Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 1 of 38
NEXGEN PLC
8 Channel Analog Input Module
(Ordering Code 4308)
Document No.:ED-2002-015
Version: 1.01
MESSUNG SYSTEMSEL-2, J- Block MIDC Bhosari,
Pune 411026.(INDIA)
Tel: (+91)-020-2712 0807, 2712 2807.Email : [email protected]
WEB:www.messung.com
mailto:[email protected]:[email protected]://www.messung.com/http://www.messung.com/http://www.messung.com/http://www.messung.com/mailto:[email protected]8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
2/38
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
3/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 3 of 38
INDEX
1. Module Overview ............................................................................................................71.1 Analog Input Module Overview...................................................................................71.2 LED Indications...........................................................................................................91.3 General Specifications..............................................................................................10
2. Module Operation .........................................................................................................112.1 Block Diagram...........................................................................................................112.2 Analog Input types and range of binary values.........................................................122.3 On-Board Processor Operations...............................................................................12
2.3.1 Power On Operations..........................................................................................122.3.2 Analog to Digital Conversion...............................................................................132.3.3 Averaging ............................................................................................................14
2.4 Module Information ...................................................................................................152.4.1 Input Output Image Mapping...............................................................................152.4.2 Memory Mapping ................................................................................................162.4.3 Commands..........................................................................................................172.4.4 Module Status Bits ..............................................................................................17
3. Installations and Wiring ...............................................................................................183.1 Module Installation....................................................................................................183.2 Connection Details....................................................................................................183.3 Precautions to be taken ............................................................................................20
4. Configuration and Programming ................................................................................214.1 Slot Configuration .....................................................................................................214.2 Channel Configuration ..............................................................................................224.3 Programming with Nexgen 4000 CPU......................................................................264.4 Programming with Nexgen 5000 CPU......................................................................30
5. Troubleshooting ...........................................................................................................355.1 LED Indications for Diagnostics................................................................................36
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
4/38
NEXGEN PLC I/O Modules Messung Systems
Published Feb 2004 8 Ch Analog Input Module (4308)Page 4 of 38 Document No.: ED-2002-015/V1.01
Index of Figures
Figure 1 : Front View.................................................................................................................8Figure 2 : Block diagram .........................................................................................................11Figure 3 : ADC Conversion Cycle ...........................................................................................13Figure 4 : Input Output Image Mapping...................................................................................15Figure 5 : Memory Mapping ....................................................................................................16Figure 6 : Connection diagram................................................................................................19
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
5/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 5 of 38
Guidelines for the Safety of the user and protection of I/O Modules.
This manual provides information for the use of the I/O Modules. The manual hasbeen written to be used by trained and competent personnel. The definition of such aperson or persons is as follows:
a) Any engineer who is responsible for the planning, design and construction ofautomatic equipment using the product associated with this manual should be of acompetent nature, trained and qualified to the local and national standards required tofulfill that role. These engineers should be fully aware of all aspects of safety withregards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained andqualified to the local and national standards required to fulfill that job. These engineersshould also be trained in the use and maintenance of the completed product. ThisIncludes being completely familiar with all associated documentation for the saidproduct. All maintenance should be carried out in accordance with established safetypractices.
c) All operators of the completed equipment should be trained to use that product in asafe and coordinated manner in compliance to established safety practices. The
operators should also be familiar with documentation, which is connected with theactual operation of the completed equipment.
Note: The term-completed equipment refers to a third party constructed device, whichcontains or uses the product associated with this manual. Note on the Symbol used inthis ManualAt various times through out this manual certain symbols will be used to highlightpoints of Information, which are Intended to ensure the users personal safety andprotect the integrity of equipment. Whenever any of the following symbols areencountered its associated.
Note must be read and understood. Each of the symbols used is listed below; with abrief description of its meaning.
Warning !
This product can only function correctly and safely if it is transported,stored, setup, and installed correctly, and operated and maintained asrecommended.
Warning !
The specifications of product and contents of manual are subject tochange without notice.
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
6/38
NEXGEN PLC I/O Modules Messung Systems
Published Feb 2004 8 Ch Analog Input Module (4308)Page 6 of 38 Document No.: ED-2002-015/V1.01
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
7/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 7 of 38
1. Module Overview
This chapter describes the followingAnalog Input Module Overview
LED IndicationsGeneral Specifications
1.1 Analog Input Module Overview
This analog input module converts input voltage or current values into equivalentbinary values. This is sigma - delta type A/D conversion. It provides 8 non-isolated channels. The individual channel can be configured for specific typeof voltage or current input. The voltage and current ranges are
-10 to 10V0 to 10 V0 to 5 V
1 to 5 V0 to 20 mA4 20 mA
The resolution of ADC is 305.176 V / 1.221 A for voltage / current input irrespectiveof range. The parameters that are passed to the module for advancedprocessing are
input filter frequency (50 / 60 / 250 / 500 Hz)open circuit valuenumber of averaging samples
The module provides diagnostic information for each channel. It includes open circuit
invalid configuration
This is an intelligent module with on-board processor and memory. The data transferbetween CPU module and analog input module takes place by 'READ_W' /IM_Read and 'WRITE_W' / IM_Write functions in the application program.The module status is available in input image and commands can be issuedthrough output image.
The figure on next page shows front view of analog input module
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
8/38
NEXGEN PLC I/O Modules Messung Systems
Published Feb 2004 8 Ch Analog Input Module (4308)Page 8 of 38 Document No.: ED-2002-015/V1.01
01
02
03
04
05
06
07
11
10
09
08
13
14
15
16
17
18
19
22
21
12
20
23
24
25
26
27
28
29
33
3231
30
35
36
37
38
34
COM 0
V IN0
V IN1
I IN0
I IN1
COM 1
+ 24 V
GND
EARTH
COM 2
V IN2
V IN3
I IN2
I IN3
COM 3
COM 4
V IN4
V IN5
I IN4
I IN5
COM 5
COM 6
V IN6
V IN7I IN6
I IN7
COM 7
NO 24 V SUPPLY
CPU ERROR
CONF. ERROR
CH0
CH1
CH2
CH3
CH4
CH5
CH6
CH7
4308ANALOG INTPUT
8 CH V/I
Figure 1 : Front ViewThe module provides LED indications on the front. Brief information about channel can
be written on the front door. Below the front door, 38-pin removable terminalblock is provided for interfacing analog signals. The connection details areshown on backside of the front door.
Front ShieldPlate
Terminal BlockFixing Screw
ConnectionDetails
Front Door
IO Label
LEDIndications
Channe
StatusLEDs
ModuleStatusLEDs
Terminal BlockFixing Screw
38 PinTerminalBlock
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
9/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 9 of 38
The analog module can be configured in any IO slot of the PLC. The number of analoginput modules is limited by back panel current capacity. In general a channelrequires following information
registers to hold configuration information (2 words)register to hold data (1 word) andregisters to hold status information (1 word)
1.2 LED Indications
The following table explains significance of 11 numbers of LEDs provided on themodule.
No. LED Color Status DescriptionOFF 24 VDC supply to module healthy.
24 VDC supply to module absent.1 NO 24 V SUPPLY OrangeON
24 VDC circuit on-board glass fuse blown.OFF Module hardware healthy and module is ready.
Module in self test.
CPU watchdog faulty.2 CPU ERROR Orange
ONModule busy.
OFF Channel configuration valid.3 CONF. ERROR Orange
ON Channel configuration invalid.OFF Channel not enabledON Channel enabled and healthy
Open circuit for input type 1- 5 VDC and 4 -20 mA.Over range
4Channel Status(Eight for eightchannels)
GreenFlashing
Under range
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
10/38
NEXGEN PLC I/O Modules Messung Systems
Published Feb 2004 8 Ch Analog Input Module (4308)Page 10 of 38 Document No.: ED-2002-015/V1.01
1.3 General Specifications
General specifications of 8 channel analog input module are as given below.
Number of Input channels 8 Non isolated.
Conversion Method Sigma Delta-10 to 10 V DC0 to 10 V DC0 to 5 V DC
Voltage
1 to 5 V DC0 to 20 mA
Analog Inputtypes
Current4 to 20 mAFilterfrequency
Channel Updatetime
Significant bits
50 Hz 60 ms 16 bits60 Hz 50 ms 16 bits250 Hz 12 ms 13 bits
Analog to Digital conversion time
500 Hz 6 ms 10 bitsDigital output -32768 to 32767
Voltage / Current range Significant bits Resolution per LSB-10 to 10 V DC 16 bits 305.176 V0 to 10 V DC 15 bits 305.176 V0 to 5 V DC 14 bits 305.176 V1 to 5 V DC 13.67 bits 305.176 V0 to 20 mA 14 bits 1.2207 A
Number ofsignificant bits( With 50 Hzfilter )
4 to 20 mA 13.67 bits 1.2207 AAmbient at 25C, 5C Ambient at 58C, 5CAccuracy at filter frequency 50 HzLarger value 20 counts or0.1 % of FSD
Larger value 60 counts or0.3 % of FSD
Channel to channel NoIsolation
Channel to internal circuit 1.5 KV opticalVoltage 15 VDCAbsolute maximum
input Current 30 mAVoltage 1 M Ohms
Input ImpedanceCurrent 250 Ohms
External voltage requirement 24 V DC, 200 mA (18 to 30 VDC including ripple)External supply protection 315 mA miniature glass fuse on module
Reverse polarity protection
Indications
No 24 V Supply CPU error Configuration error Channel status (8 nos.)
Back-plane current consumption 210 mAIO points consumed 8 input bits and 8 output bitsTermination Removable 38 pin terminal blockOrdering code 4308
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
11/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 11 of 38
2. Module Operation
This chapter helps in getting started with the analog input module. It describes thebasic operation of the module. This chapter explains operational details of:
Block Diagram
Analog input Types and Range. On-Board Processor Operations Module Information
At the time of application program development, the module can be configured usingthe programming software so that above special features can be used..
2.1 Block Diagram
Block diagram of analog input module is shown below.
Figure 2 : Block diagram
CPUModule
+ 5 V
GND
/ Analog to
DigitalConverter
OPTICAL
ISOL
ATION
On boardProcessor
Memory forConfiguration,Data, StatusInformation
ModuleInterfaceCircuit
WatchDog
Amplifier
Multiplexer
DC-to-DCConverter
+15 V
-15 V
+5 V
-5 V
+ 24 VDC
GND
EarthGND
No 24 V Supply
Supply forADC Circuit
V IN0
I IN0
COM0250
22 K
4K7PF
Tranzorb
Analog Ground
V IN7
I IN7
COM7250
22 K
4K7PF
Tranzorb
Analog Ground
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
12/38
NEXGEN PLC I/O Modules Messung Systems
Published Feb 2004 8 Ch Analog Input Module (4308)Page 12 of 38 Document No.: ED-2002-015/V1.01
The module provides eight analog to digital channels for voltage/ current input. CPUbus is optically isolated from ADC circuit. ADC operates on the data from thechannels. The enabled channel input signals are multiplexed and thenamplified for ADC input. Thus sigma-delta (/ ) ADC converts only enabledanalog channels to digital value one by one. The converted count for eachchannel is manipulated by on-board processor and binary data is transferred
to module memory, which holds channel data information.
If averaging is required, depending on the averaging count, on-board processorperforms averaging of those many previous readings and updates channeldata information.
The configuration, data, status information is available in dual port RAM on themodule. The configuration of all channels is transferred to the module memoryusing WRITE_W / IM_Write function in the application program. Similarly dataand status of all channels can be read by READ_W / IM_Read function in theapplication program.
The module requires external 24 VDC supply for ADC circuit operation. Internally DC-to-DC converter generates 15 VDC and 5 VDC as required by each
channel. If 24 VDC is absent or on-board glass fuse is blown, modulegenerates 'No 24 V Supply' signal for main CPU. The fuse protection forexternal 24 VDC supply is provided on module.
2.2 Analog Input types and range of binary values
This section describes the analog input types and data range of binary values.
Input Type Binary Value Range
-10 to 10 VDC -32000 to 320000 to 10 VDC 0 to 320000 to 5 VDC 0 to 160001 to 5 VDC 3200 to 16000
0 to 20 mA 0 to 160004 to 20 mA 3200 to 16000
2.3 On-Board Processor Operations
The analog input module is intelligent module with on-board processor. The functionsof on-board processor are explained in the sections below.
2.3.1 Power On Operations
After power ON, if 24 V supply to module is absent or on-board fuse is blown then on-board processor sets Ix.0 bit of input image. After power ON, this processorcarries out self test. During self-test and if hardware error is detected, Ix.0 bitis set. Also CPU fault LED on front panel is put ON indicating that module isnot accessible. During module operation, if module hardware is found faulty orwatchdog error is detected, Ix.0 bit is set.
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
13/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 13 of 38
If the module hardware is OK, Ix.0 bit is cleared. The module waits for configurationfrom the CPU module. After reception of valid configuration of input channels,the module starts sampling and digital conversion cycle of enabled channels.
The module continues sampling, converting the channels and updating modulememory even after the PLC is put in STOP mode. But In this case, CPUmodule does not read the channel data and status.
2.3.2 Analog to Digital Conversion
The module samples the input channel and converts voltage or current input to itsdigital value one by one. After power on, as shown in the figure below, onlyenabled channels are converted. If any error like invalid configuration isdetected, channel is not converted. The disabled channels are bypassedretaining earlier values. After one channel conversion, module initiates nextchannel conversion. During this conversion period, module processesconverted data of previous channel. This process includes averaging as perconfiguration. Thus the processed data for previous channel is made availableduring this period. After converting all healthy channels, processed data andstatus information of all the channels is transferred to respective memory areaon the module. This cycle continues. Thus when the processor moduleperforms READ_W operation, it reads either old or new information i.e. dataand status of channels.
Figure 3 : ADC Conversion Cycle
The module takes certain time to sample all enabled channels and convert into digitalvalue. The required time is the module update time. The factors affectingmodule update time is filter frequency selected and number of channelsenabled. The module update time is minimum when only one channel is
enabled. Likewise the module update time is maximum when all channels areenabled.
Channel 0disabled
Channel 1disabled
Channel 2disabled
Channel 3disabled
Channel 7disabled
Channel 6disabled
Channel 5disabled
Channel 4disabled
Channel 0Conversion
Channel 1Conversion
Channel 2Conversion
Channel 3Conversion
Update allchannel dataand status
Channel 7Conversion
Channel 6Conversion
Channel 5Conversion
Channel 4Conversion
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
14/38
NEXGEN PLC I/O Modules Messung Systems
Published Feb 2004 8 Ch Analog Input Module (4308)Page 14 of 38 Document No.: ED-2002-015/V1.01
The module incorporates a digital low pass filter to reject noise on the input signal. Thedigital filter is programmable. It provides better noise rejection for low filterfrequencies. Its noise rejection decreases as filter frequency is increased. Alsofilter frequency affects channel update time. The channel update time reducesas filter frequency is increased. The following shows update times required fordifferent filter frequencies.
Filter Frequency Channel Update time50 Hz 60 ms60 Hz 50 ms250 Hz 12 ms500 Hz 6 ms
2.3.3 Averaging
The module provides user selectable averaging facility so that stable value is availablefor processing and necessary control action. The module samples andconverts enabled channels one by one. The module keeps digital value into
different memory locations. Depending on the averaging count, the moduleperforms averaging of those many previous readings and updates channeldata information.
Thus if the averaging counts of channel 0, 1 and 2 are 0, 4 and 8 respectively, theninitially data of channel 0, 1 and 2 are updated after 1, 4 and 8 conversioncycles respectively. After that, it gets updated in every cycle. One conversioncycle means sampling and converting all enabled channels as explained inchapter 2.3.2.Thus combination of filter frequency and averaging count canbe selected to get optimum channel update time and stable temperaturereading.
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
15/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 15 of 38
2.4 Module Information
This section explains the entire information required and available with analog inputmodule. The following points are discussed.
Input Output Image Mapping Memory Mapping Commands Module Status Bits
2.4.1 Input Output Image Mapping
Input output image mapping related to analog input module is shown below.
Figure 4 : Input Output Image Mapping
The module consumes 8 input bits (1 byte) of input image and 8 output bits (1 byte)of output image. CPU reads the status of module in input scan. CPU writesuser commands to module in output scan. For immediate updation of inputand output image in application program, IMM_IN / Refresh_In and IMM_OUT
/ Refresh_Out functions can be used in application program wheneverrequired. For the details refer chapter 2.4.3and 2.4.4.
CPU Module
Input ImageNo 24 V Supply or
CPU fault. Ix.0Invalid configuration
or out of range.Ix.1
ModuleInterface
circuit
Output ImageAuto calibration Qx.0
Input Scan
Logic Scan
SLOT
ENO
IMM_IN
EN
Output Scan
Logic Scan
SLOT
ENO
IMM_OUT
EN
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Analog Input Module
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
16/38
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
17/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 17 of 38
2.4.3 Commands
As discussed in chapter 2.4.1,output image bits are used as user commands tomodule. User can issue various commands to module through application
program. CPU writes commands in output image area of module in outputscan. The module reads output image area cyclically and takes appropriateaction. If 'IMM_OUT' / Refresh_Out function is executed in logic scan for aparticular slot, it stops current logic scan, executes output scan for defined slotand resumes logic scan again. This is useful when ever immediate updation ofoutput image is needed. The functions of output image bits are given below.
No.Bit
AddressCommand Status Description
ON It gives command to ADC to calibrate itself.1 Qxx.0
AutoCalibration
OFF Auto calibration command is OFF.
Note Qxx.1 to Qxx.7 are reserved and should not be used.
Normally, ADC is calibrated during self test after power ON and when ever 24 VDCpower to the module is switched ON. Also, it is calibrated at regular intervalduring operation. The output image bit Qxx.0 is additional facility to the user tocalibrate ADC when ever required.
2.4.4 Module Status Bits
As discussed in chapter 2.4.1,input image bits are used as module status indications.User can check the module status through application program. The modulewrites status in its input image area cyclically. The CPU reads this input imagearea in input scan. If 'IMM_IN' / Refresh_In function is executed in logic scanfor a particular slot, it stops current logic scan, executes input scan for defined
slot and resumes logic scan again. This is useful when ever immediateupdation of input image is needed. The functions of input image bits are givenbelow
No. Bit Address Module Status Status Description24 VDC supply to module absent24 VDC circuit fuse blown.Module CPU watch dog fault.
ON
Module not ready.24 VDC Supply to module healthy
1 Ixx.0 Module Not Read
OFFModule healthy and readyInvalid static configuration
ONParameter mismatchValid static configuration
2 Ixx.1InvalidConfiguration or
Open circuit OFF Valid parameters
Note Ixx.2 to Ixx.7 are reserved and should not be used.
Whenever accessing the module, user must check the module status bit Ixx.0.
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
18/38
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
19/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 19 of 38
Figure 6 : Connection diagram
In figure, first channel is configured for voltage input where as fourth channel isconfigured for current input.
For interfacing analog signals, 38 pin removable terminal block is provided. Thevoltage input is connected to terminals V INnand COMn. Here n is channelnumber from 0 to 7. Current Input is connected to terminals I INnand COMn.To connect current input, short terminals V INnand I INnfor respectivechannel. This is shown for the channel 3 in figure.
Voltage Input connectedto channel 0
+ 24 VDCGND
EARTH
01
02
03
04
05
06
07
11
10
09
08
13
14
15
16
17
18
19
22
21
12
20
23
24
25
26
27
28
29
3332
31
30
35
36
37
38
34
COM 0
V IN0
V IN1
I IN0
I IN1
COM 1
+ 24 V
GND
EARTH
COM 2
V IN2
V IN3
I IN2
I IN3
COM 3
COM 4
V IN4
V IN5
I IN4
I IN5
COM 5
COM 6
V IN6
V IN7
I IN6
I IN7
COM 7
+
-
Current Input connected tochannel 3
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
20/38
NEXGEN PLC I/O Modules Messung Systems
Published Feb 2004 8 Ch Analog Input Module (4308)Page 20 of 38 Document No.: ED-2002-015/V1.01
Being susceptible to industrial noise, analog signal is to be carried out on the fieldthrough shielded twisted cable. Connect both ends of shield to Earth busbarin control panel.
For functioning of analog input module, external 24 VDC supply is required. Connect24 VDC supply between terminals 36 (+ 24 V) and 37 (GND). Connect terminal38 to earth busbar in the control panel.
3.3 Precautions to be taken
All the normal precautions concerning the wiring and protection of an electronicequipment in an industrial environment should be observed. To guard againstcoupling noise from one conductor to another, follow the guidelines givenbelow.
Inside control panel
Following guidelines to be observed inside control panel.
All power circuit wiring e.g. connected to Power Supply Module, powercontactors, etc i.e. high voltage wiring should be kept separate andapart from analog signals.
Digital Input wiring and Digital Output wiring (especially, relay outputand AC output) should be separately bundled and kept as apart aspossible from analog signals.
Analog signals should be carried through shielded cables.
Outside control panel
Following guidelines to be observed outside control panel.
Depending upon the type of modules used in PLC, separate ducts should be providedfor
Power circuit wiring and power cables. Input cables. Output cables. All cables carrying low level signals for analog IO modules,
thermocouple/ RTD input modules, for communication, high frequencypulse input and output.
Wherever possible, it is recommended to Avoid parallel routing of cables carrying analog signals and power
cables, etc over long distances Ensure that cables carrying analog signals cross at right angles to
power cables so that minimum length of cable will be in close vicinityof power cables.
Run cables on metallic surfaces Avoid number of joints Keep cable lengths as short as possible.
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
21/38
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
22/38
NEXGEN PLC I/O Modules Messung Systems
Published Feb 2004 8 Ch Analog Input Module (4308)Page 22 of 38 Document No.: ED-2002-015/V1.01
4.2 Channel Configuration
The analog input module can be configured in any slot of the PLC. The 8 channelscan be independently configured for different types of analog inputs.
After power on the configuration of one or more channels can be transferred to themodule using WRITE_W / IM_Write function. The PLC variables hold channel
configuration. The channel configuration information includes Input typeFilter frequencyOpen circuit valueChannel Enable
Averaging
The configuration of channels is to be written at module memory adress starting from256. This information is stored in bit form in 2 consecutive words for eachchannel. The tables below give information required to configure any channel.The valid combination of bits must be set. Any invalid combination of bits mayresult in unpredictable module operation.
Configuration word 1 for a channel -
Item Description 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0-10 to +10V 0 0 0 0 00 to 10V 0 0 0 0 10 to 5V 0 0 0 1 01 to 5V 0 0 0 1 10 to 20mA 0 0 1 0 0
InputType
4 to 20mA 0 0 1 0 150 Hz 0 0 060 Hz 0 0 1250 Hz 0 1 0
Filterfrequency
500 Hz 0 1 1Zero 0 0Upper scale 0 1
Lower scale 1 0
Open
CircuitValueInvalid 1 1
Reserved -- 0Disabled 0Channel
Status Enabled 1Reserved 0 0 0 0
Configuration Word 2 for a channel -
Item Description 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 00 0 04 0 18 1 0
Averaging
16 1 1
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
23/38
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
24/38
NEXGEN PLC I/O Modules Messung Systems
Published Feb 2004 8 Ch Analog Input Module (4308)Page 24 of 38 Document No.: ED-2002-015/V1.01
The module detects open circuit of a channel for 4-20 mA and 1 to 5 V input types. Insuch open circuit condition, the channel value can be set to any one of aboveoptions considering safety in control action. If such open circuit is detected fora channel, corresponding channel LED starts flashing.
Channel Enable
Bit11 defines the enable status of the channel. If it is 0 Channel is disable and if it is1 Channel is enable. The module samples only enabled channels andconverts into digital value. Thus enabling only used channels can minimize thechannel update time.
Bit12 to Bit15 are reserved and these must be 0
Averaging
Next two Bits, Bit16 and Bit 17 define the selection of sampling value for averaging.
Bit16 Bit17 Averaging Sample0 0 No0 1 41 0 81 1 16
The module provides averaging facility so that stable value is available for processingand necessary control action. The module samples and converts enabledchannels one by one. The module keeps digital value into different words.Depending on the averaging count, the module performs averaging of thosemany words and updates channel data information.
Thus if the averaging counts of channel 0, 1 and 2 are 0, 4 and 8 respectively, then
data of channel 0, 1 and 2 are updated every 1, 4 and 8 conversion cyclesrespectively. One conversion cycle means sampling and converting allenabled channels. Thus combination of filter frequency and averaging countcan be selected to get optimum channel update time.
Channel Data
The module memory words MMW #0 to MMW #14 are module memory words forchannel data. For enabled channels, this information is updated cyclically inmodule. The data is read and stored in PLC variables using READ_W /IM_Read function in application program.
MMW#0 Channel 0 dataMMW#2 Channel 1 data
MMW#12 Channel 6 dataMMW#14 Channel 7 data
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
25/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 25 of 38
Channel Status
The module continuously updates status of all channels into its memory. Theprocessor module can read the status information as required using READ_Wfunction. This information is also useful to check validity of configuration data.
This status information is stored in bit form in one word for each channel starting frommodule memory address 16. The following table gives status bit informationavailable.
Item Description 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0-10 to +10V 0 0 0 0 00 to 10V 0 0 0 0 10 to 5V 0 0 0 1 01 to 5V 0 0 0 1 10 to 20mA 0 0 1 0 0
InputType
4 to 20mA 0 0 1 0 150 Hz 0 0 0
60 Hz 0 0 1250 Hz 0 1 0Filterfrequency
500 Hz 0 1 1Zero 0 0Upper scale 0 1Lower scale 1 0
OpenCircuitValue
Invalid 1 1Reserved -- 0
Disabled 0ChannelStatus Enabled 1
Valid 0ConfigInvalid 1No open circuit 0Open
Ckt. Open circuit 1No under range 0Under-
range Under range 1No over range 0Over
range Over range 1
The copy of Bit 0 to Bit 11 from configuration word is available in status word as it is.This information is useful to check validity of configuration as written byWRITE_W function when ever configuration is set or modified. The applicationprogram should confirm validity of configuration before reading channel data.
MMW#16 Channel 0 statusMMW#18 Channel 1 status
MMW#28 Channel 6 statusMMW#30 Channel 7 status
The copy of Bit 0 to Bit 11from configuration word.
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
26/38
NEXGEN PLC I/O Modules Messung Systems
Published Feb 2004 8 Ch Analog Input Module (4308)Page 26 of 38 Document No.: ED-2002-015/V1.01
Configuration Error
Bit 12 of status word is set ifInvalid configuration is writtenBit 12 to 15 in configuration word are non zero
If configuration error bit is set, configuration Error LED ( yellow colour )on moduleglows.
Open Circuit Error
Open circuit detection is applicable forInput type 1 to 5 VInput type 4 to 20 mA
Bit 13 of status word is set ifInput voltage is less than 0.75 V for input type 1 to 5 VInput current is less than 3 mA for input type 4 to 20 mA
If open circuit error bit is set for a channel , corresponding input indication LED (green
colour) on module starts flashing. The channel data holds the data as perconfiguration. It can be zero or upper scale reading or lower scale reading.
4.3 Programming with Nexgen 4000 CPU
The configuration data in PLC variables is transferred to the analog input modulewhen 'WRITE_W' function is executed. The data in the PLC variables can beupdated using functions like 'MOV_W', arithmetic or any other functions. Thedata from analog input module memory can be transferred to PLC variableswhen 'READ_W' function is executed.
The WRITE_W function below shows data transfer from the CPU module's memory toanalog input module memory. The details of transfer are - The analog input module is configured in slot 2 of PLC Start address of memory on the CPU module is MW50 Length of data area to be transferred is 16 words Address on the analog input module in slot 2 is #256
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
27/38
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
28/38
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
29/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 29 of 38
When 'WRITE_W' function is executed successfully, ENO output becomes ON, WhenENO is ON, set 'Static Configuration Write' command bit informing the moduleto accept the static configuration or change in configuration. Once thisinformation is transferred to module, it is valid as long as PLC power ispresent. It is recommended to enable 'WRITE_W function when
Warm start is observed i.e. System bit S0.6 is ON
Cold start is observed i.e. System bit S0.7 is ON Module Error bit becomes OFF i.e. System bit S4.2 is ON Module Not OK bit becomes OFF i.e. Input bit I8.0 is ON.
S0.6 ------ WRITE_W ---- M3.0+---| |---+---------+---------|EN ENO|-+---(S )---
| | |S0.7 | | |
+---| |---+---------| #2 -|SLOT || | |
S4.2 M0.4 | | |+---| |---+---|N|---| MW66 -|DATA |
| | |I8.0 M0.5 | | |
+---| |---+---|N|---+ #16 -|LEN |
| || |
#256 -|ADDR || |-------------------
S4.2 M3.4 M3.0+---| |---+---|P|---+---------|--------|---------|---(R )---|
||
I8.0 M3.5 |+---| |---+---|P|---
If 'WRITE_W' function is executed, M3.0 bit is set. If this bit is not ON even if function
enable conditions are ON, declare fault and take appropriate action. The bitM3.0 is reset. If any error is detected.
After transferring configuration data to analog module memory, module configures thechannels and starts functioning accordingly. It takes about 500 ms time formodule to take necessary action if configuration is changed. So after a properdelay (say 1 sec), enable 'READ_W' function. When 'READ_W' function isexecuted, the binary values of channels stored in module memory MMW#0 toMMW#14 are transferred to CPU memory MW#100 to MW#114 respectively.
M3.0 S4.2 I8.0 ---- TON100MS ----- M3.1+---| |---+---|/|---+---|/|---|EN ENO|-+---( )---
| || |
#10 -|PT ET || || |
T#10 -|TNO || |
---------- -------------------
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
30/38
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
31/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 31 of 38
The IM_Write function below shows data transfer from the CPU module's memory toanalog input module memory. The details of transfer are -
The analog input module is configured in slot 2 of PLC The configuration information is stored in an 16 word array Config Length of data area to be transferred is 32 bytes Address on the analog input module in slot 2 is 256
'IM_Write' function gets executed when BOOLean input 'Config_Wr' is TRUE.BOOLean output 'Config_Dn' becomes TRUE, when function is executedsuccessfully. It is is FALSE if
Parameters of function are invalid or not within specified range. analog input module is not accessible to CPU module
So 16 words configuration information from CPU memory is transferred to the memoryat address 256 onwards of analog input module fitted in slot 2.
The 'IM_Read function shows data transfer from the analog input module memory toCPU memory. The details of transfer are -
The analog input module is configured in slot 2 of PLC Address on the analog input module in slot 2 is 0
The data to be stored in PLC variable array AIData Length of data area to be transferred is 8 words
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
32/38
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
33/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 33 of 38
Configuration Word 1 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 016#801 0 0 0 0 1 0 0 1 0 0 0 0 0 0 0 1
Configuration Word 2 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 016#3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1
So configuration words should contain 2049(16#801) and 3, for the configurationrequired. This information is transferred to analog module memory MMW256to MMW286, when 'IM_Write' function is executed. The application programrequired to handle analog input module is shown below along with commentsand PLC variable declaration.
Reserved Returnvalue ofupper
scaleChannelEnable
50 HzFilter
010 VDC type oinput
16averaginsamples
Reserved
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
34/38
NEXGEN PLC I/O Modules Messung Systems
Published Feb 2004 8 Ch Analog Input Module (4308)Page 34 of 38 Document No.: ED-2002-015/V1.01
Once analog input data is read successfully, the data can be processed as theapplication requirement. If anaolg input data read is to be displayed on HMI orSCADA, the varaible AIData should be mapped to any memory varaible whiledeclaration like
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
35/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 35 of 38
Here the analog input data for the channels is stored in memory variable %MW100 to%MW114 in integer format. Channel 0 data is stored in %MW100 whilechannel 7 data is stored in %MW14.
If input image bit %IX4.0 or %IX4.1 is TRUE, the appropriate error should be declaredand further processing of anaolg input data read should be hold.
If input image bit %IX4.1 is TRUE, the status of all the channels can be read andindividual channel error and exact cause can be located with the help of anapplication program as shown below.
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
36/38
NEXGEN PLC I/O Modules Messung Systems
Published Feb 2004 8 Ch Analog Input Module (4308)Page 36 of 38 Document No.: ED-2002-015/V1.01
5. Troubleshooting
In this chapter, following points related to analog input module are discussed.
LED Indications for diagnostics
5.1 LED Indications for Diagnostics
The following table explains significance of LED provided for module status anddiagnostic purpose on the module.
No. LED Color Status DescriptionOFF 24 VDC supply to module healthy.
24 VDC supply to module absent.1 NO 24 V SUPPLY OrangeON
24 VDC circuit on-board glass fuse blown.OFF Module hardware healthy and module is ready.
Module in self test.CPU watchdog faulty.2 CPU ERROR Orange ONModule busy.
OFF Channel configuration valid.3 CONF. ERROR Orange
ON Channel configuration invalid.OFF Channel not enabledON Channel enabled and healthy
Open Circuit for input type 1- 5 VDC and 4 -20 mA.Over range
4Channel Status(Eight for eightchannels)
GreenFlashing
Under range
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
37/38
Messung Systems NEXGEN PLC I/O Modules
8 Ch Analog Input Module (4308) Published Feb 2004Document No.: ED-2002-015/V1.01 Page 37 of 38
8/12/2019 ED-2002-015 8 Ch Analog Input Module (4308).pdf
38/38
NEXGEN PLC I/O Modules Messung Systems
Published Feb 2004 8 Ch Analog Input Module (4308)Page 38 of 38 Document No : ED-2002-015/V1 01
MESSUNG SYSTEMS