up the wiring. A grommet is providedfor the wiring feed-through.
31 - 2 Indicating contacts on cradle• Replacement
31 - 3 After disconnecting the wiring, remove theassembly with the support in order to facilitatereplacement of the faulty contact.
31 - 5 Extract the mounting pins (2)· Remove the contact
31 - 4 Remove the rings (1)
2
1
S800 - 2500A S3200 - 4000A
Spectronic Air Circuit Breaker - Operating Instructions
74
71
32 - 1 Screw the support/contact assembly ontothe craddle.
32 - Coupled Contact With plug-in Control
• Adaptation
32 - 2 Connect up the wiring, a grommetis provided for the
33 - Coupled Contact With plug-in Control
• Adaptation
33 - 1 Screw the support/contact assembly onto
the craddle.
33 - 2 Connect up the wiring, a grommetis provided for the wiring feed-through.
S800 - 2500A
S3200 - 4000A
Spectronic Air Circuit Breaker - Operating Instructions
75
Replacement PartsgnitaR eloP ot gnidroccA rebmuNnoitpircseD
S 800 1000 1250 1600 2000 2500111111stcatnoc gnicra dexiF543333stcatnoc gnicra eliboM222222sreirrab crA444444tnemhcatta reirrab crA
Arc chute 500V 1 1 1 1 1 1690V 1 1 1 1 1 1
111111SMR esaeler rof liocpirTNumber According to Pole Rating
S 3200 400064stcatnoc gnicra dexiF64stcatnoc gnicra eliboM
Arc chute 1 111SMR esaeler rof liocpirT
Number Per BreakerRating RMS7 800 1000 1250 1600 2000 2500 3200 4000
In 400A 1In 600A 1In 800A 1In 800A 1In 1000A 1
1A0521 nIIn 800A 1In 1200A 1In 1600A 1In 1200A 1In 2000A 1In 1600A 1In 2500A 1In 1600A 1In 3200A 1In 2500A 1In 4000A 1
)xam( rekaerB reP rebmuNnoitpircseDRMS7 1
Release RMS7 EX RMS 1Options RMS7 1RMS9D 2000 3P 1
Release RMS10/RMS12 RMS9D 2000 4P 1RMS9D 3200 3P 1RMS9D 3200 4P 1RMS9D 4000 3P 1RMS9D 4000 4P 1
Voltmetric ReleasesEA 50 Hz 110V 2
220V 2415V 2
EA DC 24V 2110V 2220V 2
UV 50Hz 220V 2415V 2
UV DC 24V 2110V 2
UVRD 50Hz 220V 2250 ms
To seenotes
RMS10/RMS12EX is built in
EX is built in
Spectronic Air Circuit Breaker - Operating Instructions
76
73
Description Number Per Breaker (max)
8CN1 + ON1 stcatnoc yrailixuAResetting motor for electrical operation S800-2500 S3200-4000
11V011zH0511V02211V42CD11V011
Closing coil for electrical operation S800-2500 S3200-400011V011zH0511V02211V42CD11V011
Economy resistor for DC closing coil24V R 11 1 1110V R 330 1 1
Insertion contact of 1 1economy resistor for closing coilClosing prevention device S800-2500 S3200-4000
11V011zH0511V02211
Spectronic Air Circuit Breaker - Operating Instructions
7774
Schematic DiagramRMS 7 : protection and monitoring unitDiagram showing de-energised circuits, open circuit breaker, connected, reset, handles not inserted.
Legend
Overcurrent releasesBA Overload and short-circuit fault contact
K1 Fault signalling relay
R1 Booster voltage for 220V
S1 Fault cancelling push-button
GF Ground fault indicator lamp
ST-I Instantaneous or short circuittripping indicator lamp
LT Long time trip (overload) tripping indicator lamp
Voltmetric releasesC41 Trip contact UVR-UVRD
C43 Undervoltage contact UVR-UVRD
C31 Trip contact EA
Ra-R6 Booster resistor for direct current voltages
S1 Optional disconnecting switch UVR-UVRD(break out of service)
Operation with energy storageM Motor
FCA Resetting limit switchManual setting
CA 1-8 Auxiliary contacts
EE Closing coil
EA Shunt Trip
S2 Remote tripping control
S5 Remote closing control
S3 Remote closing and tripping controlchangeover switch
C22 Reset contact of the spring
C20 Contact coupled with local reset tripping push-button
FE Closing prevention device
WithdrawableC51.52 Contacts ‘connected’ position
C61.62 Contacts ‘withdrawn’ position
C71 Pre-trip contact coupled with insertion control
Spectronic Air Circuit Breaker - Operating Instructions
7875
Schematic Diagram
End user connections
Withdrawable Circuit BreakerConnection by terminals 6.3 x 0.8For electrical operation of EA, BA1, BA2, UVR, UVRD, RMS7, LMZ7use the allocated numbers.Other accessories : numbers are increasing in the directionshown (use reserved terminals if they are available).
LT Disconnects
Spectronic Air Circuit Breaker - Operating Instructions
7976
Schematic DiagramRMS10, RMS12 : protection and monitoring unitDiagram showing de-energised circuits, open circuit breaker, connected, reset, crank not inserted.
Stored Energy ControlM Motor
FCA Resetting limit switch
Manual reset
AS 1-8 Auxiliary switches
Ra Economy resistor for selected voltages in directcurrent
EE Closing coil
EA Shunt Trip
S2 Remote trip push-button
S5 Remote closing push-button
S3 Remote closing and tripping changeover switch
C22 Spring reset contact
C20 Contact coupled with local resetting push-button
FE Closing prevention device
LegendAmmetricBA Overload and short-circuit fault contact
K1 Fault signalling relay
S1 Fault cancelling push-button
GF Ground fault display
ST-I Instanatneous or short-circuit tripping indicator lamp
LT Long time (overload) tripping display
Voltmetric ReleasesC41 Trip contact UVR-UVRD
C43 Undervoltage contact UVR-UVRD
C31 Trip contact EA
RQ-R6 Economy resistor for direct current voltages
S4 Optional disconnecting switch UVR-UVRD(circuit breaker disconnected)
WithdrawableC51.52 “Connected” position contact
C61.62 “Withdrawn” position contact
C71 Pre-tripping contact associated with plug-in controldevice
RMS10,RMS12
Spectronic Air Circuit Breaker - Operating Instructions
8077
Schematic Diagram
End user connections
Withdrawable circuit breakerConnection by terminals 6.3 x 0.8For electrical operation of EA, BA1, BA2, UVR, UVRD, RMS9D use the allocated numbers.Other accessories : numbers are increasing in the direction shown (use reserved terminals ifthey are available).
Spectronic Air Circuit Breaker - Operating Instructions
81
Ground fault Pickup setting to be done on 1250A Spectronic ACB GF Fault Threshold value of current corresponding
to the steps in adjoining tableGF Pickup to be set
Amps xX(steps in display of release)325 0.2
337.5 0.21350 0.22
362.5 0.23375 0.23
387.5 0.24400 0.25
412.5 0.26425 0.26
437.5 0.27450 0.28
462.5 0.29475 0.29
487.5 0.3500 0.31
512.5 0.32525 0.33
537.5 0.33550 0.34
562.5 0.35575 0.36
587.5 0.36600 0.37
612.5 0.38625 0.39
637.5 0.4650 0.4
662.5 0.41675 0.42
687.5 0.43700 0.44
712.5 0.44725 0.45
737.5 0.46750 0.47
762.5 0.48775 0.48
787.5 0.49800 0.5
812.5 0.51825 0.51
837.5 0.52850 0.53
862.5 0.54875 0.55
887.5 0.55900 0.56
912.5 0.57925 0.58
937.5 0.58950 0.59
962.5 0.6