B YC H R I S P . R O U S S E A U , P E , L E E D A P B D + C
Updates to ANSI/ASHRAE/ASHE Standard 170-2008,
Ventilation of Health Care Facilities
27th Annual AHCA/FHEA SeminarOrlando, Florida
September 26, 2011
History of Standard
a. Roots in ASHRAE Standard 62 and AIA Guidelinesb. First ASHRAE Standard to be co-sponsored with ASHEc. First Standard Project Committee Meeting – 2002d. Standard Issued – 2008e. Standing Committee Status – 2009f. Included as Part 6 in FGI Guidelines - 2010
Addenda – Overall Status
7 Addenda Approved 1 Addendum Rescinded 1 Addendum on Hold 3 Addenda Reviewing Public Comments 2 Addenda Pending ASHRAE Approval for Public
Review 6 Addenda in Committee
Addendum a
Status – Approved Topic – Miscellaneous Revisions/Clarifications
Revised newborn intensive care temperature Clarified “corridor” requirements Clarified RH range requirements – “min/max allowable at any
point within the design temperature range required for that space”
Addendum a Table
©2011 American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc. (www. ashrae.org) Reprinted by permission from 2011 ASHRAEStandard 70-2008. This material may not be copied or distributed in either paperor digital form without ASHRAE’s permission.
Addendum b
Status - Approved Topic – Miscellaneous Revisions/Clarifications
Changed MERV 17 to HEPA Exempted relief air from outside air intake limitations Required individual temperature control for operating rooms Added differential pressure requirement for morgue and autopsy Table 7-1 changes:
-added intermediate care, revised triage, radiology waiting-added “design” to RH column header-allowed recirculated room HVAC units in laboratories-revised pressure relationship requirements for critical and intensive care and burn units-corrected endoscopy air change rate
Addendum b Table
Addendum c
Status - Rescinded Topic - Recirculating Room HVAC Units
Addendum d
Status - Approved Topic - Critical Area Humidity Requirements
Reduced minimum relative space humidity from 30% RH to 20% RH in these short stay spaces:
Class B and C Operating RoomsOperating/Surgical Cystoscopic RoomsDelivery RoomsTreatment RoomsTrauma RoomsLaser Eye RoomsClass A Operating/Procedure RoomsGastrointestinal Endoscopy Procedure Rooms
Addendum e
Status - Approved Topic - Exhaust Ductwork Clarification
Exhaust ductwork negative anywhere in the building Interior exhaust ductwork on discharge side of fan - Seal Class A
Addendum f
Status - Approved Topic - AII Anterooms/Combination AII/PE Rooms
AII rooms may be used for non-infectious patients No specific pressure differential required between AII Room and
associated toilet room Differential pressure monitoring of AII and PE rooms required Anteroom requirements (if provided) Combination AII/PE Rooms
Addendum f Table
Addendum g
Status - Approved Topic - Displacement Ventilation
Allows Group D diffusers for single bed patient rooms Includes minimum requirements for design of displacement
ventilation systems
Addendum g Table
Addendum h
Status - Approved Topic - Recirculating Room HVAC Units
All ventilation air must be filtered per Table 6-1 Rules for recirculating room HVAC units
- all outside air supplied to units must be filtered and conditioned- may only serve a single space- MERV6 filter required if any surface designed to condense
moisture Recirculated airflow counts towards Total Air Change Rates
required by Table 7-1
Addendum i
Status - On Hold Topic - Alternate Compliance Method
Addendum j
Status - Reviewing Public Comments Topic - Nursing Home Requirements
Restored requirement for second filter bank (MERV 13) in skilled nursing, sub-acute care, and dementia facilities
Restored filtration requirements for hospice and assisted living facilities (MERV 7)
Added ventilation requirements for resident corridors and personal services spaces
Addendum k
Status - In Committee Topic - Energy Recovery
Looking at 3 types of systems:- No potential for cross-contamination (run around coils) (0%)- Some potential for cross-contamination (heat pipes, air to air
heat exchangers) (<2%)- More potential for cross-contamination (rotating wheels) (<5%)
AII Rooms – 0% Areas with potential airborne contaminates (ER waiting, autopsy,
lab, bronchoscopy, etc.) - <2% Other spaces - <5%
Addendum l
Status - Reviewing Public Comments Topic - Caesarean Delivery Rooms/New Spaces
Operating/surgical cytoscopic rooms and caesarean delivery rooms have same air distribution requirements as Class B and C operating rooms
New spaces added to Table 7-1
Addendum l Table
Addendum m
Status - Reviewing Public Comments Topic – Ducted Return Air Systems
In addition to spaces listed in Table 7-1 that have differential pressure requirements, these spaces also must be served by ducted return air systems:
- Recovery Rooms- Critical and Intensive Care- Intermediate Care- Burn Unit
Addendum n
Status - Pending ASHRAE Approval for Public Review
Topic - Ventilation Air Quantity Calculations Minimum ventilation rate – sum of room totals based on Table 7-1 Alternate approach – Ventilation Rate Procedure (multiple space
formula) in Standard 62
Addendum o
Status - In Committee Topic - Office Surgeries
Addendum p
Status - Pending ASHRAE Approval for Public Review
Topic - Nourishment Stations Added ventilation requirements for nourishment stations in Table
7-1
Addendum p Table
Addendum q
Status - In Committee Topic - Pharmacy Pressure Relationships
Clarifies potential negative pressure requirements for areas compounding hazardous chemicals (USP 797)
Addendum r
Status - In Committee Topic - Coordination with FGI
Add definitions of “Absorption Distance” and “Essential Accessories”
Delete second filter bank for psychiatric facilities Require coordination between air handling unit zones and smoke
zones to minimize smoke dampers Allow high returns in operating rooms, in addition to low returns Require - 0.01” differential pressure for bronchoscopy Require continuous operation of operating and caesarean delivery
room ventilation systems
Addendum s
Status - In Committee Topic - Humidifier Types
Steam humidifiers only
Addendum t
Status - In Committee Topic- Additional FGI Coordination
Definition of volume of ER and Radiology waiting areas Duct lining requirements Anesthesia scavenging Unoccupied mode of operation for operating rooms and AII rooms
Republication
Anticipated 2013 Part of 2014 Guidelines
Future Issues
Return Air Plenums in Outpatient Occupancies Rooftop Air Handling Unit Gas Vents Chilled Beam Systems Individual Room Temperature Control ER Exam Room Ventilation Requirements
Questions?