  • 8/3/2019 delMP

    1/4

    48

    Three-phaseUPS DELPHYSMP

    from 60 to 200 kVAyour protection up to 1 200 kVA

    There are two versions to meetyour requirements:

    DELPHYSMP with an SCR rectifier,

    DELPHYSMP elitewith an IGBT rectifierfor a sinusoidal current intput.

    High quality power supply

    Delivered by SVM digital modulation(Space Vector Modulation).

    Adapted to supplying new IT loads with aleading power factor up to 0.9.

    With sinusoidal voltage for non-linear loads(Crest Factor 3:1).

    High availabilityA fault tolerant architecture with redundancy

    of basic functions, such as the ventilationsystem.

    A variety of architectures for paralleloperations, to deal with redundancy,management and changes in poweroutput.

    Easily integrated equipment

    An IGBT rectifier which virtually eliminatesharmonic distortion, thus removing anystress on your power supply network.

    Reduced current consumption due to an

    input power factor of: 0.99.

    The ideal solution for grouping withgenerator sets without using an excessivelylarge generator.

    Battery availability at all timesAn innovative load algorithm which adapts

    to the environmental conditions and thecondition of the battery to increase its life.

    A highly-developed monitoring system,capable of locating and correcting anyproblems interacting with the chargingdevice.

    Cost effective equipment

    A compact unit for a smaller footprint.

    An IGBT rectifier, which reduces the need toinvest in infrastructure (generator anddistribution).

    The ENERGY SAVER function, in parallelmode, to optimise efficiency and operatingcosts.

    User-friendly operation

    A control panel with graphic display formore ergonomic operation.

    An array of com-slot plug-in communicationinterfaces, for upgrading your operatingrequirements.

    Simplified maintenance

    An advanced diagnostic system.

    A remote access device connected to theremote maintenance centre.

    Easy access to subassemblies andcomponents, facilitating tests and reducingmaintenance time (MTTR).

    > Data centre> Industry

    > Telecommunications> Processes

    Your protectionfor

    DEFYS

    121A

    1CAT

  • 8/3/2019 delMP

    2/4

    49

    Three-phaseUPS DELPHYSMP

    from 60 to 200 kVA

    The SVM digital modulation SVM (Space Vector Modulation) fitted to the transformer

    integrated downstream of the inverter allowssupply to your installations with:

    precise voltage even when the loadbetween phases is completely unbalanced,

    stable output voltage during significant andquick variations in loads ( 2 % in less than5 ms),

    sinusoidal THDV output voltage < 2% withlinear loads and < 3% with non-linearloads,

    active power without de-rating, with loadswith a lagging power factor and up to 0.9

    leading, a high short-circuit capacity, up to 4 In,

    which facilitates the selection of protectivedevices for selectivity in the downstreamdistribution,

    secure galvanic isolation between the DCbus and supplied units.

    High quality power adapted to new IT loads

    Guaranteed available back-up time

    DELPHYSMP eliteeasy to integrate into your electrical networkA clean IGBT rectifier

    It eliminates any disturbance on theupstream network (source and distribution).

    The cutting rectifier guarantees the supplyof current with an exceptionally low rate ofharmonic distortion: THDI < 2.5%.

    A consistent rectifier

    The performance of the IGBT rectifier isindependent of frequency variations thatcould be produced by the generating set.

    The power factor and THDI at the rectifierinput are constant whatever the batterycharge status (continuous voltage level)and the load rate of the UPS.

    [Info. p. 91]

    An economical IGBT rectifier

    The power factor upstream of the rectifier:0.99 lagging, reducing the kVA used by30% when compared with conventionaltechnology. The reduction in input currentresults in a saving in terms of the scale ofsources, cables and protective devices.

    Rectifier capabilities:

    - low upstream THDI,- gradual, timed restarting,- possibility of suspending battery rechargewhen operating with a generator set, allowthe impact caused when the generator set isengaged and the energy used to be reduced,along with the footprint.

    EBS technology (Expert Battery System)

    This exclusive feature prolongs battery life.

    It carries out the charge according to analgorithm which adapts to the environmentalconditions and the condition of the battery.

    It reduces corrosion and drying out of theseparators often caused by permanentfloating loads.

    It reduces the residual ripple of the current,one of the causes of premature battery wear.

    BHC Technology (Battery Health Check)

    Guaranteed battery availability:

    the battery and DC circuit are regularlyautomatically tested and the operator isnotified of their condition,

    the optional BHC function tests andanalyses the following parameters: currentby branch, voltage by segment or block. Incase of drift, the interactive systemautomatically takes corrective charging

    measures. If the drift continues, an alarmwith the location of the failure (branch,segment or block) allows the necessarypreventive repairs to be made.

    DEFYS

    127A

    1CAT

    DEFYS

    036A

    2CAT

    DEFYS

    091B

    GB

    100%kva

    100%

    kVA

    cosos0,60,6cosos0,70,7cosos0,80,8 cosos0,80,8cosos 0,90,9cosos0,90,9

    0,25,25

    0,50,50

    0,75,751 cosos

    11100% kW00% kW

    kWW

    Without deratingithout derating

    -1 -0,8 -0,6 -0,4 -0,2 0 0,2 0,4 0,6 0,8 1

    cos0,6

    cos0,7cos0,8

    cos0,8cos 0,9cos0,9

    0,25

    0,50

    0,75

    1cos 1100% kW

    kVAr

    kW

    Without derating

    LEADINGEADING LAGGINGAGGINGLEADING LAGGING

  • 8/3/2019 delMP

    3/4

    50

    Parallel systems

    IT-SWITCH

    LTM 1

    LTM 2

    Load 1

    Load 2

    Load 3

    DELPHYS

    MPelite

    DELPHYS

    MPelite

    ACS

    ACS

    In order to meet the most demandingavailability requirements, and the need for

    the installation to be flexible andupgradable, up to 6 DELPHYSMP can runin parallel.

    DELPHYSMP modular,

    development without constraint.

    DELPHYSMP centralised bypass,

    progressive development.

    DELPHYSMP redundant bypass,

    yet more availability.

    DELPHYSMP double bypass,

    to simplify operation.

    DELPHYSMPmulti bypass,

    to separate application types.

    DELPHYSMP a twin channel architecturewith Static Transfer Systems: LTM andIT SWITCH[Info. p. 66 and 70].

    DEFYS

    093A

    DEFYS

    094A

    DEFYS

    065A

    DEFYS

    059B

    DEFYS

    026A

    DEFYS128A

    GB

    Three-phaseUPS DELPHYSMP

    from 60 to 200 kVA

    Standard equipment

    Slots for 7 communication boards.

    Protection backfeed: detection circuit.

    Standard interface:- 3 inputs (emergency stop, generating set,

    battery protection),- 4 outputs (general alarm, back-up, bypass,

    preventive maintenance needs).

    Accessories

    BHC battery unit monitoring.

    EBS (Expert Battery System)[Info. p. 99].

    Colour touch screen.

    ACS function for synchronisation with anexternal source[Info. p. 68 and 72].

    Reinforced IP protection degree.

    Ventilation filters.

    Ventilation control.

    Communication options

    Remote control panel.

    ADC (Advanced Dry Contacts) data inputand output by dry contacts[Info. p. 98].

    RS232, RS422, RS 485 serial portJBUS/MODBUS or PROFIBUS protocol[Info. p. 98].

    NET VISIONinterface for the LAN Ethernetnetwork[Info. p. 87].

    TOP VISIONsoftware for supervision withWindowsTM [Info. p. 89].

    Remote maintenance

    e.SERVICE for continuous monitoring theSOCOMEC SICON UPS maintenanceservice.

    [Info. p. 100]

    Preventive maintenancerequest

    Access to installation mimicpanel

    UPS load rate(bar graph)

    Help menu forcorrect operation

    DEFYS

    111A

    GB

    Graphic display

    Design adapted to the user: control panel with LEDs and LCD display.

    Colour touch screen

    The operator has access to the control functions with only a few intuitive touches of the screen.

    Quick access to eachinstallation module

    Direct access zonesto sub-unit menus

    Status bar

    DEFYS

    102A

    Operating modeicons

  • 8/3/2019 delMP

    4/4

    51

    Three-phaseUPS DELPHYSMP

    from 60 to 200 kVA

    Automatic

    Bypass

    Maintenance

    Bypass

    Rectifier Inverter

    Battery

    Q4

    Q5

    Q3

    Q20

    Bypass cabinet

    The coupling and centralised bypass functions.

    On line double conversion[Info. p. 91]

    1930

    800W

    60 800 280

    80 800 280

    120 800 280

    200 800 300

    250 800 300

    300 800 320

    400 800 320

    500 800 330

    800 1000 420

    1200 1300 600

    DEFYS

    125A

    GB

    Technical data

    RECTIFIER INPUT

    TechnologyDELPHYSMP SCRDELPHYSMP elite PFC - IGBT

    Voltage three-phase 380 V - 400 V - 415 V (1)

    Acceptable tolerance 340 to 460 V

    Frequency 50 - 60 Hz (45 to 65 Hz)

    Power factor: DELPHYSMP elite 0.99

    Distortion rate: DELPHYSMP elite THDI: 2.5%

    OUTPUT

    Voltage (configurable) three-phase + N 380 V - 400 V - 415 V (1)

    Voltage toleranceStatic load < 1%Dynamic load conditions from 0 to 100% 2 % in 5 ms

    Voltage distortion rate THDU < 2%

    Acceptable crest factor without de-rating 3:1

    PF acceptable without de-rating lagging to 0.9 lead.

    Frequency (configurable) 50 - 60 Hz

    Autonomous frequency tolerance 0.2%

    Overload 1 min: 150%10 min: 125%

    EfficiencyGlobal (2) up to 93.5%In ECO-MODEconfiguration 98%

    ENVIRONMENT

    Noise level (ISO 3746)(2) 68 dBA

    Compliance to standardsSafety IEC62040-1-2/IEC60950EMC IEC62040-2Technical data IEC62040-3

    Classification as per IEC62040-3 UPS VFI (3) - SS - 111

    (1) Three-phase 220-230-240V on demand. - (2) As per power range. - (3) Voltage Frequency Independent.

    DEFYS

    124B

    GB

    UPS and batteries

    A compact and integrated system.

    DEFYS

    126A

    F

    60/48 640 680 800 800 800 1000

    80/64 660 700 800 1000 800 1300

    100 / 80 790 820 800 1300 800 1700

    120 / 96 810 840 800 1700 1600 1900

    160 / 128 920 970 1600 1900 1600 2500

    200 / 160 950 1000 1600 2500 2400 3000

    1930

    800A*

    B

    * DELPHYSMP A = 800 mm

    DELPHYSMP elite A = 1000mm

    Bypass transformer

    For galvanic isolation.

    1930

    800W

    60 600 400

    80 600 450

    120 600 550

    200 800 850

    300 1000 1250

    400 1200 1500

    DEFYS

    087A

    GB

    (1) For other power ranges, please consult us.

    UPS DELPHYSMP DELPHYSMP Battery for back-up timeelite 10 minutes 15 minutes

    UPS power Weight Weight B Weight B Weight

    kVA/kW kg kg mm kg mm kg

    Power(1) W Weight

    kVA mm kg

    Power(1) W Weight

    kVA mm kg