Translation of Test Report No. (3136/2315) –CM from 2.12.2005 Seite 1 Test Report DIN EN 1365-2: 2000-02 in conjunction with DIN EN 1363-1: 1999-10 English translation prepared by Hilti Original signed version in German language from IBMB/MPA Braunschweig Document No.: (3136/2315) – CM from 2 nd of Decemer 2005 Client: Hilti Entwicklungsgesellschaft mbH Hiltistraße 6 D-86916 Kaufering Order date: 28th of September 2004 Order Ref.: Mr. Hartmann Order received: 15th of February 2005 Subject: Testing the fire resistance of a load-bearing, room closing, 200 mm thick reinforced concrete slab with 100 mm thick Heraklith "Tektalan TK" segmented wood-wool panels; in combination with Hilti IDMS insulating pins with 80 mm retention plates in galvanized zinc- plated steel and Hilti IDMR insulating pins in A2 stainless steel (material number 1.4301) with 80 mm retention plates in galvanized zinc-plated steel, to determine the fire resistance rating for exposure to fire from the underside of the structure. Test basis: DIN EN 1365-2: 2000-02 in conjunction with DIN EN 1363-1 : 1999-10 Samples received: Week 12 of 2005 Tested on: 31th of March 2005 Valid until: unlimited This test report contains ….. pages including the title page and 19 annexes.

Transcript of Test Report - България · PDF fileThis test report contains ... 2 Description of the...

Page 1: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

Translation of Test Report No. (3136/2315) –CM from 2.12.2005 Seite 1

Test Report

DIN EN 1365-2: 2000-02 in conjunction with DIN EN 1363-1: 1999-10

English translation prepared by Hilti

Original signed version in German language from IBMB/MPA Braunschweig

Document No.: (3136/2315) – CM from 2nd of Decemer 2005

Client: Hilti Entwicklungsgesellschaft mbH

Hiltistraße 6

D-86916 Kaufering

Order date: 28th of September 2004

Order Ref.: Mr. Hartmann

Order received: 15th of February 2005

Subject:

Testing the fire resistance of a load-bearing, room closing, 200 mm thick reinforced concrete slab with 100 mm thick Heraklith "Tektalan TK" segmented wood-wool panels; in combination with Hilti IDMS insulating pins with 80 mm retention plates in galvanized zinc-plated steel and Hilti IDMR insulating pins in A2 stainless steel (material number 1.4301) with 80 mm retention plates in galvanized zinc-plated steel, to determine the fire resistance rating for exposure to fire from the underside of the structure.

Test basis: DIN EN 1365-2: 2000-02 in conjunction with DIN EN 1363-1 : 1999-10

Samples received: Week 12 of 2005

Tested on: 31th of March 2005

Valid until: unlimited

This test report contains ….. pages including the title page and 19 annexes.

Page 2: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

1 General

TI1e contract provides for the testing of the fire resistance of a 300 mm thick, load-bearing, room

closing, heat insulating floor structure according to DIN EN 1365-2 : 2000-02 in conjunction with DIN

EN 1363-1 : 1999-10, in particular the determination of the fire resistance rating for exposure to fire

from the underside of the structure. The floor structure cornprised:

- a 200 mm thick reinforced concrete slab (concrete cover c = 35 mm) of concrete quality ~

C 20/25 - 100 mm thick Heraklith "Tektalan TK" segmented wood-wool panels in combination with

- Hilti IDMS insulating pins with 80 mm retention plates in galvanized zinc-plated steel and

- Hilti IDMR insulating pins in A2 stainless steel (material number 1.4301) with 80 mm retention

plates in galvanized zinc-plated steel.

The test was carried out as specified by DIN EN 1363-1, and comprised a comprehensive

description of the installation procedure and test conditions, and specification of the results obtained

for the structural component with which this report is concerned. The report does not cover possible

deviations from the standard regarding dimensions, structural details, loads, or stress or boundary

conditions, except those that are permissible under the test procedure for direct application to

similar, untested, floor structures.

Owing to the particular circumstances applying to the fire resistance rating test, and the problems

arising from these in quantifying the uncertainties involved in measuring the fire resistance rating, it

is not possible to specify a precise uncertainty range for the results.

The Materials Testing Institute Braunschweig (German: Materialprüfungsanstalt Braunschweig) was

not responsible for the choice of the test specimen.

2 Description of the test structure

The load-bearing, room closing, heat insulating floor structure to be tested consisted of a 200 mm

thick reinforced concrete slab (concrete cover c =35 mm) to which to a 100 mm thick Heraklith

"Tektalan TK" segmented wood-wool panel was fixed using Hilti IDMS insulating pins with 80 mm

retention plates in galvanized zinc-plated steel and Hilti IDMR insulating pins in A2 stainless steel

(material number 1.4301) with 80 mm retention plates in galvanized zinc-plated A2 stainless steel

(material number 1.4301).

The 200 mm thick reinforced steel concrete floor slab having the dimensions of 1910 rnrn x 5000 rnm

(W x L) was tested in respect of its qualities as a floor element in a horizontal position with line

loading according to DIN EN 1365-2: 2000-02. A Heraklith "Tektalan TK" segmented wood-wool

panel having the dimensions of 500 mm x 1000 mm x 100 mm (485 mm x 985 mm x 100 mm) (W x

Page 3: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

L x H) was fixed to the reinforced concrete slab. The Heraklith "Tektalan TK" segmented wood-wool

panels consisted of an approx. 90 mm thick Heralan mineral wool fiber core positioned at right

angles to the surface of the slab and covered on both sides with approx. 5 mm thick magnesium

impregnated wood-wool cladding. The panel was. The Heraklith "Tektalan TK" segmented wood­

wool panels were provided with a rabbet edge having a step width of 15 mm. To fix these, holes

(08.0 mm) were bored through the Heraklith "Tektalan TK" segmented wood-wool panels into the

reinforced concrete slab, in which the IDMS or IDMR insulating pins were driven using a hammer.

For each segmented panel, six IDMS or IDMR insulating pins (08.0 mm x 170 mm) and

corresponding retention plates (0 80 mm) were used. The positioning of the insulating pin dowels is

shown in Annex 1.2.

The gap between the floor structure and the wall was stuffed with mineral wool (material class A1

according to DIN 4102-01; melting point> 1000CC).

The test specimen was supported on a side wall of the furnace.

Note that a 50 mm thick Heraklith "Tektalan TK" segmented wood-wool panel was installed

additionally on the floor of the fire room. The temperatures measured at the top of the slab are given

in Annex 2.7.

Further details on the construction of the floor structure are given in Annexes 1.2 ff. of this report.

3 Test specimen and material properties

The strength and humidity of the test specimen at the time of testing corresponded approximately to

the values that pertain in normal use.

The material classification, data on specific weights per m2, absolute densities and humidity of the

test specimen and the building matertals contained in it are given in Annex 1.5.

4 Test layout and performance

The test specimen described in Section 2 was installed by the client's specialists in the form of a

horizontal room closure above a fire room having the overall dimensions of 4000 mm x 1910 mm

(Iength x width =Lexp x W exp) .

The floor slab was loaded by four line loads at right angles to it and positioned at 1/8 land 3/8 I (I = supported span) from each support. The line loads were applied via four load distribution beams and

two hydraulic presses, each with a total load of 39.89 kN, in accordance with the layout given in DIN

Page 4: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

5

1045-1 : 2001-07 for the determination of breaking load (under consideration of the weight of the

slab itself and that of the loading equipment).

The fire room was flame heated in accordance with the standard temperature-time curve according

to DIN EN 1363-1 : 1999-10, Section 5.1.1. The temperatures in the fire room were measured using

six plate thermometers ("plates") with Ni-Cr/Ni-AI thermocouples (type K), D 1.0 mm, according to

DIN EN 1363-1 : 1999-10, Section 4.5.1.1, and positioned at a distance of a =100 mrn from the

underside of the heated surface as specified in DIN EN 1365-2 : 2000-02, Section 9.11(a).

During the test, the static overpressure in the fire room on the upper side of the test specimen

corresponded to the value given in Annex 2.11.

The temperatures in the layer between the concrete slab and the Heraklith "Tektalan TK" segmented

wood-wool panels were measured by 19 thermocouples as specified in DIN EN 1363-1, Section

4.5.1.2. Furthermore, the concrete slab was provided with three sensor cables, each having 5

thermocouples, to rneasure the temperatures at intervals of 10 mm from the underside of the slab.

The sensor cables were situated at intervals of Lexp/4 from one end, where Lexp is the length of the

slab. The temperatures on the unheated side of the test specimen were measured by one NiCr-Ni

thermocouple, IJ 0.5 mm.

Annex 1.2 shows the position of the measurement points.

The vertical deflection of the test specimen was measured at the center as specified in DIN EN

1365-2 : 1999-10, Section 9.3, and shown in Annex 2.9.

A schematic of the test arrangement, the position of the thermocouples in the furnace, the positions

of the pressure measurement points and that of the deflection point are given in Annexes 1.1 ff.

Test results and observations

The test results for the temperature rise above the initial temperature on the unheated side of the

test specimen, and within the body of the specimen, the temperatures in the fire room, the ambient

temperature, the deflection of the test specimen, the error function and the differential pressure are

shown graphically in Annexes 2.1 to 2.11.

The observations made during the test are shown in Annex 2.12.

Page 5: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

6 Summary of the test results and performance criteria according to DIN EN 1365-01 : 1999­10 in conjunction with DIN EN 1363-1 : 1999-10

The test on the 300 mm thick load-bearing, room closing, heat insulating floor structure consisting in

the main of a 200 mm thick reinforced concrete slab (concrete cover c =35 mm) in concrete quality

~ C20/25 and 100 mm thick Heraklith "Tektalan TK" segmented wood-wool panels in conjunction

with Hilti IDMS insulating pins with 80 mm retention plates in galvanized zinc-plated steel and Hilti

IDMR insulating pins in A2 stainless steel (material number 1.4301) with 80 rnrn retention plates in

galvanized zinc-plated steel was carried out on 31.3.05 to determine the fire protection qualities

according to DIN EN 1365-2: 2000-02 in conjunction with DIN EN 1363-1 : 1999-10, that is, to

determine the fire resistance rating for exposure to fire on the underside of the structure.

The summary of the test results and performance criteria according to DIN EN 1365-2 : 2000-02 in

conjunction with DIN EN 1363-1 : 1999-10 for load-bearing, room c1osing, heat insulating floor

structures for fire exposure to the underside of the structure as shown in Table 1 of this report.

Page 6: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

7

Table 1 Test results and performance criteria according to DIN EN 1365-2 : 2000-02 in conjunction with DIN EN 1363-1: 1999-10 for load-bearing, room closing, heat insulating floor structures for fire exposure to the underside of the structure

Une Referenc e

Description Test Results

Data according

to

DIN EN 1363-1: 1999-10

Description Test specimen 1

Section:

1 I-- ­

2

11.1 Load-bearing capacitv

Limiting value for vertical deflection

Limiting value for vertical rate of deflection

The Iimiting value was exceeded after

The limiting value was exceeded after

min.

min.

-3 11.2 Room closure

Inflammation of the cotton wadding

Inflammation of the cotton wadding occurred after mln."

-4 i.e. avoidance of: Appearance of cracks

A feeler gauge could be pushed through after rnln."

5 Appearance of f1ameson the unheated side

Continuous flame penetration occurred after min.

6 11.3 Heat insulation(2): Test duration in minutes 30 60 90 110

7 - Temperature on the concrete slab max. measured temperature: individual values in K 0 1 4 7

- Temperature between the concrete slab and the segmented wood-wool panel

223 [MP 12]

368 [MP 12]

1029 [MP 12]

1041 [MP 10]

8 - Temperature in the sensor cables (with 10 mm concrete cover)

max. measured temperature:

individual values in "C: 47

[MP31] 196

[MP 31] 285

[MP 31] 537

[MP 31]

- Temperature in the sensor cables (with 20 mm concrete cover):

33 [MP 32]

123 [MP32]

155 [MP32]

281 [MP 27]

-9

10

5.6

Ambient temperature in the laboratoryat beginning of test

The ambient temperature rose/fell during the test by max.

20 'C

0.9 K

11 5.2.2.1 Other data Pressure in the fire room according to DIN EN 1363-1 : 1999-10,

Annex 2.11

12 ....­13 ....­14

10.4.4

Test duration in minutes

Deflection at center of slab

110(3)

70.2 mm

(1) Test unnecessary and therefore not performed (2) As opposed to the procedure given in DIN EN 1362-2: 2000-02, a single measurement point only was provided on the unheated

side, which showed a maximum temperature rise of less than 7 K (3) The majority of the segmented wood-wool panels fell into the fire room. From then onwards the concrete slab was unprotected

and therefore subjected directly to the heat.

Conclusions based on DIN EN 1365-2 : 2000-02 in conjunction DIN EN 1363-1 : 1999-10, and recommendations

The following Table 2 surnmarizes the main test results based on the performance criteria specified

in DIN EN 1365-2 : 2000-02 in conjunction with DIN EN 1363-1 : 1999-10.

Page 7: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

8

labia 2 Performance criteria in accordance with DIN EN 1365-2 : 2000-02 in conjunction with DIN EN 1363-1 : 1999-10 for load-bearing, room closing, heat-insulating floor structures for exposure to fire on the underside of the structure.

Criteria according to the standard Failure after [minutes]

R Load-bearing capacity 110 (1)

E Room closure (continuous appearance of flames, cotton wadding, feeler gauge)

110 (1)

I Heat insulation 110 (1)

(1) The test was terminated after 110 minutes, since most of the floor panels had fallen off.

On the basis of the test results obtained (see Tables 1 and 2) over the duration of the test from the

beginning of flame heating up to the end of the test of 110 minutes, it can be recommended that for

the floor structure tested with regard to load-bearing capacity, roorn closure and heat insulation, and

line loads positioned as for the determination of the breaking load (under consideration of the weight

of the structure itself and that of the loading equipment (see Section 4)), and exposure to fire on the

underside of the structure, it can be recommended in accordance with DIN EN 13 501-2 : 2003-12

that the structure be assigned the fire resistance class REI 90 or RE 90.

Range of applicability in accordance with DIN EN 1365-2 : 2000-02, Section 13

The test results are directly applicable to similar, untested, floor structures on condition that the

following applies with regard to the load-bearing component:

- The maximum moments and transverse loads on the test specimen are not exceeded, the

calculation of these being based on the method for determining the permissible load.

- The concrete cover must be c ~ 15 mm. For corrosion protection, layout of the reinforcement

cage, etc., further evidence of compliance is required.

i.A. RR Dr. Ing. Nause Dipl.-Ing. Maertins Leiterder Prüfstelle Sachbearbeiter

Page 8: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

List of Annexes

Annex 1.1 Test arrangement

Annex 1.2 Design and position of the furnace thermocouples, measurement points

and loading

Annexes 1.3 - 1.4 Installation layout and design data

Annex 1.5 Material properties

Annex 2.1 Temperatures in fire room

Annexes 2.2-2.7 Temperatures in test specimen

Annex 2.8 Ambient temperature

Annex 2.9 Deflection of test specimen

Annex 2.10 Error function

Annex 2.11 Differential pressure in fire room

Annex 2.12 Observations during the fire test

The drawings in Annexes 1.2 ff. were made available by the client. The design data of the test

specimen were verified by the testing institute.

Page 9: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

<:J OC! M cn Il)

F1 ~. -

T 37 '-.../ '-.../ U1 T16 ...../, /, 00 .... ....

F1 ~. -

T38 Cl

'-.../ T17 '-.../ C! U1 C! /, /'-... Cl ..... Cl

Cl 00 Il)

Cl .... ..... ~ .... ~

P01 (Q) P02 e F1

~. -

Il)

T39 '-.../ '-.../ ..... T18 00/, /, .... ....

F1 ~. -

OC! M cn Il)

.<J 1 11910.

T16-18 + 37-39 Fire room temperature measurement points: plate thermometers ("plates") with

Ni-Cr/Ni-AI thermocouples (type K), 0 1.0 mm

P01 - P02 Pressure measurement sensor

Test arrangement

Dimensions in mm

Annex 1.1 of

Material Testing Laboratory for Architecture Department for Building Materials, Solid Building and Fire Prevention of the

Technical University Braunschweig

Test Report

No.(3136/2315) -CM

Page 10: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

1-:;;­~" ~1l -, 1:

~I / ' '\t"" / /11' 1I . ,.. / //

)

f\" " 1

k 1 '1 ,j

I -, ~1 1

....., j ....... d

;'! t~

~1\\ ; : -"10­ :!

ik ·1

I \.... j

r"" ~!, 10D 1

k :1

! -, I

:1 ~ ...

i

,\, 'i

i ..... j

'j

~ I­

.1

!

I '\ 0 00 c:i1\ 0 Ll"l 0'1

10 r-­ 01t '''', ...;t ..;t 1.[1'1

k j

j' ..........

k !:: '­r .... iI, >­1'",,­ l

i

I ' '" !

l" Q)

!a 0.. , OJ) J

\", Q ;

I \, ~ ;{ .1

~'" ;;J fj

-, .a ;1

I' ~ j

jI .......... >­ § iI " ~

1-., .:!<l 1

I-, <l)

r-­ :

~I :j

" / 7( i

,/ " /, ! ,.,/ ./ ,.,Ä :!

!\i '\, .,Lr--­ y

LL

•ttg

g

8

48)~loa 4D~loa 48)~1 -­sr --------~I

'(iI: =S1ainless Steel I

'.. =S1eel gzp ~

1--. - ~ - ---(11----, l­ - -~-

20 )<7 10 ~

~ e' - , 9)(

II 1 <2 3><

)( 619 9 .~• •

~k lVI...3 )<1 8)'

J2 2... , • , • • D<4 20>< x 5

18 8• • ~

I

, M.2 4Z,,®A

.~ D 3 CI>I QQ

)-( 11 12)( @l @ ~17 7

X 15 ),10 18 ' 1\1I..117)( y '.I / 4

'QSl I! ~ ~ ~51 I!l

-( 13 x 14 ~ ~ '61

16 ]5 6 5

,,16 1-4i)----1 -~-cIlo­ - - - ~ J ­ - ~-i

:

'ca 48)s-loa I-ca­ - - - ­ - - ­

F Dimensions in mm

@ A Defleetion measurement points

Temperature measurement points, NiCr-Ni 00.5 mm:

X 1 - 9, 20 Temperature measurement points ('C) pos ition - steel qzp, X 10 ­ 17,42 Temperature measurement points ('C) position - stainless steel A2 X 39 Temperature measurement point ('C) position - ambient temperature X ML 1 (21-25) Temperature measurement points ('C) - Messleiter 1 X ML 2 (26-30) Temperature measurement points ('C) - Messleiter 2 X ML 3 (31-35) Temperature measurement points ('C) - Messleiter 3 X 19 Temperature measurement point (180 K) - on the reinforced concr te

ftoor (unheated side)

Design and position of the furnace thermocouples, measurement points and loading

Annex 1.2 of

Material Testing Laboratory for Architecture Department for Building Materials, Solid Building and Fire Prevention of the

Technical University Braunschweig

Test Report

No.(3136/2315) -CM

Page 11: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

Installation layout / design data Hilti IDMS insulating pins / Hilti IDMR insulating pins

Material Testing Laboratory for Architecture Department for Building Materials, Solid Building and Fire Prevention of the

Technical University Braunschweig

Annex 1.3 of

Test Report

No.(3136/2315) -CM

Setting details on IDMS / IDMR Insulating pin

Isolierdorn IDMS 0/3 IDMS 3/6 IDMS 6/9 IDMS 9/121) IDMS 12/15

Setting details IDMR 0/3 IDMR 3/6 IDMR 6/9

t f ix [mm] 0 - 30 30 - 60 60 -90 90 - 120 120 - 150

h1 [mm]

l [mm] 80 110 140 170 200

t f ix [mm] 8

Drill

60

TE-CX-8/22

Dimensions in mm

Page 12: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

--

r 1485·mm 500·mm

l L _ J 1000mm

~b==================::::l

985·mm1- -I +-+­E ® E

L() CX) ~

.985 mm 1985mm

® ®

'.':\\-I='@}==~==::::(@}:==~~=~l===== E E

L() ® ® CX) ~

® ®

...,

I

Dimensions in mm

Design data Heraklith "Tektalan TK" segmented wood-wool panels

Material Testing Laboratory for Architecture Department for Building Materials, Solid Building and Fire Prevention of the

Technical University Braunschweig

Annex 1.4 of

Test Report

No.(3136/2315) -CM

Page 13: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

Thick- Absolute Material ness

Speci'ficManu-facturerMaterial Humidit~ density(1) content' ) weight classification.

at installation time Certification mark

mm kg/m 3 % bywt.kg/m 2

B1: according to segmented panel according

HeraklithTektalan TK wood-wool GmbH 16.9 169.2 4.0 DIN 4102-04 :

to DIN EN 13168 100

Simbach 1994-03

A1: according to -Reinforced concrete slab -(1) -(1) -(1)200 DIN 4102-04 :

1994-03 B 25 according to DIN 1045

A1: according to HiltiIDMS pin DX51D, material 06.8 -(1)-(1) -(1) DIN 4102-04 : Entwicklungsnumber 1.0226 +Z (5.4)

GmbH 1994-03according to DIN EN 10142

A1: according to HiltiIDMR pin 06.8 -(1)-(1) -(1) DIN 4102-04 : EntwicklungsA2 stainless steel (5.4) 1994-03GmbH(material number 1.4301)

Pressed retention plate (t = A1: according to 0.5 mm), DX51D, material -(1) -(1) -(1) DIN 4102-04 : Heraklith 80.0number 1.0226 +Z, 1994-03according to DIN EN 10142

(1) not determined

Material properties

Annex 1.5 of

Material Testing Laboratory for Architecture Test Report Department for Building Materials, Solid Building and Fire Prevention of the

Technical University Braunschweig No.(3136/2315) -CM

Page 14: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

ETK DIN EN 1363-1

1200 -r----.---.----,

~ o

GO I

1000

800

600

400

-------~-------------~-----I r

I I I

I I I

I 1

1

e

1

I

I I I 1

----~-------------~------------~-----r I I 1 I I

I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I

I I I I t ---~ L ~ - L ~ _

I I I I I I I I I I I I

I I I r

I I I I

I I 'I I I I I I I I I I I I I r I I I I I I I J I I I [I I I

t I I I ----------~--------- L j L ~ _

I I I I I I I I I I I I I I I I I I I 1 I I I I

I I I I I I

: 1 : I :: : I

200 ------------r-------------~------------r------------- ------------~-----~ I I

I I I I I I I I I I I r

r I I

r I r I I I I I I r I I

r I I r I r

I I I I I IO+------i-------i-------:------.:...­ ~---.J

o 20 40 60 80 100 Test Time [min]

1-- Soll. -- Min. -- Max. -X-T31 -)K-T32 ~T33 -+-T34 --T35 -T36!

Date of Test: 31.03.05

Temperature in the fire room Test 1

Material Testing Laboratory for Architecture Department for Building Materials, Solid Building and Fire

Prevention of the Technical University Braunschweig

Annex 2.1 of

Test Report

No.(3136/2315) -CM

Page 15: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

I 1200

1000

800

600

400

200

Metering point between Reinforeed Conerete Floor and Tektalanpanel

I I I I I I

I I I I I I

I I I I

------~-----~------~------~------~------~------~-----~------I I I I I I I I I I I I I I I 1 I t I I I I I \

I I I I I I I I I I I I I I I I 1 I I I 1 I I I I I I I I \ I I I I I I I I 1 I I I I I I I I I I I 1 I I I I I , \ I I I I I

______ L I I I I I I I I I

-----~-----_~ L L I J __

I I I I 1 I I 1 I r \ I I I I J I I I I I I I J I I I I I I I I I I I I 1

I I I

I I I

I I I

G' I: o I I

~ -------------~------~------ ------~-----I I I

I I I

I I I I I I I I I I I I I I I I I I I I I I I

I I I I I I

I I I I r ------~------,------T------r------r-

I I I I 1 I I I I \ I , I I I , I

I I I

I I I I I I I I I

I I I I I I I I

I I --~-\ ------~------I------

I I I I I I I I I I I I I I I I 1 I I I

+--_~O+---+---+---+---+---+---+---+---+--_+-__o 10 20 30 40 50 60 70 80 90 100 110

TestTime[min]

-<>-MSt. 1 -0-MSt. 2 --l:r- MSt. 3 -X- MSt. 4 -X- MSt. 5 -0- MSt. 6 -+-MSt. 7

-MSt. 8 -MSt. 9 -<>-MSt.10 -o-MSt. 11 -A-MSt. 12 -X-MSt. 13 -X-MSt.14

-o-MSt.15 -+-MSt.16 -MSt.17 -MSt.18 -<>-MSt. 20

Ternperature in Test Itern

Material Testing Laboratory for Arehiteeture Departrnent for Building Materials, Solid Building and

Fire Prevention of the Teehnieal University Brau nsehweig

End of Flame Impingement after 110 min

Annex 2.2 of

Test Report

No.(3136/2315) -CM

Page 16: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

Measuring Channel No.1, Metering Point NO.22 breakdown

180 -r------,----,---,-----r-----r----r-----,---.......-----.----,-----,

160

140

120

100

80

60

40

20

0" o ..... CI)

~ :::s.­E CI) a. E CI)

I­I

I I

I

I I

-----f------­I

I

I

I

I I

I

O-+----;----+-----+----+----i-----l----+----+----+----+------i o 10 20 30 40 50 60 70

Test Time [min] 80 90 100 110

1-<>-- MSt. 21 -0- MSt. 23 --A- MSt. 24 -X-MSt. 251

End of Impingement 110 min

Flame after

Temperatures in Test Item Annex 2.3 of

Test Report

No.{3136/2315) -CM

Material Testing Laboratory for Architecture Department for Building Materials, Solid Building and Fire

Prevention of the Technical University Braunschweig

Page 17: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

Measuring Channel No.2, Metering Point No.26 breakdown

300 -r-----,----,----r-----,.---.,....---r------,-----.----,----,---,

_1­ _

I I

I I I I I I

I r

I I

I I I

0' Cl

I I I I

I I I I I I I I I

I I I I I I I I , 1

~------~------------~------4------,------~------~------T------~---I I I I I I I I I I I I t I I I I J

r I I t I I I I I

I I I t I I I I I I I I I I , I

I I t I \ 1 I I I I I I , I

I I I I t I I r ! 1 I I I I

r I I I , I

r I r I , I I I I , , I

I I I I t I I I I I I t I

- - - - - - I­ - - - - - -1­ - - - - - -1- ­ - - - - -\ - - - - - - -1­ - - - - - -I - - - - - - -I - - - - - - -+ - - - - - - + ­ - - - - - - - - - - -1 I I J I I I I I I I I I I I I I I I I I I I I I I I I I I

r I r 1 I I I I I I I , I 1 I I I I I I I I I I I I I I I I I I I I , I I I I I I I I I I I I I I , I I I I r I I I I I I I I I I I I I I I I t I I I I I I I I I 1 I I I I I I I I I 1 I I I I I I I , I I I I I I I I I

- - - - - -I- ­ t 1 1 -1 -l ~ -! .j. _ _ _ __ .J­ _

I I I I r \ I I I J

t I I I I 1 I I I I I I I I I I t I I I I I I I I I I I I I I I I I I I I I I [ I I I I I I j I I I I , I I I I I I , I I I 1 I I I J I I I I I I 1 r I I I I I I I I I I 1 I I I I I J I I I , , I I I I I I I

I I 1 I I 1 I I I ______ L 1 1 1 -' .J .1 _ _ _ _ _ _ _ .1.

I I I I I I I 1 I I 1 1 I I

r I , I I I I

I 1 I 1 I I I

I 1 I 1 1 r I

I 1 \ 1 1 I

I , I I I I

1 , I 1 I I

I r I I I 1 1 \ I I 1 1 I I I \ I 1

I I I I 1 I I I I I 1 I

I I I I I

- - - - - -:­ - - - - ­ -:- - - - ­ - -:- - - - - - -: - - - - - - -: ­ - - - ­I I , I I

I I I I 1 I I 1 I I I I I 1 1 1 I I I I I I I

50

100

150

200

250

o 10 20 30 40 50 60 70

Test Time [min]

80 90 100 110

I ~MSt. 27 -0- MSt. 28 -i:r-MSt. 29 -X-MSt. 30 I

End of Flame Impingement after 110 min

Ternperature in the Test Itern Annex 2.4 of

Test Report

No.(3136/2315) -CM

Material Testing Laboratory for Architecture Departrnent for Building Materials, Solid Building and

Fire Prevention of the Technical University Braunschweig

Page 18: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

7

6

5

4

3

2

On Concrete Slab

--·:----;------:---~r----,r------,.,---....,.-----,..----r-----r----I

I I I I I I

g: : : : , I I I I I

(\) r I I I

tn \ I r I I I I I I . Ins

CJ f

I I I I I I I I I I I I I \ I

.5 I 1 I J I I I I I I r - - - - - - T - - - - - - T - - - - - - .,. - - - - - - .., - - - - - - --, - - - - - - -1- - - - - - -1- - - - - - -1- - - - - - - r - - - - ­I , I I I I I I I I

I I 1 I I I I I I I -Ef I I 1 I I I I I r I

:s \ 1 I I r I I I I I I t I I I I I I I I I 1 I I

1 I 1 I I I I I (\) I t t I I I I I

E Q. I I I I I , I

I I I I I I ,

I I I I I I I I (\) I I I I I I I I I ,

r - - - - - - T - - - - - - T - - - - - - .,. - - - - - - .., - - - - - - -I - - - - - - -1- - - - - - -1- - - - - - -1- - - - - ,------­I ­ 1 I I I I I I I 1 , I I I I I J I I I , I I I I I I I I I , t I I I I 1 I I I , I I I I I I I I I I I I I I I I I I I , I I I [ I I I I I , I 1 I r J I I I I I I I I I 1 I I I I I I I , I J I I I I , 1 I I I I I I I I , I I I I I I t I I ,

- - - - - - r - - - - - - - - - - - - - T - - - - - - -; - - - - - - , - - - - - - ,- - - - - - -,- - - - - - -,- - - - - - -,- -----1------­I I I I I I I t I I \ r I I I , \ I I [I I I , I I I I I I I I I I I I I I I I I I I I

I \ I I ,I I I I I I

I I I I I , I I I I I I I I I \ , I I \ I Ir, , ,

- - - - - - j"" - - - - - - - - - - - -. T - - - - - - 1 - - - - - - I - - - - - - -I - - - - - - -,- - - - - - -1- - ­ - - -1- - - - - - - ,- - - - - - ­

I I, I I I I , I r I I I I I

I I I I I \ r , I I' I I I 1 , I I I I I I I I I I I I I I , I I 1 I t I I I I I I I I I I I I I I I I I I I I I I I I I I 1 t I I I I I I I I I I I

------r------i------T------l------l------~------~-- -----------~------r------I Ir, 1 I I I , I I 'I I I , I I I I I r , I I 1 I I , , I I I I 1 , , I I 1 \ I , I

I I I I I , I I I I I , I I I I , I I I I I I I 1 \ , I I I I I I I I------I------r------ ------1------1­

---~------~--------------,-------~------'I , I I I I

" , I I I I

" , I I I I , I

I I I I I ,

I I I I I I I t

, , , I

I I l 1, 1 I I t

I I I,

I " I " I I'O-/-"---+---i-----+---i-----+---+---+----+---+---+------1

o

Zeit Imin]

Mittelwert

Maximum

Messstelle

10

30

< 1K

< 1K

19

60

1 K

1K

19

20

90

4K

4K

19

30 40 fin Rn 7n Test Time [min]

!-MSt. 19 1

110

7K

7K

19

Temperature of Test Itern

Material Testing Laboratory for Architecture Departrnent for Building Materials, Solid Building and

Fire Prevention of the Technical University Braunschweig

80 90 100 11

End of Flame Impingement after 110 min

Annex 2.7 of

Test Report

No.(3136/2315) -CM

Page 19: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

__

On the Concrete Slab 30 -r-------r---r---......---~-____,.--__,_--"""T"""--.,..._-____,.--__,

t I I I I I I t I I I I

0' J I I I I I I , I I I I o

25

I 1 J I I r I I I I I I ! r I I 1 I I I I I I I I , I f I I I I 1 1 I I I I I I I 1 I I I I I I I I I I I 1 I I I I I I I I I I I I I I , I I I

I I , I I I I I ·------r------r------r------r------,------r------r-- __--r------ - _ I I I I I I I I I I I I I I I I I I , I I I I I I I , I I I I I I I , I I I I I

r r , I I I I I

I I 1 I I I I I

I I I I I I I I I I I [ I I ,

I , I r I I I r I I I I I

I I I I 1 'I

20 ~~ -~- - - -~- ~~- - - - - ~ - - - -~ - - - - -.~ - - - - - -~ - - - - - ~ - - - - - :I :--~ I I I I I I I

f , I I I I I I I

I 'I I I I I I I I , I I I I I I

I 1 I I I I I I , I I I I I I I I

I 1 I I I I I I I I I I I 1 I I I I I I t I , I I I I I t I I I I I I , I I I I I I I I I I I I I I I I I ,

15 ------~------~------~ ~ h ~ ~ ~ ~- ~ _

1 J I I I I I I I I ! I I I I I I I I I I I , I I r 1 I I I I I I I I I

1 I I I I I I I I I I I I I I I

I I I I I I I , I I I , I I I I I

I I I I I I I I I I I I 1 I I I I I I I , I I I I I I I I I I I I I I I I I I I I I I , I t I I I I I J 1 I

----- L------L------L L L L L L L L _10 I I I I I 1 I I I I I I I I I I I I I I , I r I I I J

I I I I t I I I I I I I I I I I I I I I I I r I 1 I I I I I I I I r I I I t I

I I I I I

I I I 1 ) I I

5 ------~------~------ ------ ------I-------------~------~------L_-----I I I I I

I r I I I J I I I I I

------1 I I I I I I r I I I I I I I I I I

I I I I " I I I I I I I I J I I I I I I J I I I I I I I t r I I I r I I I I I I I I I I I I IO+---+---i--------i---+---+----+---+---+-- +-_~i__---iI

o 10 20 30 40 50 60 70

Test Time [min]

I-MSt. 39 1

Ambient Temperature

Material Testing Laboratory for Architecture Department for Building Materials, Solid Building and

Fire Prevention of the Technical University Brau nschweig

80 90 100 110

End of Flame Impingement after 110 min

1 IQ....I 1 IIV 1111111

Annex 2.8 of

Test Report

No.(3136/2315) -CM

Page 20: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

I

On the Concrete siab

I I I

-r----­I I I I J

I I I

I I- 1­ _

I I I

I I

I

I I I-----1-----­I I I

I I I I I I

I I \ I -r------r------,------r----­

I I I I I I I I I I , I

I I I I

I I I I I I t I I I I I

J I I 1 I I I 1

I I I \ I

------~------~------~------~------~-----I \ I I I I I I I I I I I I I I I [ I I I I I I I I I I I I I I I I I I I I I I I

1 I \

E E.....

j --_"_.-­ _"._-,--_..,..._ _,1 [I I

I I I

I I I I I [

I I I

I I II[I I I I I I I

I I I I I I I t I I

~------~------~------~------~------~------~------~------~------~-----I I I 1 I , I I I I

I 1 I I I I I I I I I I I I I I 1 I I I I I t I I , I I I I I 1 I I I I I I \ I I

I I \ I I I I I I I I r

I I I I r

I I I I I

------~------~------ ------~------~------~------~------~------~------I I I I I I I I r I I I I I I [

I I I I I I I I I [ I I I I

I I 1 I I I I I I I I I I t I I I I I I I I I I I I I I I I I I I I I

I I I 1 I I I I ------r------r-----­ ------r------r------r------r------r------r---­

I I I I I I I , I

1 I I I I I I I I \ I I I I I t I I t I I I I I I , I

I I I I I I 1 I I I I I I I I I 1 \

I I I t , I 1 I I I r J I ( t I

I I I 1 I 1 I I I I I I \ , I I I

------~------~------~------~------~------~------~------~------I I 1 I I I I I I \ I I I I I I

I I I I I I I I

I I I I I I I ,

I I I I I I I I

I r I , I 1 I I

I I I 1 I 1 I 1

I I J I I 1 I I I I I I I \ I I r I I I I I I I

I I I I I I I I------1------1------1------1------1------1------1------I I I I I I I I I I I I , I I , [I I I I

I I r I I I 1 t I I I I I I I I I I I I I J I I I I I J I I I I I t I I I 1 I I I

------r------r------r------r------r------r---­I I I I r I I I I I I I I I I I I I I I I I I I I I I I I I I t I I I I I I I I I I 1 I I I I 1 I I I I I I

------~------~------~------~-----I I I t I I I I I I I I I I I \ I I I I I I \ I I

I I I I I I

0-+---F==..:......--r--+---+----:----+---+---+---+----1-~

70

80

40

50

10

20

60

30

o 10 20 30 40 50 60 70 80 90 100

Test Time [min]

I-MSt,41!

End of Flame Impingement after 110 min

Forrning of the Test Itern Annex 2.9 of

Test Report

No.(3136/2315) -CM

Material Testing Laboratory for Architecture Departrnent for Building Materials, Solid Building and Fire

Prevention of the Technical University Braunschweig

Page 21: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

Difference of the Integral of Fire-Room-Temperatures of the Must Value-Integral

20 ..,.------·~-----i ,v I

1 : I 1 I I I I I , I I

1----..., - - - - - -i- ------------~ ------------" ;-------------~ -------------j- -----'I15 I I 1 I I I , I I I

: : : : : II I I I I I I I IL J I- L _

10 ~

I I \ , I

I I I I I I ,t I t \ I I I I I I I I I I I I I I I I I5 - - - - - - - - - - - - -,- - - - - - - - - - -1- - - - - - - - - - - - - - - - - - - - - - - - - -1- - - - - - - - - - - - - -,- - - - - ­

1 " 1 I I 1

1 1 1 I I I I o - - - -- - -1- -- - - - - - - - - - - .,-- - - - -- --- - - - T - - - - -- -- - - -- -r -- - - -- - - --- - -1- - -- - ­1 1 I 1 I I 1 1

I I I 1

-5 ------------------ -----~-------------~-------------~------------~------I I I I I I I ,

I I I I , I I I , I , I

I I I I

I 1 I \ ____________ l L 1 _

-10 ~

I , I I

I I I I , I I ,

I I I I f 1 I I

-15 -Inf--_.L - - - - - -,- - - - - - - - - - - - - ~ - - - - - - - - - - - - - ~ - - - - - - - - - - - - -l- -------------! ------I 1 I I I I

I I I I I I I I I I I I I I I I I I I I I \ I I I I I I I I

- - - - -1- - - - - - - - - - - - -"1- - - - - - - - - - - - - 1" - - - - - - - - - - - - -r- - - - - - - - - - - - - -/- - - - - ­, I I I I

I I I I I I I I I I J I I I I I I I I I I I I t I I r I I I

-20

_ - - - -1 .J J.. - - - - - - - -1- - - - - _~-25 I I 1 1 I 1 I I I I 1 I I I I I I I I I , I I I I I I I I I I I I I I

_____1 J 1 ... 1 _I~

-30 I I I I 1 , I I I I 1 1 I I I \ I I I I I I I I 1 I I I I I I I I I I I I I I I-35 +------.--------T----------T---------~-----T__---J

o 20 40 60 80 100

Test Time [min]

I~ % Difference ~ I Upper Range of -lr-I Lower Range Of Tollerance Tollerance

s, =19 -c Date of Test 31.03.05

Reporting of the Error Integral Annex 2.10 of

Test Report Material Testing Laboratory for Architecture Department for Building Materials, Solid Building and Fire No.(3136/2315) -CM

Prevention of the Technical University Braunschweig

Page 22: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

25

20

15

10

5

o

-5

-10

1

1

I I I

I

I I I I

_1 _

I I

1

1

I

I

I

I I I I I

I I I

1 I

---------~---I

I

I

I \

I I I I

I I

I I I I

I I I t -----------l-------------T-------------r------------~------

I I I I

I I I I I I I I

I I I I I I I I I I I I I I I I

I I I I I I I I

I 1 I I I

- - - - - - - - -1- - - - - - - - - - - - - "1 - - - - - - - - - - - - - 1" - - - - - - - - - - - - - t- - - - - - - - - - - - - -1- - - - - ­I 1 I I I I I I I I I I

I I I I

I I I I I I I I I I I

I I I I I I I

- - - - - - - - -; ­ - - - - - - - - - - -I

- ~ - - - - - ­ - - - -I

- - - ~ - - - - - - - ­ -I

- - - -:­ - - - - - - - - - ­ - -I

-~ - - - - - -I I I I I I I I I I I I I I I I I I 1 I

: : : : : II I I 1 1 1 I I , I

_

I I . I 1 I-------------J-------------,-------------T-------------r-------------I-----­I I 1 I I 1 I I I I I I I I I I I , I I

tri I I 1 r I I ,

1 I I I I I I I

I I I I I I I I I _ 1 ..J J,. I- 1_ - - - __

I I I I 1 I I I I I

I I I I I I I I I I I I I I I I I I I I I I t I I I I I I r I I I I I I I r I I

-------------:-------------~-------------~-------------~------------~------I I I r I I I I I I I I I I I I I , I I I J I I

I I I I I I

I I I I I I

20 40 60 80 100

Test Time [min]

Date of Test 31.03.05 ÖD =19 -c

Differential Pressure in the Fire room Annex 2.11 of

Test Report Material Testing Laboratory for Architecture Department for Building Materials, Solid Building and Fir No.(3136/2315) -CM

Prevention of the Technical University Braunschweig

Page 23: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

2

Testing Length (min)

10

13

24

29

50

71

75

77

83

87

93

98

103

110

*) F= A=

Side *)

F

F

F

F

F

F

F

F

-

fire facing site

Notices during the Fire Test on the 31st of March 2005

The panels are fading black.

The plates are drawing in the covering of the sheathing.

The gap opens up to 3mm.

The panels are c1earagain. The plates continued drawing in the covering of the sheathing.

The sheathing covers the anchor plates.

The panels are sagging round bodied between the anchors.

The panel (8) slowly starts to tilt (gap = 3mm).

The gaps of panel (7), (11) and (15) keep on rupturing.

Panel (8) fell down in the Fire room.

Panel (7) fell down in the Fire room.

Panel (11) fell down partial. Panel (9) is Iying on a thermocouple.

Panel (6) fell down in the Fire room.

Panels (9), (10) and (14) have fallen down in the Fire room.

Panel (5) fell down in the Fire room.

End of flame imoinqement.

fire averted site

Evaluation during the Fire Test

Material Testing Laboratory for Architecture Department for Building Materials, Solid Building

and Fire Prevention of the Technical University Braunschweig

Annex 2.12 of

Test Report

No.(3136/2315) -CM

Page 24: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

Pictures:1 Day before the Fire test

Photodokumentation

Material Testing Laboratory for Architecture Department for Building Materials, Solid Building an d Fire

Prevention of the Technical University Braunschweig

Annex 3.1 of

Test Report

No.(3136/2315) -CM

Page 25: Test Report - България · PDF fileThis test report contains ... 2 Description of the test structure The load-bearing, room closing, ... six plate thermometers

Pictures: During the Fire Test

Pictures: 1 Day after the Fire Test

Photodokumentation

Material Testing Laboratory for Architecture Department for Building Materials, Solid Building an d Fire

Prevention of the Technical University Braunschweig

Annex 3.2 of

Test Report

No.(3136/2315) -CM