04_Multi_V_ENG

download 04_Multi_V_ENG

of 44

Transcript of 04_Multi_V_ENG

  • 8/10/2019 04_Multi_V_ENG

    1/44

    For continual product development, LG reserves the right to change specifications without notice.

    LG Electronics Inc. Printed in Korea Jan.2004

    ht t p ://www.lg e.c om

    ht t p ://www.lg c ac .c om

    20 Yoido-dong, Youngdungpo-gu, Yoido P.O.Box 355 Seoul 150-721, Korea

    Phone: 82-2-3777-7969 Fax: 82-2-3777-5135/6

  • 8/10/2019 04_Multi_V_ENG

    2/44

    Air Conditioning System

  • 8/10/2019 04_Multi_V_ENG

    3/44

    LG air conditioners: recognized as the best across the world...

    According to Fuji-Keizai, one of Japans top market research

    companies, LG Electronics (LGE) maintained its No.1 global

    position for the fourth consecutive year since 2000 in terms of

    AC unite sales a total of 8 million units (US$2billion) in 2003.

    LGE started its air conditioner business in 1968. Although it was

    a difficult time to enter the market during the Asian currency

    crisis in 1997, the company expanded its export drive and

    invested in R&D and production lines. Sales grew rapidly: from

    4.1 million units in 2000, 4.9 million 1n 2001, 6.7 million in 2002

    and then 8 million units in 2003. With a 25% CAGR (compound

    annual growth rate), LGE continues to defend its prime position

    in the AC units industry

    LG Electronics, Worlds Top for 4 Years

    Welcome to LG Air Condit ioning Division

    The Worlds Best Seller

    New Leader in Multi V Technology

  • 8/10/2019 04_Multi_V_ENG

    4/44

    Caringfor Environment

    1

    Environment FriendlyThe environment of the future at LG Air conditioners

    Keeping pace with developments in global environment policies, the

    company has developed a new refrigerant

    to replace Freon gas (R22), ahead of it being banned due to its

    environmentally - damaging greenhouse effects.

    On completion of market tests in 1999, the company launched its wall and

    window mounted product ranges in 2000.

    With a ceiling-type duct to be supplied from 2001, the company is

    positioned to cover all air conditioner market sectors. This is our

    environment-friendly policy protecting the environment for the future.

  • 8/10/2019 04_Multi_V_ENG

    5/44

    Great Company Great People

    Welcome to LG Air Condit ioning Division

    Brief History

    Establ ishment

    1947 Establishment of LG Group

    1958 Establishment of LG Electronics Inc.

    1962 Establishment of Digital Appliance Company

    Growth

    1968 Manufactured Koreas first Air Conditioners

    1985 Introduced Koreas first Inverter Air Conditioners

    1986 Exported Koreas first Window Air Conditioner to U.S.A

    1989 Won the approval of ULs MDP & CSAs EEVP1993 Obtained ISO 9001 Certification from BSI-QA

    1994 Export Records USD 100 Mil.

    Global Expansion

    1995 Establishment of LGETA in China

    1997 Establishment of LGEIL in India

    1999 Establishment of LGEAT in Turkey

    1999 Establishment of LGEMH in Vietnam

    2001 Establishment of LGEAZ in Brazil

    2002 Establishment of LGETH in Thailand

    2002 Establishment of LGEIN in Indonesia

    2002 Turnover of 1.8 Billion dollars (Expected)

    Test Tower

    LG Air Conditioners World-winning Technology...LG offers a more advantageous business environment for its customers with its range of air conditioner features. Its

    PLASMA Air Purifying System, first developed and marketed in 1999, has proved its effectiveness, and LG has since in

    2000 developed the world's first semi-permanent PLASMA Heat Exchanger, enhancing the functionality of the core

    component.

    In 2001 the company introduced state-of-the-art digital telephone remote control technology, and developed the

    Tele-control air conditioner, which is activated or stopped remotely via an ordinary telephone. To maintain its product

    leadership in the market, LG Air conditioners places a lot of emphasis on improvements such as reduced energy

    consumption, high efficiency, low noise compressors, ventilation systems and compact product dimensions, etc.

    New Leader in Multi V Technology

  • 8/10/2019 04_Multi_V_ENG

    6/44

    LG Air Conditioning Division, Korea LGE Tianjin Appliance Co., Ltd. China LG Electronics Thailand. Thailand

    LG Electronics Arcelik. Turkey LGE New Delhi Ltd. India LGE Haiphong Inc. Vietnam

    LGE da Amazonia Ltd. Brazil LG Electronics Indonesia. Indonesia

    LGETA China Tianjin

    LGEAZ Brazil

    LGE Korea

    LGEIL India

    LGEMH VietnamLGEIN Indonesia

    LGETH Thailand

    LGEAT Turkey

    The Future is Bright for LG Air Conditioners

    LG Air conditioners, which first manufactured window type air conditioners in Korea in 1968, has undergone

    tremendous growth to achieve a turnover of 1.8 billion dollars in 2002.

    The company supplies over 7 million units to markets worldwide through its manufacturing sites in Korea,

    China, India, Turkey, Vietnam, Thailand, Indonesia and Brazil.

    Overseas Manufacturing Bases

    3

  • 8/10/2019 04_Multi_V_ENG

    7/44

    Mult i V Installat ion Reference

    New Leader in Multi V Technology

    Madrid, SPAIN

    Doctor Garcia Tapia

    Installation:Confaire

    Cervia(Ravenna), ITALY

    Hotel Lady Mary

    Installation:Casa Service di Tosi Mario

  • 8/10/2019 04_Multi_V_ENG

    8/44

    Installation Reference

    5

    Philippine

    KoreaChina

    Australia

    Singapore

    Spain

    UKBelgiumGermany

    Hungary

    Russia

    South Africa

    ItalyPortugal

    France

    Pampilhosa da serra, PORTUGAL

    District Court

    Installation:Climacer

    Gennevilliers, FRANCE

    Office Building

    Installation:Alize Clim

    LG Air Conditioner into to the Global

  • 8/10/2019 04_Multi_V_ENG

    9/44

    If you need highly efficient air conditioning system in your building, LG MULTI V is the right choice for you.

    What is Mult i V ?

    New Leader in Multi V Technology

  • 8/10/2019 04_Multi_V_ENG

    10/44

    What is ?It's an inverter multi system with single connecting refrigerant pipe, which is composed of one outdoor

    unit and some indoor units in series, so it saves energy greatly and makes the installation easy.

    This efficient piping system allows a flexible assembly so that it can be

    connected to various types of indoor unit while it reduces the installation cost.

    Ease of installation with size and routing of pipework compared to water based systems, and also with the advantage of

    less space for the outdoor units and flexible internal unit requirements, means that there are has lower installation

    fees and reduced running costs.

    VRF (individual A/C-Air Cooled) Chiller (Central A/C-Water cooled)

    - Easy pipe work(small pipe diameter) - Hard pipe work (large pipe diameter)- Fit for New B/D, extension B/D and reconstruction - Hard to apply to existing facilities.

    - Both individual and automatic central - manually individual controlcontrol based on MICOM control or central control in a machine room

    - Small installation area & light weight - More than 3 times installation area

    - Low initial cost - High initial & operational costs- Low operational cost Required continuous maintenance

    Piping Work

    Control System

    Installation

    InstallationOperational Costs

    System Structure

    7

  • 8/10/2019 04_Multi_V_ENG

    11/44

    Internet control

    Central Control

    Model Line up

    4.5 HP

    10 HP

    CRUN4580S

    CRUN10080S

    Multi V system has a flexible piping connection and

    exists in various types so that it can be used in any

    kinds of spaces. Within the outdoor units capacity,

    6~30 indoor units can be assembled in flexible

    arrangement. This makes the designing and

    installation much easier.

    Also, a separate control for each room is possible

    as well as various types of central controller

    New Leader in Multi V Technology

  • 8/10/2019 04_Multi_V_ENG

    12/44

    9

    The LG Multi V system for R407C heat pump is a rapid response system in which up to 16 indoor units can operate on

    the same refrigerant circuit in conjunction with a single outdoor unit. An inverter compressor enables the output of

    the outdoor unit to be modulated in accordance with the cooling/heating demand of the zone which it controls.

    1-Way Cassette Type 4-Way Cassette Type Ceiling Concealed Duct Type

    Low Static High Static

    Floor Standing Type

    ART COOL Mirror Wall Mounted Type ART COOL Ceiling & Floor Type Floor Standing(exposed) Type

    The flexible indoor unit assembly is appropriate for different spaces, makes the installation easy and reduces the cost.

    Various assem bly of Mult i V indoor unit s

    9

  • 8/10/2019 04_Multi_V_ENG

    13/44

    for DesignWe meet your needs with unique

    LG technologyMULTI V will meet your needs with our unique technology.

    First to innovate, First to perfect. It's the real technology!

    for InstallationAnyone can install it simply

    and easilyWe believe you will be impressed with an air conditioner

    installation diagram as simple as this.

    Now, simpler and easier!

    - Technology of Suitability for Building

    - Gold Fin

    - Urethane Coated PCB

    - Plasma Air Purifying Filter

    - Environment-friendly Refrigerant

    - Wide Variety of Indoor Units

    - Ventilation System

    - LG One Stop Quotation

    - Long Piping System

    - Auto Addressing

    - Non-polarized Wire

    - Auto Restart

    - Sequential Start

    - Self Diagnostic Program

    New Leader in Multi V Technology

  • 8/10/2019 04_Multi_V_ENG

    14/44

    for UseAlways pleasant to use and highly

    efficient in a variety ofenvironments

    Air conditioners must perform well in any kind of climate

    environment. Highly efficient heating and cooling system,

    Any where Any climate

    We have achieved a higher level of product reliability through 2 years of testing in the field and in our

    MULTI V Test Tower, and through a differentiated design. Using an indoor unit automated addressing

    and non-polarized wire communication, MULTI V has achieved convenience of installation and a zero

    error rate. The system can be linked to a variety of stylish indoor units only offered by LG, and its

    heating and cooling performance is superior than competitors in any climate.

    Number 1 in the World For 3 Years - LG Air Conditioner!

    for ControlYou can choose a control system

    exactly right for youIf your needs are different, then the solutions must be

    different. A new MULTI V control system to meet your

    needs !

    - Cooling for Low Ambient Temperature

    - Heating for Extremely Cold Region

    - Highest COP Level

    - Wide Range of Operation

    - Heat Recovery

    - System Expansion

    - Simple Central Controller

    - Deluxe Central Controller

    - Various Controllers of MULTI V

    11

  • 8/10/2019 04_Multi_V_ENG

    15/44

    Technology of Suitability for BuildingLG has developed an outdoor fan which creates high air volume with low noise. This has been achieved using air flow analysis on the

    building's periphery and the outdoor unit's characteristics. This increases the acceptability of the unit in buildings by minimizing the noise

    and vibration of the outdoor unit.

    Anti Rust Gold FinThe system's condensing coils durability has been increased by utilising gold fins with superior anti-corrosive qualities.

    Salt Spray Test Result: After 360 hours [ Test Standard: KS D 9502, ASTM B-117 ]

    Uncoated Aluminum

    ConventionalStarting to corrode

    After 15 Days

    Salt Spray Test for 15 Days

    Gold Coated Aluminum

    LG Gold FinCorrosion Free

    After 15 Days

    New Leader in Multi V Technology

    We meet your needs with unique LG technologyMULTI V will meet your needs with our unique technology. First to innovate, First to perfect. It's the real technology!

    for Design

    Around the Building

    External wind analysis Velocity field analysis

    Around the Outdoor Units

    Without the Hood With the Hood

  • 8/10/2019 04_Multi_V_ENG

    16/44

    13

    Urethane Coated PCB Conventional

    Urethane Coated PCBFirst in the industry to coat the PCB with urethane, the MULTI V switches

    and connectors are fully protected from moisture, dust etc to reduce the

    risk of external shock.

    Designed for Environment-friendly RefrigerantThe MULTI V uses environment-friendly refrigerant to prevent

    destruction of the ozone.

    PLASMA Air Purifying FilterThe indoor unit has a unique plasma air purifying filter which removes

    impurities, such as dust, Odor and allergens, and supplies clean, fresh and

    Odor free air.

    Ventilation SystemThe ventilation system linked to the MULTI V uses a specially developed medium as a heat exchanger which in comparison to existing

    metal heat exchangers, is three times more energy efficient. By allowing water molecules to pass through, the system maintains an

    ideal 40-60% humidity and eliminates mold and viruses.

    Wide Variety of Indoor UnitsFrom 1, 2, and 4-way cassette types to convertible, concealed duct, wall mounted, Art Cool and the latest Art Cool mirror model,

    LG offers a wide variety of indoor unit designs that will create an aesthetically pleasing interior.

    Polluted Air

    Clean Air

    Plasma ionizerRating Voltage=4.8kV

    Case

    Powerinput terminal

    Cover

    Photo-CatalystCoated Mesh

    Dust Free! / Odor Free! / Anti-Allergy !

  • 8/10/2019 04_Multi_V_ENG

    17/44

    LG One Stop QuotationBased on information regarding the expected MULTI V installation location, we could carry out a selection of the position, size and most

    efficient indoor unit type. We have specially developed software that can automatically design the capacity, piping, and wiring for the system.

    The LGOSQ easily carries out this process step-by-step, providing you with a timely, simple and accurate proposal, cost estimate, and all the

    information you need prior to installation.

    New Leader in Multi V Technology

    for InstallationAnyone can install it simply and easilyWe believe you will be impressed with an air conditioner installation diagram as simple as this. Now, simpler and easier!

    Long Piping SystemThis is the MULTI V tower, a new equipment testing facility for conducting air

    conditioner experiments at different altitudes.

    MULTI V tubing can be installed with a maximum piping length of 125 meters,and a maximum vertical height of 50 meters.

    The system achieves the highest

    performance in the world, compared

    to standard-length tubing, by using a

    unique software algorithm which

    optimally controls heating/cooling

    load, overheating and overcooling

    levels.

    50m

    15m

    Outdoor unit(10HP)

    Outdoor unit

    Longest piping

    length 100m

    Introduction Load Calculation

    Load Report Equipment Selection(Tree)

    Annual EnergyConsumption

    Indoor Air Flow andTemperature Distribution

    Equipment Selection(Worksheet) Layout

    Quotation

  • 8/10/2019 04_Multi_V_ENG

    18/44

    Auto AddressingThe outdoor unit automatically confirms the status of each indoor unit without the use of cumbersome dip switches, by storing and sending

    specific numbers to the EEPROM, a part within the indoor unit. With auto addressing, the installation time is greatly reduced

    15

    Auto RestartWhen there is a power cut during operation, the system will automatically restart from the same working condition when the power is

    restored.

    Sequential StartIf there are many outdoor units operating simultaneously, they are started sequentially to reduce power surge and increase safety.

    Non-polarized WireUnlike the existing products where communication between the outdoor and indoor units is impossible if the polarization is different, you

    can simply connect the outdoor and indoor units and the MULTI V algorithm will automatically find the correct polarity and enable

    communications for a simple and easy installation.

    Self Diagnostic ProgramDuring installation, operation after installation, and after service, all problems can be

    diagnosed easily and conveniently using a PC or notebook. If any error occurs, its error code

    will be displayed on the controller screen making it convenient for the user to know about

    the problem.

    Outdoor unit

    (10HP)

    Indoor unit

    Transmission Line

    A B

    A B

    A BB A B A

    Outdoor Unit Control Box

  • 8/10/2019 04_Multi_V_ENG

    19/44

    Cooling for Low Ambient TemperatureIt is an ideal system for superior air conditioning performance, and for places requiring year-around constant temperature. Based on

    temperature and pressure sensor information, the MULTI V system can control the fan speed and expansion valve using hot gas bypass

    technology. This control is available even when the outdoor temperature drops to minus 5 degrees Celsius. It is an ideal system for places

    requiring year-around constant temperature, such as computer rooms.

    Inverter air conditioning /heating system boasts a wide operational range which

    is a result of applying highly advanced new technologies such as the inverter

    scroll compressor and electronic expansion valve. The operation is possible up

    to 43C of outdoor temperature when cooling and down to -20C of outdoor

    temperature while heating.

    Heating for Extremely Cold RegionWhen the outdoor temperature is minus 10 degrees Celsius, the MULTI V can achieve air discharge temperatures exceeding 40~47 degrees

    Celsius. With its unique anti-freezing refrigerant circuit technology, the system is capable of heating without additional heating

    equipment even in cold climates where temperatures go below minus 20 degrees Celsius.

    Cooling

    Heating

    Region of frost prevention

    Check ValveOutdoor'sHEX

    LEV

    Available temperature of cooling/Heating

    - Inverter Scroll Compressor is designed for prevention of liquid compression

    - Refrigerant sub cooling circuit prevents from growing in outdoors

    HEX at heating operation

    New Leader in Multi V Technology

    Always pleasant to use and highly efficient in a variety of environmentsAir conditioners must perform well in any kind of climate environment. Highly efficient heating and cooling system, Any where Any climate

    for Use

  • 8/10/2019 04_Multi_V_ENG

    20/44

    17

    Highest COP LevelWe have achieved the highest level of COP in the industry by optimizing the design of the heat exchanger for even distribution of the

    refrigerant, and by minutely controlling refrigerant with various sensors and electronic control.

    Heat RecoveryThe true worth of MULTI V three pipe system is evident during its simultaneous automatic operation of heating and cooling with 1 system.

    Wide Range of OperationThe MULTI V always provides safe heating and air conditioning, even when the indoor unit load varies severely between 10 and 130 percent

    of the outdoor unit's capacity, by employing a control algorithm that is distinctly different from other compressors.

    System ExpansionAfter completing installation of the MULTI V, if the indoor load changes so that it exceeds capacity, the system can easily be expanded by

    adding extra indoor and outdoor units with capacities between 5HP and 30HP.

    Inverter Driven Capacity Control

    10HPInverter Compressor

    CompressorCapacityControl

    NormalCompressor

    Large Load

    100%

    100%

    10%10%

    Small

    30 Hz - 120 Hz

    Out

    In

    Inverter Motor

    Inverter Compressor

  • 8/10/2019 04_Multi_V_ENG

    21/44

    Various Controllers of MULTI VThe MULTI V can be centrally controlled through the Internet without the need for additional servers through an interface between the

    Internet and an RS-485 communications network.

    LAN

    Remote Control PC

    -Direct access to internet without computer

    -Simple installation and operation using LAN cable

    and user friendly simple GUI

    -Remote control and monitoring by internet

    -Schedule timer

    -Individual or group control

    -Indoor unit max 256

    -Automatic upgrade of contents

    -Available Ethernet protocol BMS

    New Leader in Multi V Technology

    You can choose a control system exactly right for youIf your needs are different, then the solutions must be different. A new MULTI V control system to meet your needs !

    for Control

  • 8/10/2019 04_Multi_V_ENG

    22/44

    19

    Deluxe Central ControllerAnd especially, with an intuitively designed GUI and a user-friendly touch panel, you can simultaneously control up to 256 indoor units, and

    the system can be linked to the building management system.

    Simple Central ControllerFirst, We have a simple central controller that can operate up to 128 units simultaneously.

    - Indoor unit max 256

    - 8.0 TFT LCD (800*600)

    - Touch screen panel

    - Available Ethernet protocol

    - Time schedule function

    - Error display and lock function

    - Length max 1km

    - indoor unit max 16

    - individual or total control

    - Length max 1km

  • 8/10/2019 04_Multi_V_ENG

    23/44

    Indoor Unit Type7K 9K 12K 18K 24K 28K 36K 42K 48K

    Inverter short piping multi (For air cooling/heating)

    Wall Mounted Type

    Wall Mounted Type (ART COOL Mirror)

    Volume table of indoor unit

    New Leader in Multi V Technology

    Wall Mounted Type (ART COOL Wide)

    1-Way Cassette Type

    4-Way Cassette Type

    Wall Mounted Type (ART COOL)

  • 8/10/2019 04_Multi_V_ENG

    24/44

    21

    Indoor Unit Type7K 9K 12K 18K 24K 28K 36K 42K 48K

    Inverter short piping multi (For air cooling/heating)

    Ceiling Duct Type (High Static)

    Convertible Type

    Ceiling Duct Type (Low Static)

    Floor Standing (Slim)

    Floor Standing (Exposed)

  • 8/10/2019 04_Multi_V_ENG

    25/44

    Wall Mounted Type

    New Leader in Multi V Technology

    Mirror

    Wide

    CRNN076SU

    *0

    CRNN096SU*0CRNN126SU*0

    CRNN076SRA0

    CRNN096SRA0

    CRNN126SRA0CRNN186STA0

    CRNN096SP

    *0

    CRNN126SP*0CRNN186SV

    *0

    R : Mirror

    M : Metal

    B : Blue

    *

    D : Wood

    B : Blue

    M : Metal

    *

  • 8/10/2019 04_Multi_V_ENG

    26/44

    Rear Guide

    Stabilizer

    Cross Flow Fan

    Indoor unit

    Je t Cool

    Jet cool function is for quick cooling. In this mode, strong and cool air isblown at high speeds for 30 minutes until the room temperature reaches to

    18 C.

    6ms

    12ms

    Tempera ture Ga p

    1.7C

    1.3C

    Preference ofComfortable Feeling

    55%

    76%

    Cooling Speed

    7Min6Min

    Air-flowSpreading Area

    Auto SwingCHAOS Sw ing

    3.17m 2Improved

    80%1.76m 2

    Improved

    14%Improved38%

    Improved

    24%

    Healthy Dehumidification

    With the use of a newly designed compressor, humidity is eliminated tocreate a comfortable atmosphere without overcooling the room.

    Low Noise Air Flow System

    To provide a comfortable, pleasant, and well balanced environment, LG air

    conditioners utilize a streamlined air fan and a unique design which create

    smooth air flow from the air conditioner so that it operates under the lowest

    noise level. The cross flow fan, stabilizer, and rear guide which are the

    causes of noise, have been redesigned by hydraulic engineering.

    The number of revolutions has been decreased while increasing the amount

    of wind. With the best structure for the air path, the amount of friction has

    been decreased providing the most quiet air conditioners in the world.

    Natural breeze by CHAOS Swing

    The most pleasant air flow for the human body can be found within nature.

    Countless data and verification resulted in the application of the new CHAOS

    theory to LG Air conditioners. The new CHAOS theory is a technology that

    revives more natural air by controlling the angle and speed of the movement

    of the vane. Compared with the frequency, the CHAOS air flow proved to be

    very similar to natural air flow. The CHAOS swing also makes the room more

    evenly cooled to stimulate a more natural environment which is most

    comfortable for the human body.

    Auto Cleaning(Art Cool Only)

    Remove odor & Save time to clean-upAuto Clean helps to remove odor and save clean-up time. After using air-

    conditioner, Auto Clean makes the inner part of Air conditioner dry for 30

    min. It removes moisture and mould so you can enjoy odor-free air and save

    time to cleam up.

    After Cooling Operation, Start Auto-Clean

    automatically

    In 30 minutes Auto-Clean makes

    the inner part of Air conditioner be Dry

    23

    Wind-up Effects:

    The Wind-up Effect is controlled

    by the Vane Angle

    Control to evenly distribute nature-like air

    throughout the room.

    Up speed :12ms(Slow)Down speed :6ms(fast)

  • 8/10/2019 04_Multi_V_ENG

    27/44

    Ceiling Cassette Type

    New Leader in Multi V Technology

    CRNN076TCA0

    CRNN096TCA0

    CRNN126TCA0

    CRNN366TDA0CRNN126TEA0

    CRNN186TEA0

  • 8/10/2019 04_Multi_V_ENG

    28/44

    Indoor unit

    PLASMA Air Purifying System(Optional)

    The PLASMA Air Purifying System developed uniquely by LG not only removesmicroscopic contaminants and dust, but also removes house mites, pollen,

    and pet fur to help prevent allergic diseases like asthma. With a filter that

    can be used over and over again by simply washing with water, you can enjoy

    clean fresh air without having to worry about changing the filter every two

    years as in the past and save costs.

    5m

    1.5m

    36

    37

    40

    31

    28

    High-Ceiling corresponding operation

    According to the height of the ceiling, RPM of fan motor is selectable toincrease air reaching distance.

    Low Noise with 3-Dimensional Turbo FanAccording to the height of the ceiling, RPM of fan motor is selectable to

    increase air reaching distance.

    Dust Free! / Odor Free! / Allergy Free!

    Noise output measured in anechoic test room

    Air Velocity Distribution

    25

    2

    3.0General

    High Ceiling

    1

    2

    2.7

    1

    0 11 22 33 4 (M)4

    Hygienic and Easy-to-Clean Air Filter

    Easy Detachment Filter Long life Anti-Bacteria Filter

    Optimal Air Distribution

    Optimal air distribution with 4-way direcitional Air flow system.

    4-way Auto Swing

    Auto Changeover

    With heat pump model,Cooling and heating operation is changed

    automatically on the base of setting temp.

    Initial Setting Temp:18C:(Memory the final setting temp)

    Control of setting temp.

    -Wired Remoted Controller:18~30C

    -Reset Button in indoor unit: finally memorized temp.

    -Wireless Remoted Controller: 23~27C

  • 8/10/2019 04_Multi_V_ENG

    29/44

    Ceiling Concealed Duct Type

    New Leader in Multi V Technology

    CRNN186BHA0

    CRNN246BHA0

    CRNN076BNG0

    CRNN096BJG0

    CRNN126BJG0

  • 8/10/2019 04_Multi_V_ENG

    30/44

    Indoor unit

    Linear *E.S.P Control * E.S.P: External Static Pressure

    Always Air volume and sound kept as design regardless ofE.S.P change Using This Technology , You can

    - Optimize Duct work Installation

    - Keep Capacity & Sound level as desired

    - Simplify model numbers

    The Phase control motor Technology gives benefit of saving

    money to Installer .

    Desired Air Volume is obtained by controlling the Phase of Motor While

    installing the product and this makes your Duct Work system flexible E.S.P is

    controlled from 0 to 8~10mmAq, Linearly

    Two Thermistor Control

    The twin thermistor control regulates the difference between the indoor

    temperature and the temperature of the air the product produces, as to

    ensure uniform room temperature. This is accomplished by taking two

    temperatures, one for room and one for the air being discharged. Then the

    sensors readings are adjusted for optimum room temperature.

    Weekly Program

    If necessary, an operator can make an On/Off reservation of the product for a

    period of one week.

    Child Lock Function

    This function prevents children or others from tampering with the control

    buttons on the unit.

    It is then controlled by the remote controller.

    -All the buttons on indoor display panel will be locked.

    -The unit will be controlled only by remote controller.

    27

    2 4 6 8 10 12Static pressure(mmAq)

    Airvolume H

    ML

    H

    M

    L

    Air volumeat 10 mmAq

    Air volumeat 2 mmAq

    1 7035 140105 215175 245

    Airvolume

    Controller

    1 2 16

    Wired Remot e

    Controller

    GND

    Signal Line

    12V DC Powe r

    Group Control

    Operation SummaryWhere several products are linked, one specific control device can control a

    specific number of products.

    Specific Operation

    - Connecting line is linked to each of the indoor equipments

    forcommunication. A specific control device is connected to each of them and

    this control device can control the same function.

    - Group control function is enabled by cutting an optional jump wire in the

    wired remote control. At this time, the main system will not respond in order

    to prevent data collision.

    - While executing group control command, use the random data (0-3minutes)

    in the main body of indoor equipment for limiting starting current.

    - Control device can control up to 16 indoor equipments.

    Zero power consumption use in standby

    mode by adopting SMPS(Swiching Mode Power Supply)

    Power waste due to standby power

    - Power is wasted if a plug is connected to an outlet even though

    the appliance is turned off.

    Development of super power-saving SMPS

    (Swiching Mode Power Supply)

    - Zero standby power by reducing 90% of standby power.

    - No need to pull out every plug when appliance is not in use.

  • 8/10/2019 04_Multi_V_ENG

    31/44

    Ceiling and Floor Type

    New Leader in Multi V Technology

    CRNN186VBA0 CRNN076CAA0

    CRNN096CBA0

    CRNN126CCA0

    CRNN186CDA0

    CRNN246CEA0

  • 8/10/2019 04_Multi_V_ENG

    32/44

    21

    Indoor unit

    29

    Press Start/Stop Botton

    Select Auto Operation Mode

    Check the Room temperature

    Operation

    Are Automatically Decided By Fuzzy Rule.

    Intake-airTemperature Below 21 C

    Heating Soft Dry CoolingOperation Mode

    Over 21 C~Below 24 C Over 24 C

    Indoor Fan Speed

    Setting Temperature

    If initial mode is decided, that mode is continued without the room temperature changing.

    Tempera ture Ga p

    1.7C

    1.3C

    Preference ofComfortable Feeling

    55%

    76%

    Cooling Speed

    7Min6Min

    Air-flowSpreading Area

    Auto SwingCHAOS Swin g

    3.17m2Improved

    80%1.76m2

    Improved

    14%Improved38%

    Improved

    24%

    Auto Operation

    The operation procedure is as following.

    Natural breeze by CHAOS Swing

    The most pleasant air flow for the human body can be found within nature.

    Countless data and verification resulted in the application of the new CHAOS

    theory to LG Air conditioners.

    The new CHAOS theory is a technology that revives more natural air by

    controlling the angle and speed of the movement of the vane. Compared with

    the frequency, the CHAOS air flow proved to be very similar to natural air

    flow. The CHAOS swing also makes the room more evenly cooled to

    stimulate a more natural environment which is most comfortable for the

    human body.

    Horizontal

    D o w n w a r d

    Vertical Airflow Direction Control.

    Airflow Direction Control

    The airflow direction can be adjusted as desired by using the remote

    controller.

    This is effective when you want to cool yourself directly.

    Airflow Direction Control

    Horizontal Airflow Direction Control.Manual Control

    Adjust the horizontal airflow direction by manually moving the horizontal

    airflow direction louver by hand.

    Auto Restart Function

    In the event of sudden power failure, the auto start mechanism will

    restore the A/C to its previous setting when power returns.

    Sleep Mode Auto Control

    A touch of the Sleep Mode Button automatically programs the room air

    conditioner to turn off, controls the indoor fan speed, and adjusts the setting

    temperature to create a more comfortable sleep.

    Wind from conventional A/CWind from chaos A/C

  • 8/10/2019 04_Multi_V_ENG

    33/44

    Floor Standing Type

    New Leader in Multi V Technology

    CRNN286PKA0

  • 8/10/2019 04_Multi_V_ENG

    34/44

    Indoor unit

    PLASMA Air Purifying System (Optional)

    The PLASMA Air Purifying System within the air conditioner removesmicroscopic contaminants and dust to eliminate offensive odors and prevent

    allergic reactions. It can also be used as an air-purifying unit even though the

    air-cooling function is off.

    Neuro Fuzzy Control

    According to the temperature, air volume, and air velocity, the sensor will

    automatically operate to make the most pleasant atmosphere.

    31

    IonizerPro-filterDust part icles

    dustsOdour

    Dust electrode discharge

    Odor mo leculea lumimum coatedelectrode(-)(3.25KV discharge)

    Generatingplasma

    ++

    +

    +

    +

    Dusts Collector

    Polluted

    Air

    Purified

    fresh Air

    + 6.5KVdischarge

    Child Lock Function

    This function prevents children or others from tampering with the controlbuttons on the unit.

    It is then controlled by the remote controller.

    -All the buttons on indoor display panel will be locked.

    -The unit will be controlled only by remote controller.

    Anti-Bacteria Filter

    It removes dust in the air as well as bacteria proliferation, making the indoor

    atmosphere healthy.

    2-Way Auto Swing

    Hot or cold air can be evenly distributed throughout the room as the auto

    swing function blows air in 2 directions.

    Germ culture takenfrom unfiltered air

    Bacteria grows freely

    With normal filter

    Bacteria grows well

    With LG Bio filter

    98.5% Bacteria free

  • 8/10/2019 04_Multi_V_ENG

    35/44

    Remote Controller

    New Leader in Multi V Technology

    Deluxe Central Controller

    Simple Central Controller

    - Indoor unit max 256

    - 8.0 TFT LCD (800*600)

    - Touch screen panel

    - Available Ethernet protocol

    - Time schedule function

    - Error display and lock function

    - Length max 1km

    - indoor unit max 16

    - individual or total control

    - Length max 1km

    LCD Wired Remote Controller (Ceiling Cassette Type)

    24-Hour ON/ OFF Timer in 1 hour intervals

    TEST RUN Mode

    Self-Diagnosis function

    3-Step Fan Speed selection

    Operation Indication

    Room Temperature Display

    Only 20mm thick

    LCD Wired Remote Controller (Ceiling Duct Type)

    24-Hour ON/ OFF Timer in 1hour intervals

    TEST RUN Mode

    Self-Diagnosis function

    3-Step Fan Speed selection

    Operation Indication

    Room Temperature Display

    Only 20mm thick

    LCD Wireless Remote Controller

  • 8/10/2019 04_Multi_V_ENG

    36/44

  • 8/10/2019 04_Multi_V_ENG

    37/44

    Specifications

    New Leader in Multi V Technology

    Notes:1.Capacities are based on the following conditions:

    Cooling - Indoor temp. 27C(80.6F) DB/19C(66.2F) WB- Outdoor temp. 35C(95F) DB/24C(75.2F) WB- Interconnecting Piping Length 7.5m- Level Difference of Zero.

    Heating - Indoor temp. 20C(68F) DB/15C(59F) WB- Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB- Interconnecting Piping Length 7.5m- Level Difference of Zero.

    2.Capacities are Net Capacities.3.Due to our policy of innovation some specifications may be changed without notification.4.L.E.V.:Linear Expansion Valve5.To be added for more available Models

    CRUN458S0 CRUN1008T0

    13.0 28.0

    11,200 24,000

    44,000 95,500

    14.1 31.5

    12,091 27,080

    48,000 107,500

    WARM GRAY IVORY

    900*1,225*370 1,246*1,519*700

    35.43*48.42*13.57 49.07*58.84*27.56

    8.24 8.93

    10.00 10.24

    2.56 (2.08) 2.67 (2.25)

    2.93 (2.37) 3.00 (2.53)

    -5~43 / -10~16 -5 ~48 / -20 ~ 21

    JT100BEVYE JT100BEVTYE + JT212DATYE

    Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type

    53.4 53.4+117.3

    6,750 6,750, 3,450

    3.5 x 1 (3.5 + 3.75) x 1

    Direct on Line Direct on Line

    OBM-4012P2 ARE676E01

    Propeller Fan Propeller Fan

    84*2 271*2

    70 180

    2471 6354

    Capacitor Run Capacitor Run

    12.7(1/2) 15.88(5/8)

    19.05(3/4) 28.58(1 1/8)

    125 300

    57 60

    Deicer Deicer

    10~115 10~130

    R407C R408C

    3.5 10

    L.E.V. L.E.V.

    DAPHNE FVC68D DAPHNE FVC68D

    1,200 1,800

    3, 380~415, 50 3, 380~415, 50

    Model

    Cooling Capacity (kW)

    (kcal/h)

    (Btu/hr)

    Heating Capacity (kW)

    (kcal/h)

    (Btu/hr)

    Casing Color

    Dimensions (WxHxD) (mm)

    (inch)

    EER Cooling Btu/hrW

    Heating Btu/hrW

    COP Cooling W/W (kcal/hrW)

    Heating W/W (kcal/hrW)

    Setting temperature range(Cooling/Heating)

    Compressor Model

    Type

    Piston Displacement cm3/rev

    Number of Revolution r.p.m

    Motor Output x Number kW

    Starting Methed

    Fan Model

    Type

    Motor Output x Number W

    Air Flow Rate(High) cmm

    cfm

    Drive

    Pipe connections Liquid Side mm(inch)

    Gas Side mm(inch)

    Net Weight kg(lbs)

    Noise Level(Sound Press, 1m, H/L/M) dBA

    Safety Device

    Defrost Method

    Control range of capacity %

    Refrigerant Refrigerant Name

    Charge

    Control

    Refrigerant Oil Refrigerant Oil

    Charge Volume CC

    Power Supply ,V,Hz

    High Pressure Switch, Fan Motor Safety

    Thermostat, Inverter Overload Protector,

    Over Current Relay, Fusible Plugs, Fuse

    High Pressure Switch, Fan Motor Safety

    Thermostat, Inverter Overload Protector,

    Over Current Relay, Fusible Plugs, Fuse

    Conversion Formula

    kcal/h = kW x 860

    Btu/h = kW x 3414

    cfm = m3/min x 35.3

    Outdoor Unit

  • 8/10/2019 04_Multi_V_ENG

    38/44

    35

    Notes:1.Capacities are based on the following conditions:

    Cooling - Indoor temp. 27C(80.6F) DB/19C(66.2F) WB- Outdoor temp. 35C(95F) DB/24C(75.2F) WB- Interconnecting Piping Length 7.5m- Level Difference of Zero.

    Heating - Indoor temp. 20C(68F) DB/15C(59F) WB- Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB- Interconnecting Piping Length 7.5m- Level Difference of Zero.

    2.Capacities are Net Capacities.3.Due to our policy of innovation some specifications may be changed without notification.

    4.L.E.V.:Linear Expansion Valve5.To be added for more available Models

    CRNN076SRA0 CRNN096SRA0 CRNN126SRA0 CRNN186STA0 CRNN126SPA0

    2,100 2,600 3,500 5,300 3,500

    1,806 2,235 3,009 4,557 3,009

    7,165 8,871 11,942 18,084 11,942

    2,363 2,925 3,938 5,963 3,938

    2,031 2,515 3,385 5,127 3,385

    8,061 9,980 13,435 820,345 13,453

    900*285*156 900*285*156 900*285*156 1090*314*172 570*570*137

    35.4*11.2*6.1 35.4*11.2*6.1 35.4*11.2*6.1 42.9*12.4*6.8 22.4*22.4*5.4

    2*12*20 2*12*20 2*12*20 2*132*20 2*132*20

    1.0 1.0 1.2 2.2 1.5

    Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan Turbo Fan

    7.5 7.5 14.4 22 24

    5.6 6.0 9.5 13.5 8.7

    196 212 336 477 307

    Phase control Phase control Phase control Phase control Phase control

    Microprocessor, Thermostat for cooling and heating

    Foamed polystyrene Foamed polystyrene Foamed polystyrene Foamed polystyrene Foamed polystyrene

    Resin Net(Washable) Resin Net(Washable) Resin Net(Washable) Resin Net(Washable) (Washable)

    Fuse Fuse Fuse Fuse Fuse

    6.35 (1/4) 6.35 (1/4) 6.35 (1/4) 9.52(3/8) 6.35(1/4)

    12.7 (1/2) 12.7 (1/2) 12.7 (1/2) 15.88 (5/8) 12.7(1/2)

    25 25 25 25 12.2

    7(15.4) 7(15.4) 8(17.6) 12(26.5) 35(77.2)

    33 / 31 / 28 36 / 33 / 29 40 / 38 / 36 40 / 39 / 34 40/36/31

    1,220~240,50 1,220~240,50 1,220~240,50 1,220~240,50 1,220~240,50

    12:3*2.5 12:3*2.5 12:3*2.5 12:3*2.5 12:3*2.5

    L.E.V L.E.V L.E.V L.E.V L.E.V

    Model

    Cooling Capacity W

    kcal/h

    Btu/h

    Heating Capacity Kw

    kcal/h

    Btu/h

    Dimensions (W*H*D) mm

    inch

    Coil Rows x Steps x FPI mm

    Moisture removal l/h.

    Type

    Fan Motor Output x Number W

    Air Flow Rate(High) cmm

    cfm

    Drive

    Temperature Control

    Sound Absorbing Thermal Insulation Material

    Air Filter

    Safety Device

    Pipe Liquid Side mm(inch)

    Connections Gas Side mm(inch)

    Drain Pipe(Internal Dia.) mm

    Net Weight kg(lbs)

    Noise Level (Sound Press,1m, H/M/L) dB3

    Power Supply ,V,Hz

    Power Cable AWG#:P*mm2

    Refrigerant Control

    Conversion Formula

    kcal/h = kW x 860

    Btu/h = kW x 3414

    cfm = m3/min x 35.3

    Indoor unit | Wall Mounted Type

  • 8/10/2019 04_Multi_V_ENG

    39/44

    Specifications

    New Leader in Multi V Technology

    Notes:1.Capacities are based on the f ollowing conditions:

    Cooling - Indoor temp. 27C(80.6F) DB/19C(66.2F) WB- Outdoor temp. 35C(95F) DB/24C(75.2F) WB

    - Interconnecting Piping Length 7.5m- Level Difference of Zero.Heating - Indoor temp. 20C(68F) DB/15C(59F) WB

    - Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB- Interconnecting Piping Length 7.5m- Level Difference of Zero.

    2.Capacities are Net Capacities.3.Due to our policy of innovation some specifications may be changed without notification.4.L.E.V.:Linear Expansion Valve5.To be added for more available Models

    CRNN076TCA0 CRNN096TCA0 CRNN126TCA0

    2,100 2,600 3,500

    1,806 2,235 3,009

    7,165 8,871 11,942

    2,363 2,925 3,938

    2,031 2,515 3,385

    8,061 9,980 13,435

    Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate

    860*390*180 860*390*180 860*390*180

    33.8*15.3*7.0 33.8*15.3*7.0 33.8*15.3*7.0

    12 x 2 x 18 12 x 2 x 21 12 x 2 x 21

    1.0 1.0 1.5

    AMR-023E7 AMR-023E7 AMR-023E7

    Cross Flow Fan Cross Flow Fan Cross Flow Fan

    14 x 1 14 x 1 14 x 1

    6/5/4 7/6/5 10/9/8

    225/197/168 246/216/195 353/317/283

    Phase Control Phase Control Phase Control

    Microprocessor, Thermostat for cooling and heating

    Foamed polystyrene

    Fuse, Thermal Fuse for Fan Motor

    6.35 (1/4) 6.35 (1/4) 6.35 (1/4)

    12.7 (1/2) 12.7 (1/2) 12.7 (1/2)

    25 25 25

    17(37.5) 17(37.5) 17(37.5)

    35/32/29 37/34/31 39/36/35

    1,220~240,50 1,220~240,50 1,220~240,50

    12:3*2.5 12:3*2.5 12:3*2.5

    L.E.V L.E.V L.E.V

    1050*480*30 1050*480*30 1050*480*30

    41.3*18.9*1.2 41.3*18.9*1.2 41.3*18.9*1.2

    Model

    Cooling Capacity W

    kcal/h

    Btu/h

    Heating Capacity Kw

    kcal/h

    Btu/h

    Casing

    Dimensions (W*H*D) mm

    inch

    Coil Rows x Steps x FPI inch

    Moisture removal l/h.

    Fan Model

    Type

    Motor Output x Number W

    Air Flow Rate(H/M/L) cmm

    cfm

    Drive

    Temperature Control

    Sound Absorbing Thermal Insulation Material

    Safety Device

    Pipe Connections Liquid Side mm(inch)

    Gas Side mm(inch)

    Drain Pipe(Internal Dia.) mm

    Net Weight kg(lbs)

    Noise Level (Sound Press,1.5m, H/M/L) dB3

    Power Supply ,V,Hz

    Power Cable AWG#:P*mm2

    Refrigerant Control

    Decoration Panels Panel Color

    (Option) Dimensions (W*H*D) mm

    inch

    Conversion Formula

    kcal/h = kW x 860

    Btu/h = kW x 3414

    cfm = m3/min x 35.3

    Indoor unit | Ceiling Cassette Type

  • 8/10/2019 04_Multi_V_ENG

    40/44

    37

    Notes:1.Capacities are based on the following conditions:

    Cooling - Indoor temp. 27C(80.6F) DB/19C(66.2F) WB- Outdoor temp. 35C(95F) DB/24C(75.2F) WB

    - Interconnecting Piping Length 7.5m- Level Difference of Zero.Heating - Indoor temp. 20C(68F) DB/15C(59F) WB

    - Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB- Interconnecting Piping Length 7.5m- Level Difference of Zero.

    2.Capacities are Net Capacities.3.Due to our policy of innovation some specifications may be changed without notification.4.L.E.V.:Linear Expansion Valve5.To be added for more available Models

    CRNN126TEA0 CRNN186TEA0 CRNN366TD0

    3,500 5,300 10,600

    3,009 4,557 9,114

    11,942 18,084 36,168

    3,938 5,963 11,925

    3,385 5,127 10,253

    13,435 20,345 40,689

    Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate

    570*570*269 570*570*269 840*840*288

    22.4*22.4*10.5 22.4*22.4*10.5 33.0*33.0*11.3

    2*11*19 2*11*19 2*12*21

    1.0 1.9 4.0

    IC-9630LGAC IC-9630LGAC IC-1630LGPJ

    Turbo Fan Turbo Fan Turbo Fan

    20 22.4 52.5

    11 / 10 / 9 13 / 12 / 10 25 / 23 / 21

    388/353/318 459/423/353 883/812/742

    Phase control Phase control Phase control

    Microprocessor, Thermostat for cooling and heating

    Foamed polystyrene Foamed polystyrene Foamed polystyrene

    Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor

    6.35 (1/4) 9.52 (3/8) 9.52 (3/8)

    12.7 (1/2) 15.88 (5/8) 19.05 (3/4)

    25 25 25

    19(41.9) 19(41.9) 32(70.5)

    38/35/32 41 / 39 / 37 40 / 38 / 36

    1,220~240,50 1,220~240,50 1,220~240,50

    12:3*2.5 12:3*2.5 12:3*2.5

    L.E.V L.E.V L.E.V

    White White White

    670*670*30 670*670*30 950*950*30

    26.4*26.4*1.2 26.4*26.4*1.2 37.4*37.4*1.2

    Model

    Cooling Capacity W

    kcal/h

    Btu/h

    Heating Capacity Kw

    kcal/h

    Btu/h

    Casing

    Dimensions (W*H*D) mm

    inch

    Coil Rows x Steps x FPI inch

    Moisture removal l/h.

    Fan Model

    Type

    Motor Output x Number W

    Air Flow Rate(H/M/L) cmm

    cfm

    Drive

    Temperature Control

    Sound Absorbing Thermal Insulation Material

    Safety Device

    Pipe Connections Liquid Side mm(inch)

    Gas Side mm(inch)

    Drain Pipe(Internal Dia.) mm

    Net Weight kg(lbs)

    Noise Level (Sound Press,1.5m, H/M/L) dB3

    Power Supply ,V,Hz

    Power Cable AWG#:P*mm2

    Refrigerant Control

    Decoration Panels Panel Color

    (Option) Dimensions (W*H*D) mm

    inch

    Conversion Formula

    kcal/h = kW x 860

    Btu/h = kW x 3414

    cfm = m3/min x 35.3

    Indoor unit | Ceiling Cassette Type

  • 8/10/2019 04_Multi_V_ENG

    41/44

    Specifications

    New Leader in Multi V Technology

    Notes:1.Capacities are based on the f ollowing conditions:

    Cooling - Indoor temp. 27C(80.6F) DB/19C(66.2F) WB- Outdoor temp. 35C(95F) DB/24C(75.2F) WB- Interconnecting Piping Length 7.5m- Level Difference of Zero.

    Heating - Indoor temp. 20C(68F) DB/15C(59F) WB- Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB- Interconnecting Piping Length 7.5m- Level Difference of Zero.

    2.Capacities are Net Capacities.3.Due to our policy of innovation some specifications may be changed without notification.4.L.E.V.:Linear Expansion Valve5.To be added for more available Models

    CRNN186BHA0 CRNN246BHA0

    5,300 7,000

    4,557 6,019

    18,084 23,885

    5,963 7,875

    5,127 6,771

    20,345 26,870

    Galvanized Steel Plate Galvanized Steel Plate

    880*260*450 880*260*450

    34.6*10.2*17.7 34.6*10.2*17.7

    2*10*21 3*10*21

    2.0 2.5

    IC-13450LG13C IC-13450LG13C

    Sirocco Fan Sirocco Fan

    118 118

    16.5 / 14.5 / 13 18 / 16.5 / 14

    583 / 512 / 459 636 / 583 / 494

    78.5 78.5

    Phase control Phase control

    Microprocessor, Thermostat for cooling and heating

    Foamed polystyrene Foamed polystyrene

    Accossory Accossory

    Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor

    9.52 (3/8) 9.52 (3/8)

    15.88 (5/8) 15.88 (5/8)

    25 25

    34(74.9) 35(77.2)

    36 / 34 / 32 48 / 45 / 32

    1,220~240,50 1,220~240,50

    12:3*2.5 12:3*2.5

    L.E.V L.E.V

    Model

    Cooling Capacity W

    kcal/h

    Btu/h

    Heating Capacity Kw

    kcal/h

    Btu/h

    Casing

    Dimensions (W*H*D) mm

    inch

    Coil Rows x Steps x FPI inch

    Moisture removal l/h.

    Model

    Type

    Fan Motor Output x Number W

    Air Flow Rate(H/M/L) cmm

    cfm

    External Static Pressure Pa

    Drive

    Temperature Control

    Sound Absorbing Thermal Insulation Material

    Air Filter

    Safety Device

    Liquid Side mm(inch)

    Pipe Connections Gas Side mm(inch)

    Drain Pipe(Internal Dia. ) mm

    Net Weight kg(lbs)

    Noise Level (Sound Press,1.5m, H/M/L) dB3

    Power Supply ,V,Hz

    Power Cable AWG#:P*mm2

    Refrigerant Control

    Conversion Formula

    kcal/h = kW x 860

    Btu/h = kW x 3414

    cfm = m3/min x 35.3

    Indoor unit | Ceiling Concealed Duct Type

  • 8/10/2019 04_Multi_V_ENG

    42/44

    39

    Notes:1.Capacities are based on the following conditions:

    Cooling - Indoor temp. 27C(80.6F) DB/19C(66.2F) WB- Outdoor temp. 35C(95F) DB/24C(75.2F) WB- Interconnecting Piping Length 7.5m- Level Difference of Zero.

    Heating - Indoor temp. 20C(68F) DB/15C(59F) WB- Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB- Interconnecting Piping Length 7.5m- Level Difference of Zero.

    2.Capacities are Net Capacities.3.Due to our policy of innovation some specifications may be changed without notification.4.L.E.V.:Linear Expansion Valve5.To be added for more available Models

    CRNN076BNG0 CRNN096BJG0 CRNN126BJG0

    2,100 2,600 3,500

    1,806 2,235 3,009

    7,165 8,871 11,942

    2,363 2,925 3,938

    2,031 2,515 3,385

    8,061 9,980 13,435

    Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate

    783*220*520 873*220*520 873*220*520

    30.8*8.7*20.5 34.4*8.7*20.5 34.4*8.7*20.5

    0.375(9.52) 0.375(9.52) 0.375(9.52)

    14 14 14

    D-7K D-9K D-12K

    Condenser inducted Condenser inducted Condenser inducted

    Sirocco Fan Sirocco Fan Sirocco Fan

    1/150 1/150 2/150

    3 3 3

    730/670/620 590/540/510 810/720/650

    Thermistor

    6.4/6.0/5.4 7.0/6.5/6.0 10.2/9.2/8.2

    6.35 (1/4) 6.35 (1/4) 6.35 (1/4)

    12.7 (1/2) 12.7 (1/2) 12.7 (1/2)

    25 25 25

    30 30 30

    24(52.9) 26(57.3) 26(57.3)

    36/34/32 37/35/33 38/36/34

    1,230,50 1,230,50 1,230,50

    L.E.V L.E.V L.E.V

    R407C R407C R407C

    783*220*520 873*220*520 873*220*520

    30.8*8.7*20.5 34.3*8.7*20.5 34.3*8.7*20.5

    Model

    Cooling Capacity W

    kcal/h

    Btu/h

    Heating Capacity W

    kcal/h

    Btu/h

    Casing

    Dimensions (W*H*D) mm

    inch

    Indoor Coil Tube Size(OD) inch(mm)

    Fins per inch

    Indoor Fan Model

    motor Type

    Indoor Fan Type

    No. Used/Diameter EA/(mm)

    Motor Step

    Indoor Fan RPM Indoor (H/M/L)

    Temperature Controller

    Air Circulation CMM(CFM)

    Pipe Connections Liquid Side mm(inch)

    Gas Side mm(inch)

    Drain Hose In diameter mm

    Out diameter mm

    Net Weight kg(lbs)

    Noise Level (Sound Press,1m, H/M/L) dB3

    Power Supply ,V,Hz

    Refrigerant Control

    Refrigerant Charge type

    Dimensions (W*H*D) mm

    inch

    Conversion Formula

    kcal/h = kW x 860

    Btu/h = kW x 3414

    cfm = m3/min x 35.3

    Indoor unit | Ceiling Concealed Duct Type

  • 8/10/2019 04_Multi_V_ENG

    43/44

    Specifications

    New Leader in Multi V Technology

    Notes:1.Capacities are based on the f ollowing conditions:

    Cooling - Indoor temp. 27C(80.6F) DB/19C(66.2F) WB- Outdoor temp. 35C(95F) DB/24C(75.2F) WB- Interconnecting Piping Length 7.5m- Level Difference of Zero.

    Heating - Indoor temp. 20C(68F) DB/15C(59F) WB- Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB

    - Interconnecting Piping Length 7.5m- Level Difference of Zero.

    2.Capacities are Net Capacities.3.Due to our policy of innovation some specifications may be changed without notification.4.L.E.V.:Linear Expansion Valve5.To be added for more available Models

    CRNN186VBA0

    5,300

    4,557

    18,084

    5,963

    5,127

    20,345

    White

    1200*615*205

    47.24*24.21*8.07

    2*12*18

    2.5

    IC-9430LGCG

    Cross Flow Fan

    30

    13.5

    477

    Phase control

    Microprocessor, Thermostat for cooling and heating

    Foamed polystyrene

    Accossory

    Fuse, Thermal Fuse for Fan Motor

    9.52 (3/8)

    15.88 (5/8)

    17

    30(66.1)

    43 / 40 / 37

    1,220~240,50

    12:3*2.5

    L.E.V

    Model

    Cooling Capacity W

    kcal/h

    Btu/h

    Heating Capacity Kw

    kcal/h

    Btu/h

    Casing

    Dimensions (W*H*D) mm

    inch

    Coil Rows x Steps x FPI inch

    Moisture removal l/h.

    Model

    Type

    Fan Motor Output x Number W

    Air Flow Rate(High) cmm

    cfm

    Drive

    Temperature Control

    Sound Absorbing Thermal Insulation Material

    Air Filter

    Safety Device

    Liquid Side mm(inch)

    Pipe Connections Gas Side mm(inch)

    Drain Pipe(Internal Dia.) mm

    Net Weight kg(lbs)

    Noise Level (Sound Press,1.5m, H/M/L) dB3

    Power Supply ,V,Hz

    Power Cable AWG#:P*mm2

    Refrigerant Control

    Conversion Formula

    kcal/h = kW x 860

    Btu/h = kW x 3414

    cfm = m3/min x 35.3

    Indoor unit | Ceiling and Floor Type

  • 8/10/2019 04_Multi_V_ENG

    44/44

    Notes:1.Capacities are based on the following conditions:

    Cooling - Indoor temp. 27C(80.6F) DB/19C(66.2F) WB- Outdoor temp. 35C(95F) DB/24C(75.2F) WB- Interconnecting Piping Length 7.5m- Level Difference of Zero.

    Heating - Indoor temp. 20C(68F) DB/15C(59F) WB- Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB- Interconnecting Piping Length 7.5m- Level Difference of Zero.

    2.Capacities are Net Capacities.3.Due to our policy of innovation some specifications may be changed without notification.4.L.E.V.:Linear Expansion Valve5.To be added for more available Models

    CRNN076CAA0

    2,100

    1,806

    7,165

    2,363

    2,031

    8,061

    1050*620*218

    41.3*24.4*8.6

    0.375(9.52)

    14

    Condenser inducted

    Blower

    2/150

    3

    -

    Thermistor

    6.4/5.9/5.4

    6.35 (1/4)

    12.7 (1/2)

    15

    22(48.5)

    36/34/32

    1,230,50

    L.E.V

    R407C

    1050*620*218

    41.3*24.4*8.6

    CRNN096CAA0

    2,600

    2,235

    8,871

    2,925

    2,515

    9,980

    1170*620*218

    46.1*24.4*8.6

    0.375(9.52)

    14

    Condenser inducted

    Blower

    2/150

    3

    -

    Thermistor

    7.0/6.5/6.0

    6.35 (1/4)

    12.7 (1/2)

    15

    25(55.1)

    36/34/32

    1,230,50

    L.E.V

    R407C

    1050*620*218

    41.3*24.4*8.6

    CRNN126CAA0

    3,500

    3,009

    11,942

    3,938

    3,385

    13,435

    1170*620*218

    46.1*24.4*8.6

    0.375(9.52)

    14

    Condenser inducted

    Blower

    2/150

    3

    -

    Thermistor

    10.2/9.2/8.2

    6.35 (1/4)

    12.7 (1/2)

    15

    25(55.1)

    37/35/34

    1,230,50

    L.E.V

    R407C

    1050*620*218

    41.3*24.4*8.6

    CRNN186CAA0

    5,300

    4,557

    18,084

    5,963

    5,127

    20,345

    1410*620*218

    55.5*24.4*8.6

    0.375(9.52)

    14

    Condenser inducted

    Blower

    3/150

    3

    -

    Thermistor

    11.9/10.5/9.2

    9.52 (3/8)

    15.88 (5/8)

    15

    27.5(60.6)

    38/36/35

    1,230,50

    L.E.V

    R407C

    1410*620*218

    55.5*24.4*8.6

    CRNN246CAA0

    7,000

    6,019

    23,885

    7,875

    6,771

    26,870

    1530*620*218

    60.2*24.4*8.6

    0.375(9.52)

    14

    Condenser inducted

    Blower

    3/150

    3

    -

    Thermistor

    13.2/11.7/10.2

    9.52 (3/8)

    15.88 (5/8)

    15

    32.5(71.7)

    40/38/36

    1,230,50

    L.E.V

    R407C

    1530*620*218

    60.2*24.4*8.6

    Model

    Cooling Capacity W

    kcal/h

    Btu/h

    Heating Capacity W

    kcal/h

    Btu/h

    Casing

    Dimensions (W*H*D) mm

    inch

    Indoor Coil Tube Size(OD) inch(mm)

    Fins per inch

    Indoor Fan Model

    motor Type

    Indoor Fan Type

    No. Used/Diameter EA/(mm)

    Motor Step

    Indoor Fan RPM Indoor (H/M/L)

    Temperature Controller

    Air Circulation CMM(CFM)

    Pipe Connections Liquid Side mm(inch)

    Gas Side mm(inch)

    Drain Hose In diameter mm

    Out diameter mm

    Net Weight kg(lbs)

    Noise Level (Sound Press,1m, H/M/L) dB3

    Power Supply ,V,Hz

    Refrigerant Control

    Refrigerant Charge type

    Dimensions (W*H*D) mm

    inch

    Conversion Formula

    kcal/h = kW x 860

    Btu/h = kW x 3414

    cfm = m3/min x 35.3

    Indoor unit | Floor Standing(exposed) Type