Tm Vrv IV Edmt341410

724
EDMT341410 Table of Contents 3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Introduction ................................................................................................................. 5 Part 1 General Information ............................................... ................................ 7 Part 2 Indoor Units ................................................................................................... 41 Ceiling Mounted Cassette (Round Flow with Sensing) Type ... ................ 43 Ceiling Mounted Cassette (Round Flow) Type (For ASEAN) ... ................ 59 Ceiling Mounted Cassette (Compact Multi Flow) Type ........... ................ 75 4-Way Flow Ceiling Suspended Type ..................................... ................ 91 Ceiling Mounted Cassette (Double Flow) Type ...................... .............. 103 Ceiling Mounted Cassette Corner Type .................................. .............. 121 Slim Ceiling Mounted Duct Type ............................................ .............. 135 Ceiling Mounted Duct Type .................................................... .............. 159 Ceiling Mounted Duct Type .................................................... ............. 187 Ceiling Suspended Type ......................................................... .............. 201 Wall Mounted Type ................................................................. .............. 215 Floor Standing Type / Concealed Floor Standing Type .......... .............. 231 Floor Standing Duct Type ....................................................... .............. 253 Part 3 Outdoor-Air Processing Unit .................................. .......... 287 Part 4 Residential Indoor Units with Connection to BP Units... ............................ 307 Part 5 BP Unit.................................................................... ............................ 347 Part 6 Outdoor Units Cooling Only 50Hz High-COP Type ..................... .......... 365 Part 7 Outdoor Units Cooling Only 50Hz Standard Type ...................... .......... 435 Part 8 Outdoor Units Cooling Only 50Hz Space Saving Type ............... .......... 569 Part 9 Installation of Outdoor Units ................................. ............................ 647 Part 10 Option of Control .................................................... ............................ 721 1 FXFQ-S 2 FXFQ-LU 3 FXZQ-M 4 FXUQ-A 5 FXCQ-M 6 FXKQ-MA 7 FXDQ-PB / FXDQ-NB 8 FXMQ-P 9 FXMQ-MA 10 FXHQ-MA 11 FXAQ-P 12 FXLQ-MA / FXNQ-MA 13 FXVQ-M 14 FXMQ-MF 15 16 17 RXQ-TH 18 RXQ-T(N) 19 RXQ-T(S) 20 21 22 EDMT341410.book Page 3 Friday, March 28, 2014 2:06 PM

description

Daikin VRV 4 ED

Transcript of Tm Vrv IV Edmt341410

EDMT341410.bookPart 2 Indoor Units................................................................................................... 41
Ceiling Mounted Cassette (Compact Multi Flow) Type........... ................75
4-Way Flow Ceiling Suspended Type..................................... ................91
Ceiling Mounted Cassette (Double Flow) Type ...................... ..............103
Ceiling Mounted Cassette Corner Type.................................. ..............121
Slim Ceiling Mounted Duct Type ............................................ ..............135
Ceiling Mounted Duct Type .................................................... ..............159
Ceiling Mounted Duct Type .................................................... ............. 187
Ceiling Suspended Type......................................................... ..............201
Floor Standing Duct Type ....................................................... ..............253
Part 3 Outdoor-Air Processing Unit .................................. .......... 287
Part 4 Residential Indoor Units with Connection to BP Units... ............................ 307
Part 5 BP Unit.................................................................... ............................ 347
Part 6 Outdoor Units Cooling Only 50Hz High-COP Type ..................... .......... 365
Part 7 Outdoor Units Cooling Only 50Hz Standard Type ...................... .......... 435
Part 8 Outdoor Units Cooling Only 50Hz Space Saving Type............... .......... 569
Part 9 Installation of Outdoor Units ................................. ............................ 647
Part 10 Option of Control .................................................... ............................ 721
1
FXFQ-S2
FXFQ-LU3
FXZQ-M4
FXUQ-A5
FXCQ-M6
FXKQ-MA7
EDMT341410
EDMT341410.book Page 4 Friday, March 28, 2014 2:06 PM
EDMT341410 Introduction
Introduction 5
1. Introduction 1.1 Publication List of Engineering Data for VRV Products Refrigerant Type Product Series Book No. Type, Hz Model name Area Note Published
in
R410A
EDMT341410 C/O 50Hz
High-COP type RXQ12-50THY1(E)
Standard type RXQ6-60T(N)Y1(E)
Singapore, Malaysia, Vietnam
New lineup of outdoor units RXQ-T Addition of FXFQ-S, FXVQ Addition of residential indoor units Model change of FXFQ from P to LU, FXUQ from MA to A Deletion of BEVQ
Mar. 2014
Inverter P(A)
General
Addition of 6HP outdoor units (Asean and Oceania only) Model change of FXAQ from MA to P series
Dec. 2012
General
Addition of 6HP outdoor unit (Asean and Oceania only) Model change of FXAQ from MA to P series
Dec. 2012
General
New lineup of outdoor unit connecting with residential indoor units
Dec. 2011
Oceania New lineup of 6HP outdoor units Aug. 2012
EDMT37-750A H/R 50Hz REYQ8-48PY1 General Model change and addition of indoor units
Aug. 2013
ED341014 H/P 50Hz RQYQ8-48PY1 General New lineup for replacement use Outdoor unit only
Dec. 2010
New lineup for replacement use (cooling only) Outdoor unit only
Jul. 2012
Model change of FXAQ from MA to P series
Dec. 2012
H/P,H/R 60Hz
Dec. 2009
For all type OH12-01 50/60Hz For indoor and outdoor units General Option
handbook Jul. 2012
Heat Reclaim Ventilator (VAM) GJ ED71-613 50/60Hz VAM150-2000GJVE General New lineup from FA to GA series
Feb. 2006
With DX coil and humidifier (VKM-GAM) With DX coil (VKM-GA)
Mar. 2012
This time we publish EDMT341410 as shown by . H/P: Heat Pump H/R: Heat Recovery C/O: Cooling Only
EDMT341410.book Page 5 Friday, March 28, 2014 2:06 PM
Introduction EDMT341410
6 Introduction
EDMT341410
VRV and Residential Indoor Units..........................................................28
6. Selection Procedure..............................................................................31 6.1 Selection Procedure for VRV Indoor Units Only.....................................31 6.2 Selection Procedure for Mixed Combination of
VRV and Residential Indoor Units..........................................................35
Model Names of Indoor/Outdoor Units EDMT341410
8 General Information
VRV Indoor Units
Note: FXDQ has following 2 series, as shown below. FXDQ-PBVET, NBVET: without a Drain Pump FXDQ-PBVE, NBVE: with a Drain Pump
V1: 1 phase, 220-240V, 50Hz VE: 1 phase, 220-240/220V, 50/60Hz VM: 1 phase, 220-240/220-230V, 50/60Hz Y1: 3 phase, 380-415V, 50Hz
Capacity range 2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW 8.0kW 9.0kW 11.2kW 14.0kW 16.0kW 22.4kW 28.0kW 45.0kW 56.0kW Power
supply, Standard
0.8HP 1HP 1.25HP 1.6HP 2HP 2.5HP 3HP 3.2HP 4HP 5HP 6HP 8HP 10HP 16HP 20HP Capacity index 20 25 31.25 40 50 62.5 71 80 100 125 140 200 250 400 500
Ceiling Mounted Cassette (Round Flow with Sensing) Type
FXFQ — 25S 32S 40S 50S 63S — 80S 100S 125S — — — — — VM
Ceiling Mounted Cassette (Round Flow) Type
FXFQ — 25LU 32LU 40LU 50LU 63LU — 80LU 100LU 125LU — — — — — V1
Ceiling Mounted Cassette (Compact Multi Flow) Type
FXZQ 20M 25M 32M 40M 50M — — — — — — — — — — VE
4-Way Flow Ceiling Suspended Type
FXUQ — — — — — — 71A — 100A — — — — — — VEB
FXCQ 20M 25M 32M 40M 50M 63M — 80M — 125M — — — — —
VE
Ceiling Mounted Duct Type
FXMQ 20P 25P 32P 40P 50P 63P — 80P 100P 125P 140P — — — —
FXMQ — — — — — — — — — — — 200MA 250MA — — Ceiling Suspended Type
FXHQ — — 32MA — — 63MA — — 100MA — — — — — —
Wall Mounted Type FXAQ 20P 25P 32P 40P 50P 63P — — — — — — — — —
Floor Standing Type
Concealed Floor Standing Type
Floor Standing Duct Type
— — — — — — — — — — — — — — 500M Y16
EDMT341410 Model Names of Indoor/Outdoor Units
General Information 9
1 Residential Indoor Units with Connection to BP Units
Note: BP Units are necessary for residential indoor units. Residential Indoor Units can be connected with only Single Outdoor Units.
V1: 1 phase, 220-240V, 50Hz VE: 1 phase, 220-240/220V, 50/60Hz VM: 1 phase, 220-240/220-230V, 50/60Hz
BP Units
Standard Type
Space Saving Type
Y1: 3 phase, 380-415V, 50Hz E: The unit with anti corrosion treatment
Capacity range 2.5kW 3.5kW 5.0kW 6.0kW 7.1kW Power supply,
StandardCapacity index 25 35 50 60 71
Ceiling Mounted Cassette Type FCQ — 35B 50B 60B 71B VE
Ceiling Mounted Cassette (Compact Multi Flow) Type
FFQ 25B 35B 50B 60B — V1B
Ceiling Mounted Build-in Type FBQ — — — 60B 71B V1
Slim Ceiling Mounted Duct Type FDKS
25EA 35EA — — —
VMB25CA 35CA — — —
— — 50C 60C —
2 Ports BPMKS967A2
Series Model Name Power Supply
Cooling Only RXQ 12TH 14TH 16TH 18TH 20TH 22TH 24TH 26TH 28TH 30TH
Y1(E) 32TH 34TH 36TH 38TH 40TH 42TH 44TH 46TH 48TH 50TH
Series Model Name Power Supply
Cooling Only RXQ
6T 8T 10T 12T 14T 16T 18TN 20TN 22TN 24TN
Y1(E)26TN 28TN 30TN 32TN 34TN 36TN 38TN 40TN 42TN 44TN
46TN 48TN 50TN 52TN 54TN 56TN 58TN 60TN — —
Series Model Name Power Supply
Cooling Only RXQ 18T 20T 22TS 24TS 26TS 28TS 30TS 32TS 34TS 36TS
Y1(E) 38TS 40TS 42TS 44TS 46TS 48TS 50TS — — —
EDMT341410.book Page 9 Friday, March 28, 2014 2:06 PM
Model Names of Indoor/Outdoor Units EDMT341410
10 General Information
Combination of Outdoor Units (Space Saving Type)
Capacity range 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP
Model name RXQ12TH RXQ14TH RXQ16TH RXQ18TH RXQ20TH RXQ22TH RXQ24TH RXQ26TH
Outdoor unit 1 RXQ6T RXQ6T RXQ8T RXQ6T RXQ6T RXQ6T RXQ8T RXQ8T
Outdoor unit 2 RXQ6T RXQ8T RXQ8T RXQ6T RXQ6T RXQ8T RXQ8T RXQ8T
Outdoor unit 3 – – – RXQ6T RXQ8T RXQ8T RXQ8T RXQ10T
Capacity range 28HP 30HP 32HP 34HP 36HP 38HP 40HP 42HP
Model name RXQ28TH RXQ30TH RXQ32TH RXQ34TH RXQ36TH RXQ38TH RXQ40TH RXQ42TH
Outdoor unit 1 RXQ8T RXQ8T RXQ8T RXQ8T RXQ8T RXQ12T RXQ12T RXQ14T
Outdoor unit 2 RXQ8T RXQ10T RXQ12T RXQ12T RXQ14T RXQ12T RXQ14T RXQ14T
Outdoor unit 3 RXQ12T RXQ12T RXQ12T RXQ14T RXQ14T RXQ14T RXQ14T RXQ14T
Capacity range 44HP 46HP 48HP 50HP
Model name RXQ44TH RXQ46TH RXQ48TH RXQ50TH
Outdoor unit 1 RXQ14T RXQ14T RXQ16T RXQ16T
Outdoor unit 2 RXQ14T RXQ16T RXQ16T RXQ16T
Outdoor unit 3 RXQ16T RXQ16T RXQ16T RXQ18T
Capacity range 6HP 8HP 10HP 12HP 14HP 16HP
Model name RXQ6T RXQ8T RXQ10T RXQ12T RXQ14T RXQ16T
Capacity range 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP
Model name RXQ18TN RXQ20TN RXQ22TN RXQ24TN RXQ26TN RXQ28TN RXQ30TN RXQ32TN
Outdoor unit 1 RXQ8T RXQ8T RXQ8T RXQ10T RXQ12T RXQ14T RXQ14T RXQ14T
Outdoor unit 2 RXQ10T RXQ12T RXQ14T RXQ14T RXQ14T RXQ14T RXQ16T RXQ18T
Outdoor unit 3 – – – – – – – –
Capacity range 34HP 36HP 38HP 40HP 42HP 44HP 46HP 48HP
Model name RXQ34TN RXQ36TN RXQ38TN RXQ40TN RXQ42TN RXQ44TN RXQ46TN RXQ48TN
Outdoor unit 1 RXQ10T RXQ12T RXQ8T RXQ12T RXQ12T RXQ12T RXQ14T RXQ14T
Outdoor unit 2 RXQ12T RXQ12T RXQ12T RXQ12T RXQ14T RXQ16T RXQ14T RXQ16T
Outdoor unit 3 RXQ12T RXQ12T RXQ18T RXQ16T RXQ16T RXQ16T RXQ18T RXQ18T
Capacity range 50HP 52HP 54HP 56HP 58HP 60HP
Model name RXQ50TN RXQ52TN RXQ54TN RXQ56TN RXQ58TN RXQ60TN
Outdoor unit 1 RXQ14T RXQ16T RXQ18T RXQ18T RXQ18T RXQ20T
Outdoor unit 2 RXQ18T RXQ18T RXQ18T RXQ18T RXQ20T RXQ20T
Outdoor unit 3 RXQ18T RXQ18T RXQ18T RXQ20T RXQ20T RXQ20T
Capacity range 18HP 20HP
Model name RXQ18T RXQ20T
Capacity range 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP
Model name RXQ22TS RXQ24TS RXQ26TS RXQ28TS RXQ30TS RXQ32TS RXQ34TS RXQ36TS
Outdoor unit 1 RXQ10T RXQ12T RXQ8T RXQ12T RXQ12T RXQ12T RXQ16T RXQ18T
Outdoor unit 2 RXQ12T RXQ12T RXQ18T RXQ16T RXQ18T RXQ20T RXQ18T RXQ18T
Outdoor unit 3 – – – – – – – –
Outdoor unit 1 RXQ18T RXQ20T RXQ12T RXQ12T RXQ12T RXQ12T RXQ12T
Outdoor unit 2 RXQ20T RXQ20T RXQ12T RXQ12T RXQ16T RXQ18T RXQ18T
Outdoor unit 3 – – RXQ18T RXQ20T RXQ18T RXQ18T RXQ20T
EDMT341410.book Page 10 Friday, March 28, 2014 2:06 PM
EDMT341410 Model Names of Indoor/Outdoor Units
General Information 11
Outdoor-air processing unit
Note: For details, refer to Engineering Data ED71-440B.
V1: 1 phase, 220-240V, 50Hz
Heat Reclaim Ventilator (VAM series)
Note: For details, refer to Engineering Data ED71-613.
VE: 1 phase, 220-240/220V, 50/60Hz
Series Model name Power supply FXMQ 125MF 200MF 250MF V1
Series Model name Power supply Heat Reclaim Ventilator with DX coil
VKM
50GAM 80GAM 100GAM
Series Model name Power supply Heat Reclaim Ventilator VAM 150GJ 250GJ 350GJ 500GJ 650GJ 800GJ 1000GJ 1500GJ 2000GJ VE
EDMT341410.book Page 11 Friday, March 28, 2014 2:06 PM
External Appearance EDMT341410
12 General Information
Ceiling mounted cassette (Round flow with sensing) type
FXFQ-S
FXFQ-LU
FXZQ-M
FXUQ-A
FXCQ-M
FXKQ-MA
FXDQ-PB FXDQ-NB
EDMT341410 External Appearance
General Information 13
BP units
FDKS-C(A)
FFQ-B
FDKS-EA
EDMT341410.book Page 13 Friday, March 28, 2014 2:06 PM
External Appearance EDMT341410
14 General Information
RXQ34TH RXQ36TH RXQ38TH
RXQ12 / 14 / 16TH RXQ18 / 20 / 22 / 24 / 26 / 28 / 30 / 32TH
RXQ40TH RXQ42 / 44 / 46 / 48 / 50TH
EDMT341410.book Page 14 Friday, March 28, 2014 2:06 PM
EDMT341410 External Appearance
General Information 15
1 Standard Type
RXQ42 / 44TN
RXQ14 / 16T
RXQ34 / 36TN
RXQ38 / 40TN RXQ46 / 48 / 50 / 52 / 54 / 56 / 58 / 60TN
EDMT341410.book Page 15 Friday, March 28, 2014 2:06 PM
External Appearance EDMT341410
16 General Information
Space Saving Type
VKM-GA VKM-GAM
with DX coil (GA) with DX coil and humidifier (GAM)
Heat Reclaim Ventilator (VAM series)
VAM-GJ
RXQ18 / 20T RXQ22 / 24TS
EDMT341410.book Page 16 Friday, March 28, 2014 2:06 PM
EDMT341410 Combination of Outdoor Units
General Information 17
1 3. Combination of Outdoor Units High-COP Type
Note: 1 For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
System capacity Number of units
Module Outdoor Unit Multi Connection Piping Kit 1kW HP 6 8 10 12 14 16 18
32.0 12 2
BHFP22P10038.4 14 2
44.8 16 2
48.0 18 3
Combination of Outdoor Units EDMT341410
18 General Information
Standard Type
Note: 1 For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
Space Saving Type
Note: 1 For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
System capacity Number of units
Module Outdoor Unit Multi Connection Piping Kit 1kW HP 6 8 10 12 14 16 18 20
16.0 6 1
System capacity Number of units
Module Outdoor Unit Multi Connection Piping Kit 1kW HP 8 10 12 14 16 18 20
50.0 18 1 —
56.0 20 1
61.5 22 2
EDMT341410 Nomenclature
General Information 19
1 4. Nomenclature
VRV Indoor Unit
Power Supply Symbol VE: 1 phase, 220-240/220V, 50/60Hz V1: 1 phase, 220-240V, 50Hz VM: 1 phase, 220-240/220-230V, 50/60Hz Y1: 3 phase, 380-415V, 50Hz
Indicates Major Design Category
Capacity indication Conversion to kW (Horsepower) 25: 2.8 kW (1 HP) 125: 14.0 kW (5 HP) 250: 28.0 kW (10 HP)
Refrigerant Q: R410A
Type F : Ceiling Mounted Cassette (Round Flow with Sensing / Round Flow) Z : Ceiling Mounted Cassette (Compact Multi Flow) U : 4-Way Flow Ceiling Suspended C: Ceiling Mounted Cassette (Double Flow) K : Ceiling Mounted Cassette Corner D : Slim Ceiling Mounted Duct M: Ceiling Mounted Duct H: Ceiling Suspended A : Wall Mounted L : Floor Standing N : Concealed Floor Standing V: Floor Standing Duct
Series category X: Inverter
F 25 VEPQXF
Nomenclature EDMT341410
Model Change Symbol Progress with each design change
Capacity Indication Rated cooling capacity (kW at 50 Hz) × 10
Refrigerant S: R410A
Shape T: Wall mounted D: Duct connected
Unit category F: Indoor unit for pair or pair/multi use C: Indoor unit for multi use
K 35 VMDSTF
Power Supply Symbol VE: 1 phase, 220-240/220V, 50/60 Hz V1: 1 phase, 220-240V, 50 Hz
Model Change Symbol Progress with each design change
Capacity Indication Rated cooling capacity (kW at 50 Hz) × 10
Refrigerant Q: R410A · Heat Pump or Cooling Only
Shape C: Ceiling mounted cassette (Round/Multi flow) F: Ceiling mounted cassette (Compact multi flow) B: Ceiling mounted built-in
Unit category F: Air cooled split indoor unit
C 71 VEBQF
EDMT341410 Nomenclature
Y1TN54QR X E
Power Supply Symbol Y1: 3 phase, 380-415V, 50Hz
Indicates Major Design Category TH: High-COP Type T, TN: Standard Type (Only T: Single Unit) T, TS: Space Saving Type (Only T: Single Unit)
Capacity indication Conversion to kW (Horsepower) 6: 16.0 kW (6 HP) 10: 28.0 kW (10 HP) 60: 168 kW (60 HP)
Refrigerant Q: R410A
Series category X: Inverter
Power supply symbol V1: 1 phase, 220-240V, 50Hz
Moisture M: With humidifier elements Nothing: Without humidifier elements
Indicates major design category
Air flow rate (H) 50: 500m3/h, 80: 750m3/h, 100: 950m3/h
V M V1MGA50K
Indicates major design category
Mounted type
Capacity Range EDMT341410
22 General Information
5. Capacity Range 5.1 Capacity Range for VRV Indoor Units Only 5.1.1 Combination Ratio
Note: If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the indoor units. * When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total connection
capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%.
Note: When outdoor-air processing mode of FXVQ-M is selected, be sure to connect as follows:
Combination ratio = Total capacity index of the indoor units
Capacity index of the outdoor units
Type Min.
combination ratio
Max. combination ratio
Types of connected indoor units Type of connected Air Treatment Equipments
FXDQ, FXMQ-P,
unit
When FXMQ-MF
connected
Triple outdoor units 130%
ASEAN
20HP FXVQ500MY1×1 FXVQ500MY16×1 RXQ20TNY1×1
EDMT341410.book Page 22 Friday, March 28, 2014 2:06 PM
EDMT341410 Capacity Range
General Information 23
1 5.1.2 Outdoor Unit Combinations High-COP Type
Notes: *1 For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. *2 Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for
single outdoor units, 160% for double outdoor units, and 130% for triple outdoor units. *3 When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%.
kW HP Capacity index Model name Combination Outdoor unit multi
connection piping kit *1 Total capacity index of
connectable indoor units *2 *3 Maximum number of
connectable indoor units *2 32.0 12HP 300 RXQ12TH RXQ6T × 2
BHFP22P100 150 to 390 (480) 19 (24)
38.4 14HP 350 RXQ14TH RXQ6T + RXQ8T 175 to 455 (560) 22 (28) 44.8 16HP 400 RXQ16TH RXQ8T × 2 200 to 520 (640) 26 (32) 48.0 18HP 450 RXQ18TH RXQ6T × 3
BHFP22P151
225 to 585 (585) 29 (29) 54.4 20HP 500 RXQ20TH RXQ6T × 2 + RXQ8T 250 to 650 (650) 32 (32) 60.8 22HP 550 RXQ22TH RXQ6T + RXQ8T × 2 275 to 715 (715) 35 (35) 67.2 24HP 600 RXQ24TH RXQ8T × 3 300 to 780 (780) 39 (39) 72.8 26HP 650 RXQ26TH RXQ8T × 2 + RXQ10T 325 to 845 (845) 42 (42) 78.3 28HP 700 RXQ28TH RXQ8T × 2 + RXQ12T 350 to 910 (910) 45 (45) 83.9 30HP 750 RXQ30TH RXQ8T + RXQ10T + RXQ12T 375 to 975 (975) 48 (48) 89.4 32HP 800 RXQ32TH RXQ8T + RXQ12T × 2 400 to 1,040 (1,040) 52 (52) 95.9 34HP 850 RXQ34TH RXQ8T + RXQ12T + RXQ14T 425 to 1,105 (1,105) 55 (55) 102 36HP 900 RXQ36TH RXQ8T + RXQ14T × 2 450 to 1,170 (1,170) 58 (58) 107 38HP 950 RXQ38TH RXQ12T × 2 + RXQ14T 475 to 1,235 (1,235) 61 (61) 114 40HP 1,000 RXQ40TH RXQ12T + RXQ14T × 2 500 to 1,300 (1,300)
64 (64)
120 42HP 1,050 RXQ42TH RXQ14T × 3 525 to 1,365 (1,365) 125 44HP 1,100 RXQ44TH RXQ14T × 2 + RXQ16T 550 to 1,430 (1,430) 130 46HP 1,150 RXQ46TH RXQ14T + RXQ16T × 2 575 to 1,495 (1,495) 135 48HP 1,200 RXQ48TH RXQ16T × 3 600 to 1,560 (1,560) 140 50HP 1,250 RXQ50TH RXQ16T × 2 + RXQ18T 625 to 1,625 (1,625)
EDMT341410.book Page 23 Friday, March 28, 2014 2:06 PM
Capacity Range EDMT341410
24 General Information
Standard Type
Notes: *1 For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. *2 Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for
single outdoor units, 160% for double outdoor units, and 130% for triple outdoor units. *3 When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%.
Space Saving Type
Notes: *1 For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required. *2 Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for
single outdoor units, 160% for double outdoor units, and 130% for triple outdoor units. *3 When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%.
kW HP Capacity index Model name Combination Outdoor unit multi
connection piping kit *1 Total capacity index of
connectable indoor units *2 *3 Maximum number of
connectable indoor units *2 16.0 6HP 150 RXQ6T RXQ6T — 75 to 195 (300) 9 (15) 22.4 8HP 200 RXQ8T RXQ8T — 100 to 260 (400) 13 (20) 28.0 10HP 250 RXQ10T RXQ10T — 125 to 325 (500) 16 (25) 33.5 12HP 300 RXQ12T RXQ12T — 150 to 390 (600) 19 (30) 40.0 14HP 350 RXQ14T RXQ14T — 175 to 455 (700) 22 (35) 45.0 16HP 400 RXQ16T RXQ16T — 200 to 520 (800) 26 (40) 50.4 18HP 450 RXQ18TN RXQ8T + RXQ10T
BHFP22P100
225 to 585 (720) 29 (36) 55.9 20HP 500 RXQ20TN RXQ8T + RXQ12T 250 to 650 (800) 32 (40) 62.4 22HP 550 RXQ22TN RXQ8T + RXQ14T 275 to 715 (880) 35 (44) 68.0 24HP 600 RXQ24TN RXQ10T + RXQ14T 300 to 780 (960) 39 (48) 73.5 26HP 650 RXQ26TN RXQ12T + RXQ14T 325 to 845 (1,040) 42 (52) 80.0 28HP 700 RXQ28TN RXQ14T × 2 350 to 910 (1,120) 45 (56) 85.0 30HP 750 RXQ30TN RXQ14T + RXQ16T 375 to 975 (1,200) 48 (60) 90.0 32HP 800 RXQ32TN RXQ14T + RXQ18T 400 to 1,040 (1,280) 52 (64) 95.0 34HP 850 RXQ34TN RXQ10T + RXQ12T × 2
BHFP22P151
425 to 1,105 (1,105) 55 (55) 101 36HP 900 RXQ36TN RXQ12T × 3 450 to 1,170 (1,170) 58 (58) 106 38HP 950 RXQ38TN RXQ8T + RXQ12T + RXQ18T 475 to 1,235 (1,235) 61 (61) 112 40HP 1,000 RXQ40TN RXQ12T × 2 + RXQ16T 500 to 1,300 (1,300)
64 (64)
119 42HP 1,050 RXQ42TN RXQ12T + RXQ14T + RXQ16T 525 to 1,365 (1,365) 124 44HP 1,100 RXQ44TN RXQ12T + RXQ16T × 2 550 to 1,430 (1,430) 130 46HP 1,150 RXQ46TN RXQ14T × 2 + RXQ18T 575 to 1,495 (1,495) 135 48HP 1,200 RXQ48TN RXQ14T + RXQ16T + RXQ18T 600 to 1,560 (1,560) 140 50HP 1,250 RXQ50TN RXQ14T + RXQ18T × 2 625 to 1,625 (1,625) 145 52HP 1,300 RXQ52TN RXQ16T + RXQ18T × 2 650 to 1,690 (1,690) 150 54HP 1,350 RXQ54TN RXQ18T × 3 675 to 1,755 (1,755) 156 56HP 1,400 RXQ56TN RXQ18T × 2 + RXQ20T 700 to 1,820 (1,820) 162 58HP 1,450 RXQ58TN RXQ18T + RXQ20T × 2 725 to 1,885 (1,885) 168 60HP 1,500 RXQ60TN RXQ20T × 3 750 to 1,950 (1,950)
kW HP Capacity index Model name Combination Outdoor unit multi
connection piping kit *1 Total capacity index of
connectable indoor units *2 *3 Maximum number of
connectable indoor units *2 50.0 18HP 450 RXQ18T RXQ18T — 225 to 585 (900) 29 (45) 56.0 20HP 500 RXQ20T RXQ20T — 250 to 650 (1,000) 32 (50) 61.5 22HP 550 RXQ22TS RXQ10T + RXQ12T
BHFP22P100
275 to 715 (880) 35 (44) 67.0 24HP 600 RXQ24TS RXQ12T × 2 300 to 780 (960) 39 (48) 72.4 26HP 650 RXQ26TS RXQ8T + RXQ18T 325 to 845 (1,040) 42 (52) 78.5 28HP 700 RXQ28TS RXQ12T + RXQ16T 350 to 910 (1,120) 45 (56) 83.5 30HP 750 RXQ30TS RXQ12T + RXQ18T 375 to 975 (1,200) 48 (60) 89.5 32HP 800 RXQ32TS RXQ12T + RXQ20T 400 to 1,040 (1,280) 52 (64) 95.0 34HP 850 RXQ34TS RXQ16T + RXQ18T 425 to 1,105 (1,360) 55 (64) 100 36HP 900 RXQ36TS RXQ18T × 2 450 to 1,170 (1,440) 58 (64) 106 38HP 950 RXQ38TS RXQ18T + RXQ20T 475 to 1,235 (1,520) 61 (64) 112 40HP 1,000 RXQ40TS RXQ20T × 2 500 to 1,300 (1,600)
64 (64)
BHFP22P151
525 to 1,365 (1,365) 123 44HP 1,100 RXQ44TS RXQ12T × 2 + RXQ20T 550 to 1,430 (1,430) 129 46HP 1,150 RXQ46TS RXQ12T + RXQ16T + RXQ18T 575 to 1,495 (1,495) 134 48HP 1,200 RXQ48TS RXQ12T + RXQ18T × 2 600 to 1,560 (1,560) 140 50HP 1,250 RXQ50TS RXQ12T + RXQ18T + RXQ20T 625 to 1,625 (1,625)
EDMT341410.book Page 24 Friday, March 28, 2014 2:06 PM
EDMT341410 Capacity Range
General Information 25
High-COP Type
Note: If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the indoor units.
Type HP Capacity index
Min. combination
ratio
FXDQ, FXMQ-P, FXAQ Including FXFQ25LU, FXFQ-S at least one unit Other indoor unit models
Max. combination
Triple outdoor
130%
29
26 650 RXQ26TH
40 1,000 RXQ40TH
Capacity Range EDMT341410
26 General Information
Standard Type
Note: If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the indoor units.
Type HP Capacity index
Min. combination
ratio
FXDQ, FXMQ-P, FXAQ Including FXFQ25LU, FXFQ-S at least one unit Other indoor unit models
Max. combination
Double outdoor
160%
36
26 650 RXQ26TN
Triple outdoor
40 1,000 RXQ40TN
EDMT341410 Capacity Range
General Information 27
1 Space Saving Type
Note: If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the indoor units.
Type HP Capacity index
Min. combination
ratio
FXDQ, FXMQ-P, FXAQ Including FXFQ25LU, FXFQ-S at least one unit Other indoor unit models
Max. combination
Double outdoor
160%
44
26 650 RXQ26TS
32 800 RXQ32TS 52
Capacity Range EDMT341410
28 General Information
5.2 Capacity Range for Mixed Combination of VRV and Residential Indoor Units 5.2.1 Combination Ratio
Notes: *1 Involve the case of Residential indoor units only. *2 When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%.
Combination ratio = Total capacity index of the indoor units
Capacity index of the outdoor units
Type Min. combination ratio
Type of connected Air Treatment Equipments
VKM FXMQ-MF
When VKM and indoor units are connected
When FXMQ-MF and indoor units are
connected
EDMT341410.book Page 28 Friday, March 28, 2014 2:06 PM
EDMT341410 Capacity Range
General Information 29
1 5.2.2 Outdoor Unit Combinations Standard Type
Notes: *1 Total capacity index of connectable indoor units must be 50% ~ 130% of the capacity index of the outdoor unit.
*2 When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%.
Space Saving Type
Notes: *1 Total capacity index of connectable indoor units must be 50% ~ 130% of the capacity index of the outdoor unit.
*2 When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%.
kW HP Capacity index Model name Combination Outdoor unit multi
connection piping kit Total capacity index of
connectable indoor units *1 *2 Maximum number of
connectable indoor units 16.0 6HP 150 RXQ6T RXQ6T — 75 to 195 (195) 9 (9) 22.4 8HP 200 RXQ8T RXQ8T — 100 to 260 (260) 13 (13) 28.0 10HP 250 RXQ10T RXQ10T — 125 to 325 (325) 16 (16) 33.5 12HP 300 RXQ12T RXQ12T — 150 to 390 (390) 19 (19) 40.0 14HP 350 RXQ14T RXQ14T — 175 to 455 (455) 22 (22) 45.0 16HP 400 RXQ16T RXQ16T — 200 to 520 (520) 26 (26)
kW HP Capacity index Model name Combination Outdoor unit multi
connection piping kit Total capacity index of
connectable indoor units *1 *2 Maximum number of
connectable indoor units 50.0 18HP 450 RXQ18T RXQ18T — 225 to 585 (585) 29 (29) 56.0 20HP 500 RXQ20T RXQ20T — 250 to 650 (650) 32 (32)
EDMT341410.book Page 29 Friday, March 28, 2014 2:06 PM
Capacity Range EDMT341410
30 General Information
5.2.3 Indoor Unit Connection Capacity Standard Type
Note: Total capacity index of connectable indoor units must be 50% ~ 130% of the capacity index of the outdoor unit.
Space Saving Type
Note: Total capacity index of connectable indoor units must be 50% ~ 130% of the capacity index of the outdoor unit.
Type HP Capacity index Model name
Types of connected indoor units
Min. combination ratio
Max. combination ratio
units
Types of connected indoor units
Min. combination ratio
Max. combination ratio
Single outdoor units
29
EDMT341410 Selection Procedure
General Information 31
1 6. Selection Procedure 6.1 Selection Procedure for VRV Indoor Units Only 6.1.1 Flowchart
6.1.2 Selection Example The following is a selection example based on Total Heat Load for cooling.
[1] Given conditions -Design conditions Indoor air temperature: 18°CWB / 25°CDB, Outdoor air temperature: 33°CDB
-Determine peak load of each room (and system peak load if necessary)
-Required heat load of each room
From the above heat load calculation, the maximum heat load for the system (system peak load) is 50.7kW.
Room A Room H Room G
Room F
Floor plan
Time Room A Room B Room C Room D Room E Room F Room G Room H Total
9:00 4.8 4.8 3.0 3.0 9.1 9.0 2.9 2.9 39.5
12:00 6.6 7.1 5.1 5.1 7.4 6.8 4.0 4.0 46.1
14:00 9.0 9.4 4.9 4.9 7.3 6.8 4.2 4.2 50.7
16:00 10.6 10.7 3.9 3.9 6.3 6.2 3.8 3.8 49.2
Total heat load (kW)
Provisionally select outdoor unit type and size based on limitation of combination ratio
Correct for cooling & heating capacity of the outdoor unit by the following items
VRV system selection is complete.
Confirm that the number of indoor units connected to the outdoor unit is within limitation.
Corrected capacity of the outdoor unit ≥ Required total heat load to the outdoor unit
2) Use the system peak load1) Use the sum of the peak load of each room
Define required total heat load to outdoor unit
Indoor unit capacity corrected for indoor air temperature (WB) ≥ Required heat load × Safety factor for the indoor units
Yes
No
-Piping length, level difference -Piping heat loss -Safety factor for the outdoor unit
-Outdoor air temperature -Indoor air temperature -Combination ratio
Given Conditions: · Design temperature and humidity (indoor & outdoor) · Required heat load of each room · System peak load (if necessary) · Piping length, level difference · Specifications of indoor units (type and number)
Define safety factor for the indoor units and outdoor unit
[1]] Given conditions
EDMT341410.book Page 31 Friday, March 28, 2014 2:06 PM
Selection Procedure EDMT341410
32 General Information
-Safety factor In this example, safety factor is not used. (i. e., safety factor = 1.0)
[2] Selection of indoor units Calculate total heat capacity of indoor units corrected for indoor air temperature. In case design temperature of the indoor air falls between temperatures listed in the table, calculate the capacity by interpolation. The corrected total heat capacity of indoor units shall satisfy the maximum heat load of each room.
Capacity table of indoor unit
TC: Total capacity: kW SHC: Sensible heat capacity: kW
Selection results of indoor units
[3] Selection of outdoor unit [3] –1 Define the required total heat load from the indoor units to the outdoor unit
Define the required total heat load (A) based on (1) the sum of the peak load of each room or (2) the system peak load. In this example, select an outdoor unit by (2). Therefore, (A) = 50.7 kW
Cooling Capacity
Model Capacity indication
Indoor air temp.
14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXFQ-LU
25 1.9 1.9 2.3 2.3 2.6 2.6 2.8 2.8 2.8 2.8 2.9 2.7 3.0 2.6
32 2.4 2.4 2.9 2.8 3.4 3.1 3.6 3.1 3.6 3.1 3.7 3.1 3.8 3.0
40 3.0 2.9 3.6 3.4 4.2 3.7 4.5 3.8 4.6 3.7 4.7 3.6 4.8 3.5
50 3.8 3.4 4.5 3.9 5.2 4.3 5.6 4.4 5.7 4.4 5.8 4.2 5.9 4.1
63 4.8 4.3 5.7 4.9 6.6 5.5 7.1 5.6 7.2 5.5 7.4 5.4 7.5 5.2
80 6.1 5.1 7.2 5.8 8.4 6.5 9.0 6.6 9.1 6.6 9.3 6.4 9.5 6.2
100 7.6 6.8 9.0 7.8 10.5 8.7 11.2 8.9 11.3 8.8 11.6 8.5 11.9 8.3
125 9.4 7.9 11.3 9.0 13.1 10.1 14.0 10.3 14.2 10.2 14.5 9.9 14.9 9.6
Room A Room B Room C Room D Room E Room F Room G Room H
Max. heat load (kW) 10.6 10.7 5.1 5.1 9.1 9.0 4.2 4.2
Selected IDU FXFQ125LUV1 FXFQ125LUV1 FXFQ50LUV1 FXFQ50LUV1 FXFQ100LUV1 FXFQ100LUV1 FXFQ40LUV1 FXFQ40LUV1
Corrected TC (kW) 13.1 13.1 5.2 5.2 10.5 10.5 4.2 4.2
Level difference 40m
Equivalent pipe length 60m
∗In case of selection based on Total Heat Load and Sensible Heat Load, select indoor units which satisfy not only the Total Heat Load but also the Sensible Heat Load of each room. The sensible heat capacity of indoor units is to be corrected for indoor air temperature. If the design temperature of indoor air falls between temperatures listed in table, calculate sensible heat capacity by using the bypass factor calculated by interpolation for each indoor air temperature.
EDMT341410.book Page 32 Friday, March 28, 2014 2:06 PM
EDMT341410 Selection Procedure
General Information 33
1 [3] –2 Provisionally select outdoor unit (1) Calculate CI (Capacity Index) of the selected indoor units.
-Using the capacity table of the outdoor unit, calculate the capacity (B) corrected for Outdoor air temperature, Indoor air temperature, and Combination ratio.
CI of VRV indoor units
CI of FXFQ125LUV1 = 125 CI of FXFQ100LUV1 = 100 CI of FXFQ50LUV1 = 50 CI of FXFQ40LUV1 = 40
Calculate the total CI of the indoor units. Total CI = 125×2 + 50×2 + 100×2 + 40×2 = 630
The combination ratio of RXQ-T shall be between 50% and 130%. As the total CI of indoor units is 630, outdoor units from 20HP to 50HP are connectable. Start from 20HP which is the smallest outdoor unit.
(3) Confirm that the number of the connected indoor unit is within the limitation.
The number of the connected indoor units = 8 The Max. number of connectable indoor units of 20HP outdoor unit = 32
[3] –3 Calculate the corrected capacity of the outdoor unit. -Calculate the combination ratio of the system. Total CI = 630, CI of RXQ20TY1 = 500 Combination ratio = 630 / 500 = 126%
(2) Provisionally select an outdoor unit based on the total CI of the indoor units
120% 126% 130%
58.0 (B) 59.0
∗ In case the outdoor air temperature, the indoor air temperature, or the combination ratio falls between temperatures listed in the table, calculate the capacity by interpolation.
Connection ratio
Cooling capacity
Selection Procedure EDMT341410
34 General Information
-Confirm capacity correction factor by piping length and level difference (K1)
-Calculate capacity correction factor by piping heat loss (K2) (K2) = 1 + (heat loss factor per meter of piping × (equivalent piping length – 7.5m)) / 100
In cooling mode, heat loss factor per meter at 33°C is calculated as below. Heat loss factor per meter = 0.022 + (0.030 – 0.022) × (33 – 30) / (35 – 30) = 0.0268
Using “Equivalent piping length = 60m” and “Heat loss factor per meter = 0.0268”, (K2) = 1 + (0.0268 × (60 – 7.5)) / 100 = 1.014
-Calculate the corrected capacity of RXQ20TY1(C) by using (K1) and (K2). Corrected capacity of RXQ20TY1 (C) = (B) × (K1) / (K2) 58.6 × 0.898 / 1.014 = 51.9 (kW)
If the corrected capacity (C) is the same or greater than the required total heat load (A), selection is complete. If (C) < (A), return to Procedure [3]–2 and provisionally select a larger outdoor unit.
In this example, 51.9kW (C) ≥ 50.7kW (A), so selection is complete.
Cooling Ambient temperature
Heat loss factor per meter of piping (%)
5°C 10°C 15°C 20°C 25°C 30°C 35°C 40°C
0.000 0.000 0.004 0.009 0.014 0.022 0.030 0.038
0.898
EDMT341410 Selection Procedure
General Information 35
1 6.2 Selection Procedure for Mixed Combination of VRV and Residential Indoor
Units 6.2.1 Flowchart
For the selection of Residential indoor units, the following procedures shall be added to the standard selection of VRV indoor units. -Correct the capacity of VRV indoor units for “Evaporating temperature (Te: 9ºC)”. -Correct the capacity of Residential indoor units for “Indoor air temperature”. -Use Correction factor to calculate the capacity of outdoor units.
6.2.2 Selection Example The following is a selection example based on Total Heat Load for cooling.
[1] Given conditions -Design conditions Indoor air temperature: 18°CWB / 25°CDB, Outdoor air temperature: 33°CDB
-Determine the peak load of each room (and the system peak load if necessary)
Table of the required heat load of each room
Total heat load (kW)
-Safety factor In this example, safety factor is not used. (i. e., safety factor = 1.0)
[2] Selection of indoor units For VRV indoor unit selection (Room A, B, C, D)
In case of mixed selection of VRV indoor units and Residential indoor units, correct the capacity of VRV indoor units for “Indoor air temperature” and “Evaporating temperature (Te: 9ºC)”. In case design temperature of the indoor air falls between temperatures listed in the table, calculate the capacity by interpolation.
-Capacity table of VRV indoor units Cooling Capacity
TC: Total Capacity SHC: Sensible Heat Capacity (kW)
Room A Room B Room C Room D Room E Room F Room G Total
3.5 4.7 4.5 5.0 4.0 3.7 4.8 30.2
Level difference 20m
Equivalent pipe length 40m
Room A Room B Room C Room D Room E Room F Room G
VRV indoor units (ducted) for Room A, B, C, D, and Residential indoor units (wall mounted) for Room E, F, G.
EDMT341410.book Page 35 Friday, March 28, 2014 2:06 PM
Selection Procedure EDMT341410
36 General Information
-Correction factors in case Te: 9ºC
For Residential indoor unit selection (Room E, F, G) Correct the capacity of Residential indoor units for “Indoor air temperature”. In case design temperature of the indoor air falls between temperatures listed in the table, calculate the capacity by interpolation.
-Capacity table of Residential indoor units Cooling Capacity
TC: Total Capacity SHC: Sensible Heat Capacity (kW)
-The corrected total heat capacity of both VRV and Residential indoor units shall satisfy the maximum heat load of each room.
Selection result of the indoor units
Model Capacity indication
Indoor air temp.
14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FTKS-DVM 25 1.5 1.4 1.8 1.7 2.3 1.9 2.5 2.0 2.7 2.1 2.9 1.9 3.1 1.9
35 2.0 1.9 2.5 2.3 3.2 2.6 3.5 2.7 3.8 2.8 4.0 2.6 4.3 2.7
FTKS-FVM
50 2.9 2.9 3.6 3.4 4.5 3.9 5.0 4.0 5.4 4.1 5.8 3.7 6.1 3.9
60 3.5 3.4 4.3 4.0 5.4 4.7 6.0 4.8 6.5 4.9 6.9 4.5 7.3 4.6
71 4.1 3.9 5.0 4.5 6.4 5.3 7.1 5.5 7.7 5.6 8.2 5.3 8.7 5.5
Room A Room B Room C Room D Room E Room F Room G
Max. heat load (kW) 3.5 4.7 4.5 5.0 4.0 3.7 4.8
Selected IDU FXDQ50NBVE FXDQ63NBVE FXDQ63NBVE FXDQ63NBVE FTKS50FVM FTKS50FVM FTKS60FVM
Corrected TC (kW) 3.9 5.1 5.1 5.1 4.5 4.5 5.4
FXDQ-PB, -NB
In order to calculate the corrected SHC, use correction factor of SHF = 1.118. SHC = 1.8kW, SHF = SHC / TC = 0.857 SHF (at Te: 9ºC) = 0.857 × 1.118 = 0.958, SHC (at Te: 9ºC) = 1.6kW × 0.958 =1.5kW
18ºCWB Correction (kW) factor
0.755 0.755 0.754 0.758 0.758 0.767
1.6 2.0 2.6 3.2 3.9 5.1
FXDQ25PB FXDQ32PB FXDQ40NB FXDQ50NB FXDQ63NB
Table of TC corrected for indoor air temp. (18ºCWB)-How to correct the capacity in case indoor air temperature = 18ºCWB. Model: FXDQ20PB TC = 2.1kW Using “correction factor for TC = 0.755”, TC = 2.1kW × 0.755 = 1.6kW
EDMT341410.book Page 36 Friday, March 28, 2014 2:06 PM
EDMT341410 Selection Procedure
General Information 37
1 [3] Selection of outdoor unit [3] –1 Define the required total heat load from the indoor units to the outdoor unit Define the required total heat load (A) based on either (1) the sum of the peak load of each room or (2) the system peak load. In this example, select an outdoor unit based on (1). Therefore, (A) = 30.2 kW
[3] –2 Provisionally select outdoor unit (1) Calculate CI (Capacity Index) of the selected indoor units. CI of VRV indoor units
CI of FXDQ50NBVE = 50 CI of FXDQ63NBVE = 62.5
CI of Residential indoor units CI of FTKS50FVM = 50 CI of FTKS60FVM = 60
Calculate the total CI of the indoor units. Total CI = 50 × 1 + 62.5 × 3 + 50 × 2 + 60 × 1 = 397.5
(2) Provisionally select an outdoor unit based on the total CI of the indoor units As the total capacity index of indoor units is 397.5, outdoor units from 14HP to 20HP are connectable. Start from 14HP which is the smallest.
(3) Confirm that the number of the connected indoor units to the outdoor unit is within the limitation. The number of the connected indoor units = 7 The Max. number of connectable indoor units of 14HP outdoor unit = 22
[3] –3 Calculate the corrected capacity of the outdoor unit. -Calculate the correction factor of the outdoor unit Correction factor of outdoor unit =
Correction factor of outdoor unit = = 0.93
-Calculate the combination ratio of the system.
Total CI = 397.5, CI of RXQ14TY1 = 350 Combination ratio = 397.5 / 350 = 114%
VRV Indoor Units
Residential Indoor Units with Connection to BP Units
Capacity range 2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW 8.0kW 9.0kW 11.2kW 14.0kW 16.0kW 22.4kW 28.0kW 45.0kW 56.0kW Power
supply, Standard
0.8HP 1HP 1.25HP 1.6HP 2HP 2.5HP 3HP 3.2HP 4HP 5HP 6HP 8HP 10HP 16HP 20HP Capacity index 20 25 31.25 40 50 62.5 71 80 100 125 140 200 250 400 500
Slim Ceiling Mounted Duct Type
FXDQ- NBVE — — — 40NB 50NB 63NB — — — — — — — — — VE
Capacity range 2.5kW 3.5kW 5.0kW 6.0kW 7.1kW Power supply,
StandardCapacity index 25 35 50 60 71
Wall Mounted Type FTKS
connectable indoor units Maximum number of
connectable indoor units 6HP 150 RXQ6T 75 to 195 (195) 9 (9) 8HP 200 RXQ8T 100 to 260 (260) 13 (13) 10HP 250 RXQ10T 125 to 325 (325) 16 (16) 12HP 300 RXQ12T 150 to 390 (390) 19 (19) 14HP 350 RXQ14T 175 to 455 (455) 22 (22) 16HP 400 RXQ16T 200 to 520 (520) 26 (26) 18HP 450 RXQ18T 225 to 585 (585) 29 (29) 20HP 500 RXQ20T 250 to 650 (650) 32 (32)
Σ (VRV indoor unit capacity index × Correction factor for Te: 9ºC for each indoor unit at rated condition) × 1.12 + Σ (Residential indoor unit capacity index)
Σ (VRV indoor unit capacity index) + Σ (Residential indoor unit capacity index)
FXDQ-PB, -NB Correction factor for Te: 9ºC
(50 × 0.781 × 1 + 62.5 × 0.793 × 3) × 1.12 + (50 × 2 + 60 × 1)
(50 × 1 + 62.5 × 3) +(50 × 2 + 60 × 1)
EDMT341410.book Page 37 Friday, March 28, 2014 2:06 PM
Selection Procedure EDMT341410
38 General Information
[3] –3 Calculate the corrected capacity of the outdoor unit. Using the capacity table of the outdoor unit, calculate capacity (B) corrected for “Outdoor air temperature”, “Indoor air temperature”, “Combination ratio”, and “Correction factor for outdoor units”.
-Confirm capacity correction factor for piping length and level difference (K1)
-Calculate capacity correction factor for piping heat loss (K2) (K2) = 1 + (heat loss factor per meter of piping × (equivalent piping length – 7.5m)) / 100
Heat loss factor per meter at 33ºC is calculated as below. Heat loss factor per meter = 0.022 + (0.030 – 0.022) × (33 – 30) / (35 – 30) = 0.0268
(?) = 33.4 + (36.4 – 33.4) × (114 – 110) / (120 – 110) = 34.6
RXQ14TY1 Cooling capacity (Capacity correction factor: 0.95) (Te: 9ºC) RXQ14TY1 Cooling capacity (Capacity correction factor: 0.90) (Te: 9ºC)
-Calculate the capacity in case combination ratio = 114%
In case correction factor = 0.95
Combination ratio 110% 114% 120% Cooling capacity 33.4 36.4
(?) = 31.6 + (34.5 – 31.6) × (114 – 110) / (120 – 110) = 32.8
In case correction factor = 0.90
Combination ratio 110% 114% 120% Cooling capacity 31.6 34.5
(B) = 32.8 + (34.6 – 32.8) × (0.93 – 0.90) / (0.95 – 0.90) = 33.9
Correction factor 0.95 0.93 0.90 Cooling capacity 34.6 32.8
-Calculate the capacity in case correction factor of outdoor unit = 0.93
(B)
EDMT341410 Selection Procedure
General Information 39
1 Using “Equivalent piping length = 40m” and “Heat loss factor per meter = 0.0268”, (K2) = 1 + (0.0268 × (40 – 7.5)) / 100 = 1.009
-Calculate the corrected capacity of RXQ14TY1 (C) by using (K1) and (K2). Corrected capacity of RXQ14TY1 (C) = (B) × (K1) / (K2) 33.9 × 0.959 / 1.009 = 32.2 (kW)
If the corrected capacity (C) is the same or greater than the required total heat load (A), selection is complete. If (C) < (A), return to Procedure [3]–2 and provisionally select a larger outdoor unit. In this example, 32.2kW (C) ≥ 30.2kW (A), so the selection is complete.
Cooling Ambient temperature
Heat loss factor per meter of piping (%)
5°C 10°C 15°C 20°C 25°C 30°C 35°C 40°C
0.000 0.000 0.004 0.009 0.014 0.022 0.030 0.038
EDMT341410.book Page 39 Friday, March 28, 2014 2:06 PM
Selection Procedure EDMT341410
40 General Information
EDMT341410
FXFQ-S Ceiling Mounted Cassette (Round Flow with Sensing) Type . . . . . . . . . . . . . 43
FXFQ-LU Ceiling Mounted Cassette (Round Flow) Type (For ASEAN) . . . . . . . . . . . . . . 59
FXZQ-M Ceiling Mounted Cassette (Compact Multi Flow) Type. . . . . . . . . . . . . . . . . . 75
FXUQ-A 4-Way Flow Ceiling Suspended Type . . . . . . . . . . 91
FXCQ-M Ceiling Mounted Cassette (Double Flow) Type . . . 103
FXKQ-MA Ceiling Mounted Cassette Corner Type . . . . . . . 121
FXDQ-PB / FXDQ-NB Slim Ceiling Mounted Duct Type . . . . . . . . . . . . 135
FXMQ-P Ceiling Mounted Duct Type. . . . . . . . . . . . . . . . . 159
FXMQ-MA Ceiling Mounted Duct Type. . . . . . . . . . . . . . . . . 187
FXHQ-MA Ceiling Suspended Type . . . . . . . . . . . . . . . . . . . 201
FXAQ-P Wall Mounted Type . . . . . . . . . . . . . . . . . . . . . . . 215
EDMT341410.book Page 41 Friday, March 28, 2014 2:06 PM
EDMT341410
FXLQ-MA / FXNQ-MA Floor Standing Type / Concealed Floor Standing Type . . . . . . . . . . . . . 231
FXVQ-M Floor Standing Duct Type . . . . . . . . . . . . . . . . . . 253
EDMT341410.book Page 42 Friday, March 28, 2014 2:06 PM
EDMT341410
1. Specifications ........................................................................................44 2. Dimensions ...........................................................................................46 3. Piping Diagrams....................................................................................49 4. Wiring Diagrams....................................................................................50 5. Electric Characteristics..........................................................................51 6. Safety Devices Setting ..........................................................................52 7. Capacity Tables ....................................................................................53
Specifications EDMT341410
44 FXFQ-S
1. Specifications
Ceiling mounted cassette (Round flow with sensing) type
Notes: 1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. 2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. 3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions. 4. Refer to Electric Characteristics for the power input.
Model FXFQ25SVM FXFQ32SVM FXFQ40SVM FXFQ50SVM
Power supply 1 phase,
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 246×840×840 246×840×840 246×840×840 246×840×840
Coil (Cross fin coil)
Rows×Stages×Fin pitch mm 2×8×1.20 2×8×1.20 2×8×1.20 3×(12+15×2)×(1.25+1.20×2)
Face area m² 0.244 0.244 0.244 0.427
Fan
Type Turbo fan Turbo fan Turbo fan Turbo fan
Motor output × Number of units W 48×1 48×1 48×1 48×1
Airflow rate (H/M/L)
l/s 208/192/167 208/192/167 242/217/183 367/292/225
cfm 441/406/353 441/406/353 512/459/388 777/618/477
Drive Direct drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Polyurethane form Polyurethane form Polyurethane form Polyurethane form
Piping connections
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection)
Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection)
Drain pipe mm VP25 (External dia. 32) VP25 (External dia. 32) VP25 (External dia. 32) VP25 (External dia. 32)
Mass kg 19 19 19 23
3 Sound pressure level (H/M/L) dB(A) 30.0/28.5/27.0 30.0/28.5/27.0 31.0/29.0/27.0 36.0/32.0/28.0
Sound power level (H/M/L) dB(A) 47.0/45.5/44.0 47.0/45.5/44.0 48.0/46.0/44.0 53.0/49.0/45.0
Safety devices Fuse Fuse Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Decoration panels (Option)
Colour Fresh white Fresh white Fresh white Fresh white
Dimensions: (H×W×D) mm 50×950×950 50×950×950 50×950×950 50×950×950
Air filter Resin net (with mould resistance)
Resin net (with mould resistance)
Resin net (with mould resistance)
Resin net (with mould resistance)
Mass kg 5.5 5.5 5.5 5.5
Standard accessories
Operation manual. Installation manual. Installation pattern paper. Drain hose. Metal clamp. Washer clamp. Sealing material. Clamp. Screw. Washer for hanger. Joint insulating material. Installation guide.
Operation manual. Installation manual. Installation pattern paper. Drain hose. Metal clamp. Washer clamp. Sealing material. Clamp. Screw. Washer for hanger. Joint insulating material. Installation guide.
Operation manual. Installation manual. Installation pattern paper. Drain hose. Metal clamp. Washer clamp. Sealing material. Clamp. Screw. Washer for hanger. Joint insulating material. Installation guide.
Operation manual. Installation manual. Installation pattern paper. Drain hose. Metal clamp. Washer clamp. Sealing material. Clamp. Screw. Washer for hanger. Joint insulating material. Installation guide.
Drawing No. C: 3D084443A
cfm=m³/min×35.3
EDMT341410 Specifications
FXFQ-S 45
2 Ceiling mounted cassette (Round flow with sensing) type
Notes: 1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. 2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. 3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions. 4. Refer to Electric Characteristics for the power input.
Model FXFQ63SVM FXFQ80SVM FXFQ100SVM FXFQ125SVM
Power supply 1 phase,
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 246×840×840 246×840×840 288×840×840 288×840×840
Coil (Cross fin coil)
Rows×Stages×Fin pitch mm 3×(12+15×2)×(1.25+1.20×2) 3×(12+15×2)×(1.25+1.20×2) 3×18×(1.25+1.20×2) 3×18×(1.25+1.20×2)
Face area m² 0.427 0.427 0.550 0.550
Fan
Type Turbo fan Turbo fan Turbo fan Turbo fan
Motor output × Number of units W 48×1 48×1 106×1 106×1
Airflow rate (H/M/L)
l/s 392/308/225 392/325/250 550/433/317 575/458/350
cfm 830/653/477 830/688/530 1,165/918/671 1,212/971/741
Drive Direct drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Polyurethane form Polyurethane form Polyurethane form Polyurethane form
Piping connections
Liquid pipes mm φ9.5 (Flare connection) φ9.5 (Flare connection) φ9.5 (Flare connection) φ9.5 (Flare connection)
Gas pipes mm φ15.9 (Flare connection) φ15.9 (Flare connection) φ15.9 (Flare connection) φ15.9 (Flare connection)
Drain pipe mm VP25 (External dia. 32) VP25 (External dia. 32) VP25 (External dia. 32) VP25 (External dia. 32)
Mass kg 23 23 26 26
3 Sound pressure level (H/M/L) dB(A) 38.0/33.0/28.0 38.0/35.0/31.0 44.0/38.0/32.0 45.0/40.0/35.0
Sound power level (H/M/L) dB(A) 55.0/50.0/45.0 55.0/52.0/48.0 60.0/54.0/48.0 61.0/56.0/51.0
Safety devices Fuse Fuse Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Decoration panels (Option)
Panel colour Fresh white Fresh white Fresh white Fresh white
Dimensions: (H×W×D) mm 50×950×950 50×950×950 50×950×950 50×950×950
Air filter Resin net (with mould resistance)
Resin net (with mould resistance)
Resin net (with mould resistance)
Resin net (with mould resistance)
Mass kg 5.5 5.5 5.5 5.5
Standard accessories
Operation manual. Installation manual. Installation pattern paper. Drain hose. Metal clamp. Washer clamp. Sealing material. Clamp. Screw. Washer for hanger. Joint insulating material. Installation guide.
Operation manual. Installation manual. Installation pattern paper. Drain hose. Metal clamp. Washer clamp. Sealing material. Clamp. Screw. Washer for hanger. Joint insulating material. Installation guide.
Operation manual. Installation manual. Installation pattern paper. Drain hose. Metal clamp. Washer clamp. Sealing material. Clamp. Screw. Washer for hanger. Joint insulating material. Installation guide.
Operation manual. Installation manual. Installation pattern paper. Drain hose. Metal clamp. Washer clamp. Sealing material. Clamp. Screw. Washer for hanger. Joint insulating material. Installation guide.
Drawing No. C: 3D084443A
cfm=m³/min×35.3
Dimensions EDMT341410
46 FXFQ-S
2. Dimensions
3D 08
43 88
EDMT341410 Dimensions
FXFQ-S 47
Dimensions EDMT341410
48 FXFQ-S
EDMT341410 Piping Diagrams
Model Gas Liquid
4D024460K
Wiring Diagrams EDMT341410
3D 08
43 49
EDMT341410 Electric Characteristics
Safety Devices Setting EDMT341410
Model FXFQ25SVM FXFQ32SVM FXFQ40SVM FXFQ50SVM FXFQ63SVM FXFQ80SVM FXFQ100SVM FXFQ125SVM
Printed circuit board fuse 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A
Drain pump thermal fuse °C – – – – – – – –
Fan motor thermal fuse °C – – – – – – – –
Fan motor thermal protector °C – – – – – – – –
C: 3D085300
EDMT341410 Capacity Tables
TC: Total capacity: kW SHC: Sensible heat capacity: kW
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system satisfies the required heat load.
2. shows rated condition.
Model Capacity indication
Indoor air temp.
14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXFQ-S
25 1.9 2.0 2.3 2.3 2.6 2.5 2.8 2.5 2.8 2.5 2.9 2.4 3.0 2.4
32 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.6 2.8 3.7 2.7 3.8 2.6
40 3.0 2.6 3.6 3.0 4.2 3.3 4.5 3.4 4.6 3.4 4.7 3.3 4.8 3.2
50 3.8 3.9 4.5 4.4 5.2 5.0 5.6 5.0 5.7 5.0 5.8 4.8 5.9 4.7
63 4.8 4.5 5.7 5.2 6.6 5.8 7.1 5.9 7.2 5.8 7.4 5.6 7.5 5.5
80 6.1 5.2 7.2 5.9 8.4 6.6 9.0 6.7 9.1 6.6 9.3 6.4 9.5 6.2
100 7.6 6.8 9.0 7.7 10.5 8.7 11.2 8.8 11.3 8.6 11.6 8.4 11.9 8.2
125 9.4 7.9 11.3 9.0 13.1 10.1 14.0 10.2 14.2 10.1 14.5 9.7 14.9 9.4
EDMT341410.book Page 53 Friday, March 28, 2014 2:06 PM
Capacity Tables EDMT341410
7.2 Correction Factor for Te: 9°C
VRV (Te: 9°C) 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
FXFQ25SVM TC 0.724 0.757 0.808 0.827 0.844 0.873 0.895
SHF 1.131 1.141 1.103 1.088 1.073 1.052 1.038
FXFQ32SVM TC 0.724 0.757 0.808 0.827 0.844 0.873 0.895
SHF 1.131 1.141 1.103 1.088 1.073 1.052 1.038
FXFQ40SVM TC 0.744 0.765 0.815 0.833 0.849 0.877 0.898
SHF 1.101 1.136 1.099 1.085 1.072 1.052 1.038
FXFQ50SVM TC 0.662 0.733 0.788 0.807 0.825 0.855 0.878
SHF 1.201 1.143 1.100 1.084 1.068 1.045 1.030
FXFQ63SVM TC 0.667 0.736 0.790 0.808 0.827 0.856 0.879
SHF 1.193 1.141 1.100 1.084 1.068 1.046 1.030
FXFQ80SVM TC 0.667 0.736 0.790 0.808 0.827 0.856 0.879
SHF 1.193 1.141 1.100 1.084 1.068 1.046 1.030
FXFQ100SVM TC 0.675 0.741 0.793 0.811 0.828 0.857 0.880
SHF 1.180 1.136 1.097 1.082 1.068 1.053 1.037
FXFQ125SVM TC 0.679 0.742 0.794 0.812 0.829 0.858 0.881
SHF 1.175 1.135 1.097 1.082 1.068 1.053 1.038
When a mixed combination of VRV and residential indoor units is connected
EDMT341410.book Page 54 Friday, March 28, 2014 2:06 PM
EDMT341410 Sound Levels
Octave Band Level 220-240/220 · 230V, 50/60Hz
Location of microphone (for sound pressure level) Notes: 1. The operating conditions are assumed to be standard
(JIS conditions). 2. These operating values were obtained in anechoic
chamber (conversion values). Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of the particular room in which the equipment installed.
dB(A)
Model
FXFQ40SVM 31.0 29.0 27.0
FXFQ50SVM 36.0 32.0 28.0
FXFQ63SVM 38.0 33.0 28.0
FXFQ80SVM 38.0 35.0 31.0
FXFQ100SVM 44.0 38.0 32.0
FXFQ125SVM 45.0 40.0 35.0
FXFQ25SVM / FXFQ32SVM FXFQ40SVM FXFQ50SVM
Sound Levels EDMT341410
EDMT341410 Centre of Gravity
FXFQ25SVM / FXFQ32SVM / FXFQ40SVM / FXFQ50SVM / FXFQ63SVM / FXFQ80SVM / FXFQ100SVM / FXFQ125SVM
Unit (mm)
C: 4D052237L
Accessories EDMT341410
58 FXFQ-S
C: 3D084501B
Note: 1. Two of four corner air outlets are closed Without T-joint pipe. Fresh air intake volume is 10% or less of airflow rate.
10.2 Optional Accessories (for Controls) Refer to page 722.
Item Note Model
Decoration panel BYCQ125B-W1
Panel spacer KDBP55H160FA
Ultra long-life filter KAFP55B160
Fresh air intake kit
1 KDDQ55B140
1 KDDP55B160K
Insulation kit for high humidity KDTP55K80 KDTP55K160
EDMT341410.book Page 58 Friday, March 28, 2014 2:06 PM
EDMT341410
1. Specifications ........................................................................................60 2. Dimensions ...........................................................................................62 3. Piping Diagrams....................................................................................65 4. Wiring Diagrams....................................................................................66 5. Electric Characteristics..........................................................................67 6. Safety Devices Setting ..........................................................................68 7. Capacity Tables ....................................................................................69
Specifications EDMT341410
60 FXFQ-LU
1. Specifications
Ceiling mounted cassette (Round flow) type
Notes: 1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. 2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. 3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions. 4. Refer to Electric Characteristics for the power input.
Model FXFQ25LUV1 FXFQ32LUV1 FXFQ40LUV1 FXFQ50LUV1
Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
1 2 Cooling capacity (19°CWB)
kcal/h 2,400 3,100 3,900 4,800
Btu/h 9,600 12,300 15,400 19,100
kW 2.8 3.6 4.5 5.6
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 246×840×840 246×840×840 246×840×840 246×840×840
Coil (Cross fin coil)
Rows×Stages×Fin pitch mm 2×6×1.2 2×6×1.2 2×6×1.2 2×6×1.2
Face area m² 0.267 0.267 0.267 0.267
Fan
Type Turbo fan Turbo fan Turbo fan Turbo fan
Motor output × Number of units W 56×1 56×1 56×1 56×1
Airflow rate (HH/H/L) m³/min 13/11.5/10 13/11.5/10 15/13/11 16/13.5/11
cfm 459/406/353 459/406/353 530/459/388 565/477/388
Drive Direct drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Polyurethane form Polyurethane form Polyurethane form Polyurethane form
Piping connections
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection)
Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection)
Drain pipe mm VP25
VP25 External dia. 32 Internal dia. 25
VP25 External dia. 32 Internal dia. 25
VP25 External dia. 32 Internal dia. 25
Mass (Weight) kg 19.5 19.5 19.5 19.5
3 Sound pressure level (HH/H/L) dB(A) 30/28.5/27 30/28.5/27 31/29/27 32/29.5/27
Safety devices Fuse Fuse Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Decoration panels (Option)
Panel colour Fresh white Fresh white Fresh white Fresh white
Dimensions: (H×W×D) mm 50×950×950 50×950×950 50×950×950 50×950×950
Air filter Resin net (with mould resistance)
Resin net (with mould resistance)
Resin net (with mould resistance)
Resin net (with mould resistance)
Mass (Weight) kg 5.5 5.5 5.5 5.5
Standard accessories
Operation manual. Installation manual. Paper pattern for installation. Drain hose. Clamp metal. Washer fixing plate. Sealing pads. Clamps. Screws. Washer for hanging bracket. Insulation for fitting. Installation guide.
Operation manual. Installation manual. Paper pattern for installation. Drain hose. Clamp metal. Washer fixing plate. Sealing pads. Clamps. Screws. Washer for hanging bracket. Insulation for fitting. Installation guide.
Operation manual. Installation manual. Paper pattern for installation. Drain hose. Clamp metal. Washer fixing plate. Sealing pads. Clamps. Screws. Washer for hanging bracket. Insulation for fitting. Installation guide.
Operation manual. Installation manual. Paper pattern for installation. Drain hose. Clamp metal. Washer fixing plate. Sealing pads. Clamps. Screws. Washer for hanging bracket. Insulation for fitting. Installation guide.
Drawing No. C: 3D081322
cfm=m³/min×35.3
EDMT341410 Specifications
FXFQ-LU 61
Ceiling mounted cassette (Round flow) type
Notes: 1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. 2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. 3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions. 4. Refer to Electric Characteristics for the power input.
Model FXFQ63LUV1 FXFQ80LUV1 FXFQ100LUV1 FXFQ125LUV1
Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
1 2 Cooling capacity (19°CWB)
kcal/h 6,100 7,700 9,600 12,000
Btu/h 24,200 30,700 38,200 47,800
kW 7.1 9.0 11.2 14.0
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 246×840×840 246×840×840 288×840×840 288×840×840
Coil (Cross fin coil)
Rows×Stages×Fin pitch mm 2×10×1.2 2×10×1.2 2×12×1.2 2×12×1.2
Face area m² 0.446 0.446 0.535 0.535
Fan
Type Turbo fan Turbo fan Turbo fan Turbo fan
Motor output × Number of units W 56×1 56×1 120×1 120×1
Airflow rate (HH/H/L) m³/min 19/16.5/13.5 21/18/15 32/26/20 33/28/22.5
cfm 671/583/477 742/636/530 1,130/918/706 1,165/989/794
Drive Direct drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Polyurethane form Polyurethane form Polyurethane form Polyurethane form
Piping connections
Liquid pipes mm φ9.5 (Flare connection) φ9.5 (Flare connection) φ9.5 (Flare connection) φ9.5 (Flare connection)
Gas pipes mm φ15.9 (Flare connection) φ15.9 (Flare connection) φ15.9 (Flare connection) φ15.9 (Flare connection)
Drain pipe mm VP25
VP25 External dia. 32 Internal dia. 25
VP25 External dia. 32 Internal dia. 25
VP25 External dia. 32 Internal dia. 25
Mass (Weight) kg 22 22 25 25
3 Sound pressure level (HH/H/L) dB(A) 34/31/28 36/33.5/31 43/37.5/32 44/39/34
Safety devices Fuse Fuse Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Decoration panels (Option)
Panel colour Fresh white Fresh white Fresh white Fresh white
Dimensions: (H×W×D) mm 50×950×950 50×950×950 50×950×950 50×950×950
Air filter Resin net (with mould resistance)
Resin net (with mould resistance)
Resin net (with mould resistance)
Resin net (with mould resistance)
Mass (Weight) kg 5.5 5.5 5.5 5.5
Standard accessories
Operation manual. Installation manual. Paper pattern for installation. Drain hose. Clamp metal. Washer fixing plate. Sealing pads. Clamps. Screws. Washer for hanging bracket. Insulation for fitting. Installation guide.
Operation manual. Installation manual. Paper pattern for installation. Drain hose. Clamp metal. Washer fixing plate. Sealing pads. Clamps. Screws. Washer for hanging bracket. Insulation for fitting. Installation guide.
Operation manual. Installation manual. Paper pattern for installation. Drain hose. Clamp metal. Washer fixing plate. Sealing pads. Clamps. Screws. Washer for hanging bracket. Insulation for fitting. Installation guide.
Operation manual. Installation manual. Paper pattern for installation. Drain hose. Clamp metal. Washer fixing plate. Sealing pads. Clamps. Screws. Washer for hanging bracket. Insulation for fitting. Installation guide.
Drawing No. C: 3D081322
cfm=m³/min×35.3
Dimensions EDMT341410
62 FXFQ-LU
2. Dimensions
3D 08
15 56
EDMT341410 Dimensions
FXFQ-LU 63
Dimensions EDMT341410
64 FXFQ-LU
EDMT341410 Piping Diagrams
Model Gas Liquid
4D024460K
Wiring Diagrams EDMT341410
3D 08
08 79
EDMT341410 Electric Characteristics
Safety Devices Setting EDMT341410
Model FXFQ25LUV1 FXFQ32LUV1 FXFQ40LUV1 FXFQ50LUV1 FXFQ63LUV1 FXFQ80LUV1 FXFQ100LUV1 FXFQ125LUV1
Printed circuit board fuse 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A
Fan motor thermal fuse °C – – – – – – – –
Fan motor thermal protector °C – – – – – – – –
C: 3D006691T
EDMT341410 Capacity Tables
TC: Total capacity: kW SHC: Sensible heat capacity: kW
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system satisfies the required heat load.
2. shows rated condition.
Model Capacity indication
Indoor air temp.
14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXFQ-LU
25 1.9 1.9 2.3 2.3 2.6 2.6 2.8 2.8 2.8 2.8 2.9 2.7 3.0 2.6
32 2.4 2.4 2.9 2.8 3.4 3.1 3.6 3.1 3.6 3.1 3.7 3.1 3.8 3.0
40 3.0 2.9 3.6 3.4 4.2 3.7 4.5 3.8 4.6 3.7 4.7 3.6 4.8 3.5
50 3.8 3.4 4.5 3.9 5.2 4.3 5.6 4.4 5.7 4.4 5.8 4.2 5.9 4.1
63 4.8 4.3 5.7 4.9 6.6 5.5 7.1 5.6 7.2 5.5 7.4 5.4 7.5 5.2
80 6.1 5.1 7.2 5.8 8.4 6.5 9.0 6.6 9.1 6.6 9.3 6.4 9.5 6.2
100 7.6 6.8 9.0 7.8 10.5 8.7 11.2 8.9 11.3 8.8 11.6 8.5 11.9 8.3
125 9.4 7.9 11.3 9.0 13.1 10.1 14.0 10.3 14.2 10.2 14.5 9.9 14.9 9.6
EDMT341410.book Page 69 Friday, March 28, 2014 2:06 PM
Capacity Tables EDMT341410
7.2 Correction Factor for Te: 9°C
VRV (Te: 9°C) 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
FXFQ25LUV1 TC 0.696 0.741 0.794 0.813 0.831 0.861 0.884
SHF 1.156 1.151 1.107 1.091 1.077 1.053 1.037
FXFQ32LUV1 TC 0.673 0.728 0.784 0.803 0.820 0.851 0.874
SHF 1.175 1.155 1.107 1.091 1.077 1.052 1.036
FXFQ40LUV1 TC 0.681 0.732 0.786 0.805 0.821 0.852 0.875
SHF 1.165 1.152 1.106 1.090 1.077 1.053 1.036
FXFQ50LUV1 TC 0.662 0.692 0.755 0.779 0.800 0.834 0.858
SHF 1.173 1.183 1.121 1.096 1.079 1.054 1.035
FXFQ63LUV1 TC 0.664 0.693 0.756 0.781 0.803 0.834 0.858
SHF 1.168 1.182 1.121 1.095 1.078 1.054 1.035
FXFQ80LUV1 TC 0.670 0.693 0.756 0.784 0.807 0.834 0.858
SHF 1.154 1.181 1.120 1.093 1.075 1.055 1.036
FXFQ100LUV1 TC 0.678 0.697 0.763 0.790 0.810 0.834 0.858
SHF 1.140 1.174 1.115 1.089 1.073 1.060 1.048
FXFQ125LUV1 TC 0.680 0.697 0.763 0.790 0.810 0.834 0.858
SHF 1.136 1.175 1.115 1.089 1.072 1.061 1.049
When a mixed combination of VRV and residential indoor units is connected
EDMT341410.book Page 70 Friday, March 28, 2014 2:06 PM
EDMT341410 Sound Levels
Octave Band Level 220-240V, 50Hz
Location of microphone (for sound pressure level) Notes: 1. The operating conditions are assumed to be standard
(JIS conditions). 2. These operating values were obtained in anechoic
chamber (conversion values). Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of the particular room in which the equipment installed.
dB(A)
Model
FXFQ40LUV1 31 29 27
FXFQ50LUV1 32 29.5 27
FXFQ63LUV1 34 31 28
FXFQ80LUV1 36 33.5 31
FXFQ100LUV1 43 37.5 32
FXFQ125LUV1 44 39 34
FXFQ25LUV1 / FXFQ32LUV1 FXFQ40LUV1 FXFQ50LUV1
Sound Levels EDMT341410
EDMT341410 Centre of Gravity
Unit (mm)
C: 4D052237L
Accessories EDMT341410
74 FXFQ-LU
C: 3D081321A
Item Model
Decoration panel BYCP125K-W1
Panel spacer KDBP55H160FA
Fresh air intake kit
KDDP55B160
KDDP55B160K
Chamber connection kit KKSJ55KA160
EDMT341410.book Page 74 Friday, March 28, 2014 2:06 PM
EDMT341410
Specifications EDMT341410
76 FXZQ-M
1. Specifications
Ceiling mounted cassette (Compact multi flow) type
Notes: 1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m. 2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. 3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions. 4. Refer to Electric Characteristics for the power input.
Model FXZQ20MVE FXZQ25MVE FXZQ32MVE
Power supply 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz
1 2 Cooling capacity (19°CWB)
kcal/h 1,900 2,400 3,100
Btu/h 7,500 9,600 12,300
kW 2.2 2.8 3.6
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 286×575×575 286×575×575 286×575×575
Coil (Cross fin coil)
Rows×Stages×Fin pitch mm 2×10×1.5 2×10×1.5 2×10×1.5
Face area m² 0.269 0.269 0.269
Fan
Type Turbo fan Turbo fan Turbo fan
Motor output × Number of units W 55×1 55×1 55×1
Airflow rate (H/L)
l/s 150/116 150/116 158/125
cfm 318/247 318/247 335/265
Temperature control Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Foamed polystyrene/ Foamed polyethylene
Foamed polystyrene/ Foamed polyethylene
Foamed polystyrene/ Foamed polyethylene
Piping connections
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection)
Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection)
Drain pipe mm VP20
VP20 External dia. 26 Internal dia. 20
VP20 External dia. 26 Internal dia. 20
Mass (Weight) kg 18 18 18
3 Sound pressure level (H/L)
230V, 50Hz dB(A)
30/25 30/25 32/26
Sound power level (H) 230V, 50Hz
dB(A) 47 47 49
Safety devices Printed circuit board fuse. Fan motor thermal protector.
Printed circuit board fuse. Fan motor thermal protector.
Printed circuit board fuse. Fan motor thermal protector.
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve
Decoration panels (Option)
Panel colour White (6.5Y9.5/0.5) White (6.5Y9.5/0.5) White (6.5Y9.5/0.5)
Dimensions: (H×W×D) mm 55×700×700 55×700×700 55×700×700
Air filter Resin net (with mould resistance)
Resin net (with mould resistance)
Resin net (with mould resistance)
Mass (Weight) kg 2.7 2.7 2.7
Standard accessories
Operation manual. Installation manual. Paper pattern for installation. Drain hose. Clamp metal. Washer fixing plate. Sealing pads. Clamps. Screws. Washer for hanging bracket. Insulation for fitting.
Operation manual. Installation manual. Paper pattern for installation. Drain hose. Clamp metal. Washer fixing plate. Sealing pads. Clamps. Screws. Washer for hanging bracket. Insulation for fitting.
Operation manual. Installation manual. Paper pattern for installation. Drain hose. Clamp metal. Washer fixing plate. Sealing pads. Clamps. Screws. Washer for hanging bracket. Insulation for fitting.
Drawing No. C: 3D038929C
cfm=m³/min×35.3
EDMT341410 Specifications
FXZQ-M 77
Ceiling mounted cassette (Compact multi flow) type
Notes: 1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m. 2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. 3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions. 4. Refer to Electric Characteristics for the power input.
Model FXZQ40MVE FXZQ50MVE
Power supply 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz
1 2 Cooling capacity (19°CWB)
kcal/h 3,900 4,800
Btu/h 15,400 19,100
kW 4.5 5.6
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 286×575×575 286×575×575
Coil (Cross fin coil)
Rows×Stages×Fin pitch mm 2×10×1.5 2×10×1.5
Face area m² 0.269 0.269
Fan
Motor output × Number of units W 55×1 55×1
Airflow rate (H/L)
Temperature control Microprocessor thermostat for cooling and heating Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Foamed polystyrene/Foamed polyethylene Foamed polystyrene/Foamed polyethylene
Piping connections
Drain pipe mm VP20
VP20 External dia. 26 Internal dia. 20
Mass (Weight) kg 18 18
3 Sound pressure level (H/L)
230V, 50Hz dB(A)
dB(A) 53 58
Safety devices Printed circuit board fuse. Fan motor thermal protector.
Printed circuit board fuse. Fan motor thermal protector.
Refrigerant control Electronic expansion valve Electronic expansion valve
Decoration panels (Option)
Model BYFQ60B8W1 BYFQ60B8W1
Panel colour White (6.5Y9.5/0.5) White (6.5Y9.5/0.5)
Dimensions: (H×W×D) mm 55×700×700 55×700×700
Air filter Resin net (with mould resistance)
Resin net (with mould resistance)
Mass (Weight) kg 2.7 2.7
Standard accessories
Operation manual. Installation manual. Paper pattern for installation. Drain hose. Clamp metal. Washer fixing plate. Sealing pads. Clamps. Screws. Washer for hanging bracket. Insulation for fitting.
Operation manual. Installation manual. Paper pattern for installation. Drain hose. Clamp metal. Washer fixing plate. Sealing pads. Clamps. Screws. Washer for hanging bracket. Insulation for fitting.
Drawing No. C: 3D038929C
cfm=m³/min×35.3
Dimensions EDMT341410
78 FXZQ-M
2. Dimensions
3D 03
90 05
EDMT341410 Piping Diagrams
(mm)
EDMT341410.book Page 79 Friday, March 28, 2014 2:06 PM
Wiring Diagrams EDMT341410
C : 3
D 06
48 43
EDMT341410 Electric Characteristics
Safety Devices Setting EDMT341410
Model FXZQ20MVE FXZQ25MVE FXZQ32MVE FXZQ40MVE FXZQ50MVE
Printed circuit board fuse 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A
Fan motor thermal fuse °C – – – – –
Fan motor thermal protector °C OFF: 130±5 ON : 83±20
OFF: 130±5 ON : 83±20
OFF: 130±5 ON : 83±20
OFF: 130±5 ON : 83±20
OFF: 130±5 ON : 83±20
C: 3D006691T
EDMT341410 Capacity Tables
TC: Total capacity: kW SHC: Sensible heat capacity: kW
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system satisfies the required heat load.
2. shows rated condition.
Model Capacity indication
Indoor air temp.
14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXZQ-M
20 1.5 1.3 1.8 1.5 2.1 1.7 2.2 1.7 2.2 1.6 2.3 1.5 2.3 1.4
25 1.9 1.5 2.3 1.8 2.6 2.0 2.8 2.0 2.8 1.9 2.9 1.8 3.0 1.7
32 2.4 1.9 2.9 2.1 3.4 2.4 3.6 2.4 3.6 2.2 3.7 2.2 3.8 2.1
40 3.0 2.5 3.6 2.9 4.2 3.2 4.5 3.3 4.6 3.2 4.7 3.1 4.8 2.9
50 3.8 3.1 4.5 3.6 5.2 4.0 5.6 4.1 5.7 4.1 5.8 3.9 5.9 3.7
EDMT341410.book Page 83 Friday, March 28, 2014 2:06 PM
Capacity Tables EDMT341410
7.2 Correction Factor for Te: 9°C
VRV (Te: 9°C) 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
FXZQ20MVE TC 0.655 0.695 0.757 0.779 0.797 0.832 0.860
SHF 1.196 1.179 1.118 1.095 1.080 1.052 1.031
FXZQ25MVE TC 0.655 0.695 0.757 0.779 0.797 0.832 0.860
SHF 1.196 1.179 1.118 1.095 1.080 1.052 1.031
FXZQ32MVE TC 0.656 0.694 0.757 0.779 0.797 0.833 0.876
SHF 1.194 1.180 1.119 1.095 1.080 1.051 1.032
FXZQ40MVE TC 0.666 0.687 0.751 0.775 0.794 0.826 0.856
SHF 1.174 1.189 1.125 1.099 1.081 1.056 1.034
FXZQ50MVE TC 0.674 0.691 0.753 0.777 0.798 0.832 0.856
SHF 1.150 1.182 1.121 1.096 1.077 1.055 1.036
When a mixed combination of VRV and residential indoor units is connected
EDMT341410.book Page 84 Friday, March 28, 2014 2:06 PM
EDMT341410 Air Velocity and Temperature Distributions (Reference Data)
FXZQ-M 85
FXZQ20MVE / FXZQ25MVE (Cooling)
Air Velocity and Temperature Distributions (Reference Data) EDMT341410
86 FXZQ-M
FXZQ40MVE (Cooling)
FXZQ50MVE (Cooling)
EDMT341410 Sound Levels
Octave Band Level (230V, 50Hz)
Location of microphone (for sound pressure level) Notes: 1. The operating conditions are assumed to be standard (JIS
conditions) 2. These operating values were obtained in anechoic
chamber (conversion values). Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of the particular room in which the equipment installed.
dB(A)
Model
230V, 50Hz 240V, 50Hz 230V, 50Hz 240V, 50Hz
H L H L H H
FXZQ20MVE FXZQ25MVE 30 25 32 26 47 49
FXZQ32MVE 32 26 34 28 49 51
FXZQ40MVE 36 28 37 29 53 54
FXZQ50MVE 41 33 42 35 58 59
FXZQ20MVE / FXZQ25MVE FXZQ32MVE
Sound Levels EDMT341410
FXZQ40MVE FXZQ50MVE
4D040492A 4D040491A
4D040490A 4D040293A
EDMT341410 Centre of Gravity
4D040158A
Accessories EDMT341410
90 FXZQ-M
C: 3D038933B
Item Model
Decoration panel BYFQ60B8W1
Panel spacer KDBQ44BA60A
EDMT341410.book Page 90 Friday, March 28, 2014 2:06 PM
EDMT341410
1. Specifications ........................................................................................92 2. Dimensions ...........................................................................................93 3. Piping Diagrams....................................................................................94 4. Wiring Diagrams....................................................................................95 5. Electric Characteristics..........................................................................96 6. Safety Devices Setting ..........................................................................97 7. Capacity Tables ....................................................................................98
Specifications EDMT341410
92 FXUQ-A
1. Specifications
4-way flow ceiling suspended type
Notes: 1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m. 2. The capacity of the indoor unit is only for reference. The actual capacity of the indoor unit is based on the total capacity index. 3. Anechoic chamber conversion value, measured at a point 1m in front of the unit and 1m downward. During actual operation, these values
are normally somewhat higher as a result of ambient conditions. 4. Refer to Electric Characteristics for the power input.
Model FXUQ71AVEB FXUQ100AVEB
1 2 Cooling capacity (19°CWB)
kcal/h 6,900 9,600
Btu/h 27,300 38,200
kW 8.0 11.2
Casing colour Fresh white Fresh white
Dimensions: (H×W×D) mm 198×950×950 198×950×950
Coil (Cross fin coil)
Rows×Stages×Fin pitch mm 3×10×1.2 3×10×1.2
Face area m² 0.330 0.330
Fan
Motor output × Number of units W 46×1 106×1
Airflow rate (H/M/L)
Temperature control Microprocessor thermostat for cooling and heating
Microprocessor thermostat for cooling and heating
Insulation Heat insulation Heat resistant foamed polyethylene / Regular foamed polyethylene
Heat resistant foamed polyethylene / Regular foamed polyethylene
Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Piping connections
Drain pipe mm VP20 (External dia. 26 Internal dia. 20)
VP20 (External dia. 26 Internal dia. 20)