unit 3

62
www.ravivarmans.hpage.com with some simple PV applications in today’s society, such as calculators and

description

RES Renewable Energy Souces

Transcript of unit 3

Page 1: unit 3

www.ravivarmans.hpage.com

with some simple PV applications in today’s society, such as calculators and

— —

Page 2: unit 3

www.ravivarmans.hpage.com

Page 3: unit 3

www.ravivarmans.hpage.com

Page 4: unit 3

www.ravivarmans.hpage.com

Page 5: unit 3

www.ravivarmans.hpage.com

method is known as phase control and converters are also called “phase contro

converters”. Since thyristors can block voltage in both directions it is possible to reverse

g in the “inverting

mode”. The thyristors in the converter circuit are commutated with the help of the supply

voltage in the rectifying mode of operation and are known as “Line commutated

converter”. The same circuit while operating in the inverter mode r

counter emf for commutation and is referred to as the “Load commutated inverter”.

Page 6: unit 3

www.ravivarmans.hpage.com

→ T → T

→ T → T → T → T

α angle after the positive going zero crossing of v

Page 7: unit 3

www.ravivarmans.hpage.com

α each thyristor is fired “α” angle after the

positive going zero crossing of the line voltage with which it’s firing is associated. Once

is converter is also called the “six pulse” converter. The input

Page 8: unit 3

www.ravivarmans.hpage.com

Page 9: unit 3

www.ravivarmans.hpage.com

α < 90°. It follows from

of the converter. However if α is made larger than

Page 10: unit 3

www.ravivarmans.hpage.com

Page 11: unit 3

www.ravivarmans.hpage.com

α in the range 90° < α < 180° it is observed from Fig.

dc voltage is negative and the displacement angle φ of the fundamental component of the

input ac line current is equal to α > 90°. Therefore, power in the ac side flows from the

commutation is impressed with a negative voltage of duration β = π – α. For successful

β ≥ ωtq, tq is the thyristor turn off time

Therefore πα ≥ ωtq or α ≤ πωtq.

This imposes an upper limit on the value of α. In practice this upper value of α is

Page 12: unit 3

www.ravivarmans.hpage.com

Page 13: unit 3

www.ravivarmans.hpage.com

Page 14: unit 3

www.ravivarmans.hpage.com

Page 15: unit 3

www.ravivarmans.hpage.com

Page 16: unit 3

www.ravivarmans.hpage.com

Page 17: unit 3

www.ravivarmans.hpage.com

Page 18: unit 3

www.ravivarmans.hpage.com

Page 19: unit 3

www.ravivarmans.hpage.com

Page 20: unit 3

www.ravivarmans.hpage.com

Page 21: unit 3

www.ravivarmans.hpage.com

Page 22: unit 3

www.ravivarmans.hpage.com

Page 23: unit 3

www.ravivarmans.hpage.com

Page 24: unit 3

www.ravivarmans.hpage.com

Page 25: unit 3

www.ravivarmans.hpage.com

Page 26: unit 3

www.ravivarmans.hpage.com

Page 27: unit 3

www.ravivarmans.hpage.com

δ.T:

Using the two previous equations, δ is:

Page 28: unit 3

www.ravivarmans.hpage.com

and δ by their respective expressions yields:

Page 29: unit 3

www.ravivarmans.hpage.com

Install equipment according to manufacturer’s specifications, using installation

Page 30: unit 3

www.ravivarmans.hpage.com

day’s

Page 31: unit 3

www.ravivarmans.hpage.com

Page 32: unit 3

www.ravivarmans.hpage.com

Page 33: unit 3

www.ravivarmans.hpage.com

Page 34: unit 3

www.ravivarmans.hpage.com

Page 35: unit 3

www.ravivarmans.hpage.com

Page 36: unit 3

www.ravivarmans.hpage.com

Page 37: unit 3

www.ravivarmans.hpage.com

Page 38: unit 3

www.ravivarmans.hpage.com

Page 39: unit 3

www.ravivarmans.hpage.com

Page 40: unit 3

www.ravivarmans.hpage.com

Page 41: unit 3

www.ravivarmans.hpage.com

Page 42: unit 3

www.ravivarmans.hpage.com

Page 43: unit 3

www.ravivarmans.hpage.com

Page 44: unit 3

www.ravivarmans.hpage.com

This is a delta configuration. Across any one (of 3 transformers) there’s 240V. On

two poles there’s 480V, and between any pole and neutral there’s 277V. The

Page 45: unit 3

www.ravivarmans.hpage.com

tracker performance. During cloud cover, a solar PV string’s DC voltage can drop

Solar PV panels or receivers should be connected in series to form “strings”. Strin

A solar PV’s D

Page 46: unit 3

www.ravivarmans.hpage.com

Page 47: unit 3

www.ravivarmans.hpage.com

Page 48: unit 3

www.ravivarmans.hpage.com

Page 49: unit 3

www.ravivarmans.hpage.com

Page 50: unit 3

www.ravivarmans.hpage.com

Page 51: unit 3

www.ravivarmans.hpage.com

Page 52: unit 3

www.ravivarmans.hpage.com

Page 53: unit 3

www.ravivarmans.hpage.com

Page 54: unit 3

www.ravivarmans.hpage.com

Page 55: unit 3

www.ravivarmans.hpage.com

3 .1 Voltage Source Inverters

3.1.1 The Two-level VSI

Page 56: unit 3

www.ravivarmans.hpage.com

3.1.2 Square-wave Operation

3.1.3 Carrier-based PWM (CB-PWM)

Page 57: unit 3

www.ravivarmans.hpage.com

‘’ ‘’

‘’ ‘ˆ ’

Page 58: unit 3

www.ravivarmans.hpage.com

Page 59: unit 3

www.ravivarmans.hpage.com

3.1.4 Switching Frequency Optimal PWM (SFO-PWM)

3.1.4.1 Trapezoidal Modulating Function

Page 60: unit 3

www.ravivarmans.hpage.com

3.1.4.2 Third Harmonic Modulating Function

‘’

‘’ ‘’

‘ ’ ‘ ’

Page 61: unit 3

www.ravivarmans.hpage.com

Page 62: unit 3

www.ravivarmans.hpage.comwww.ravivarmans.hpage.com

Grid-Tie Inverter

A grid-tie inverter, or a (GTI) is a special type of inverter that is used in a renewable energy power system to convert direct current into alternating current and feed it into the utility grid. The technical name for a grid-tie inverter is "grid-interactive inverter". They may also be called synchronous inverters. Grid-interactive inverters typically cannot be used in standalone applications where utility power is not available.

Residences and businesses that have a grid-tied electrical system are permitted in many countries to sell their energy to the utility grid through a policy known as "net metering", whereby the entity that owns the renewable energy power source receives compensation from the utility for its net outflow of power. So for example, if during a given month a power system feeds 500 kilowatt-hours into the grid and uses 100 kilowatt-hours from the grid, it would receive compensation for 400 kilowatt-hours. In the US, net metering policies vary by jurisdiction.

Typical Operation

Inverters work by taking the DC power from the source, such as an array of photovoltaic modules (typically 250 to 600 volts DC) or micro hydroelectric turbines, and inverting it to AC power so it can be fed into the grid. The inverter must also synchronize its frequency with that of the grid (e.g. 60 Hz) using a local oscillator and limit the voltage to no higher than the grid voltage. Typical modern GTI's have a fixed unity power factor, which means its output voltage and current are perfectly lined up, and its phase angle is within 1 degree of the AC power grid. The inverter has an on board computer which will sense the current AC grid waveform, and output a voltage to correspond with the grid.Grid-tie inverters are also designed to quickly disconnect from the grid if the utility grid goes down. This is an NEC requirement that ensures that in the event of a blackout, the grid tie inverter will shut down to prevent the energy it produces from harming any line workers who are sent to fix the power grid.

Technology

Grid-tie inverters that are available on the market today use a number of different technologies. The inverters may use the newer high-frequency transformers, conventional low-frequency transformers, or even use no transformer. Instead of converting DC current directly to 120 or 240 volts AC, high-frequency transformers employ a computerized multi-step process that involves converting the power to high-frequency AC and then back to DC and then to the final AC output voltage. Transformerless inverters, which boast lighter weight and higher efficiencies than their counterparts with transformers, are popular in Europe. However, transformerless inverters have been slow to enter the US market. Until 2005, NEC code required all solar electric systems to be negative grounded, an electrical configuration that interferes with the operation of transformerless inverters. The issue at stake currently is that there are concerns about having transformerless electrical systems feed into the public utility grid since the lack of galvanic isolation between the DC and AC circuits could allow the passage of dangerous DC faults to be transmitted to the AC side.

Most solar grid-interactive inverters on the market include a maximum power point tracker that enables the inverter to extract an optimal amount of power from the solar array by tracking the array's maximum power point.