– Aquafire testing and certification in English
Transcript of – Aquafire testing and certification in English
ACQUA e FUOCOTWO ELEMENTS, ONE SOLUTION
TEST AND
CERTIFICATIONS
“…di tanto in tanto arriva un prodotto rivoluzionario che cambia tutto…”.
“…every once in a while a revolutionary product comes along that changes everything…”.
(Steve Jobs, 2007)
1‐ ETA 14‐0375 (WARRINGTON) 2‐ CERTIFICATE OF CONFORMITY OF FPC (WARRINGTON) 3‐ CLASSIFICATION REPORT A1 CSI/0238C/11/RF (CSI) 4‐ TEST REPORT RINA MED205314CS NON‐COMBUSTIBILE MATERIAL FOR MARINE EQUIPMENT (RINA) 5‐ TEST REPORT FOR LEED N° 13‐3621 DEL 10/10/2013 (LABO CONSULT) 6‐ TEST REPORT N° 315705 FREEZE ‐ THAW 7‐ TEST REPORT N° 297767 HEAT ‐ RAIN 8‐ TEST REPORT N° 315704 SOAK ‐ DRY 9‐ TEST REPORT N° 299803 WATER IMPERMEABILITY 10‐ TEST REPORT N° 315972 WATER VAPOUR TRASMISSION 11‐ TEST REPORT N° 317123 SHEAR LOAD RESISTANCE OF MECHANICAL FASTENING SYSTEM 12‐ TEST REPORT N° 315708 PULL‐THROUGH RESISTANCE OF MECHANICAL FASTENERS 13‐ TEST REPORT N° 315710 RESISTANCE TO ECCENTRIC VERTICAL LOAD 14‐ TEST REPORT N° 315706 RESISTANCE TO SOFT BODY IMPACT 15‐ TEST REPORT N° 315707 RESISTANCE TO HARD BODY IMPACT 16‐ TEST REPORT N° 315354 TENSILE STRENGTH PERPENDICULAR TO THE PLANE 17‐ TEST REPORT N° 315353 TENSILE STRENGTH PARALLEL TO THE PLANE 18‐ TEST REPORT N° 315963 TENSILE STRENGTH PARALLEL TO THE PLANE 19‐ TEST REPORT N° 316280 DIMENSIONAL CHANGES ASSOCIATED TO MOISTURE VARIATION 20‐ TEST REPORT N°315703 MECHANICAL BENDING PROPERTIES (MOE/MOR) 21‐ TEST REPORT N° CSI‐DC‐TTS‐14‐1 THERMAL CONDUCTIVITY (CSI)
WCL is part of the Warringtonfire Research Group which is a subsidiary of Exova Group (UK) Ltd
Warrington Certification Ltd
Holmesfield Road
Warrington
WA1 2DS
United Kingdom
T : +44 (0) 1925 646 669
F : +44 (0) 1925 646 667
W : www.exova.com
W:: www.warringtonfire.net
Registered Office: Exova (UK) Ltd, Lochend Industrial Estate, Newbridge, Midlothian EH28 8PL United Kingdom. Reg No.SC 70429
Notified Body: 1121 Warrington Certification Limited, Holmesfield Road, Warrington,WA1 2DS, Great Britain
Certificate of Conformity of the Factory Production
Control
This Certificate applies to the construction product
“AQUAFIRE” Fibre Cement Board
produced by or for
BiFire S.R.L
Via Lavoratori Autobianchi 1 20832 Desio (MB)
Italy
and produced in the manufacturing plant
BiFire S.R.L Via Lavoratori Autobianchi 1
20832 Desio (MB) Italy
This certificate attests that, after completion of a successful audit inspection, Warrington Certification Ltd are satisfied that the Quality Management Systems and Processes in operation, at the above
manufacturing address, are fully in compliance with the Factory Production Control requirements for the construction product concerned.
This certificate was first issued on 17/04/2014 and will remain valid, until the below date, as long as the manufacturing conditions in the plant and the factory production control itself are not modified
significantly.
Signed:
Issue Date: 17
th April 2014
Valid to: 14
th November 2015
Comp. AV
Revis. PB
This test report consists of 6 sheets.
This document is the English translation of the test report No. 315705 dated 09/05/2014 issued in Italian; in case of dispute
the only valid version is the Italian one. Date of translation: 13/06/2014.
Sheet
1 of 6
CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
TEST REPORT No. 315705
Place and date of issue: Bellaria-Igea Marina - Italy, 09/05/2014
Customer: BIFIRE S.r.l.- Via Carducci, 8 - 20123 MILANO (MI) - Italy
Date test requested: 20/01/2014
Order number and date: 61981, 21/01/2014
Date sample received: 20/01/2014 and 02/04/2014
Test date: from 29/01/2014 to 23/04/2014
Purpose of test: freeze-thaw cycling of fibre-cement flat sheets in accordance with clause 7.4.1 of
standard UNI EN 12467:2012
Test site: Istituto Giordano S.p.A. - Via Erbosa, 72 - 47043 Gatteo (FC) - Italy
Sample origin: sampled by Istituto Giordano in accordance with the procedure specified in sample
report dated 14/01/2014 and supplied by the Customer
Identification of sample received: No. 2014/0109
Sample name*
The test sample is called “AQUAFIRE”.
Description of sample*
The test sample comprises untreated fibre-reinforced lightweight cement boards and 10 test pieces of size
250 × 100 mm and thickness 12,5 mm that the Customer arranged to cut from sheets of the same type in ac-
cordance with the requirements of standard UNI EN 12467:2012.
(*) according to that stated by the Customer.
(Test report No. 315705 dated 09/05/2014) sheet 2 of 6 follows
The boards have the following specifications:
– density = 960 kg/m³ ± 15 %;
– width = (1200 ± 3,6) mm;
– length = (2000 ± 5,0) mm;
– thickness = (12,5 ± 1,2) mm.
5 of these test pieces were cut in the machine direction “M” and 5 at right angles to the machine “T”.
The lot of test pieces was supplied by the Customer after performing the freeze-thaw conditioning cycles spec-
ified by standard UNI EN 12467:2012.
Normative References
The test was carried out in accordance with the requirements of standard UNI EN 12467:2012 dated
11/10/2012 “Fibre-cement flat sheets - Product specification and test methods”, in particular:
– requirements in accordance with clauses 5.2.2 “Category A” and 5.5.2 of standard UNI EN 12467:2012;
– test method specified by subclause 7.4.1 “Freeze-thaw” of standard UNI EN 12467:2012.
Test apparatus
The following equipment was used to carry out the test:
– IG 10000 digital force gauge manufactured by Istituto Giordano S.p.A., speed range 0,05-300 mm/min,
clear span between support columns of 640 mm and effective travel 2000 mm (apparatus in-house identifi-
cation code FT161);
– AEP load cell, capacity 10 kN (apparatus in-house identification code EDI073);
– steel test frame complying with clause 7.3.2.2.1 with radius of supports and loading bar of 10 mm and span
between the supports ls = 10 mm;
– Mitutoyo Corporation digital calliper gauge with 10 micron resolution (apparatus in-house identification
code EDI066).
(Test report No. 315705 dated 09/05/2014) sheet 3 of 6 follows
Test method
The test pieces were split into two lots of which:
– the first comprising test pieces obtained in the laboratory from untreated boards of type “M” and “T” and
designated for testing in the untreated condition;
– the second comprising Customer-supplied test pieces of type “M” and “T” designated for testing after
freeze-thaw conditioning.
The specimens from both lots were immersed in water for 24 h at ambient temperature 23 ± 2 °C.
The specimens from both lots then underwent the bending strength test in accordance with subclause 7.3.2.3 of
standard UNI EN 12467:2012. The rate of loading was set to 30 mm/min such that breakage occurs within 10
s and 30 s.
Cylindrical supports were used of radius 10 mm arranged so that the span between the centres of the supports
“lS” is 200 mm.
The following were calculated for each test piece:
– modulus of rupture MOR, in MPa, in accordance with clause 7.3.2.4 “Expression and interpretation of re-
sults” of standard UNI EN 12467:2012, as given by the following formula.
MOR=3F·lS
2·b·e2
where: F = breaking load, in N;
lS = span between the axes of supports, in mm;
b = width of the test piece, in mm;
e = thickness of the test piece, in mm;
– modulus of elasticity MOE, in MPa, in accordance with clause 7.3.2.4.2 of standard UNI EN 12467:2012,
as given by the following formula.
EF2-F1 lS
3
4 b e3 f2-f1
where: lS = span between the axes of supports, in mm;
F1 and F2 = loads, taken from two points within the linear section of the plot, below the limit of
proportionality;
b = width of the test piece, in mm;
e = thickness of the test piece, in mm;
f1 and f2 = deflections corresponding to the load selected, in mm.
(Test report No. 315705 dated 09/05/2014) sheet 4 of 6 follows
– individual ratio, MRi in accordance with clause 7.4.1.4 of standard UNI EN 12467:2012, calculated as fol-
lows:
MRi=MORfi
MORfci
where: MORfi = modulus of rupture of the specimen from the ith pair after freeze-thaw cycling (second
lot);
MORfci = modulus of rupture of the specimen from the ith pair tested for reference (first lot).
Finally, the average, R, and standard deviation, s, of the individual ratio, MRi, were calculated along with the
lower estimation, RL, of the mean of the ratios at 95% confidence level as follows:
RL=R-0,58·s
comparing the result with the requirements of clause 5.5.2 of standard UNI EN 12467:2012.
Environmental conditions during test
Ambient temperature (23 ± 2) °C
Relative humidity (50 ± 5) %
(Test report No. 315705 dated 09/05/2014) sheet 5 of 6 follows
Test results
Lot Direction of test
Test piece Condition-ing
Measured thickness
“e”
Breaking load “F”
Modulus of rupture
“MORfci”
Modulus of elasticity
“MOE”
[No.] [No.] [mm] [N] [MPa] [MPa]
1
M
1
none
12,3 326 6,4 501
2 12,1 193 6,0 515
3 12,5 301 5,8 635
4 12,1 300 6,2 481
5 12,2 273 5,5 546
T
1 12,2 292 5,9 1646
2 12,4 272 5,4 1413
3 12,3 252 5,0 1451
4 12,2 270 5,4 1506
5 12,3 305 6,0 1736
Mean 12,3 288 5,8 1043
Standard deviation 0,1 37 0,4 544
2
M
1
freeze-thaw
12,2 297 6,0 1087
2 12,6 305 5,8 1245
3 12,6 302 5,7 1235
4 12,3 321 6,3 1611
5 12,5 293 5,7 1456
T
1 12,2 301 6,0 1712
2 12,4 298 5,8 1588
3 12,4 287 5,6 1870
4 12,4 292 5,7 1428
5 12,4 321 6,3 1234
Mean 12,4 302 5,9 1447
Standard deviation 0,1 11 0,3 249
R (average MRi) 0,98
s (standard deviation of MRi) 0,21
RL (lower estimation of MRi) 0,86*
(*) In accordance with subclause 5.5.2 of standard UNI EN 12467:2012, the ratio RL shall be not less than 0,75.
(Test report No. 315705 dated 09/05/2014) sheet 6 of 6 follows
Findings
On the basis of the test performed, the results obtained and the provisions of subclauses 5.5.2 and 7.4.1 of
standard UNI EN 12467:2012, as regards the freeze-thaw cycling test, the test sample, comprising fibre-
cement flat sheets called “AQUAFIRE” submitted by the company BIFIRE S.r.l.- Via Carducci, 8 - 20123
MILANO (MI) - Italy, meets the requirements specified for
Category A
The results given refer exclusively to the test sample itself and are only valid under the same conditions in
which testing was carried out.
This test report alone shall not be considered a certificate of conformity.
Test Technician: Dott. Ing. Paolo Bertini
Head of Security and Safety Laboratory: Dott. Andrea Bruschi
Chief Executive Officer (Dott. Arch. Sara Lorenza Giordano)
............................................
Comp. AV
Revis. PB
This test report consists of 5 sheets.
This document is the English translation of the test report No. 297767 dated 11/09/2012 issued in Italian.
Date of translation: 05/12/2013.
Sheet
1 of 5
CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
TEST REPORT No. 297767
Place and date of issue: Bellaria-Igea Marina - Italy, 11/09/2012
Customer: BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO (MI) - Italy
Date test requested: 30/07/2012
Order number and date: 57225, 01/08/2012
Date sample received: 02/08/2012
Test date: from 02/08/2012 to 31/08/2012
Purpose of test: Heat-rain cycling of fibre-cement flat sheets in accordance with subclauses 5.5.3
and 7.4.2 of standard UNI EN 12467:2007
Test site: Istituto Giordano S.p.A. - Blocco 4 - Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) -
Italy and Istituto Giordano S.p.A. - Via Erbosa, 72 - 47043 Gatteo (FC) - Italy
Sample origin: sampled and supplied by the Customer
Identification of sample received: No. 2012/1709
Sample name*
The test sample is called “AQUAFIRE”.
(*) according to that stated by the Customer.
(Test report No. 297767 dated 11/09/2012) sheet 2 of 5 follows
Description of sample*
The test sample comprises lightweight silicate fibre-cement flat sheets whose characteristics are specified in
the table here below.
Width 1200 mm ± 1 %
Length 2000 mm ± 1 %
Thickness 12,5 mm ± 1 %
Density 960 kg/m3 ± 15 %
Normative References
The test was carried out in accordance with the requirements of standard UNI EN 12467:2007 dated
25/01/2007 “Lastre piane di fibrocemento - Specifica di prodotto e metodi di prova” (“Fibre-cement flat sheets -
Product specification and test methods”), in particular:
– requirements in accordance with subclauses 5.2.2 “Category A” and 5.5.3 of standard UNI EN 12467:2007;
– test method specified by clause 7.4.2 “Heat-rain” of standard UNI EN 12467:2007.
Description of specimens
2 specimens of size 2000 × 1200 mm and 2000 × 600 mm were cut from the sample and laid horizontally in
order to create a test area when joined of 3,5 m2.
Test apparatus
The following equipment was used to carry out the test:
– temperature and humidity chamber (apparatus in-house identification code FT152) with temperature range
of (−20 ± 2) °C to (+60 ± 2) °C;
(*) according to that stated by the Customer.
(Test report No. 297767 dated 11/09/2012) sheet 3 of 5 follows
– light radiation apparatus fitted with Osram Ultra-Vitalux 300 W lamps such as to guarantee a total irradi-
ance level of (900 ± 100) W/m²;
– water spray system complete with flow meter, capable of providing complete wetting on the board face
with an output of approximately 1 l/min/m2.
Test method
The boards were joined and installed in the centre of the climate chamber in order to have ambient temperature
on one side of the boards and the temperatures set by the radiant heat and rain cycles on the other.
In accordance with the Customer’s instructions, the side with the rough surface is exposed to radiation.
The black body temperature is considered and regulated during radiant heating at (60 ± 5) °C.
In accordance with table 11 of the reference standard, the specimen underwent the following heat-rain cycle:
Steps Duration
[h:min]
Water spray (1 l/min/m2)
2:50 ± 0:05
Pause 0:10 ± 0:01
Radiant heat (black body temperature = 60 ± 5 °C)
2:50 ± 0:05
Pause 0:10 ± 0:01
Total cycle 6:00 ± 0:12
50 cycles for category A were carried out as requested by subclause 5.5.3 of standard UNI EN 12467:2007.
(Test report No. 297767 dated 11/09/2012) sheet 4 of 5 follows
As requested by subclause 5.5.3 of standard UNI EN 12467:2007, after testing it was verified that any visible
cracks, delamination, warping and bowing or other defects in the boards were not of such a degree as to affect
their performance in use. Subsequently, the water impermeability test was carried out in accordance with 5.4.4
and 7.3.3 of the reference standard.
Test results
Upon completion of the test in accordance with 5.5.3 of standard UNI EN 12467:2007, no visible cracks, de-
lamination, warping and bowing or other defects in the sheets were noted of such a degree as to affect their
performance in use.
In accordance with 5.4.4 and 7.3.3 of standard UNI EN 12467:2007, no formation of drops of water occurred
during the impermeability test.
Photo of specimen during the impermeability test
(Test report No. 297767 dated 11/09/2012) sheet 5 of 5 follows
Findings
On the basis of the test performed, the results obtained and the provisions of subclauses 5.5.3 and 7.4.2 of
standard UNI EN 12467:2007, as regards the heat-rain cycling test, the test sample, comprising fibre-cement
flat sheets called “AQUAFIRE” submitted by the company BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO
(MI) - Italy, meets the requirements specified for
Category A
The results given refer exclusively to the test sample itself and are only valid under the same conditions in
which testing was carried out.
This test report alone shall not be considered a certificate of conformity.
Test Technician (Dott. Alessandro Trevisani)
Head of Wood Technology / Con-ditioning Laboratory
(Dott. Alessandro Trevisani)
Managing Director (Dott. Ing. Vincenzo Iommi)
............................................
............................................
............................................
Test Technician (Dott. Ing. Paolo Bertini)
Head of Security and Safety Laboratory
(Geom. Roberto Porta)
............................................
............................................
Comp. AV
Revis. PB
This test report consists of 6 sheets.
This document is the English translation of the test report No. 315704 dated 09/05/2014 issued in Italian; in case of dispute
the only valid version is the Italian one. Date of translation: 13/06/2014.
Sheet
1 of 6
CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
TEST REPORT No. 315704
Place and date of issue: Bellaria-Igea Marina - Italy, 09/05/2014
Customer: BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO (MI) - Italy
Date test requested: 20/01/2014
Order number and date: 61981, 21/01/2014
Date sample received: 20/01/2014 and 02/04/2014
Test date: from 29/01/2014 to 23/04/2014
Purpose of test: soak-dry testing of fibre-cement flat sheets in accordance with subclause 7.3.6 of
standard UNI EN 12467:2012
Test site: Istituto Giordano S.p.A. - Via Erbosa, 72 - 47043 Gatteo (FC) - Italy
Sample origin: sampled by Istituto Giordano in accordance with the procedure specified in sample
report dated 14/01/2014 and supplied by the Customer
Identification of sample received: No. 2014/0109
Sample name*
The test sample is called “AQUAFIRE”.
Description of specimen*
The test sample comprises untreated fibre-reinforced lightweight cement boards and 10 test pieces of size
250 × 100 mm and thickness 12,5 mm that the Customer arranged to cut from sheets of the same type in ac-
cordance with the requirements of standard UNI EN 12467:2012.
(*) according to that stated by the Customer.
(Test report No. 315704 dated 09/05/2014) sheet 2 of 6 follows
The boards have the following specifications:
– density = 960 kg/m³ ± 15 %;
– width = (1200 ± 3,6) mm;
– length = (2000 ± 5,0) mm;
– thickness = (12,5 ± 1,2) mm.
5 of these test pieces were cut in the machine direction “M” and 5 at right angles to the machine “T”.
The lot of test pieces was supplied by the Customer after performing the soak-dry conditioning cycles speci-
fied by standard UNI EN 12467:2012.
Normative References
The test was carried out in accordance with the requirements of standard UNI EN 12467:2012 dated
11/10/2012 “Fibre-cement flat sheets - Product specification and test methods”, in particular:
– requirements in accordance with clauses 5.2.2 “Category A” and 5.5.5 of standard UNI EN 12467:2012;
– test method specified by subclause 7.3.6 “Soak-dry” of standard UNI EN 12467:2012.
Description of test pieces
In accordance with standard UNI EN 12467:2012, 10 test pieces were cut from the untreated board of size
250 × 100 mm and original product thickness.
5 of the ten test pieces were cut in the machine direction “M” and 5 at right angles to the machine “T”.
Test apparatus
The following equipment was used to carry out the test:
– IG 10000 digital force gauge manufactured by Istituto Giordano S.p.A., speed range 0,05-300 mm/min,
clear span between support columns of 640 mm and effective travel 2000 mm (apparatus in-house identifi-
cation code FT161);
– AEP load cell, capacity 10 kN (apparatus in-house identification code EDI073);
(Test report No. 315704 dated 09/05/2014) sheet 3 of 6 follows
– steel test frame complying with clause 7.3.2.2.1 with radius of supports and loading bar of 10 mm and span
between the supports ls = 10 mm;
– Mitutoyo Corporation digital calliper gauge with 10 micron resolution (apparatus in-house identification
code EDI066).
Test method
The test pieces were split into two lots of which:
– the first comprising test pieces obtained in the laboratory from untreated boards of type “M” and “T” and
designated for testing in the untreated condition;
– the second comprising Customer-supplied test pieces of type “M” and “T” designated for testing after soak-
dry conditioning.
The specimens from both lots were immersed in water for 24 h at ambient temperature (23 ± 2) °C.
The specimens from both lots then underwent the bending strength test in accordance with subclause 7.3.2.3 of
standard UNI EN 12467:2012. The rate of loading was set to 30 mm/min such that breakage occurs within 10
s and 30 s.
Cylindrical supports were used of radius 10 mm arranged so that the span between the centres of the supports
“lS” is 200 mm.
The following were calculated:
– modulus of rupture MOR, in MPa, in accordance with clause 7.3.2.4 “Expression and interpretation of re-
sults” of standard UNI EN 12467:2012, as given by the following formula.
MOR=3F·lS
2·b·e2
where: F = breaking load, in N;
lS = span between the axes of supports, in mm;
b = width of the test piece, in mm;
e = thickness of the test piece, in mm;
– modulus of elasticity MOE, in MPa, in accordance with clause 7.3.2.4.2 of standard UNI EN 12467:2012,
as given by the following formula.
EF2-F1 lS
3
4 b e3 f2-f1
(Test report No. 315704 dated 09/05/2014) sheet 4 of 6 follows
where: lS = span between the axes of supports, in mm;
F1 and F2 = loads, taken from two points within the linear section of the plot, below the limit of
proportionality;
b = width of the test piece, in mm;
e = thickness of the test piece, in mm;
f1 and f2 = deflections corresponding to the load selected, in mm.
– individual ratio, MRi in accordance with clause 7.3.6.4 of standard UNI EN 12467:2012, calculated as fol-
lows:
MRi=MORfi
MORfci
where: MORfi = modulus of rupture of the ith specimen after the soak-dry cycles (second lot);
MORfci = modulus of rupture of the specimen from the ith pair tested for reference (first lot).
Finally, the average, R, and standard deviation, s, of the individual ratio, MRi, were calculated along with the
lower estimation, RL, of the mean of the ratios at 95% confidence level as follows:
RL=R-0,58·s
comparing the result with the requirements of clause 5.5.5 of standard UNI EN 12467:2012.
Environmental conditions during test
Ambient temperature (23 ± 2) °C
Relative humidity (50 ± 5) %
(Test report No. 315704 dated 09/05/2014) sheet 5 of 6 follows
Test results
Lot Direction of test
Test piece Condition-ing
Measured thickness
“e”
Breaking load “F”
Modulus of rupture
“MORfci”
Modulus of elasticity
“MOE”
[No.] [No.] [mm] [N] [MPa] [MPa]
1
M
1
none
12,3 326 6,4 501
2 12,1 193 6,0 515
3 12,5 301 5,8 635
4 12,1 300 6,2 481
5 12,2 273 5,5 546
T
1 12,2 292 5,9 1646
2 12,4 272 5,4 1413
3 12,3 252 5,0 1451
4 12,2 270 5,4 1506
5 12,3 305 6,0 1736
Mean 12,3 288 5,8 1043
Standard deviation 0,1 37 0,4 544
2
M
1
soak-dry
12,2 278 5,6 961
2 12,3 315 6,2 837
3 12,2 303 6,1 1132
4 12,6 295 5,6 1098
5 12,6 329 6,2 1183
T
1 12,4 288 5,7 910
2 12,4 260 5,1 799
3 12,1 278 5,7 838
4 12,2 295 5,9 1062
5 12,6 333 6,3 963
Mean 12,4 297 5,8 978
Standard deviation 0,2 23 0,4 135
R (average MRi) 1,03
s (standard deviation of MRi) 0,05
RL (lower estimation of MRi) 1,00*
(*) In accordance with subclause 5.5.5 of standard UNI EN 12467:2012, the ratio RL shall be not less than 0,75.
(Test report No. 315704 dated 09/05/2014) sheet 6 of 6 follows
Findings
On the basis of the test performed, the results obtained and the provisions of subclauses 5.5.5 and 7.3.6 of
standard UNI EN 12467:2012, as regards the soak-dry cycling test, the test sample, comprising fibre-cement
flat sheets called “AQUAFIRE” submitted by the company BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO
(MI) - Italy, meets the requirements specified for
Category A
The results given refer exclusively to the test sample itself and are only valid under the same conditions in
which testing was carried out.
This test report alone shall not be considered a certificate of conformity.
Test Technician: Dott. Ing. Paolo Bertini
Head of Security and Safety Laboratory: Dott. Andrea Bruschi
Chief Executive Officer (Dott. Arch. Sara Lorenza Giordano)
............................................
Comp. AV
Revis. PB
This test report consists of 5 sheets.
This document is the English translation of the test report No. 299803 dated 12/11/2012 issued in Italian.
Date of translation: 05/12/2013.
Sheet
1 of 5
CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
TEST REPORT No. 299803
Place and date of issue: Bellaria-Igea Marina - Italy, 12/11/2012
Customer: BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO (MI) - Italy
Date test requested: 30/07/2012
Order number and date: 57225, 01/08/2012
Date sample received: 02/08/2012
Test date: from 30/08/2012 to 31/08/2012
Purpose of test: Water impermeability of fibre-cement flat sheets in accordance with clause 7.3.3 of
standard UNI EN 12467:2007
Test site: Istituto Giordano S.p.A. - Via Erbosa, 72 - 47043 Gatteo (FC) - Italy
Sample origin: sampled and supplied by the Customer
Identification of sample received: No. 2012/1709
Sample name*
The test sample is called “AQUAFIRE”.
(*) according to that stated by the Customer.
(Test report No. 299803 dated 12/11/2012) sheet 2 of 5 follows
Description of sample*
The test sample comprises lightweight silicate cement board whose characteristics are given in the following
Customer-supplied technical data sheet.
TECHNICAL DATA SHEET
PRODUCT DESCRIPTION
Manufacturer Bifire S.r.l.
General Lightweight silicate cement board
Type of material anisotropic
Production system Mix of cement and aggregates
Bulk process Curing
Component assembly Mixing, kneading, impregnation and extrusion
Installation Screwed to supporting framework
Use Building
TECHNICAL SPECIFICATIONS
Description Unit Value Tolerances
Density [kg/m3] 960 ± 15 %
Width [mm] 1200 ± 1 %
Length [mm] 2000 ± 1 %
Thickness [mm] 12,5 ± 1,0 mm
(*) according to that stated by the Customer.
(Test report No. 299803 dated 12/11/2012) sheet 3 of 5 follows
Normative References
The test was carried out in accordance with the requirements of standard UNI EN 12467:2007 dated
25/01/2007 “Lastre piane di fibrocemento - Specifica di prodotto e metodi di prova” (“Fibre-cement flat sheets -
Product specification and test methods”), in particular:
– requirements in accordance with clauses 5.2.2 “Category A” and 5.4.4 of standard UNI EN 12467:2007;
– test method specified by clause 7.3.3 “Water impermeability” of standard UNI EN 12467:2007.
Description of specimens
The customer arranged to cut 3 specimens from the sample, size 600 × 500 mm and thickness 12,5 mm, in ac-
cordance with the requirements of clause 7.3.3.1.
Test apparatus
The following equipment was used to carry out the test:
– Mitutoyo Corporation digital calliper gauge with 10 micron resolution (apparatus in-house identification
code EDI066);
– digital chronometer.
Test method
A suitable frame was sealed on top of the specimen in order to leave a clear test area of 550 × 450 mm. The
frame was filled with water to a height of 20 mm above the face of the sheet. This arrangement was placed in
an environment chamber with controlled temperature and humidity so that the underside can be viewed with-
out moving the specimen during the test. The duration of the test was 24 h.
(Test report No. 299803 dated 12/11/2012) sheet 4 of 5 follows
Environmental conditions during test
Ambient temperature (23 ± 2) °C
Relative humidity (50 ± 5) %
Test results
Specimen Height of water above specimen
Duration of test Effect
[No.] [mm] [h]
1 20 24 no traces of moisture or drops of
water
2 20 24 no traces of moisture or drops of
water
3 20 24 no traces of moisture or drops of
water
Photo of a specimen during testing
(Test report No. 299803 dated 12/11/2012) sheet 5 of 5 follows
Findings
On the basis of the test performed, the results obtained and the provisions of subclauses 5.4.4 and 7.3.3 of
standard UNI EN 12467:2007, as regards the water impermeability test, the test sample, comprising fibre-
cement flat sheets called “AQUAFIRE” submitted by the company BIFIRE S.r.l. - Via Carducci, 8 - 20123
MILANO (MI) - Italy, meets the requirements specified for
Category A
The results given refer exclusively to the test sample itself and are only valid under the same conditions in
which testing was carried out.
This test report alone shall not be considered a certificate of conformity.
Test Technician (Dott. Ing. Paolo Bertini)
Head of Security and Safety Laboratory
(Geom. Roberto Porta)
Managing Director (Dott. Ing. Vincenzo Iommi)
............................................
............................................
............................................
Comp. AV
Revis. PR
Il presente rapporto di prova è composto da n. 5 fogli ed è emesso in formato bilingue (italiano e inglese); in caso di dubbio, è valida la versione in lingua italiana.
This test report is made up of 5 sheets and it is issued in a bilingual format (Italian and English); in case of doubt, please refer to the Italian version.
Foglio / Sheet
1 / 5
CLAUSOLE: il presente documento si riferisce solamente al campione o materiale sottoposto a prova e non può essere riprodotto parzialmente, salvo approvazione scritta dell’Istituto Giordano. CLAUSES: This document relates only to the specimen or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
RAPPORTO DI PROVA N. 315972 TEST REPORT No. 315972
Luogo e data di emissione: Place and date of issue:
Bellaria-Igea Marina - Italia, 20/05/2014
Committente: Customer:
BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO (MI) - Italia
Data della richiesta della prova: Date test requested:
23/01/2014
Numero e data della commessa: Order number and date:
61981, 23/01/2014
Data del ricevimento del campione: Date sample received:
20/01/2014
Data dell’esecuzione della prova: Test date:
dal/from 31/01/2014 al/to 24/02/2014
Oggetto della prova: Purpose of test:
proprietà di trasmissione del vapore d’acqua secondo la norma UNI EN ISO 12572:2006 di materiali e prodotti da costruzione water vapour transmission properties of building materials and products in accordance with standard UNI EN ISO 12572:2006
Luogo della prova: Place of test:
Istituto Giordano S.p.A. - Blocco 1 - Via Rossini, 2 - 47814 Bellaria-Igea Ma-rina (RN) - Italia
Provenienza del campione: Sample origin:
campionato da Istituto Giordano secondo le procedure definite nel ver-bale di prelievo del 14/01/2014 e fornito dal Committente sampled by Istituto Giordano in accordance with the procedure specified in sample report dated 14/01/2014 and supplied by the Customer
Identificazione del campione in accettazione: Identification of sample received:
2014/0109
Denominazione del campione*. Sample name*.
Il campione sottoposto a prova è denominato “AQUAFIRE”. The test sample is called “AQUAFIRE”.
Descrizione del campione*. Description of sample*.
Il campione in esame è costituito da una lastra in cemento alleggerito fibrorinforzato, avente spessore nomina-
le 12,5 mm. The test sample consists of No. 2 slabs made of lightweight fiber-reinforced concrete, with a nominal thickness of 12,5 mm.
(*) Secondo le dichiarazioni del Committente. According to information supplied by the Customer.
(Rapporto di prova n. / Test report No. 315972 del / dated 20/05/2014) segue - foglio 2 di 5 / sheet 2 / 5 follows
Fotografie del campione. Photos of test sample.
Riferimenti normativi. Normative references.
La prova è stata eseguita secondo le prescrizioni della norma UNI EN ISO 12572:2006 del 12/10/2006
“Prestazione igrotermica dei materiali e dei prodotti per edilizia. Determinazione delle proprietà di
trasmissione del vapore d’acqua”, utilizzando la procedura interna di dettaglio PP001 revisione 21 del
12/02/2014 “Determinazione delle proprietà di trasmissione del vapore acqueo”. The test was carried out in accordance with the requirements of standard UNI EN ISO 12572:2006 dated 12/10/2006 “Hygrothermal
performance of building materials and products. Determination of water vapour transmission properties”.
(Rapporto di prova n. / Test report No. 315972 del / dated 20/05/2014) segue - foglio 3 di 5 / sheet 3 / 5 follows
Descrizione delle provette. Specimen description.
Dal campione in esame sono state ricavate, mediante taglio, n. 5 (+ 2 di riferimento) provette cilindriche di
diametro nominale 200 mm. No. 5 specimens (+ 2 dummies specimens) of diameter 200 mm have been made from the sample under examination by cutting.
Fotografia delle provette. Photo of the specimens
Condizionamento delle provette. Specimen conditioning.
Prima della prova le provette sono state sottoposte a un condizionamento a temperatura di 23 °C e U.R. del
50 %, per 24 h. The specimens were conditioned for 24 h at a temperature of 23 °C and 50 % of relative humidity.
Modalità della prova. Test methods.
Le provette sono state installate sull’apertura dei recipienti di prova contenenti del sale essiccante al fine di
mantenere l’umidità relativa all’interno del 0 %.
Le provette sono state inserite all’interno di una camera climatica alla temperatura di 23 °C ed al 50 % di
umidità relativa. The specimens were fitted on the opening of the test cups containing desiccant salt in order to maintain a relative humidity inside the
cups of 0 %.
The specimens were placed inside a climatic chamber at a temperature of 23 °C and 50 % relative humidity.
(Rapporto di prova n. / Test report No. 315972 del / dated 20/05/2014) segue - foglio 4 di 5 / sheet 4 / 5 follows
Condizioni di prova. Test conditions.
Pressione atmosferica Atmospheric pressure
1013 mbar
Temperatura Temperature
23 °C
Condizioni di prova Set of conditions
C: 23 - 50/93
Umidità relativa e pressione di vapore all’interno del contenitore Relative humidity and vapour pressure inside test cup
94 % 2639 Pa
Umidità relativa e pressione di vapore nell’ambiente climatizzato Relative humidity and vapour pressure in climatic chamber
50 % 1404 Pa
Caratteristiche delle provette. Specimens properties.
Condizioni di prova: Set of conditions:
Provetta Specimen
C: 23 - 50/93 n. 1 n. 2 n. 3 n. 4 n. 5 Spessore Thickness
[mm] 11,90 12,00 11,95 11,98 12,13
Superficie della provetta Specimens area
[mm²] 32700 32510 32430 32240 32160
Superficie di misura Exposed area
[mm²] 277780 27720 27740 27690 27740
Massa volumica dopo il condizionamento Density after conditioning
[kg/m³] 11207 1124 1118 1171 1162
(Rapporto di prova n. / Test report No. 315972 del / dated 20/05/2014) segue - foglio 5 di 5 / sheet 5 / 5 follows
Risultati della prova. Test results.
Condizioni di prova
Set of conditions
Provetta Specimen
Velocità di trasmissione del vapore Water vapour transmission
rate
Permeanza Permeance
Resistenza Resistance
Permeabilità al vapore
Water vapour permeability
Fattore di resistenza
alla diffusione
Diffusion resistance
factor
Spessore d’aria
equivalente Equivalent air layer thickness
g W Z δ µ Sd [n.] [kg/(s·m²)] [kg/(m²·s·Pa)] [m²·s·Pa/kg] [kg/(m·s·Pa)] [-] [m]
C: 23 - 50/93 1 6,01·10-7 5,12·10-10 1,95·109 6,09·10-12 32,0 0,381
2 6,59·10-7 5,65·10-10 1,77·109 6,77·10-12 28,8 0,345
3 6,11·10-7 5,21·10-10 1,92·109 6,22·10-12 31,4 0,375
4 5,99·10-7 5,10·10-10 1,96·109 6,11·10-12 31,9 0,383
5 6,32·10-7 5,40·10-10 1,85·109 6,54·10-12 29,8 0,361
Condizioni di prova Set of conditions
C: 23 - 50/93
Valore medio della velocità di trasmissione del vapore “g” Mean water vapour transmission rate
[kg/(s·m²)] 6,2·10-7
Valore medio della permeanza “W” Mean permeance
[kg/(m²·s·Pa)] 5,3·10-10
Valore medio della resistenza “Z” Mean resistance
[m²·s·Pa/kg] 1,9·109
Valore medio del fattore di resistenza alla diffusione “µ” Mean diffusion resistance factor
[-] 31
Valore medio dello spessore d’aria equivalente “Sd” Mean equivalent air layer thickness
[m] 0,37
Valore medio della permeabilità al vapore “δ” e relativa incertezza estesa Mean water vapour permeability “δ”and relative expanded uncertainty
[kg/(m·s·Pa)] (6,4·10-12 ± 0,7·10-12)
Livello di fiducia “p” dell’incertezza estesa Expanded uncertainty confidence level “p”
[%] 95
Fattore di copertura “kp” dell’incertezza estesa Expanded uncertainty coverage factor “kp”
[-] 2,00
Nota: l’incertezza estesa della permeabilità al vapore “δ” comprende anche la dispersione dei valori di per-
meabilità al vapore misurati sulle provette. Note: the expanded uncertainty of the water vapour permeability “δ” also includes the dispersion of the values of water vapour per-
meability measured on test specimens.
Il Responsabile Tecnico di Prova
Test Technician (Dott. Ing. Paolo Ricci)
Il Responsabile del Laboratorio di Fisica Tecnica
Head of Applied Physics Laboratory (Dott. Ing. Vincenzo Iommi)
L’Amministratore Delegato Chief Executive Officer
(Dott. Nazario Giordano)
............................................
............................................
............................................
Comp. AV
Revis. PB
This test report consists of 5 sheets.
This document is the English translation of the test report No. 317123 dated 07/07/2014 issued in Italian; in case of dispute
the only valid version is the Italian one. Date of translation: 07/07/2014.
Sheet
1 of 5
CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
TEST REPORT No. 317123
This test report cancels and replaces test report No. 315709
dated 09/05/2014 issued by Istituto Giordano
Place and date of issue: Bellaria-Igea Marina - Italy, 07/07/2014
Customer: BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO (MI) - Italy
Date test requested: 17/03/2014
Order number and date: 62576, 18/03/2014
Date sample received: 14/04/2014
Test date: 16/04/2014
Purpose of test: determination of the shear load resistance of a screw installed through a fibre-
cement flat sheet in accordance with clause 5.1.4.1.2 of guideline ETAG 018-
4:2011
Test site: Istituto Giordano S.p.A. - Via Erbosa, 72 - 47043 Gatteo (FC) - Italy
Sample origin: sampled by Istituto Giordano in accordance with the procedure specified in sam-
ple report dated 14/01/2014 and supplied by the Customer
Identification of sample received: No. 2014/0768
Sample name*
The test sample is called “AQUAFIRE”.
(Test report No. 317123 dated 07/07/2014) sheet 2 of 5 follows
Description of sample*
The test sample comprises fibre-reinforced lightweight cement boards with the following specifications:
– density = 960 kg/m³ ± 15 %;
– width = (1200 ± 3,6) mm;
– length = (2000 ± 5,0) mm;
– thickness = (12,5 ± 1,2) mm.
Description of test pieces
5 test pieces were cut transversely from the sample of size 150 x 50 mm and original product thickness.
Normative References
The test was carried out according to the method specified in ETAG 018-4:2011 dated 01/12/2011 “Guideline
for European technical approval of fire protective products - Part 4: Fire protective board, slab and mat
products and kits”.
Test apparatus
The following equipment was used to carry out the test:
– Istituto Giordano S.p.A. IG 10000 digital force gauge, speed range 0,05-300 mm/min or load rate 9-300
N/s, clear span between support columns of 640 mm and effective travel 2000 mm (apparatus in-house
identification code FT161);
– AEP load cell, capacity 2 kN (apparatus in-house identification code FT480);
– Borletti digital calliper gauge with 10 micron resolution (apparatus in-house identification code EDI066).
(*) according to that stated by the Customer.
(Test report No. 317123 dated 07/07/2014) sheet 3 of 5 follows
Test method
The test was carried out in accordance with 5.1.4.1.2 “Shear load resistance of mechanical fastening sys-
tems” of guideline ETAG 018-4:2011.
Each test piece is held tightly in the testing machine. A screw, head diameter 10 mm and body diameter 4
mm, is installed in accordance with the manufacturer's specifications and subjected to a shear load with a
tensioning speed of 0,5 mm/min. The test continues until the screw has been pulled completely from the test
piece, the maximum shear load being recorded.
Test assembly layout
Environmental conditions during test
Ambient temperature (23 ± 2) °C
Relative humidity (50 ± 5) %
(Test report No. 317123 dated 07/07/2014) sheet 4 of 5 follows
Test results
Test piece Maximum withdrawal force Mode of failure
[No.] [N] [kg]
1 721 73,5 board shear failure
2 965 98,4 board shear failure
3 778 79,3 board shear failure
4 797 81,2 board shear failure
5 939 95,7 board shear failure
Mean 840 85,6 //
Standard deviation 106 10,8 //
Photo of a test piece during testing Example of failure
(Test report No. 317123 dated 07/07/2014) sheet 5 of 5 follows
Findings
On the basis of the tests performed and the results obtained, the test sample, comprising fibre-reinforced
lightweight cement board called “AQUAFIRE” submitted by BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO (MI)
- Italy, meets the shear load resistance requirements for mechanical fasteners given in the following table.
Test Test standard Mode of failure Mean failure load
[N]
shear load resistance clause 5.1.4.1.2
ETAG 018-4:2011 board shear failure 840
The results given refer exclusively to the test sample itself and are only valid under the same conditions in
which testing was carried out.
This test report alone shall not be considered a certificate of conformity.
Test Technician:
Dott. Ing. Paolo Bertini
Head of Security and Safety Laboratory:
Dott. Andrea Bruschi
Chief Executive Officer
(Dott. Arch. Sara Lorenza Giordano)
............................................
Comp. AV
Revis. PB
This test report consists of 5 sheets.
This document is the English translation of the test report No. 315708 dated 09/05/2014 issued in Italian; in case of dispute
the only valid version is the Italian one. Date of translation: 16/06/2014.
Sheet
1 of 5
CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
TEST REPORT No. 315708
Place and date of issue: Bellaria-Igea Marina - Italy, 09/05/2014
Customer: BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO (MI) - Italy
Date test requested: 17/03/2014
Order number and date: 62576, 18/03/2014
Date sample received: 14/04/2014
Test date: 16/04/2014
Purpose of test: determination of the pull-through resistance of a screw from a fibre-cement flat
sheet in accordance with clause 5.1.4.1.1 of guideline ETAG 018-4:2011
Test site: Istituto Giordano S.p.A. - Via Erbosa, 72 - 47043 Gatteo (FC) - Italy
Sample origin: sampled by Istituto Giordano in accordance with the procedure specified in sample
report dated 14/01/2014 and supplied by the Customer
Identification of sample received: No. 2014/0768
Sample name*
The test sample is called “AQUAFIRE”.
Description of sample*
The test sample comprises fibre-reinforced lightweight cement board with the following specifications:
– density = 960 kg/m³ ± 15 %;
(*) according to that stated by the Customer.
(Test report No. 315708 dated 09/05/2014) sheet 2 of 5 follows
– width = (1200 ± 3,6) mm;
– length = (2000 ± 5,0) mm;
– thickness = (12,5 ± 1,2) mm.
Description of test pieces
10 test pieces were cut from the sample of size 250 × 250 mm and original product thickness.
Normative References
The test was carried out according to the method specified in ETAG 018-4:2011 dated 01/12/2011 “Guideline
for European technical approval of fire protective products - Part 4: Fire protective board, slab and mat prod-
ucts and kits”.
Test apparatus
The following equipment was used to carry out the test:
– Istituto Giordano S.p.A. IG 10000 digital force gauge, speed range 0,05-300 mm/min or load rate
9-300 N/s, clear span between support columns of 640 mm and effective travel 2000 mm (apparatus in-
house identification code FT161);
– AEP load cell, capacity 2 kN (apparatus in-house identification code FT480);
– Borletti digital calliper gauge with 10 micron resolution (apparatus in-house identification code EDI066).
(Test report No. 315708 dated 09/05/2014) sheet 3 of 5 follows
Test method
The test was carried out in accordance with 5.1.4.1.1 “Pull-through resistance of mechanical fasteners” of
guideline ETAG 018-4:2011.
Each test piece is held tightly in the testing machine. A screw, head diameter 10 mm and body diameter 4 mm,
is installed in accordance with the manufacturer's specifications and subjected to a tensile force having a con-
stant crosshead speed of 20 mm/min. The test continues until the screw has been pulled completely through
the test piece, the maximum pull-through resistance being recorded. The test is then repeated on test pieces
immersed in water at a temperature of 20 °C for 1 h in accordance with clause 5.1.4.1.1.2 “After immersion in
water” of guideline ETAG 018-4:2011.
Test apparatus layout
Environmental conditions during test
Ambient temperature (23 ± 2) °C
Relative humidity (50 ± 5) %
(Test report No. 315708 dated 09/05/2014) sheet 4 of 5 follows
Test results
Test piece Conditioning Maximum pull-through re-sistance
Mode of failure
[No.] [N] [kg]
1
none
771 78,6 screw pulled completely from board
2 829 84,5 screw pulled completely from board
3 858 87,5 screw pulled completely from board
4 851 86,7 screw pulled completely from board
5 704 71,8 screw pulled completely from board
Mean 803 81,8 //
Standard deviation 65 6,6 //
6
immersion in water at 20 °C
for 1 h
567 57,8 screw pulled completely from board
7 423 43,1 screw pulled completely from board
8 586 59,7 screw pulled completely from board
9 365 37,2 screw pulled completely from board
10 468 47,7 screw pulled completely from board
Mean 482 49,1 //
Standard deviation 94 9,6 //
Photo of a test piece during testing Example of failure with pull-out of screw
(Test report No. 315708 dated 09/05/2014) sheet 5 of 5 follows
Findings
On the basis of the tests performed and the results obtained, the test sample, comprising fibre-reinforced
lightweight cement board called “AQUAFIRE” submitted by BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILA-
NO (MI) - Italy, meets the pull-through resistance requirements for mechanical fasteners given in the follow-
ing table.
Test Test standard Test conditions Mode of failure Mean failure load
[N]
Screw pull-through resistance
clause 5.1.4.1.1 ETAG 018-4:2011
dry screw pulled com-pletely from board
803
after immersion in water for 1 h
screw pulled com-pletely from board
482
The results given refer exclusively to the test sample itself and are only valid under the same conditions in
which testing was carried out.
This test report alone shall not be considered a certificate of conformity.
Test Technician: Dott. Ing. Paolo Bertini
Head of Security and Safety Laboratory: Dott. Andrea Bruschi
Chief Executive Officer (Dott. Arch. Sara Lorenza Giordano)
............................................
Comp. AV
Revis. PB
This test report consists of 5 sheets.
This document is the English translation of the test report No. 315710 dated 09/05/2014 issued in Italian; in case of dispute
the only valid version is the Italian one. Date of translation: 18/06/2014.
Sheet
1 of 5
CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
TEST REPORT No. 315710
Place and date of issue: Bellaria-Igea Marina - Italy, 09/05/2014
Customer: BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO (MI) - Italy
Date test requested: 17/03/2014
Order number and date: 62576, 18/03/2014
Date sample received: 14/04/2014
Test date: 15/04/2014
Purpose of test: resistance to functional failure from eccentric vertical load of a fibre-cement flat
sheet in accordance with clause 5.1.4.2.3 of guideline ETAG 018-4:2011
Test site: Istituto Giordano S.p.A. - Via Erbosa, 72 - 47043 Gatteo (FC) - Italy
Sample origin: sampled by Istituto Giordano in accordance with the procedure specified in sample
report dated 14/01/2014 and supplied by the Customer
Identification of sample received: No. 2014/0768
Sample name*
The test sample is called “AQUAFIRE”.
Description of sample*
The test sample comprises fibre-reinforced lightweight cement boards with the following specifications:
– density = 960 kg/m³ ± 15 %;
(*) according to that stated by the Customer.
(Test report No. 315710 dated 09/05/2014) sheet 2 of 5 follows
– width = (1200 ± 3,6) mm;
– length = (2000 ± 5,0) mm;
– thickness = (12,5 ± 1,2) mm.
Normative References
The test was carried out according to the method specified in ETAG 018-4:2011 dated 01/12/2011 “Guideline
for European technical approval of fire protective products - Part 4: Fire protective board, slab and mat prod-
ucts and kits”.
Test apparatus
The following equipment was used to carry out the test:
– calibrated iron ballast, weight 5 kg and 10 kg;
– test rig (apparatus in-house identification code EDI011);
– Sola Tri-Matic 5 m/19 mm metric tape measure (apparatus in-house identification code AV044);
– Bosch DLE 50 Professional laser rangefinder (apparatus in-house identification code AV114);
– Borletti digital calliper gauge with 10 micron resolution (apparatus in-house identification code EDI066);
– complementary accessories.
Test method
The test was carried out in accordance with clause 5.1.4.2.3 “Resistance to functional failure from eccentric
vertical load” of guideline ETAG 018-4:2011.
The board is securely fixed to a steel frame and the load test assembly is screwed to the board. A ballast of
steel disks is used to subject the test piece to a set of three gradually-increasing loads, each lasting 24 h. The
test continues until the system collapses, the maximum load being recorded.
(Test report No. 315710 dated 09/05/2014) sheet 3 of 5 follows
Eccentric load test assembly
Environmental conditions during test
Ambient temperature (23 ± 2) °C
Relative humidity (50 ± 5) %
(Test report No. 315710 dated 09/05/2014) sheet 4 of 5 follows
Test results
Load step Applied load
Duration Result
[No.] [kg] [h]
1 20 24 Compliant, no effect
2 30 24 Compliant, no effect
3 35 24 Board cracked, fixing screw failure
Photo of sample during test
(Test report No. 315710 dated 09/05/2014) sheet 5 of 5 follows
Findings
On the basis of the tests performed and the results obtained, the test sample, comprising fibre-reinforced
lightweight cement board called “AQUAFIRE” submitted by BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILA-
NO (MI) - Italy, meets the resistance to withdrawal requirements for mechanical fasteners given in the follow-
ing table.
Test Test standard Requirement Applied load
[kg]
eccentric vertical load clause 5.1.4.2.3
ETAG 018-4:2011 clause 5.1.4.2.3
ETAG 018-4:2011 30
The results given refer exclusively to the test sample itself and are only valid under the same conditions in
which testing was carried out.
This test report alone shall not be considered a certificate of conformity.
Test Technician: Dott. Ing. Paolo Bertini
Head of Security and Safety Laboratory: Dott. Andrea Bruschi
Chief Executive Officer (Dott. Arch. Sara Lorenza Giordano)
............................................
Comp. AV
Revis. PB
This test report consists of 4 sheets.
This document is the English translation of the test report No. 315706 dated 09/05/2014 issued in Italian; in case of dispute
the only valid version is the Italian one. Date of translation: 13/06/2014.
Sheet
1 of 4
CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
TEST REPORT No. 315706
Place and date of issue: Bellaria-Igea Marina - Italy, 09/05/2014
Customer: BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO (MI) - Italy
Date test requested: 23/01/2014
Order number and date: 61981, 23/01/2014
Date sample received: 14/04/2014
Test date: 15/04/2014
Purpose of test: resistance to soft body impact of a fibre-cement flat sheet in accordance with
clause 5.1.4.2.1 of guideline ETAG 018-4:2011
Test site: Istituto Giordano S.p.A. - Via Erbosa, 72 - 47043 Gatteo (FC) - Italy
Sample origin: sampled by Istituto Giordano in accordance with the procedure specified in sample
report dated 14/01/2014 and supplied by the Customer
Identification of sample received: No. 2014/0768
Sample name*
The test sample is called “AQUAFIRE”.
Description of sample*
The test sample comprises a untreated fibre-reinforced lightweight cement board, with the following specifica-
tions:
– density = 960 kg/m³ ± 15 %;
(*) according to that stated by the Customer.
(Test report No. 315706 dated 09/05/2014) sheet 2 of 4 follows
– width = (1200 ± 3,6) mm;
– length = (2000 ± 5,0) mm;
– thickness = (12,5 ± 1,2) mm.
Normative References
The test was carried out in accordance with the following documents:
– ETAG 018-4:2011 dated 01/12/2011 “Guideline for European technical approval of fire protective products
- Part 4: Fire protective board, slab and mat products and kits”;
– EOTA TR 001:2003 dated February 2003 “Determination of impact resistance of panels and panel assem-
blies”.
Test apparatus
The following equipment was used to carry out the test:
– test rig (apparatus in-house identification code EDI011);
– soft body impactor comprising spherical bag filled with glass spheres, mass 50 kg (apparatus in-house iden-
tification code EDI062);
– metric ruler (apparatus in-house identification code EDI083);
– Mitutoyo Corporation digital tape measure (apparatus in-house identification code: FT364);
– digital assay balance (apparatus in-house identification code RZF135).
Test method
The test was carried out in accordance with clause 5.1.4.2.1 “Resistance to functional failure from soft
body impact load - 50 kg bag” della guida ETAG 018-4:2011.
The test was carried out by striking the sample at the midpoint between two studs. Residual deflection was
measured 5 min after each impact.
(Test report No. 315706 dated 09/05/2014) sheet 3 of 4 follows
Environmental conditions during test
Ambient temperature (20 ± 3) °C
Relative humidity (50 ± 15) %
Test results
Photo of sample during test
(Test report No. 315706 dated 09/05/2014) sheet 4 of 4 follows
Impact Mass Impact energy
Drop height
Residual deflection
Result
[No.] [kg] [J] [m] [mm]
1 50 60 0,122 1,0 no damage
2 50 100 0,204 4,1 no damage
3 50 120 0,245 2,2 no damage
4 50 130 0,265 2,1 no damage
5 50 200 0,408 19,7 stud bent
6 50 300 0,612 // no collapse, no penetration or
projection
7 50 400 0,815 // no collapse, no penetration or
projection
8 50 500 1,019 // collapse of board
Findings
On the basis of the tests performed and the results obtained, the test sample, comprising a fibre-reinforced
lightweight cement board called “AQUAFIRE” submitted by BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILA-
NO (MI) - Italy, meets the resistance to soft body impact requirements given in the following table.
Test Test reference Requirement Conditions Energy
[J]
soft body impact clause 5.1.4.2.1
ETAG 018-4:2011 clause 2
EOTA TR 001:2003
serviceability <130
safety in use <400
The results given refer exclusively to the test sample itself and are only valid under the same conditions in
which testing was carried out.
This test report alone shall not be considered a certificate of conformity.
Test Technician: Dott. Ing. Paolo Bertini
Head of Security and Safety Laboratory: Dott. Andrea Bruschi
Chief Executive Officer (Dott. Arch. Sara Lorenza Giordano)
............................................
Comp. AV
Revis. PB
This test report consists of 4 sheets.
This document is the English translation of the test report No. 315707 dated 09/05/2014 issued in Italian; in case of dispute
the only valid version is the Italian one. Date of translation: 13/06/2014.
Sheet
1 of 4
CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
TEST REPORT No. 315707
Place and date of issue: Bellaria-Igea Marina - Italy, 09/05/2014
Customer: BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO (MI) - Italy
Date test requested: 23/01/2014
Order number and date: 61981, 23/01/2014
Date sample received: 14/04/2014
Test date: 16/04/2014
Purpose of test: resistance to hard body impact of a fibre-cement flat sheet in accordance with
clause 5.1.4.2.2 of guideline ETAG 018-4:2011
Test site: Istituto Giordano S.p.A. - Via Erbosa, 72 - 47043 Gatteo (FC) - Italy
Sample origin: sampled by Istituto Giordano in accordance with the procedure specified in sample
report dated 14/01/2014 and supplied by the Customer
Identification of sample received: No. 2014/0768
Sample name*
The test sample is called “AQUAFIRE”.
Description of sample*
The test sample comprises a untreated fibre-reinforced lightweight cement board, with the following specifica-
tions:
– density = 960 kg/m³ ± 15 %;
(*) according to that stated by the Customer.
(Test report No. 315707 dated 09/05/2014) sheet 2 of 4 follows
– width = (1200 ± 3,6) mm;
– length = (2000 ± 5,0) mm;
– thickness = (12,5 ± 1,2) mm.
Normative References
The test was carried out in accordance with the following documents:
– ETAG 018-4:2011 dated 01/12/2011 “Guideline for European technical approval of fire protective products
- Part 4: Fire protective board, slab and mat products and kits”;
– EOTA TR 001:2003 dated February 2003 “Determination of impact resistance of panels and panel assem-
blies”.
Test apparatus
The following equipment was used to carry out the test:
– steel ball impactor, mass 0,5 kg (apparatus in-house identification code EDI013);
– Borletti digital calliper gauge with 10 micron resolution (apparatus in-house identification code EDI066);
– Mitutoyo digital gauge (apparatus in-house identification code EDI004);
– Mitutoyo Corporation digital tape measure (apparatus in-house identification code: FT364);
– digital assay balance (apparatus in-house identification code RZF135).
Test method
The test was carried out in accordance with clause 5.1.4.2.2 “Resistance to functional failure from hard body
impact load - 0,5 kg steel ball” of guideline ETAG 018-4:2011.
The test was carried out by the striking the centre of the horizontally-positioned sample.
(Test report No. 315707 dated 09/05/2014) sheet 3 of 4 follows
Environmental conditions during test
Ambient temperature (20 ± 3) °C
Relative humidity (50 ± 15) %
Test results
Impact Mass Impact energy
Drop height
Indentation diameter
Indentation depth
Result
[No.] [kg] [J] [m] [mm] [mm]
1 0,5 1,30 265 0,0 0,0 no visible damage
2 0,5 2,50 510 10,3 0,31 visible indentation
3 0,5 3,75 765 15,2 0,87 no collapse,
penetration or projection
4 0,5 6,00* 1223 13,6 1,06 no collapse,
penetration or projection
(*) Maximum energy level specified by the standard
Photo of sample during test
(Test report No. 315707 dated 09/05/2014) sheet 4 of 4 follows
Findings
On the basis of the tests performed and the results obtained, the test sample, comprising a fibre-reinforced
lightweight cement board called “AQUAFIRE” submitted by BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILA-
NO (MI) - Italy, meets the resistance to hard body impact requirements given in the following table.
Test Test reference Requirement Conditions Energy
[J]
0,5 kg hard body impact
clause 5.1.4.2.2 ETAG 018-4:2011
clause 3 EOTA TR 001:2003
serviceability <1,3
safety in use <6,0
The results given refer exclusively to the test sample itself and are only valid under the same conditions in
which testing was carried out.
This test report alone shall not be considered a certificate of conformity.
Test Technician: Dott. Ing. Paolo Bertini
Head of Security and Safety Laboratory: Dott. Andrea Bruschi
Chief Executive Officer (Dott. Arch. Sara Lorenza Giordano)
............................................
Comp. AV
Revis. AT
This test report consists of 5 sheets.
This document is the English translation of the test report No. 315354 dated 29/04/2014 issued in Italian; in case of dispute
the only valid version is the Italian one. Date of translation: 13/06/2014.
Sheet
1 of 5
CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
TEST REPORT No. 315354
Place and date of issue: Bellaria-Igea Marina - Italy, 29/04/2014
Customer: BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO (MI) - Italy
Date test requested: 23/01/2014
Order number and date: 61981, 23/01/2014
Date sample received: 20/01/2014
Test date: 22/04/2014
Purpose of test: determination of tensile strength perpendicular to the plane of fibre-reinforced
lightweight cement board in accordance with standard UNI EN 319:1994
Test site: Istituto Giordano S.p.A. - Blocco 1 - Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) -
Italy
Sample origin: sampled by Istituto Giordano in accordance with the procedure specified in sample
report dated 14/01/2014 and supplied by the Customer
Identification of sample received: No. 2014/0109
Sample name*
The test sample is called “AQUAFIRE”.
(*) according to that stated by the Customer.
(Test report No. 315354 dated 29/04/2014) sheet 2 of 5 follows
Description of sample*
The test sample comprises fibre-reinforced lightweight cement boards, nominal thickness 12,5 mm, taken from
the following batches:
1) Batch 4354 dated 18/11/2013 - 140114 B1/from 1 to 50;
2) Batch 4473 dated 25/11/2013 - 140114 B2/from 1 to 50;
3) Batch 4534 dated 27/11/2013 - 140114 B3/from 1 to 50;
4) Batch 4602 dated 02/12/2013 - 140114 B4/from 1 to 50.
Description of test pieces
8 test pieces of nominal size 50 × 50 mm and the original thickness were cut from the sample.
Sampling took place in accordance with clause 5.2 of the standard. After cutting, the test pieces were bonded
to special steel plates using KERAKOLL KERABUID ECO EPOBOND adhesive. Each test piece was as-
signed a letter ranging from A to H.
Photo of board and a test piece
(*) according to that stated by the Customer.
(Test report No. 315354 dated 29/04/2014) sheet 3 of 5 follows
Normative References
The test was carried out according to the requirements of standard UNI EN 319:1994 dated 31/07/1994 “Parti-
cleboards and fibreboards. Determination of tensile strength perpendicular to the plane of the board”.
Test apparatus
The following equipment was used to carry out the test:
– digital calliper gauge with 10 micron resolution (in-house identification code LG023);
– digital force gauge (in-house identification code TDL016) with 10 000 N load cell (in-house identification
code TDL029).
Test method
Conditioning of test pieces
The test pieces were conditioned to constant mass for at least 48 h at a temperature of (20 ± 2) °C and rela-
tive humidity of (65 ± 5) %.
Test method
The test was carried out with force gauge rate of cross-head movement of 3 mm/min so that the maximum
load is reached within (60 ± 30) s as specified by clause 6.1 of the reference standard.
After stabilising with the conditioning described above, the test pieces are loaded at a constant rate until
rupture occurs.
Tensile strength perpendicular to the plane of the test piece is calculated according to the following formu-
la:
ba
Ff max
1t⋅
=
where: ft1 = tensile strength perpendicular to the plane, expressed in N/mm²;
Fmax = breaking load, in N;
a, b = length and width of the test piece, in mm.
(Test report No. 315354 dated 29/04/2014) sheet 4 of 5 follows
Photo of a test piece during testing
Environmental conditions during test
Ambient temperature (18 ± 2) °C
Relative humidity (48 ± 5) %
(Test report No. 315354 dated 29/04/2014) sheet 5 of 5 follows
Test results
Test piece Length a
Width
b
Maximum force
Fmax
Tensile strength ft1
[No.] [mm] [mm] [N] [N/mm²]
A 50,20 50,49 2585 1,02
B 50,55 49,92 2412 0,96
C 50,75 50,29 2351 0,92
D 50,96 50,71 2687 1,04
E 50,48 50,30 2599 1,02
F 50,39 51,02 2368 0,92
G 50,48 50,40 2741 1,08
H 51,03 50,77 2516 0,97
Mean 50,61 50,49 2532 0,99
Standard deviation 0,29 0,34 146 0,06
Note: in no case was the test piece detached from the rigid plates.
After-test photo of a test piece
Test Technician: Dott. Alessandro Trevisani
Head of Wood Technology/Conditioning Laboratory: Dott. Alessandro Trevisani
Chief Executive Officer (Dott. Arch. Sara Lorenza Giordano)
............................................
Comp. AV
Revis. AT
This test report consists of 5 sheets.
This document is the English translation of the test report No. 315353 dated 29/04/2014 issued in Italian; in case of dispute
the only valid version is the Italian one. Date of translation: 13/06/2014.
Sheet
1 of 5
CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
TEST REPORT No. 315353
Place and date of issue: Bellaria-Igea Marina - Italy, 29/04/2014
Customer: BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO (MI) - Italy
Date test requested: 23/01/2014
Order number and date: 61981, 23/01/2014
Date sample received: 20/01/2014
Test date: 15/04/2014
Purpose of test: determination of planar shear properties of fibre-reinforced lightweight cement
board in accordance with clause 11 of standard UNI EN 789:2005
Test site: Istituto Giordano S.p.A. - Via Erbosa, 72 - 47043 Gatteo (FC) - Italy
Sample origin: sampled by Istituto Giordano in accordance with the procedure specified in sample
report dated 14/01/2014 and supplied by the Customer
Identification of sample received: No. 2014/0109
Sample name*
The test sample is called “AQUAFIRE”.
(*) according to that stated by the Customer.
(Test report No. 315353 dated 29/04/2014) sheet 2 of 5 follows
Description of sample*
The test sample comprises fibre-reinforced lightweight cement boards, nominal thickness 12,5 mm, taken from
the following batches:
1) Batch 4354 dated 18-11-2013 - 140114 B1/from 1 to 50;
2) Batch 4473 dated 25-11-2013 - 140114 B2/from 1 to 50;
3) Batch 4534 dated 27-11-2013 - 140114 B3/from 1 to 50;
4) Batch 4602 dated 02-12-2013 - 140114 B4/from 1 to 50.
Description of test pieces
8 test pieces of nominal size 100 × 255 mm and the original thickness were cut from the sample.
Sampling was carried out in accordance with the schedule specified in clause 5.2 of the standard using test
pieces numbered from 33 to 40. After cutting, the test pieces were bonded to special steel plates using MAPEI
Keraflex maxi s1 adhesive following application of Eco Prim T primer diluted 1:1.
Photo of board and some test pieces
(*) according to that stated by the Customer.
(Test report No. 315353 dated 29/04/2014) sheet 3 of 5 follows
Normative References
The test was carried out according to the requirements of clause 11 of standard UNI EN 789:2005 dated
01/05/2005 “Timber structures - Test methods - Determination of mechanical properties of wood based pan-
els”.
Test apparatus
The following equipment was used to carry out the test:
– temperature and humidity chamber with a temperature of (20 ± 2) °C and relative humidity (65 ± 5) % (in-
house identification code TDL001);
– force gauge with 10 000 N load cell (in-house identification codes FT161 and FT193);
– digital calliper gauge with 10 micron resolution (in-house identification code FT334).
Test method
The test pieces were first conditioned to constant mass in the temperature/humidity chamber for at least 24 h.
The test was carried out in accordance with clause 11.4.1 of the reference standard with force gauge rate of
cross-head movement of 2 mm/min.
The planar shear strength “fr” (in N/mm²) of each test piece is calculated from the following formula:
lb
F=f max
r
where: l = length of the test specimen, in mm;
b = width of the test specimen, in mm;
Fmax = maximum load, in newtons.
(Test report No. 315353 dated 29/04/2014) sheet 4 of 5 follows
Photo of a test piece during testing
Conditions during test
Ambient temperature (20 ± 5) °C
Relative humidity (50 ± 10) %
(Test report No. 315353 dated 29/04/2014) sheet 5 of 5 follows
Test results
Test piece Direction Length Width Maximum load Planar shear strength
l b Fmax fr
[No.] [mm] [mm] [N] [N/mm²]
33 L 225,00 101,05 26385 1,160
34 L 225,00 100,42 25347 1,122
35 L 225,00 100,46 20846 0,922
36 L 225,00 100,72 28307 1,249
37 T 225,00 100,63 22784 1,006
38 T 225,00 100,29 20787 0,921
39 T 225,00 100,22 20157 0,894
40 T 225,00 100,51 26543 1,174
Mean / 225,00 100,54 23895 1,056
After-test photo of a test piece
Test Technician: Dott. Alessandro Trevisani
Head of Wood Technology/Conditioning Laboratory: Dott. Alessandro Trevisani
Chief Executive Officer (Dott. Arch. Sara Lorenza Giordano)
............................................
Comp. AV
Revis. AT
This test report consists of 5 sheets.
This document is the English translation of the test report No. 315963 dated 20/05/2014 issued in Italian; in case of dispute
the only valid version is the Italian one. Date of translation: 13/06/2014.
Sheet
1 of 5
CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
TEST REPORT No. 315963
Place and date of issue: Bellaria-Igea Marina - Italy, 20/05/2014
Customer: BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO (MI) - Italy
Date test requested: 16/04/2014
Order number and date: 61981, 23/01/2014
Date sample received: 20/01/2014
Test date: 15/04/2014
Purpose of test: determination of planar shear properties of fibre-reinforced lightweight cement
board in accordance with clause 11 of standard UNI EN 789:2005
Test site: Istituto Giordano S.p.A. - Via Erbosa, 72 - 47043 Gatteo (FC) - Italy
Sample origin: sampled by Istituto Giordano in accordance with the procedure specified in sample
report dated 14/04/2014 and supplied by the Customer
Identification of sample received: No. 2014/0109
Sample name*
The test sample is called “AQUAFIRE”.
(*) according to that stated by the Customer.
(Test Report No. 315963 dated 20/05/2014) sheet 2 of 5 follows
Description of sample*
The test sample comprises fibre-reinforced lightweight cement boards, nominal thickness 12,5 mm, taken from
the following batches:
1) Batch 4354 dated 18-11-2013 - 140114 B1/from 1 to 50;
2) Batch 4473 dated 25-11-2013 - 140114 B2/from 1 to 50;
3) Batch 4534 dated 27/11/2013 - 140114 B3/from 1 to 50;
4) Batch 4602 dated 02/12/2013 - 140114 B4/from 1 to 50.
Description of test pieces
8 test pieces of nominal size 100 × 255 mm and the original thickness were cut from the sample.
Sampling was carried out in accordance with the schedule specified in clause 5.2 of the standard using test
pieces numbered from 33 to 40. After cutting, the test pieces were bonded to special steel plates using
Kerakoll KERABUID ECO EPOBOND adhesive.
Close-up of a board belonging to the sample
(*) according to that stated by the Customer.
(Test Report No. 315963 dated 20/05/2014) sheet 3 of 5 follows
Normative References
The test was carried out according to the requirements of clause 11 of standard UNI EN 789:2005 dated
01/05/2005 “Timber structures - Test methods - Determination of mechanical properties of wood based pan-
els”.
Test apparatus
The following equipment was used to carry out the test:
– temperature and humidity chamber with a temperature of (20 ± 2) °C and relative humidity (65 ± 5) % (in-
house identification code TDL001);
– force gauge with 10 000 N load cell (in-house identification codes FT161 + FT193);
– digital calliper gauge with 10 micron resolution (in-house identification code FT334).
Test method
The test pieces were first conditioned to constant mass in the temperature/humidity chamber for at least 24 h.
The test was carried out in accordance with clause 11.4.1 of the reference standard with force gauge rate of
cross-head movement of 2 mm/min.
The planar shear strength “fr” (in N/mm²) of each test piece is calculated from the following formula:
lb
F=f max
r
where: l = length of the test specimen, in mm;
b = width of the test piece, in mm;
Fmax = maximum load, in newtons.
(Test Report No. 315963 dated 20/05/2014) sheet 4 of 5 follows
Photo of a test piece during testing
Conditions during test
Ambient temperature (20 ± 5) °C
Relative humidity (50 ± 10) %
(Test Report No. 315963 dated 20/05/2014) sheet 5 of 5 follows
Test results
Test piece Direction Length Width Maximum load Planar shear strength
l b Fmax fr
[No.] [mm] [mm] [N] [N/mm²]
33 L 225 100 30317 1,3474
34 L 225 100 32498 1,4444
35 L 225 100 31109 1,3826
36 L 225 100 30783 1,3681
37 T 225 100 26960 1,1982
38 T 225 100 33758 1,5004
39 T 225 100 38524 1,7122
40 T 225 100 32916 1,4629
Mean / 225 100 32108 1,4270
After-test photo of a test piece
Test Technician: Dott. Alessandro Trevisani
Head of Wood Technology/Conditioning Laboratory: Dott. Alessandro Trevisani
Chief Executive Officer (Dott. Arch. Sara Lorenza Giordano)
............................................
Comp. AV
Revis. AT
This test report consists of 7 sheets.
This document is the English translation of the test report No. 316280 dated 30/05/2014 issued in Italian; in case of dispute
the only valid version is the Italian one. Date of translation: 30/06/2014.
Sheet
1 of 7
CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
TEST REPORT No. 316280
Place and date of issue: Bellaria-Igea Marina - Italy, 30/05/2014
Customer: BIFIRE S.r.l. - Via Carducci, 8 - 20123 MILANO (MI) - Italy
Date test requested: 18/03/2014
Order number and date: 61981, 23/01/2014
Date sample received: 20/01/2014
Test date: from 18/03/2014 to 27/05/2014
Purpose of test: determination of dimensional changes associated with changes in relative humidity
of fibre-reinforced lightweight cement board with reference to standard UNI EN
318:2003
Test site: Istituto Giordano S.p.A. - Blocco 4 - Via San Mauro, 8 - 47814 Bellaria-Igea Marina
(RN) - Italy
Sample origin: sampled by Istituto Giordano in accordance with the procedure specified in sample
report dated 14/01/2014 and supplied by the Customer
Identification of sample received: No. 2014/0109
Sample name*
The test sample is called “AQUAFIRE”.
(*) according to that stated by the Customer.
(Test report No. 316280 dated 30/05/2014) sheet 2 of 7 follows
Description of sample*
The test sample comprises fibre-reinforced lightweight cement boards, nominal thickness 12,5 mm, taken from
the following batches:
1) Batch 4354 dated 18-11-2013 - 140114 B1/from 1 to 50;
2) Batch 4473 dated 25-11-2013 - 140114 B2/from 1 to 50;
3) Batch 4534 dated 27/11/2013 - 140114 B3/from 1 to 50;
4) Batch 4602 dated 02/12/2013 - 140114 B4/from 1 to 50.
Normative References
The test was carried out in accordance with the requirements of standard UNI EN 318:2003 dated 01/03/2003
“Wood-based panels - Determination of dimensional changes associated with changes in relative humidity”.
Description of test pieces
The test sample was cut in each panel direction (length = L and width = T) in order to obtain 2 sets of 8 test
pieces (4L + 4T). The test pieces are of nominal size 350 × 50 mm and the original thickness.
Photo of a test piece and close-up of a sample batch ID
(*) according to that stated by the Customer.
(Test report No. 316280 dated 30/05/2014) sheet 3 of 7 follows
Test apparatus
The test was performed using the following equipment requested by clause 4 of the reference standard:
– digital calliper gauge with 10 micron resolution (in-house identification code FT334);
– Angelantoni temperature and humidity chamber (in-house identification code FT137);
– digital micrometer (in-house identification code FT363);
– digital balance (in-house identification code TDL006).
Test method
Preliminary treatment
The choice for preliminary treatment was based on the provisions of clause 6.2 of the reference standard
with the following conditioning climates:
– “step II” (20 °C - 65 % RH) for both sets;
– “step III” (20 °C - 85 % RH) for set I and (20 °C - 30 % RH) for set II.
The test was then carried out in accordance with subclause 6.3 of the reference standard.
Determination of the moisture content and the change in length and thickness
The following tables, one for each set of test pieces, give details of the measurements carried out and the
following calculations:
– moisture content: as a percentage, calculated using an in-house method;
– change in length: calculated according to the equations:
– using set I results:
1000l
ll=lδ
65
658585,65
– using set II results:
1000l
ll=lδ
65
653030,65
where lx is the length between measurement points at 20 °C with X% relative humidity;
(Test report No. 316280 dated 30/05/2014) sheet 4 of 7 follows
– change in thickness: calculated as the mean change in thickness for the three measured points accord-
ing to the equations:
– using set I results:
100t
ttt
65
658585,65 ⋅
−=δ
– using set II results:
100t
ttt
65
653030,65 ⋅
−=δ
where tx is the thickness recorded at the measurement points at 20 °C with X% relative humidity.
(Test report No. 316280 dated 30/05/2014) sheet 5 of 7 follows
Test results
Set I, measurement after step II (20 °C - 65 % RH)
Test piece Length Thickness Mass
Moisture content
[mm] [mm] [g] [%]
L1 200,78 12,57 242,2 2,8
L2 200,72 12,37 227,3 2,6
L3 200,72 12,41 246,9 2,5
L4 200,75 12,39 257,4 3,4
T1 200,66 12,25 258,0 2,8
T2 200,68 12,35 254,7 4,4
T3 200,63 12,52 259,3 4,7
T4 200,65 12,21 259,7 4,3
Mean 200,70 12,38 250,7 3,4
Set II, measurement after step II (20 °C - 65 % RH)
Test piece Length Thickness Mass
Moisture content
[mm] [mm] [g] [%]
L1 200,76 12,36 250,9 5,2
L2 200,66 12,45 249,2 4,2
L3 200,78 12,40 228,9 4,9
L4 200,83 12,41 247,3 5,1
T1 200,68 12,39 258,9 5,0
T2 200,64 12,32 256,2 4,9
T3 200,68 12,30 255,6 4,7
T4 200,68 12,45 260,9 5,8
Mean 200,71 12,39 251,0 5,0
(Test report No. 316280 dated 30/05/2014) sheet 6 of 7 follows
Set I, measurement after step III (20 °C - 85 % RH)
Test piece Length Thickness Mass
Moisture content
[mm] [mm] [g] [%]
L1 200,82 12,70 246,3 4,5
L2 200,83 12,46 230,8 4,2
L3 200,83 12,53 250,8 4,1
L4 200,90 12,56 258,9 4,0
T1 200,64 12,30 262,4 4,6
T2 200,81 12,47 256,4 5,1
T3 200,71 12,72 261,1 5,5
T4 200,68 12,43 261,8 5,1
Mean 200,78 12,52 253,6 4,6
Set II, measurement after step III (20 °C - 30 % RH)
Test piece Length Thickness Mass
Moisture content
[mm] [mm] [g] [%]
L1 200,76 12,39 247,6 3,8
L2 200,67 12,56 246,8 3,2
L3 200,74 12,39 226,4 3,7
L4 200,66 12,34 244,5 4,0
T1 200,60 12,18 256,3 4,0
T2 200,49 12,38 253,4 3,8
T3 200,50 12,33 253,2 3,7
T4 200,55 12,40 257,1 4,3
Mean 200,62 12,37 248,2 3,8
(Test report No. 316280 dated 30/05/2014) sheet 7 of 7 follows
Determination of change in length and thickness
Set 1
Test piece Change in length δl65-85
Change in thickness δt65-85
[mm/m] [%]
L1 0,20 1,69
L2 0,55 1,54
L3 0,55 1,58
L4 0,75 0,58
T1 -0,10 1,71
T2 0,65 0,67
T3 0,40 0,69
T4 0,15 0,81
Mean 0,39 1,16
Set II
Test piece Change in length δl65-30
Change in thickness δt65-30
[mm/m] [%]
L1 0,00 -1,32
L2 0,05 -0,96
L3 -0,20 -1,09
L4 -0,85 -1,13
T1 -0,40 -1,00
T2 -0,75 -1,09
T3 -0,90 -0,94
T4 -0,65 -1,46
Mean -0,46 -1,12
Test Technician: Dott. Alessandro Trevisani
Head of Wood Technology/Conditioning Laboratory: Dott. Alessandro Trevisani
Chief Executive Officer (Dott. Arch. Sara Lorenza Giordano)
............................................
Comp. AV
Revis. PB
This test report consists of 5 sheets.
This document is the English translation of the test report No. 315703 dated 09/05/2014 issued in Italian; in case of dispute
the only valid version is the Italian one. Date of translation: 13/06/2014.
Sheet
1 of 5
CLAUSES: This document relates only to the sample or material tested and shall not be reproduced except in full without Istituto Giordano’s written approval.
Istituto Giordano S.p.A.
Via Rossini, 2 - 47814 Bellaria-Igea Marina (RN) - Italia
Tel. +39 0541 343030 - Fax +39 0541 345540
[email protected] - www.giordano.it
PEC: [email protected]
Cod. Fisc./Part. IVA: 00 549 540 409 - Cap. Soc. € 1.500.000 i.v.
R.E.A. c/o C.C.I.A.A. (RN) 156766
Registro Imprese di Rimini n. 00 549 540 409
TEST REPORT No. 315703
Place and date of issue: Bellaria-Igea Marina - Italy, 09/05/2014
Customer: BIFIRE S.r.l.- Via Carducci, 8 - 20123 MILANO (MI) - Italy
Date test requested: 20/01/2014
Order number and date: 61981, 23/01/2014
Date sample received: 20/01/2014
Test date: 29/01/2014
Purpose of test: determination of mechanical bending properties (MOE/MOR) of fibre-cement flat
sheets in accordance with clause 7.3.2 of standard UNI EN 12467:2012
Test site: Istituto Giordano S.p.A. - Via Erbosa, 72 - 47043 Gatteo (FC) - Italy
Sample origin: sampled by Istituto Giordano in accordance with the procedure specified in sample
report dated 14/01/2014 and supplied by the Customer
Identification of sample received: No. 2014/0109
Sample name*
The test sample is called “AQUAFIRE”.
Description of sample*
The test sample comprises untreated fibre-reinforced lightweight cement boards, with the following specifica-
tions:
– density = 960 kg/m³ ± 15 %;
(*) according to that stated by the Customer.
(Test report No. 315703 dated 09/05/2014) sheet 2 of 5 follows
– width = (1200 ± 3,6) mm;
– length = (2000 ± 5,0) mm;
– thickness = (12,5 ± 1,2) mm.
Description of test pieces
In accordance with standard UNI EN 12467:2012, 10 test pieces were cut from the sample of size
250 × 100 mm and original product thickness.
5 of the ten test pieces were cut in the machine direction “M” and 5 at right angles to the machine “T”.
Photo of a test piece
(Test report No. 315703 dated 09/05/2014) sheet 3 of 5 follows
Normative References
The test was carried out in accordance with the requirements of standard UNI EN 12467:2012 dated
11/10/2012 “Fibre-cement flat sheets - Product specification and test methods”.
Test apparatus
The following equipment was used to carry out the test:
– IG 10000 electronic force gauge manufactured by Istituto Giordano S.p.A., speed range 0,05-300 mm/min,
clear span between support columns of 640 mm and effective travel 2000 mm (apparatus in-house identifi-
cation code FT161);
– AEP load cell, capacity 10 kN (apparatus in-house identification code EDI073);
– steel test frame complying with clause 7.3.2.2.1 with radius of supports and loading bar of 10 mm and span
between the supports ls = 10 mm;
– Mitutoyo Corporation digital calliper gauge with 10 micron resolution (apparatus in-house identification
code EDI066).
Test method
The test was carried out in accordance with the requirements of standard UNI EN 12467:2012 and more spe-
cifically:
– requirements in accordance with clauses 5.2.2 “Category A” and 5.5.2 of standard UNI EN 12467:2012;
– Test method in accordance with clause 7.3.2 “Mechanical characteristics - Bending strength - Modulus of
elasticity (Bending modulus)” of standard UNI EN 12467:2012.
The test pieces were conditioned for at least 7 days under standard laboratory conditions, temperature
(23 ± 2) °C and relative humidity (50 ± 5) %.
They were subsequently immersed in water for 24 h at ambient temperature (23 ± 2) °C and then underwent
the bending test in accordance with clause 7.3.2.3 of standard UNI EN 12467:2012.
Cylindrical supports were used of radius 10 mm arranged so that the span between the axes of the supports
“lS” is 200 mm.
(Test report No. 315703 dated 09/05/2014) sheet 4 of 5 follows
The following were calculated for each test piece:
– modulus of rupture MOR, in MPa, in accordance with clause 7.3.2.4.1 of standard UNI EN 12467:2012, as
given by the following formula.
MOR3 F lS
2 b e2
where: F = breaking load, in N;
lS = span between the axes of supports, in mm;
b = width of the test piece, in mm;
e = thickness of the test piece, in mm;
– modulus of elasticity MOE, in MPa, in accordance with clause 7.3.2.4.2 of standard UNI EN 12467:2012,
as given by the following formula.
EF2-F1 lS
3
4 b e3 f2-f1
where: lS = span between the axes of supports, in mm;
F1 and F2 = loads, taken from two points within the linear section of the plot, below the limit of
proportionality;
b = width of the test piece, in mm;
e = thickness of the test piece, in mm;
f1 and f2 = deflections corresponding to the load selected, in mm.
Environmental conditions during test
Ambient temperature (23 ± 2) °C
Relative humidity (50 ± 5) %
(Test report No. 315703 dated 09/05/2014) sheet 5 of 5 follows
Test results
Direction of test
Test piece Measured thickness
“e”
Breaking load “F”
Modulus of rupture
“MORfci”
Modulus of elasticity “MOE”
[n.] [N] [MPa] [MPa]
M
1 12,3 326 6,4 501
2 12,1 193 6,0 515
3 12,5 301 5,8 635
4 12,1 300 6,2 481
5 12,2 273 5,5 546
T
1 12,2 292 5,9 1646
2 12,4 272 5,4 1413
3 12,3 252 5,0 1451
4 12,2 270 5,4 1506
5 12,3 305 6,0 1736
Mean 12,3 288 5,8 1043
Standard deviation 0,1 37 0,4 544
Test Technician: Dott. Ing. Paolo Bertini
Head of Security and Safety Laboratory: Dott. Andrea Bruschi
Chief Executive Officer (Dott. Arch. Sara Lorenza Giordano)
............................................