Operators manual
Transformer protection IED RET 670
Innovation from ABB
7/28/2019 OM RET 670
2/132
Copyright 2007 ABB. All rights reserved.
Operator's manualTransformer protection IED
RET 670
About this manual
Document No: 1MRK 504 087-UENIssued: March 2007Product version: 1.1
Revision:
7/28/2019 OM RET 670
3/132
COPYRIGHT
WE RESERVE ALL RIGHTS TO THIS DOCUMENT, EVEN IN THE EVENT THAT A PATENT IS
ISSUED AND A DIFFERENT COMMERCIAL PROPRIETARY RIGHT IS REGISTERED. IMPROPER
USE, IN PARTICULAR REPRODUCTION AND DISSEMINATION TO THIRD PARTIES, IS NOT
PERMITTED.
THIS DOCUMENT HAS BEEN CAREFULLY CHECKED. HOWEVER, IN CASE ANY ERRORS ARE
DETECTED, THE READER IS KINDLY REQUESTED TO NOTIFY THE MANUFACTURER AT THE
ADDRESS BELOW.
THE DATA CONTAINED IN THIS MANUAL IS INTENDED SOLELY FOR THE CONCEPT OR
PRODUCT DESCRIPTION AND IS NOT TO BE DEEMED TO BE A STATEMENT OF GUARAN-
TEED PROPERTIES. IN THE INTERESTS OF OUR CUSTOMERS, WE CONSTANTLY SEEK TO
ENSURE THAT OUR PRODUCTS ARE DEVELOPED TO THE LATEST TECHNOLOGICAL STAN-
DARDS. AS A RESULT, IT IS POSSIBLE THAT THERE MAY BE SOME DIFFERENCES BETWEENTHE HW/SW PRODUCT AND THIS INFORMATION PRODUCT.
Manufacturer:
ABB ABSubstation Automation ProductsSE-721 59 VstersSwedenTelephone: +46 (0) 21 34 20 00Facsimile: +46 (0) 21 14 69 18www.abb.com/substationautomation
7/28/2019 OM RET 670
4/132
Contents
PageChapter
Chapter 1 Introduction ..................................................................... 1
Introduction to the operators manual .................................................. 2About the complete set of manuals for an IED ............................... 2About the operators manual .......................................................... 3Intended audience.......................................................................... 3
General...................................................................................... 3Requirement.............................................................................. 3
Related documents......................................................................... 4Revision notes ................................................................................ 5
Chapter 2 Safety information........................................................... 7
Warnings.............................................................................................. 8
Chapter 3 Overview .......................................................................... 9
Operator overview ............................................................................. 10Identify the IED .................................................................................. 11
Chapter 4 Understand the local human-machine interface ........ 13
Overview............................................................................................ 14Keypad............................................................................................... 15Key activated screens........................................................................ 17
The Help screen ........................................................................... 17The Reset screen ......................................................................... 17
LCD.................................................................................................... 18Small............................................................................................. 18Medium......................................................................................... 18
LED.................................................................................................... 19Status indication LEDs ................................................................. 19Indication LEDs ............................................................................ 19
LHMI setup and test screen............................................................... 21How to navigate................................................................................. 22
Read............................................................................................. 22Change ........................................................................................ 22Control.......................................................................................... 22
Chapter 5 Understand the HMI tree............................................... 25
Overview............................................................................................ 26
7/28/2019 OM RET 670
5/132
Contents
Menu-tree for RET 670................................................................. 26
Chapter 6 Read measured values .................................................29
Overview............................................................................................ 30View analog primary values............................................................... 31
Overview....................................................................................... 31View analog secondary values .......................................................... 32
Overview....................................................................................... 32View analog mean values.................................................................. 33
Overview....................................................................................... 33mA input module (MIM) ........................................................... 33Signal matrix for mA inputs (SMMI)......................................... 33
View monitoring values...................................................................... 34Service values .............................................................................. 34Current phasors............................................................................ 34Voltage phasors............................................................................ 34Current sequence component ...................................................... 34Voltage sequence component...................................................... 34
Three phase busbar protection (zone A) ...................................... 35Three phase busbar protection (Zone B)...................................... 35Single phase busbar protection (Zone A) ..................................... 35Single phase busbar protection (Zone B) ..................................... 35
View metering values......................................................................... 36
Chapter 7 Event l is t ........................................................................ 37
View events ....................................................................................... 38Overview....................................................................................... 38
Chapter 8 Handle disturbances ..................................................... 39
Identify a disturbance......................................................................... 40View disturbance record details......................................................... 41
View general information.............................................................. 41View disturbance indications ........................................................ 41
View event recordings .................................................................. 41View trip values............................................................................. 41Trigger a disturbance report manually............................................... 42
Chapter 9 Read and change settings............................................ 43
System time and synchronization...................................................... 44System time.................................................................................. 44
Time synchronization.................................................................... 44Overview.................................................................................. 44
TimeSynch............................................................................... 44
7/28/2019 OM RET 670
6/132
Contents
TimeSynchBIN......................................................................... 44TimeSynchSNTP ..................................................................... 44TimeSynchDSTBegin.............................................................. 44
TimeSynchDSTEnd................................................................. 44TimeZone ................................................................................ 45TimeSynch IRIG-B................................................................... 45
General settings................................................................................. 46Power system............................................................................... 46
Overview.................................................................................. 46Identifiers................................................................................. 46Primary values......................................................................... 46
Communication............................................................................. 46Overview.................................................................................. 46
TCP-IP .................................................................................... 46SPA, LON and IEC 608705103 settings.............................. 47LDCM ...................................................................................... 48
Station communication............................................................ 48Analog modules............................................................................ 49
Overview.................................................................................. 49Analog modules....................................................................... 50I/O modules ............................................................................. 50
HMI............................................................................................... 50Overview.................................................................................. 50LEDs........................................................................................ 51Screen .................................................................................... 51Functions................................................................................. 51Change lock............................................................................. 51
Differential protection.................................................................... 51
Overview.................................................................................. 51Transformer differential protection,two winding(PDIF, 87T) ............................................. 51
Transformer differentialprotection, three winding (PDIF, 87T) ........................... 52
Control.......................................................................................... 52Overview.................................................................................. 52Bay control (CBAY) ................................................................. 52Reservation input .................................................................... 52Bay reserve (CRSV)................................................................ 52Switch controller (CSWI) ......................................................... 52Circuit breaker (XCBR)............................................................ 53Circuit switch (XSWI)............................................................... 53Local/Remote switch (LocalRemote, LocRemControl)............ 53
Control commands ....................................................................... 53Single command...................................................................... 53Logic rotating switch (GGIO) ................................................... 53Selector mini switch (GGIO).................................................... 53
Tap changer control and supervision (YLTC, 84) .............. 54Tap changer control and supervision (YLTC, 84).................... 54Automatic voltage control for tapchanger (ATCC, 90) ....... 54Automatic voltage control for tapchanger (ATCC, 90) ....... 54
Monitoring..................................................................................... 54Overview.................................................................................. 54Measurements (MMXU) .......................................................... 54
7/28/2019 OM RET 670
7/132
Contents
Current phasors....................................................................... 54Voltage phasors....................................................................... 55Current sequence components (MSQI)................................... 55Voltage sequence components (MSQI)...................................55Disturbance report (RDRE)...................................................... 55Binary signals .......................................................................... 55Analog signals ......................................................................... 56Generic measured value ......................................................... 56Event function.......................................................................... 56Local signal status report......................................................... 56IEC 608705103.................................................................... 56
Metering........................................................................................ 56Overview.................................................................................. 56Pulse counter logic (GGIO)...................................................... 57Function for energy calculation anddemand handling (MMTR) ................................................. 57
Setting group N.................................................................................. 58Overview....................................................................................... 58Differential protection.................................................................... 58
Overview.................................................................................. 58Transformer differential protection,two winding(PDIF, 87T) .............................................. 58
Transformer differential protection,three winding(PDIF, 87T) ............................................ 58Restricted earth fault protection (PDIF, 87N)........................... 58High impedance differential protection (PDIF, 87X) ................ 59
Impedance protection................................................................... 59Overview.................................................................................. 59
Distance protection zones, quadrilateralcharacteristics (PDIS, 21) .................................................. 59Phase selection with load encroachment,quadrilateral characteristics (PDIS, 21) ............................. 59Faulty phase identification with loadenchroachment (PDIS, 21) .................................................. 59Directional impedance, quadrilateral (RDIR)...........................59Directional impedance element for mhocharacteristics (RDIR Directional impedancemho) ............ 59Power swing detection (RPSB, 78).......................................... 60Full-scheme distance protection,mho characteristic (PDIS, 21) ............................................ 60Additional distance protection directional function
for earth faults (RDIR) ......................................................... 60Mho impedance supervision logic (GAPC).............................. 60Full-scheme distance protection,quadrilateral for mho (PDIS, 21) ......................................... 60Power swing logic (RPSL) ....................................................... 60
Current protection......................................................................... 60Overview.................................................................................. 60Instantaneous phase overcurrent protection (PIOC, 50) ......... 61Four step phase overcurrent protection (PTOC, 51/67).......... 61Instantaneous residual overcurrent protection (PIOC, 50N).... 61Four step residual overcurrent protection (PTOC, 51N/67N) ..61
Thermal overload protection,
7/28/2019 OM RET 670
8/132
Contents
two time constants (PTTR, 49) ..................................... 61Breaker failure protection (RBRF, 50BF)................................. 61Pole discordance protection (RPLD, 52PD) ............................ 62
Broken conductor check (PTOC, 46)....................................... 62Directional over-power protection (PDOP, 32) ........................ 62Directional under-power protection (PDUP, 37) ...................... 62Sensitive directional residual over current andpower protection (PSDE, 67N) ............................................ 62
Voltage protection......................................................................... 62Overview.................................................................................. 62
Two step undervoltage protection (PTUV, 27) ........................ 62Two step overvoltage protection (PTOV, 59) .......................... 63Two step residual overvoltage protection (PTOV, 59N) .......... 63Overexcitation protection (PVPH, 24)...................................... 63Loss of voltage check (PTUV 27)............................................ 63Voltage differential protection (PTOV 60)................................ 63
Frequency protection.................................................................... 63Overview.................................................................................. 63Underfrequency protection (PTUF, 81) ................................... 63Overfrequency protection (PTOF, 81) ..................................... 64Rate-of-change frequency protection (PFRC, 81)................... 64
Multipurpose protection ................................................................ 64Overview.................................................................................. 64General current and voltage protection (GAPC)...................... 64
Secondary system supervision..................................................... 64Overview.................................................................................. 64Current circuit supervision (RDIF) ........................................... 65Fuse failure supervision (RFUF).............................................. 65
Control.......................................................................................... 65Overview.................................................................................. 65Synchrocheck and energizing check (RSYN, 25).................... 65Logic rotating switch (GGIO) ................................................... 65
Tap changer control andsupervision, 6 binary inputs (YLTC, 84) ............................ 65
Tap changer control and supervision,32 binary inputs (YLTC, 84) ............................................... 66Automatic voltage control for tapchanger,single control (ATCC, 90) .................................................. 66Automatic voltage control for tapchanger,parallel control (ATCC, 90) ................................................ 66
Scheme communication ............................................................... 66Overview.................................................................................. 66Scheme communication logicfor residual overcurrentprotection (PSCH, 85) ....................... 66Current reversal and weak-end infeed logicfor residual overcurrentprotection (PSCH, 85) ....................... 66
Logic ............................................................................................. 66Overview.................................................................................. 66
Tripping logic (PTRC, 94)........................................................ 67Trip matrix logic (GGIO, 94) .................................................... 67LogicGate ................................................................................ 67LogicSRMemory...................................................................... 67LogicTimerSet ......................................................................... 67
7/28/2019 OM RET 670
9/132
Contents
Monitoring..................................................................................... 67Overview.................................................................................. 67Event counter (GGIO).............................................................. 67
Activate setting group ........................................................................ 68Language........................................................................................... 69
Chapter 10 Diagnose IED status...................................................... 71
Find cause of internal failure.............................................................. 72Read internal events..................................................................... 72Find available functions ................................................................ 72
Chapter 11 Test the IED.................................................................... 73
Overview............................................................................................ 74IED test mode.................................................................................... 76View binary input values .................................................................... 77
Overview....................................................................................... 77Binary Input Module (BIM)....................................................... 77Signal matrix for binary input (SMBI)....................................... 77
View binary output values.................................................................. 78Overview....................................................................................... 78
Binary Output Module (BOM) .................................................. 78Signal matrix for binary outputs (SMBO) .................................78
Function test modes .......................................................................... 79
Overview....................................................................................... 79Differential protection.................................................................... 79Impedance protection................................................................... 79Current protection......................................................................... 79Voltage protection......................................................................... 79Frequency protection.................................................................... 79Multipurpose protection ................................................................ 80Scheme communication ............................................................... 80Secondary system protection ....................................................... 80Control.......................................................................................... 80Monitoring..................................................................................... 80Logic............................................................................................. 80
Function status .................................................................................. 81
Overview....................................................................................... 81View differential protection values ................................................ 81
Transformer differential protection,two winding(PDIF, 87T) .............................................. 81
Transformer differential protection,three winding(PDIF, 87T) ........................................... 81Restricted earth fault protection, low impedance (PDIF, 87N). 81High impedance differential protection (PDIF, 87)................... 81
Impedance protection .................................................................. 82Phase selection with load encroachment (PDIS, 21)............... 82Distance protection zones (PDIS, 21)...................................... 82Directional impedance (RDIR)................................................. 82
7/28/2019 OM RET 670
10/132
Contents
Power swing detection (RPSB, 78) ......................................... 82Full-scheme distance protection, mhocharacteristic (PDIS, 21) ..................................................... 82
Additional distance protection directional function forearth faults (RDIR) .............................................................. 82Mho Impedance supervision logic (GAPC).............................. 82Power swing logic (RPSL)....................................................... 83Full-scheme distance protection, quadrilateralfor mho (PDIS, 21) .............................................................. 83
Current protection......................................................................... 83Instantaneous phase overcurrent protection (PIOC, 50)......... 83Four step phase overcurrent protection (PTOC, 51/67) .......... 83Instantaneous residual overcurrent protection (PIOC, 50N).... 83Four step residual overcurrent protection (PTOC, 51N/67N) ..83
Thermal overload protection,two time constants (PTTR, 49) ................................... 84
Breaker failure protection (RBRF, 50BF)................................. 84Pole discordance protection (RPLD, 52PD) ............................ 84Sensitive directional residual over current andpower protection (PSDE, 67N) ........................................... 84Directional under-power protection (PDUP, 37) ...................... 84Directional over-power protection (PDOP, 32) ........................ 84Broken conductor check (PTOC, 46)....................................... 84
Voltage protection......................................................................... 84Two step undervoltage protection (PTUV, 59N)...................... 85Two step overvoltage protection (PTOV, 59) .......................... 85Two step residual overvoltage protection (PTOV, 59N) .......... 85Overexcitation protection (PVPH, 24)...................................... 85
Loss of voltage check.............................................................. 85Voltage differential protection (PTOV, 60)............................... 85View scheme communication values............................................ 85
Scheme communication logicfor residual overcurrentprotection (PSCH, 85) ....................... 85Current reversal and weak-end infeed logicfor residual overcurrentprotection (PSCH, 85) ....................... 86
View frequency protection values................................................. 86Underfrequency protection (PTUF, 81) ................................... 86Overfrequency protection (PTOF, 81) ..................................... 86Rate-of-change frequency protection (PFRC, 81)................... 86
Multipurpose protection ................................................................ 86General current and voltage protection (PGPF)...................... 87
Secondary system supervision..................................................... 87Current circuit supervision (RDIF) ........................................... 87Fuse failure supervision (RFUF).............................................. 87
Control.......................................................................................... 87Synchrocheck and energizing check (RSYN, 25).................... 87
Apparatus control (APC)............................................................... 88Interlocking.............................................................................. 88Interlock busbar earth switch................................................... 88Interlock bus section breaker................................................... 88Interlock bus section disconnect.............................................. 88Interlock bus coupler bay......................................................... 88Interlock, one and a half circuit breaker connection ................ 88
7/28/2019 OM RET 670
11/132
Contents
Interlock, one and a half circuit breaker line A......................... 89Interlock one and a half circuit breaker line B.......................... 89Interlock, double circuit breaker bus A..................................... 89Interlock, double circuit breaker bus B..................................... 89Interlock, double circuit breaker line........................................ 89Interlock line bay...................................................................... 89Interlock, transformer bay........................................................ 90Bay reserve ............................................................................. 90
Commands ................................................................................... 90Single command...................................................................... 90Selector switch ........................................................................ 90IEC608705103..................................................................... 90Automation bits, command function forDNP3.0 (AutomationBits) ................................................... 91Selector mini switch (GGIO) .................................................... 91
Logic............................................................................................. 91
Tripping logic (PTRC, 94)........................................................ 91Event counter .......................................................................... 91
Trip matrix logic (GGIO, 94X).................................................. 91Logic gate................................................................................ 91Logic SR memory.................................................................... 92Logic timer set ......................................................................... 92Boolean 16 to Integer conversion ........................................... 92Integer to Boolean 16 conversion............................................ 92
Monitoring..................................................................................... 92Disturbance report (RDRE)...................................................... 92Generic measured value (GGIO)............................................. 93Measured value expander block.............................................. 93
LEDs........................................................................................ 93Global positioning system........................................................ 93Binary signal status report....................................................... 93Event counter (GGIO).............................................................. 93IEC61850 generic communication I/O functions16 inputs (GGIO) ................................................................ 93IEC61850 generic communication I/O functions (GGIO)......... 94IEC61850 generic communication I/O functions (GGIO)......... 94
Metering........................................................................................ 94Pulse counter logic (GGIO)...................................................... 94
Communications........................................................................... 94Remote communication........................................................... 94View station communication values......................................... 94
View setting groups ...................................................................... 95View test data ............................................................................... 95Authorization................................................................................. 96
Test LEDs .......................................................................................... 97
Chapter 12 Control and supervise the bay ..................................... 99
Overview.......................................................................................... 100Read measured values and check apparatus status.................. 100Locating and using the single line diagram................................. 100
7/28/2019 OM RET 670
12/132
Contents
Control screen messages........................................................... 102
Chapter 13 Reset ............................................................................ 103
Reset guide...................................................................................... 104Reset LEDs ................................................................................ 104
Start and trip LEDs ................................................................ 104All indication LEDs................................................................. 104
Reset lockout.............................................................................. 104Reset counters ........................................................................... 104
Circuit breaker....................................................................... 104Circuit switch ......................................................................... 104Reset pulse counter............................................................... 105Function for energy calculation and demand
handling (MMTR) ............................................................. 105Tap changer control and supervision (YLTC)........................ 105LDCM clear counters............................................................. 105
Reset busbar protection trip ....................................................... 105Reset trip in Zone A (Single phase)....................................... 105Reset trip in Zone B (Single phase)....................................... 105Reset trip in Zone A (Three phase) ....................................... 105Reset trip in Zone B (Three phase) ....................................... 106
Reset busbar protection open current transformer..................... 106Reset open CT in Zone A (Single phase).............................. 106Reset open CT in Zone B (Single phase).............................. 106Reset open CT in Zone A (Three phase) .............................. 106Reset open CT in Zone B (Three phase) .............................. 106
Reset temperature functions ...................................................... 106
Chapter 14 Authorization ............................................................... 107
Overview.......................................................................................... 108LogOn or logOff.......................................................................... 108Authorization handling in the IED ............................................... 108
Chapter 15 Glossary ....................................................................... 111
Glossary........................................................................................... 112
7/28/2019 OM RET 670
13/132
Contents
7/28/2019 OM RET 670
14/132
1
About this chapter Chapter 1
Introduction
Chapter 1 Introduction
About this chapter
This chapter is an introduction to the operators manual, its purpose and usage.
7/28/2019 OM RET 670
15/132
2
Introduction to the operators manual Chapter 1
Introduction
1 Introduction to the operators manual
1.1 About the complete set of manuals for an IEDThe users manual (UM) is a complete set of five different manuals:
The Application Manual (AM) contains application descriptions, setting guidelines and settingparameters sorted per function. The application manual should be used to find out when and forwhat purpose a typical protection function could be used. The manual should also be used whencalculating settings.
The Technical Reference Manual (TRM) contains application and functionality descriptionsand it lists function blocks, logic diagrams, input and output signals, setting parameters and tech-nical data sorted per function. The technical reference manual should be used as a technical ref-erence during the engineering phase, installation and commissioning phase, and during normalservice.
The Installation and Commissioning Manual (ICM) contains instructions on how to installand commission the protection IED. The manual can also be used as a reference during periodictesting. The manual covers procedures for mechanical and electrical installation, energizing andchecking of external circuitry, setting and configuration as well as verifying settings and per-forming directional tests. The chapters are organized in the chronological order (indicated bychapter/section numbers) in which the protection IED should be installed and commissioned.
The Operators Manual (OM) contains instructions on how to operate the protection IED dur-ing normal service once it has been commissioned. The operators manual can be used to findout how to handle disturbances or how to view calculated and measured network data in orderto determine the cause of a fault.
The IED 670 Engineering guide (EG) contains instructions on how to engineer the IED 670products. The manual guides to use the different tool components for IED 670 engineering. Italso guides how to handle the tool component available to read disturbance files from the IEDson the basis of the IEC 61850 definitions. The third part is an introduction about the diagnostictool components available for IED 670 products and the PCM 600 tool.
The IEC 61850 Station Engineering guide contains descriptions of IEC 61850 station engi-neering and process signal routing. The manual presents the PCM 600 and CCT tool used forstation engineering. It describes the IEC 61850 attribute editor and how to set up projects andcommunication.
en06000097.vsd
Applicationmanual
Technicalreference
manual
Installation andcommissioning
manual
Operator smanual
Engineeringguide
7/28/2019 OM RET 670
16/132
3
Introduction to the operators manual Chapter 1
Introduction
1.2 About the operators manual
Use the operators manual for instruction on how to perform common tasks during normal ser-vice.
The operators manual contains the following chapters:
The chapter Safety information presents warnings and notices, which the usershould pay attention to.
The chapter Overview describes operations an operator may perform on a dailybasis or when the need arises.
The chapter Understand the local human-machine interface describes how touse the human-machine interface.
The chapter Understand the HMI tree describes the different menu trees.
The chapter Read measured values describes how to locate and identify avail-able measurement data.
The chapter Event list describes the location and nature of recorded events. The chapter Handle disturbances describes how to retrieve disturbance infor-
mation and reset alarms.
The chapter Read and change settings describes how to locate, and change set-tings and parameters.
The chapter Diagnose IED status describes the location and use of availablediagnostic tools.
The chapter Test the IED describes the tests applicable to the IED.
The chapter Control and supervise the bay describes how to use the SingleLine Diagram to open and close primary apparatuses.
The chapter Reset describes resetting procedures.
The chapter Authorizationdescribes user categories and password procedures.
The chapter Glossary describes words and acronyms used in the literature de-scribing the IED.
This manual does not contain any instructions for commissioning or testing.
1.3 Intended audience
1.3.1 General
The operators manual addresses the operator, who operates the IED on a daily basis.
1.3.2 Requirement
The operator must be trained in and have a basic knowledge of how to operate protection equip-ment. The manual contains terms and expressions commonly used to describe this kind of equip-ment.
7/28/2019 OM RET 670
17/132
4
Introduction to the operators manual Chapter 1
Introduction
1.4 Related documents
Documents related to RET 670 Identity number
Operators manual 1MRK 504 087-UEN
Installation and commissioning manual 1MRK 504 088-UEN
Technical reference manual 1MRK 504 086-UEN
Application manual 1MRK 504 089-UEN
Buyers guide 1MRK 504 091-BEN
Connection diagram, Two winding transf. Single breaker arrangements 1MRK 002 801-LA
Connection diagram, Two winding transf. Multi breaker arrangements 1MRK 002 801-HA
Connection diagram, Three winding transf. Single breaker arrangements 1MRK 002 801-KA
Connection diagram, Three winding transf. Multi breaker arrangements 1MRK 002 801-GA
Configuration diagram A, Two winding transf. with single or double busbar but
with a single breaker arr. on both sides (A30)
1MRK 004 500-93
Configuration diagram B, Two winding transf. in multi breaker arr. on one orboth sides (A40)
1MRK 004 500-94
Configuration diagram C, Three winding transf. with single or double busbarbut with a single breaker arr. on both sides (B30)
1MRK 004 500-95
Configuration diagram D, Three winding transf. in multi breaker arr. on one orboth sides (B40)
1MRK 004 500-96
Configuration diagram E, Two or three winding transf., back-up protectionpackage (A10)
1MRK 004 500-135
Configuration diagram F. Tap changer control package for two parallel trans-formers. (A25)
1MRK 004 500-140
Configuration diagram F. Tap changer control package for four parallel trans-
formers. (A25)
1MRK 004 500-140
Setting example 1, 400/230 kV 500 MVA Transformer, YNyn connected 1MRK 504 083-WEN
Setting example 2, 132/230 kV 40 MVA Transformer, YNd1 connected 1MRK 504 084-WEN
Connection and Installation components 1MRK 013 003-BEN
Test system, COMBITEST 1MRK 512 001-BEN
Accessories for IED 670 1MRK 514 012-BEN
Getting started guide IED 670 1MRK 500 080-UEN
SPA and LON signal list for IED 670, ver. 1.1 1MRK 500 083-WEN
IEC 61850 Data objects list for IED 670, ver. 1.1 1MRK 500 084-WEN
Generic IEC 61850 IED Connectivity package 1KHA001027-UEN
Protection and Control IED Manager PCM 600 Installation sheet 1MRS755552
Engineering guide IED 670 products 1MRK 511 179-UEN
7/28/2019 OM RET 670
18/132
5
Introduction to the operators manual Chapter 1
Introduction
1.5 Revision notes
Latest versions of the described documentation can be found on www.abb.com/substationautomation
Revision Description
- First release
http://www.abb.com/substationautomationhttp://www.abb.com/substationautomation7/28/2019 OM RET 670
19/132
6
Introduction to the operators manual Chapter 1
Introduction
7/28/2019 OM RET 670
20/132
7
About this chapter Chapter 2
Safety information
Chapter 2 Safety information
About this chapter
This chapter lists warnings and cautions that must be followed when handling the IED.
7/28/2019 OM RET 670
21/132
8
Warnings Chapter 2
Safety information
1 Warnings
Warning!
Do not touch circuitry during operation. Potentially lethal voltages and currents are present.
Warning!
Always connect the IED to protective earth, regardless of the operating conditions. This alsoapplies to special occasions such as bench testing, demonstrations and off-site configuration.Operating the IED without proper earthing may damage both IED and measuring circuitry andmay cause injuries in the event of an accident.
Warning!
Never remove any screw from a powered IED or from a IED connected to powered circuitry.Potentially lethal voltages and currents are present.
Warning!
Always avoid touching the circuitry when the cover is removed. The product contains electroniccircuitries which can be damaged if exposed to static electricity (ESD). The electronic circuit-ries also contain high voltage which is lethal to humans.
7/28/2019 OM RET 670
22/132
9
About this chapter Chapter 3
Overview
Chapter 3 Overview
About this chapter
This chapter presents a general overview of the Operator's manual.
7/28/2019 OM RET 670
23/132
10
Operator overview Chapter 3
Overview
1 Operator overview
The Human machine interface (HMI) on the IED provides an ideal mechanism for the day to dayoperation and even advanced use of the IED. The keypad, LCD and LEDs on the front of theIED are what constitute the HMI. Troubleshooting, apparatus control, monitoring, setting andconfiguring are all possible via this interface. Through the screens and menu elements available,as well as the keypad, the user is able to navigate throughout the menu structure and move fromscreen to screen. This document is, to a great extent, arranged in the same way as the IED soft-ware is structured and describes all aspects of operation via the HMI.
The operator can document disturbances so that their causes can be analyzed and evaluated forfuture reference. For example, the fault currents and voltages at the time of the fault can be doc-umented. The operator can also retrieve data about protected objects, providing further informa-tion for fault analysis. This implies viewing the mean value of current, voltage, power andfrequency or primary and secondary measured phasors. The operator can check the IED statusat any time.
In some cases the operator may need to change the way the IED operates. This might includechanging the active setting group or a parameter value. This must always be done strictly accord-ing to applicable regulations because un-authorized changes may lead to severe damage of the
protected object especially if a fault is not properly disconnected.
7/28/2019 OM RET 670
24/132
11
Identify the IED Chapter 3
Overview
2 Identify the IED
To identify the IED, open the diagnostics menu. The identity of the IED along with other datais found under:
Diagnostics\IED status\Product Identifiers
The type of IED, the main function type, its serial number, ordering number and production dateare found here.
7/28/2019 OM RET 670
25/132
12
Identify the IED Chapter 3
Overview
7/28/2019 OM RET 670
26/132
13
About this chapter Chapter 4
Understand the local
human-machine interface
Chapter 4 Understand thelocalhuman-machineinterface
About this chapter
This chapter describes the display, its keys (buttons) and LEDs that make up the HMI. How thekeys are used to navigate the HMI, how to interpret the graphic information on the LCD and,what the LEDs indicate is explained in the sections that follow.
7/28/2019 OM RET 670
27/132
14
Overview Chapter 4
Understand the local
human-machine interface
1 Overview
The human machine interface is used to monitor and to some extent control the way the IED op-erates. The configuration designer can add functions that alert to events requiring the attentionof the operator.
Figure 1: 1/2 x 19 case and 1/1 x 19 case with small and medium LCDs
7/28/2019 OM RET 670
28/132
15
Keypad Chapter 4
Understand the local
human-machine interface
2 Keypad
The keypad is used to monitor and operate the IED. The keypad has the same look and feel inall IEDs in the IED 670 series. LCD screens and other details may differ but the way the keysfunction is identical. The keypad is illustrated in figure 2.
Figure 2: The HMI keypad.
The keys used to operate the IED are described below in table 1.
Table 1: HMI keys on the front of the IED
Key Function
This key closes (energizes) a breaker or disconnector.
This key opens a breaker or disconnector.
The help key brings up two submenus. Key operation and IED information.
This key is used to clear entries, It cancels commands and edits.
Opens the main menu, and used to move to the default screen.
7/28/2019 OM RET 670
29/132
16
Keypad Chapter 4
Understand the local
human-machine interface
The Local/Remote key is used to set the IED in local or remote control mode.
This key opens the reset screen.
The E key starts editing mode and confirms setting changes when in editing mode.
The right arrow key navigates forward between screens and moves right in editing mode.
The left arrow key navigates backwards between screens and moves left in editing mode.
The up arrow key is used to move up in the single line diagram and in menu tree.
The down arrow key is used to move down in the single line diagram and in menu tree.
Key Function
7/28/2019 OM RET 670
30/132
17
Key activated screens Chapter 4
Understand the local
human-machine interface
3 Key activated screens
3.1 The Help screenThe help screen is activated by pressing the Help key on the front panel of the IED. It includesthe submenu listed below:
General operation
The General Operation submenu provides information about the IED keypad.
The I and O keys are used to open (OFF) and close (ON) breakers and disconnectors when usingthe Single Line Diagram (SLD) in direct control situations.
3.2 The Reset screen
The reset screen is activated by the Reset key on the front panel of the IED or via the main menu.The reset screen includes the submenus listed below:
Reset LEDs
Reset counters
Reset BBP trip
Reset BBP open CT
The Reset LEDs submenu consists of two lower level menus which are the Start and trip LEDsand All indication LEDs submenus. To reset a counter, the actual counter must first be select-ed. The submenus and the their structures are discussed in the Reset chapter of this document.
7/28/2019 OM RET 670
31/132
7/28/2019 OM RET 670
32/132
19
LED Chapter 4
Understand the local
human-machine interface
5 LED
The LED module is a unidirectional means of communicating. This means that events may occurthat activate a LED in order to draw the operators attention to something that has occurred andneeds some sort of action.
5.1 Status indication LEDs
There are three LEDs above the LCD. The information they communicate is described in thetable below.
5.2 Indication LEDs
The LED indication module comprising 15 LEDs is standard in IED 670s. Its main purpose isto present an immediate visual information for protection indications or alarm signals.
There are alarm indication LEDs and hardware associated LEDs on the right hand side of thefront panel. The alarm LEDs are found to the right of the LCD screen. They can show steady orflashing light. Flashing would normally indicate an alarm. The alarm LEDs are configurable us-ing the PCM 600 tool. This is because they are dependent on the binary input logic and can there-fore not be configured locally on the HMI. Some typical alarm examples follow:
Bay controller failure
CB close blocked
Interlocking bypassed
Differential protection trip
SF6 Gas refill
Position error
CB spring charge alarm
Oil temperature alarm
Thermal overload trip
Bucholtz trip
LED Indication Information
Green:
Steady In service
Flashing Internal failure
Dark No power supply
Yellow:
Steady Dist. rep. triggered
Flashing Terminal in test mode
Red:
Steady Trip command issued
7/28/2019 OM RET 670
33/132
20
LED Chapter 4
Understand the local
human-machine interface
The RJ45 port has a yellow LED indicating that communication has been established betweenthe IED and a computer.
The Local/Remote key on the front panel has two LEDs indicating whether local or remote con-trol of the IED is active.
7/28/2019 OM RET 670
34/132
21
LHMI setup and test screen Chapter 4
Understand the local
human-machine interface
6 LHMI setup and test screen
The contrast setting of the LCD can be adjusted from the LHMI menu tree when the IED hasstarted or from the PST tool in PCM 600. The contrast setting adjusted with one of these meth-ods is an offset to a factory set basic contrast setting.
Normally the basic contrast setting is not changed, but can if needed be adjusted as follows:
Activate the setup and test screen for the LHMI by keeping the Reset key pressed immediatelyafter the dc power to the IED has been applied.
By pressing keys according to information on the setup and test screen
the basic contrast level of the LCD screen can be changed
the LCD screen can be toggled to inverse mode
the indication LEDs can be tested
Press the I key to save and exit the screen and wait for the IED to start. Observe that only thebasic contrast setting will be saved.
Note!
The screen shows I which here means the Close key.
7/28/2019 OM RET 670
35/132
22
How to navigate Chapter 4
Understand the local
human-machine interface
7 How to navigate
7.1 ReadTo read values and access information about the objects being monitored the operator must nav-igate the menu tree using the arrow keys. The active submenu or value is highlighted.
Navigation is as follows:
Press the right arrow key to move to the main menu.
Press the down arrow key to move from the Single line diagram to the desiredsubmenu.
Use the right arrow key to move downwards in the HMI tree until the desired pa-rameter is displayed.
Press C and the down arrow key simultaneously to see the next page in the pa-
rameter screen. Press C and the up arrow key simultaneously to return to the previous parameter
screen.
Use the left arrow key to navigate back up the menu tree.
7.2 Change
To change a parameter setting the following steps should be followed:
1. Navigate to the desired parameter or quantity using the arrow keys.
2. Press the E key when the parameter to be changed is highlighted.
3. Move between digits or letters using the left and right arrow keys.
4. Use the up and down arrow keys to change the digit or letter concerned.
5. Press the E key once the desired changes have been made.
6. Press the left arrow key to move up a level in the HMI tree.
7. You will be prompted to confirm the changes, use the left and right arrow keysto toggle between yes and no in the pop up window and press the E key to confirmyour choice.
8. Press the left arrow key to move up to the next level in the HMI tree.
7.3 Control
The HMI offers the operator the opportunity to exercise direct local control over breakers and
other apparatuses in the bay using the graphic display and designated keys on the front panel ofthe IED.
By pressing the L/R key until the uppermost of the two LEDs next to the key lights up, localoperator control can be exercised from the HMI.
An apparatus is selected using the up and down arrow keys. The active apparatus is highlightedin the display.
7/28/2019 OM RET 670
36/132
7/28/2019 OM RET 670
37/132
24
How to navigate Chapter 4
Understand the local
human-machine interface
7/28/2019 OM RET 670
38/132
25
About this chapter Chapter 5
Understand the HMI tree
Chapter 5 Understand theHMI tree
About this chapter
This chapter describes the structure of the HMI. The main menu includes submenus such asMeasurements, Events, Disturbance Report, Settings, Diagnostics, Test and Reset. These branchout into a typical tree structure.
7/28/2019 OM RET 670
39/132
26
Overview Chapter 5
Understand the HMI tree
1 Overview
The local HMI has the following main menu:
Control
Measurements
Events
Disturbance records
Settings
Diagnostics
Test
Reset
Authorization
Language
Each main menu item can have several other submenus.
1.1 Menu-tree for RET 670
Main menu Sub menu Sub-sub menu
Control Single line diagram
Commands
Measurements Analog primary values
Analog secondary values
Analog mean valuesMonitoring
Metering
Events
Disturbance records Manual trig
Settings Time
General settings Power system
Communication
Analog modules
I/O modules
HMI
Differential protection
Current protection
Voltage protection
Control
Monitoring
Metering
7/28/2019 OM RET 670
40/132
27
Overview Chapter 5
Understand the HMI tree
Setting group N Differential protection
Impedance protection
Current protection
Voltage protection
Frequency protection
Multipurpose protection
Scheme communication
Secondary system supervision
Control
Monitoring
Logic
Activate setting group
Diagnostics Internal eventsIED status
Test IED test mode
Binary input values
Binary output values
Function test modes
Function status
LED test
Line differential test
Reset Reset counters
Reset internal eventlist
Reset LEDs
Reset lockout
Reset temperature
Authorization
Language
Main menu Sub menu Sub-sub menu
7/28/2019 OM RET 670
41/132
28
Overview Chapter 5
Understand the HMI tree
7/28/2019 OM RET 670
42/132
29
About this chapter Chapter 6
Read measured values
Chapter 6 Read measuredvalues
About this chapter
This chapter describes measurement categories and how to locate them using the HMI. Eachmeasurement category has a section of its own that includes a general description of the type ofquantity being measured and the path in the local HMI to the measurement.
7/28/2019 OM RET 670
43/132
30
Overview Chapter 6
Read measured values
1 Overview
The measurement menu contains primarily analog measurement data. External signals can alsobe viewed as they are or as they appear in the Signal Matrix Tool (SMT). These signals are avirtual representation of the hard wired signals on the various inputs and outputs. The SMT isonly accessible via the PCM and is intended to simplify the configuration of the IED. It allowshardware changes to be made without having to reconfigure the internal logic. Signals that can
be used in the SMT are indicated with the Suffix SMT.
The functions available under measurements are outlined below.
1. Analog primary values are the quantities measured on the primary side of the cur-rent and voltage transformers (CTs and VTs).
2. Analog secondary values are the quantities measured on the secondary side of thecurrent and voltage transformers. These are the quantities measured on the Trans-former module (TRM) inputs.
3. Analog mean values are the quantities measured at the inputs of the milliamperemodule (MIM).
4. Under Monitoring a number of submenus are available. These include Servicevalues, Current phasors, Voltage phasors, Current sequence components andVoltage sequence components.
5. Metering displays the pulse counter function. The measurements available hereshow pulse counter status data.
All measurement descriptions in this document reflect the maximum number of hardware unitspossible in any application. In reality the hardware in the IED will be chosen according to a par-ticular application. For example, it is possible to equip a 1/1 x 19 case IED with 14 I/O modules.In reality fewer I/O modules may be installed. In the measurements menu the operator will onlysee data from the hardware and software installed.
7/28/2019 OM RET 670
44/132
31
View analog primary values Chapter 6
Read measured values
2 View analog primary values
2.1 OverviewThe analog primary values are analog quantities measured on the primary side of the TRM andreflect the actual current or voltage on the primary side of the VTs and CTs. The ratio is adjustedunder settings and also depends on the rating of the TRM. 24 primary values and phase anglesare displayed in this view.
Measurements\Analog Primary Values
Displays the quantities measured by the transformer module (TRM). For each channel used theamplitude of the voltage or current and its phase angle is shown. The status of the module is al-ways shown and channels not in use are indicated with the abbreviation NC. Data from up totwo TRMs and four LDCMs can be viewed. All currents and voltages are given in RMS values.
7/28/2019 OM RET 670
45/132
32
View analog secondary values Chapter 6
Read measured values
3 View analog secondary values
3.1 OverviewAnalog secondary values shows secondary CT currents and VT voltages. These are the actualcurrent and voltage values at the TRM inputs.
Measurements\Analog Secondary Values
Displays up to 24 channels with secondary CT and VT data. RMS values are shown.
7/28/2019 OM RET 670
46/132
33
View analog mean values Chapter 6
Read measured values
4 View analog mean values
4.1 OverviewMeasurements from the Milliampere Input Module (MIM) are found in this part of the measure-ments menu. Data from either the hard wired mA module or the Signal Matrix Tool mA modulesare shown here.
4.1.1 mA input module (MIM)
Measurements\Analog Mean Values\mA modules\MIM
Displays input data from the milli-ampere module which has six inputs. Each input has a rangeof +/- 20 mA. The value displayed on the screen is however dependant on the settings for theMilli-ampere Module. In the menu for settings, the range and a transformation factor can be ad-
justed to suit the application. This means that an input 3 mA may be displayed as temperatureof 45 degrees. The output values shown are without units.
4.1.2 Signal matrix for mA inputs (SMMI)
Measurements\Analog Mean Values\SMT mA modules\Instance
Displays the input signals coming into the Milli-ampere Module. Each module has six physicalinputs with an input tolerance of +/- 20mA. The value displayed depends on the settings appliedto this board which may for example cause an input of 3mA to show a value 30. The SMT mAmodules are the virtual representation of MIMs in the Signal Matrix Tool.
7/28/2019 OM RET 670
47/132
34
View monitoring values Chapter 6
Read measured values
5 View monitoring values
5.1 Service valuesMeasurement\Monitoring\ServiceValues(MMXU)\SVR
Displays up to three instances of SVR with measured values for S, P, Q, PF, U, I, ILead, ILagand F.
5.2 Current phasors
Measurement\Monitoring\Current Phasors\CP
All three phase currents and their phase angles are displayed here. As many as 10 sets of currentdata can be shown.
5.3 Voltage phasors
Measurements\Monitoring\Voltage phasors\VP
Phase to phase voltages and phase angles are displayed here. Up to three sets of voltage data canbe displayed.
5.4 Current sequence component
Measurements\Monitoring\Current Sequence Components (MSQI)\CSQ
The current sequence component under monitoring displays the positive (I1), negative (I2) andzero sequence (I0) current values for a three phase line, both magnitude and phase angle for eachcomponent are displayed. These indicate how well balanced a system is. In an ideal balancedsystem the zero sequence current should be zero, the positive sequence current should be equalto the current of each phase with the same phase angle (relative to GPS) as the L1 phase signaland the negative sequence current should be zero.
5.5 Voltage sequence component
Measurements\Monitoring\Voltage Sequence Components (MSQI)\VSQ
The Voltage sequence component displays the positive (U1), negative (U2) and zero (U0) se-quence components in the system, and includes the magnitude and phase angle of each compo-nent. Three sets of values are shown. This data indicates how well balanced the system is.
7/28/2019 OM RET 670
48/132
35
View monitoring values Chapter 6
Read measured values
5.6 Three phase busbar protection (zone A)
Measurement\Monitoring\BBPZoneA3ph\BTZA
The magnitude of the three phase currents is displayed here. The differential current for eachphase is also shown.
5.7 Three phase busbar protection (Zone B)
Measurements\Monitoring\BBPZoneB3ph\BTZB
Displays the magnitude of the currents and the differential currents in the three phase system.
5.8 Single phase busbar protection (Zone A)
Measurements\Monitoring\BBPZoneA1ph\BSZA
Displays busbar current and differential current value.
5.9 Single phase busbar protection (Zone B)
Measurements\Monitoring\BBPZoneB1ph(PDIF, 87B)\BSZB
Displays magnitude of current and differential current value.
7/28/2019 OM RET 670
49/132
36
View metering values Chapter 6
Read measured values
6 View metering values
Measurements\Metering\Pulse counter\PC
The output data generated from the pulse counter function include data about the status of thecounter and counter values.
Measurements\Metering\ThreePhEnergMeas\ETP
The output data generated from the energy measuring function includes active forward/reverseenergy and reactive forward/reverse energy.
7/28/2019 OM RET 670
50/132
37
About this chapter Chapter 7
Event list
Chapter 7 Event list
About this chapter
This chapter describes how to find and read the event list.
7/28/2019 OM RET 670
51/132
38
View events Chapter 7
Event list
1 View events
1.1 OverviewEvents displays recorded events such as trips and breaker opened or closed.
Events
Displays a list of events in chronological order and where each event has a time stamp. The latestevent is at the top of the list.
7/28/2019 OM RET 670
52/132
39
About this chapter Chapter 8
Handle distu rbances
Chapter 8 Handledisturbances
About this chapter
This chapter describes disturbance detection and handling. This includes resetting LED alarms,triggering disturbance reports and the viewing of several fault indicators.
7/28/2019 OM RET 670
53/132
40
Identify a disturbance Chapter 8
Handle distu rbances
1 Identify a disturbance
A disturbance record can be generated manually by using the Manual Trig functionality in theHMI menu. Other disturbance records are generated automatically in the system dependant onthe settings made. Disturbance reports generate a disturbance sequence number and are timetagged. The fault location and fault loop are among the data generated in a fault record. Undereach fault report there are five categories of information available. These are described in thesections that follow.
7/28/2019 OM RET 670
54/132
41
View disturbance record details Chapter 8
Handle distu rbances
2 View disturbance record details
2.1 View general informationBy choosing General information after selecting a disturbance record in the list of disturbancerecords the screen generated displays information about the disturbance such as its sequencenumber, time of occurrence, trig-signal, fault location and fault loop. The path in the HMI isshown below.
Disturbance records\Manual trig
2.2 View disturbance indications
The Indications section of a disturbance record displays the recording number and, the time anddate of the disturbance. The path in the HMI is shown below.
Disturbance records\Record xx\Indications
2.3 View event recordings
The Event recording section in the Disturbance report shows the recording number. The path inthe HMI is shown below.
Disturbance records\Record xx\Event recording
2.4 View trip values
In the Trip values section of a disturbance recording both the pre-fault and the fault values forcurrent, voltage and phase angle can be viewed. The recording number and Trig time are alsodisplayed. The path in the HMI is shown below.
Disturbance records\Record xx\Trip Values
7/28/2019 OM RET 670
55/132
42
Trigger a disturbance report manually Chapter 8
Handle distu rbances
3 Trigger a disturbance report manually
Using the manual trigger generates an instant disturbance report. Use this function to get a snap-shotof the monitored line. Follow the path below and answer yes in the Execute manual trig di-alog box.
Disturbance Records\Manual Trig
7/28/2019 OM RET 670
56/132
43
About this chapter Chapter 9
Read and change settings
Chapter 9 Read and changesettings
About this chapter
This chapter describes how to find and change settings and parameters. The chapter is dividedinto two sections which match the way the two categories of settings are divided up in the HMI.The General settings group consists of those parameters that cause an automatic restart of theIED. The Setting group N consists of six groups of settings with default values for all parame-ters. These do not require or cause a restart once they have been changed. Time, synchronizationand the activation of setting groups are also dealt with here.
7/28/2019 OM RET 670
57/132
7/28/2019 OM RET 670
58/132
45
System time and synchronization Chapter 9
Read and change settings
1.2.7 TimeZone
Settings\Time\Synchronization\TimeSynchTimeZone
The time zone according to Coordinated Universal Time (UTC) is set here.
1.2.8 TimeSynch IRIG-B
Settings\Time\Synchronization\TimeSynchIRIG-B
The type of input, time domain, type of encoding and time zone for IRIG-B are set here.
7/28/2019 OM RET 670
59/132
46
General settings Chapter 9
Read and change settings
2 General settings
Parameters under General settings that are changed will cause the IED to restart. This occurs au-tomatically and requires no manual intervention.
2.1 Power system
2.1.1 Overview
Under Power system in General settings there are four parameter categories. These are Identifi-ers, Primary values, three phase analog group and three phase analog sum group.
2.1.2 Identifiers
Settings\General Settings\Power System\Identifiers
Displays list with Station Name, Station Number, Object Name, Object Number, Unit Name andUnit Number.
2.1.3 Primary values
Settings\General Settings\Power System\Primary Values
Displays the system frequency.
2.2 Communication
2.2.1 Overview
The parameter settings for communications are found under General Settings\Communications.Communication settings cover network interfaces, protocol, remote communication and recep-tion of interlocking information.
2.2.2 TCP-IP
Settings\General settings\Communication\Front port
The IP Address and IP mask for the ethernet port on the front panel of the IED are set here. Theseare generally used when connecting a PC directly to the IED. Remember that this is a static IPaddress and that the appropriate network settings must also be made in the PC.
Settings\General settings\Communication\TCP-IP\Rear OEM-Port AB
The IP address, IP mask and Link for the Optical Ethernet card at the rear of the IED are set here.
Settings\General settings\Communication\TCP-IP\Rear OEM-Port CD
The same as the above but with different IP address if a second port is used.
7/28/2019 OM RET 670
60/132
47
General settings Chapter 9
Read and change settings
Settings\General settings\Communication\TCP-IP\Gateway
If a gateway is used to access the system the address to that gateway is entered here.
2.2.3 SPA, LON and IEC 608705103 settings
Rear Optical LON port
The menu for the rear optical LON port has five submenus for various settings affecting LONparameters. The HMI paths to these submenus and their contents are described below.
Settings\General settings\Communication\SLM configuration\Rear optical LONport\General
In the General submenu there are three settings. These are for the Subnet address, the Node ad-dress and the NeuronID.
Settings\General settings\Communication\SLM configuration\
Rear optical LON port\ServicePinMessage
In this submenu a Service pin message can be generated. This is similar to a ping in traditionalnetworks. This sends a signal to another node in the system which is then made aware of the
Neuron ID of LON port and can respond to that port.
Settings\General settings\Communication\SLM configuration\Rear optical LONport\ADE
The Application Data Event (ADE) menu is where operation of LON is set on or off and where
the data exchange speed can be set. If LON is used primarily to send event data then the appro-priate setting is slow. Should LON be used, for example, as a channel for TRIP signals then thesetting fastwould be appropriate.
Settings\General settings\Communication\SLM configuration\Rear optical LONport\SPA
Settings for SPA over LON are made here. The operation setting is used to switch the functionon or off and the slave address setting is where the slave address is entered.
Settings\General settings\Communication\SLM configuration\
Rear optical LON port\Horizontal communication
This setting is used to activate or deactivate horizontal communication.
7/28/2019 OM RET 670
61/132
48
General settings Chapter 9
Read and change settings
Rear optical SPA-IEC port
Settings\General settings\Communication\SLM configuration\
Rear optical SPA-IEC port
In this submenu SPA or IEC is chosen and the necessary settings for the respective communica-tion protocols are made.
Settings\General settings\Communication\SLM configuration\
Rear optical SPA-IEC port\Protocol selection SPA or IEC103 operation.
SPA and IEC cannot run at the same time and in this submenu one of the options is chosen.
Settings\General settings\Communication\SLM configuration\
Rear optical SPA-IEC port\SPA
When SPA is chosen the baud rate and slave address are set here.
Settings\General settings\Communication\SLM configuration\
Rear optical SPA-IEC port\IEC608705103
When IEC 608705103 is used the settings Slave address, Baud rate, RevPolarity and Cyc-MeasRepTime are done here.
2.2.4 LDCM
Settings\General settings\Communication\LDCM configuration\LDCM
Four identical sets of settings for Remote Binary Communication (CRB) and four for RemoteMulti Communication (CRM). The multi communication block can send both binary and analogdata whereas the binary can only send binary data.
Each instance of CRB has seven settable parameters where the channel mode can be set on oroff, terminal numbers can be entered, synchronization can be set to master or slave and opto
power can be set high or low.
Each instance of CRM has 17 settable parameters. These include those above and others such astransmission delay and transmission current.
2.2.5 Station communication
Multicommand send
Settings\General settings\Communication\Station communication\Multicommand-Send\MT
The up to ten instances ofMulticommandSendsettings allow the user to adjust the maximumand minimum cycle time.
7/28/2019 OM RET 670
62/132
49
General settings Chapter 9
Read and change settings
Multicommand receive
Settings\General settings\Communication\Station communication\Multicommandreceive\CM
The up to 60 instances ofMulticommandReceive settings available here allow the user to adjustthe maximum and minimum cycle time, the pulse duration and mode of operation. The mode ofoperation is either steady or pulsed.
IEC6185081
Settings\General Settings\Communication\Station communication\IEC6185081
Includes settings for the IED name, operation (on/off) and GOOSE.
GOOSE Binary receive
Settings\General settings\Communication\
Station communication\GOOSEBinReceive\GB
There are up to ten sets of settings here with one parameter (GB 01 GB10) per setting. The set-ting is Operation ON or OFF.
Receiving interlock information
Settings\General settings\Communication\
Station Communication\ReceivingInterlInfo\GR
Includes up to 59 parameters (GR01GR59) for horizontal communication via GOOSE. Eachinstance or set can be switched on or off via the operation parameter.
Settings\General settings\Communication\Station Communication\DNP3.0
The DNP 3.0 related parameters are found here.
2.3 Analog modules
2.3.1 Overview
Under Analog modules in the General settings menu there are settings for Analog inputs and I/Omodules. Within each instance of analog input there are settings for all 12 channels that includethe name of the channel, star point of the CT circuit, the primary and secondary values from the
measuring transformers (CTs and VTs). The channel type and ratings are shown but cannot bechanged.
The settings for binary inputs and outputs even include the milliampere input modules. A mixof up to 14 instances of BIM, BOM and IOM is possible depending on the physical configurationof the IED. Operation ON or OFF can be set for all of these and for the BIMs oscillation releaseand oscillation block settings are available. These settings are on board level and apply to all bi-nary inputs or outputs on a board.
7/28/2019 OM RET 670
63/132
50
General settings Chapter 9
Read and change settings
2.3.2 Analog modules
Settings\General Settings\Analog modules\AnalogInputs
Displays all variations of analog input modules with parameters. The analog input modules havedifferent combinations of current and voltage inputs. Each channel has parameters where thetype of channel is set, the primary and secondary values from VTs and CTs and for CurrentTransformers the star point location (line side or busbar side) is set.
Settings\General Settings\Analog modules\3PhAnalogGroup\PR
Here, settings for the Fourier filters, the minimum system voltage required to measure frequen-cy, the item designation of CTs or VTs, and the system voltage are set. These settings are re-quired by the preprocessing blocks and are usually only adjusted during the initial engineering
phase.
Setting\General Settings\Analog modules\3PhAnalogSummationGroup\SU
Here is where the settings for the summation block are done. The summation type, Fourier filterreference frequency, minimum voltage for frequency measurement and the system voltage aresome of the parameters that can be set here.
2.3.3 I/O modules
Settings\General Settings\I/O Modules
Settings for binary inputs and outputs (BIM, BOM, IOM), and under each binary module thereare one or more adjustable parameters. In the I/O modules folder there is also a reconfiguresetting that starts a dialog box prompting the user to confirm or cancel the command. Since only
I/O modules installed in the IED are shown, the parameters available for setting depend on thephysical configuration of the IED. All I/O modules include the operation parameter which en-ables the operator to switch the module on or off.
The milliampere modules (MIMs) are also found in the I/O Modules folder. Parameters possibleto set here are dead band settings and various current threshold values.
2.4 HMI
2.4.1 Overview
Under HMI in General settings there are submenus for LEDs, Screen, Functions, Referencechannel service values and the Change lock function. In the LED submenu there are settings for
operation, illumination times, and sequence types for the LEDs on the IED front panel. In theScreen submenu Contrast level, Default screen, Auto repeat and Timeout display can be set. Inthe Functions submenu the Event list sorting order and Distance presentation can be set.
7/28/2019 OM RET 670
64/132
51
General settings Chapter 9
Read and change settings
2.4.2 LEDs
Settings\General settings\HMI\LEDs
Parameters such as Operation, tRstart, tMax and 15 instances of SeqTypeLED can be set here.The SeqTypeLED offers several options for the type of illumination sequence the LEDs shouldfollow.
2.4.3 Screen
Settings\General Settings\HMI\Screen
Local HMI setting parameters such as Language, Contrast level and Default menu can be sethere.
2.4.4 Functions
Settings\General Settings\HMI\Functions
The settings here are used to determine the way information is presented in the HMI.
2.4.5 Change lock
Settings\General settings\HMI\Change lock
The operation of the Change lock function can be activated or deactivated here.
2.5 Differential protection
2.5.1 OverviewThis group of settings covers differential protection of transformers. The system needs rated datato function properly. If the protection object is for example, a transformer, the rated current andvoltage per winding as well as other relevant data will be needed. The submenus under differ-ential protection contain many other settable parameters such as connection type (line side or
busbar side), tap positions, CT ratings etc. The data required depends on the protected object.
2.5.2 Transformer differential protection, two winding (PDIF, 87T)
Settings\GeneralSettings\Differential protection\TransformerDiff2Wind(PDIF)\
T2D
Parameters for available instances of T2D can be set here. These include the rated voltages and
currents for windings, the connection types, the current transformer ratings and various other pa-rameters.
7/28/2019 OM RET 670
65/132
52
General settings Chapter 9
Read and change settings
2.5.3 Transformer differential protection, three winding (PDIF, 87T)
Settings\General Settings\ Differential protection\TransformerDiff3Wind\T3D
Parameters for T3D can be set here. These include rated voltages and currents, connection types(Y, D), current transformer ratings and various other parameters.
2.6 Control
2.6.1 Overview
Under Control in General settings, parameters for Apparatus control can be adjusted. These arethe parameters for among others Bay control, Switch controller, Reservation input, Circuit
breakers and Circuit switches. The parameters include delay times, dependencies, pulse timesand characteristics.
2.6.2 Bay control (CBAY)Settings\General Settings\Control\Apparatus Control\Bay Control\CB
Displays up to six instances of the bay control function (CB) with a setting that gives the localoperator priority over the remote operator or vice versa.
2.6.3 Reservation input
Settings\General Settings\Control\Apparatus Control\ReservationInput\RE
Displays available instances of the Reservation input function (RE) with one settable parameterper function for future use.
2.6.4 Bay reserve (CRSV)Settings\General Settings\Control\Apparatus Control\Bay Reserve\CR
Displays up to four instances of the bay reserve function (CR) with nine parameter settings. Thefirst is for setting the supervision time to cancel a reservation and the other eight are for the res-ervation of the own bay only at the selection of an apparatus.
2.6.5 Switch controller (CSWI)
Settings\General Settings\Control\Apparatus Control\SwitchController\CS
Displays instances of the switch controller function (CS) with eight settable parameters. These
are settings for the control model, position dependency and various threshold times.
7/28/2019 OM RET 670
66/132
53
General settings Chapter 9
Read and change settings
2.6.6 Circuit breaker (XCBR)
Settings\General Settings\Control\Apparatus Control\CircuitBreaker\XC
Displays available instances of the circuit breaker function with parameter settings for varioustime limits and pulse lengths. For example, different circuit breakers may require different pulselengths to react. The setting tOpenPulse is used to set the length of the pulse required to open a
breaker.
2.6.7 Circuit switch (XSWI)
Settings\General Settings\Control\Apparatus Control\CircuitSwitch\XS
Displays available instances of the circuit switch function (XS) with a number of settable param-eters per instance for time and pulse settings, output reset and switch type.
2.6.8 Local/Remote switch (LocalRemote, LocRemControl)
Settings\General Settings\Control\Apparatus control\LocalRemote\LR
Displays available instances of the local/remote function (LR) that permit the user to set the con-trol mode.
2.7 Control commands
2.7.1 Single command
Settings\General settings\Control\Commands\Single command\CD
The mode for single command is set here.
2.7.2 Logic rotating switch (GGIO)
Settings\General settings\Control\Commands\Selector switch (GGIO)\SL
A number of selector switches (LRS) can be configured in the system. These are substitutes forrotating physical switches. There is only one parameter setting per switch. This is StopAt Ex-tremes which is used to disable or enable the end position of the switch.
2.7.3 Selector mini switch (GGIO)
Settings\General settings\Control\Commands\Versatile switch\VS
Parameters such as control model according to IEC61850 and operation mode for the versatileswitch is set here.
7/28/2019 OM RET 670
67/132
54
General settings Chapter 9
Read and change settings
2.7.4 Tap changer control and supervision (YLTC, 84)
Settings\General settings\Control\TransformerTapControl\TCL
Tap changer parameters such as tap positions for low and high voltage and type of code conver-sion are set here.
2.7.5 Tap changer control and supervision (YLTC, 84)
Settings\General settings\Control\TransformerTapControl\TCM
Tap changer parameters such as tap positions for low and high voltage and type of code conver-sion are set here.
2.7.6 Automatic voltage