7/30/2019 Fcu M Leaflet
1/11
FAN COIL M SERIES FC 245/AE
Ceiling Concealed MCW
Ducted MCC
Ceiling Cassette MCK
Wall Mounted MWM
7/30/2019 Fcu M Leaflet
2/11
Note: Air flow and Performances referred to EUROVENT 6/3 conditions:
1. Cooling: Air temperature entering the unit: 27C d.b.; 19C w.b.; water inlet temperature: 7C; T 5K.2. Heating: Air temperature entering the unit: 20C; water inlet temperature: 50C; water flow rate same as for cooling mode
3. Heating (auxiliary coil): Air temperature entering the unit: 20C; water inlet temperature: 70C; T 5K.
Model 200C 300C 400C 600C 800C 1000C 1200C
m3/h (max.) 408 595 765 1138 1427 1699 2175
m3/h (med.) 306 459 663 901 1155 1308 1750Air flow rate (1)
m3/h (min.) 204 340 510 731 952 1054 1444
kW (max.) 2,3 3,4 4,2 6,5 8,2 9,2 11,9
kW (med.) 1,9 2,8 3,7 5,6 7,1 8,1 10,6Total coolingcapacity (1)
kW (min.) 1,6 2,4 3,2 5,0 6,1 7,2 8,9
kW (max.) 1,5 2,3 2,9 4,4 5,4 6,2 8,0
kW (med.) 1,3 2,0 2,6 3,7 4,6 5,3 7,0Sensible coolingcapacity (1)
kW (min.) 1,0 1,5 2,1 3,2 3,8 4,6 5,6
Water flow rateL/h
420 600 780 1080 1740 1800 2280Pressure drop kPa 16 13 22 47 33 26 45
W (max.) 3,9 5,7 7,5 11,3 14,2 15,8 20,5
W (med.) 3,4 4,8 6,6 9,5 12,1 13,1 17,4Total heatingcapacity (2)
W (min.) 2,8 4,1 5,4 8,3 10,8 11,6 15,1
W (max.) 2,6 3,4 5,0 6,0 6,7 9,1 10,2
W (med.) 2,1 2,9 4,5 5,1 5,8 7,7 8,9
Total heatingcapacity auxiliarycoil (3) W (min.) 1,6 2,3 3,8 4,5 5,1 6,6 7,8
Static pressure Pa 60 60 60 60 60 60 60
Water flow rate L/h 420 600 780 1080 1740 1800 2280
Pressure drop kPa 16 13 22 47 33 26 45
Power supply 230V 1 ph 50 Hz
Power input W 51 69 83 149 205 219 281
Absorbed current A 0,22 0,29 0,36 0,64 0,93 1,04 1,22Connection inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4
The high external static pressure makes units
ideal for both ducted and free air delivery
applications.
MCW are able to satisfy every requirement in
terms of air conditioning in wide space
requiring the ceiling installation.
The quite contained height makes units ideal
for false ceiling installation even in vin buildings
with narrow ceiling spaces
Concealed
7/30/2019 Fcu M Leaflet
3/11
Model 200C 300C 400C 600C 800C 1000C 1200C
dB (A) (max) 36,0 37,0 37,0 39,0 39,0 39,0 40,0
dB (A) (med) 35,0 35,0 35,0 36,0 37,0 38,0 36,0
dB (A) (min) 34,0 34,0 34,0 35,0 35,0 35,0 35,0
Model 200C 300C 400C 600C 800C 1000C 1200C
Height mm 251 251 251 251 251 251 251Length mm 714 884 1014 1214 1464 1564 1824
Width mm 490 490 490 490 490 490 490
Weight Kg 19 22 26 30 41 44 46
The extremely compact and lightweight design
facilitates the delivery and installation of units.
Height is barely 251mm allowing the installation
in all false ceiling types.
Water connection sides can be changed easily in
the field
7/30/2019 Fcu M Leaflet
4/11
Note: Air flow and Performances referred to EUROVENT 6/3 conditions:
1. Cooling: Air temperature entering the unit: 27C d.b.; 19C w.b.; water inlet temperature: 7C; T 5K.2. Heating: Air temperature entering the unit: 20C; water inlet temperature: 50C; water flow rate same as for cooling mode
Model 010CW 015CW 020CW 025CW 030CW 040CW 050CW 060CW
m3/h (max.) 510 730 1050 1430 1750 1960 2620 3380
m3/h (med.) 480 530 1040 1340 1390 1740 2430 3110Air flow rate (1)
m3/h (min.) 410 460 850 1090 1120 1430 2210 2770
kW (max.) 2,66 4,78 6,02 7,25 8,77 11,3 14,5 17,53
kW (med.) 2,64 3,78 5,98 6,93 7,43 10,42 13,78 16,51Total coolingcapacity (1)
kW (min.) 2,54 3,39 5,17 5,97 6,3 9,05 12,87 15,14
kW (max.) 2,04 3,52 4,36 5,31 6,52 8,47 10,74 12,75
kW (med.) 1,98 2,7 4,33 5,06 5,46 7,71 10,13 11,96Sensible coolingcapacity (1)
kW (min.) 1,83 2,39 3,69 4,32 4,6 6,58 9,39 10,92
Water flow rate L/h 455 819 1031 1242 1503 1936 2490 3004
Pressure drop kPa 14 45 86 125 86 79 56 81
W (max.) 3,34 5,22 6,44 7,85 9,72 12,8 16,33 19,33
W (med.) 3,2 3,98 6,39 7,46 8,1 11,64 15,38 18,1Total heatingcapacity (2)
W (min.) 2,85 3,52 5,43 6,34 6,78 9,92 14,25 16,5
Static pressure Pa 50 50 50 50 150 150 150 150
Water flow rate L/h 455 819 1031 1242 1503 1936 2490 3004
Pressure drop kPa 12 24 74 99 53 58 43 62
Power supply 230V 1 ph 50 Hz
Power input W 71 102 148 173 421 550 670 748Absorbed current A 0,30 0,43 0,65 0,74 1,90 2,60 2,90 3,20
Connection inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
The new line of Ducted fan coils units, offers a
wide range of solutions to air distribution
problems applicable on both new and refurbished
buildings, independently on the rooms volume.
Multiple rooms can be cooled together with only
one unit and the conditioned air can be effectively
distributed to every corner of the room through
ducting
7/30/2019 Fcu M Leaflet
5/11
Model 010CW 015CW 020CW 025CW 030CW 040CW 050CW 060CW
dB (A) (max) 33,0 37,0 38,0 40,0 49,0 51,0 53,0 55,0
dB (A) (med) 31,0 34,0 35,0 37,0 45,0 47,0 50,0 52,0
dB (A) (min) 30,0 32,0 33,0 35,0 43,0 45,0 46,0 50,0
Model 010CW 015CW 020CW 025CW 030CW 040CW 050CW 060CW
Height mm 261 261 261 261 370 370 370 370Length mm 765 905 1065 1200 919 1039 1289 1489
Width mm 411 411 411 411 589 589 589 589
Weight Kg 17 21 22 25 39 42 54 62
MCC units are specifically designed for inside ceiling
installation. Air mixing is well distributed in all space granting
the best comfort.
The small height makes unit ideal for inside ceiling
installations where space is limited.
A double drain pan prevents condensation drops
7/30/2019 Fcu M Leaflet
6/11
Note: Air flow and Performances referred to EUROVENT 6/3 conditions:
1. Cooling: Air temperature entering the unit: 27C d.b.; 19C w.b.; water inlet temperature: 7C; T 5K.2. Heating: Air temperature entering the unit: 20C; water inlet temperature: 50C; water flow rate same as for cooling mode
Model 15BW 20BW 25BW 30BW 020AW 025AW 030AW 040AW 050AW
m3/h (max.) 730 730 850 1030 1310 1380 1560 1740 1840
m3/h (med.) 630 630 770 920 1130 1180 1320 1540 1680Air flow rate (1)
m3/h (min.) 530 530 660 810 1070 1070 1210 1340 1540
kW (max.) 3,7 5,0 5,9 6,8 7,2 8,4 9,6 10,7 11,9
kW (med.) 3,4 4,4 5,4 6,3 6,5 7,5 8,4 9,8 11,1Total coolingcapacity (1)
kW (min.) 3,0 3,8 4,8 5,6 6,2 6,9 7,8 8,8 10,4
kW (max.) 2,9 3,5 4,1 4,8 5,3 6,1 6,8 7,7 8,4kW (med.) 2,6 3,1 3,8 4,4 4,7 5,4 6,0 7,0 7,8
Sensible coolingcapacity (1)
kW (min.) 2,3 2,7 3,3 3,9 4,5 5,0 5,6 6,2 7,3
Water flow rate L/h 640 855 1007 1172 1239 1436 1636 1840 2041
Pressure drop kPa 28 49 82 111 38 51 65 80 97
W (max.) 4,3 5,3 6,1 7,0 7,9 8,9 10,0 11,1 11,8
W (med.) 3,8 4,6 5,6 6,3 7,0 7,8 8,7 10,0 10,9Total heatingcapacity (2)
W (min.) 3,3 4,0 4,9 5,7 6,7 7,2 8,1 8,9 10,2
Water flow rate L/h 640 855 1007 1172 1239 1436 1636 1840 2041
Pressure drop kPa 24 43 71 96 33 44 56 69 84
Power supply 230V 1ph 50 Hz
Power input W 72 72 79 108 127 151 164 192 253
Absorbed current A 0,31 0,31 0,33 0,45 0,53 0,65 0,69 0,80 1,08
Connection inches 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
The new McQuay range of fan coils cassette
offers an excellent conditioning comfort with an
extremely easy installation.
The elegant styled cabinet easily harmonizes
with all interior fashion design while the
attractive grille fully integrates the unit both on
standard panel and on inside ceiling.
7/30/2019 Fcu M Leaflet
7/11
Model 15BW 20BW 25BW 30BW 020AW 025AW 030AW 040AW 050AW
dB (A) (max) 41,0 44,0 44,0 47,0 42,0 45,0 49,0 51,0 53,0
dB (A) (med) 39,0 41,0 40,0 44,0 39,0 42,0 45,0 48,0 52,0
dB (A) (min) 38,0 39,0 38,0 40,0 37,0 40,0 43,0 46,0 50,0
Model 15BW 20BW 25BW 30BW 020AW 025AW 030AW 040AW 050AW
Height mm 293 293 293 293 335 335 335 335 335Length mm 650 650 650 650 820 820 820 820 820
Width mm 650 650 650 650 820 820 820 820 820
Weight Kg 33 33 34 35 35 36 39 42 44
The anti-fungus and dual action ionizer/deodoriser
filters enhance the air quality.
Detection and diagnosis of any faults occurring in the
unit is possible by blinking of the LED lights.
Flexible control type selection in accordance with the
installation requirement
The unit comes with a builtin high head drain pump.Condensate water can be
pumped up to 500mm anddrain out smoothly
The 4 way air discharge andair-swing function will greatlyimprove the air distributionand circulation in the room.Innovative design of highlyefficient turbo fan producing
air circulation in alldirections
7/30/2019 Fcu M Leaflet
8/11
Note: Air flow and Performances referred to EUROVENT 6/3 conditions:
1. Cooling: Air temperature entering the unit: 27C d.b.; 19C w.b.; water inlet temperature: 7C; T 5K.2. Heating: Air temperature entering the unit: 20C; water inlet temperature: 50C; water flow rate same as for cooling mode
Model 005FW 007FW 010FW 15FW 20FW 25FW
m3/h (max.) 340 340 460 510 820 990
m3/h (med.) 290 290 400 460 730 830Air flow rate (1)
m3/h (min.) 240 240 330 390 630 650
kW (max.) 1,4 2,0 2,8 3,5 5,0 6,2
kW (med.) 1,3 1,8 2,6 3,2 4,9 5,4Total coolingcapacity (1)
kW (min.) 1,1 1,6 2,2 2,8 4,3 4,4
kW (max.) 1,2 1,5 2,1 2,5 3,7 4,5kW (med.) 1,1 1,3 1,9 2,3 3,5 3,9
Sensible coolingcapacity (1)
kW (min.) 0,9 1,2 1,6 2,0 3,1 3,2
Water flow rate L/h 214 304 436 553 839 925
Pressure drop kPa 3 6 15 25 27 18
W (max.) 2,2 2,4 3,5 4,0 5,7 7,0
W (med.) 1,9 2,1 3,1 3,6 5,1 6,0Total heatingcapacity (2)
W (min.) 1,6 1,8 2,6 3,1 4,5 4,8
Water flow rate L/h 214 304 436 553 839 925
Pressure drop kPa 3 5 13 21 23 16
Power supply 230V 1 ph 50 Hz
Power input W 23 23 25 25 53 57
Absorbed current A 0,10 0,10 0,11 0,11 0,23 0,24
Connection inches 1/2 1/2 1/2 1/2 1/2 1/2
The Wall Mounted unit has an aesthetically
stylish outlook and an elegant design easy to use
where necessary to combine high performance
and precise interior decoration.
The swing mode enables the air to be distributed
to every corner of the room. While providing a
high flow rate, the random-pitched fan blade
helps to reduce the air noise level.
7/30/2019 Fcu M Leaflet
9/11
Model 005FW 007FW 010FW 15FW 20FW 25FW
dB (A) (max) 38,0 38,0 38,0 38,0 45,0 47,0
dB (A) (med) 34,0 34,0 34,0 35,0 42,0 44,0
dB (A) (min) 30,0 30,0 30,0 31,0 39,0 42,0
Model 005FW 007FW 010FW 15FW 20FW 25FW
Height mm 290 290 290 290 306 306Length mm 815 815 815 815 1062 1062
Width mm 179 179 179 179 202 202
Weight Kg 10 11 12 12 15 15
Dehumidification mode: a computerized control
dehumidifies the surrounding without much change in
temperature.
The air intake grille can be easily removed and
washed with clean water.
3-stage air filtration:1) Antifungus filter to remove dust in
the air as well as bacteriaproliferation
2) Ionizing filter to positively charge dustparticles (0,01 micron) in the air whilethe negatively charged dust collectorattracts them
3) Deodorizing filter to minimizeunpleasant odors from sweat, cigarettesetc.
The compact LCD transmitter is able tooperate the air conditioner unit within thedistance of 9 meters. Fan motor speedcan be set at low/medium/high orautomatic. Sleep mode automaticallyincreases set temperature since roomtemperature is lower at night thusachieving comfort surrounding. Air flowdirection can be controlledautomatically. Room temperature iscontrolled by electronic thermostat. Theunit can be preset to on and offautomatically for maximum of 15 hoursby using timer on/off.
7/30/2019 Fcu M Leaflet
10/11
MONITORING OF FCUSSTATUS AND OVERRIDEFCUSSETTING (ALL,GROUP OR INDIVIDUAL)
MONITORING OF MINI CHILLER STATUS
DETERMINATION OF MINI CHILLER RUNNING MODE(BASED ONFCUSREQUEST)
ALARM MINI CHILLER AND/ORFCUFAULT
ALARM HISTORY
SMART START(START CHILLER EARLIER BEFORE SCHEDULE)
TIME SCHEDULE:7DAYS TIMER SCHEDULE,4 TIMERS IN EACH DAY
HOLIDAY SCHEDULE
Maximises EfficiencyReduces CostsSaves Energy
TTThhheee iiinnnttteeelllllliiigggeeennntttcccooonnntttrrrooolllttthhhaaatttfffuuullllllyyyiiinnnttteeegggrrraaattteeesss ttthhheee
sssyyysssttteeemmmCCChhhiiilllllleeerrr+++ FFFaaannn CCCoooiiilllmmmaaakkkiiinnngggeeeaaasssyyyiiitttsss
cccooommmpppllleeettteee cccooonnntttrrrooolll
7/30/2019 Fcu M Leaflet
11/11
We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding.
McQuay Italia S.P.A.S.S. Nettunense, km 12+300 00040 Cecchina (Roma) Italia Tel. (06) 937311 Fax (06) 9374014 E-mail: [email protected]