    OperatingManual

    Automatic A/C Charging Station

    For Refrigerant R-134a Systems Only!

  • 8/9/2019 Robinair Mod 10324

    2/16

    This equipment is intended for professional use only. The service technician should be familiarwith proper servicing of air conditioning systems as well as the dangers and use of refrigerants and

    pressurized components before using the equipment.

    WARNING Always wear safety goggles when working with refrigerants. Contact with refrigerants can causeinjury.

    Connecting hoses to the wrong ports may cause personal injury or may damage the equip-

    ment. Check the operating manual for your air conditioning system for the correct hookup.

    Disconnect hoses with extreme caution! All hoses may contain liquid refrigerant under pressure.Contact with refrigerant can cause injury. Wear proper, personal protective equipment, including safety

    goggles. Point the disconnected end of a hose away from you and anyone who is nearby.

    Use only with refrigerant type R-134a! Cross-contamination with other refrigerant types will causesevere damage to the A/C system and to service tools and equipment. Do not mix refrigerant types

    through a system or in the same container!

    Avoid breathing A/C refrigerant and lubricant vapor or mist. Exposure may irritate eyes, noseand throat. To remove R-134a from the A/C system, use service equipment certified to meet therequirements of SAE J2210 (R-134a recycling equipment). If accidental system discharge occurs,

    ventilate work area before resuming service.

    HFC-134a service equipment or vehicle A/C systems should not be pressure tested or leak tested with compressed air. Some mixtures of air/HFC-134a have been shown to be combustible atelevated pressures. These mixtures are potentially dangerous and may result in fire or explosion

    causing injury or property damage. Additional health and safety information may be obtained from

    refrigerant and lubricant manufacturers.

    Improper use or connections may cause electrical shock hazards. Read and follow these

    instructions carefully and take all necessary precautions to avoid electrical shock hazards. Before

    energizing circuits, be sure that all associated devices are properly grounded. Unplug the station from

    the power source before removing the control box.

    Safety Precautions 

    !!

    Limited Warranty 

    This product is warranted to be free from

    defects in workmanship, materials, and compo-

    nents for a period of one year from date of

    purchase. All parts and service center labor

    required to repair defective products coveredunder the warranty will be at no charge. The

    following restrictions apply:

    1. The limited warranty applies to the original

    purchaser only.

    2. The warranty applies to the product in

    normal usage situations only, as described

    in the Operating Manual. The product

    must also be serviced and maintained as

    specified.

    3. If the product fails, it will be repaired or

    replaced at the option of the manufacturer.

    4. Transportation charges for warranty service

    will be reimbursed by the factory uponverification of the warranty claim and

    submission of a freight bill for normal

    ground service. Approval from Robinair

    must be obtained prior to shipping to either

    an authorized service center or the factory.

    5. Warranty service claims are subject to

    factory inspection for product defect(s).

    6. Robinair shall not be responsible for any

    additional costs associated with a product

    failure including, but not limited to, loss of

    work time, loss of refrigerant, and non-

    authorized shipping and/or labor charges.7. All warranty service claims must be made

    within the specified warranty period. Proof-

    of-purchase date must be supplied to the

    manufacturer.

    8. Use of Robinair charging equipment with

    non-authorized refrigerants will void our

    warranty. Authorized refrigerants are listed

    on the equipment or are available through

    our Technical Service Department.

    This Limited Warranty does not apply if:

      • The product, or product part, is broken by

    accident.

      • The product is misused, tampered with, or

    modified.

      • The product is used for recharging any

    substance other than the specified refriger-

    ant type.

  • 8/9/2019 Robinair Mod 10324

    3/161R-134a Smart Cart ®  Automatic A/C Charging Station

    In troduction ................................................................................................................... 2

    Set U p Inst ructions ....................................................................................................... 2

    P repar ing the Vacuum P ump .................................................................................. 2

    Di agram of Vacuum Pump Components ................................................................. 2

    Inst a lling a Refrigera nt Ta nk .................................................................................. 3

    Di agram of Disposable Tan k I nstal lat i on ............................................................... 3

    Di agram of Refi l lable Tan k In stal l at ion ................................................................. 4

    Removing an E mpty Ta nk ........................................................................................ 4

    U sing the Hea ter B la nket ........................................................................................ 4

    Operat ing Procedures ................................................................................................... 5

    Summar y Char t of Operat in g Procedur es ............................................................... 5

    To Att a ch Hoses to the S ystem ................................................................................ 5

    To Dia gnose Sy stem P roblems ................................................................................. 5

    To Add Refrigera nt to P ar tia lly Ch ar ged S ystems .. . .. . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . .. . . .. 5

    To Recover Refrigera nt ............................................................................................. 6

    To P rogram Vacuum/Ch ar ging C ycle ...................................................................... 6

    To Use Automa tic Vacuum /Ch a rging Cycle ............................................................ 6

    To Check Fina l Syst em Opera tion ........................................................................... 7To Disconnect t he Sy stem ........................................................................................ 7

    Ma intena nce Inst ructions ............................................................................................. 7

    St oring the Sta tion .................................................................................................... 7

    Ma inta ining th e Vacuum P ump ............................................................................... 7

    Checking the Sca le Accura cy ................................................................................... 7

    Ca libra ting the Sca le ................................................................................................ 8

    U sing Ma nua l Dia gnostics ....................................................................................... 8

    Additional Operat ing G uidelines ................................................................................. 9

    How to U se the Cont rols ........................................................................................... 9

    Di agram of Contr ol Components ............................................................................. 9

    U sing t he K eypad ...................................................................................................... 10

    Di agram of K eypad ................................................................................................... 10

    U sing th e Displa y P a nel ........................................................................................... 10

    Qu i ck Refer ence Cha r t .............................................................................................. 11

    Di agram of Di splay Panel ........................................................................................ 11

    Replacement P a rt s List ................................................................................................. 12

    Troubleshooting Tips ..................................................................................................... 13

    Temperat ure/P ressure Relation Cha rt ........................................................................ 14

    Conversion Cha rt .......................................................................................................... 14

    Table of Contents 

    U.S. Patent Nos.: 4,523,897; 5,005,375; 4,688,388 RE: 33,212

    Other U.S. and Foreign Patents Pending

    A/C Air conditioning

    System The A/C sy st em bein g ser viced

    Tank  The refrigera nt supply t an k

    Station The a utoma tic A/C cha rging sta tion

    Glossary of Terms 

  • 8/9/2019 Robinair Mod 10324

    4/162 © 1991 Robinair Division, SPX Corporation

    This a utoma tic A/C cha rging st a tion is

    designed with you in mind. It is a ccura te,

    easy t o program , a nd simple to use.

    Be for e us i n g the sta t i on ,  r ead and

    unders tand a l l ins truct ions a nd w arnings

    in this operating manual.

    The 220V 50Hz m odels ha ve some

    operating exceptions, which are noted inthis operating manual.

    Introduction  In a ddition, all measurements are metrican d the ma nifold is equipped with kP a/

    bar ga uges showing tempera ture in

    degrees Celsius.

    B efore opera ting th e 220V 50Hz m odel,

    plug the short pow er cord from t he upper

    contr ol box into th e outlet on the lower

    power box. Plug the main power cordinto a 220V 50Hz power source tha t is

    free of transients and electrical noise.

    To set up th e sta tion for opera tion, you

    need to prepare the va cuum pump and

    install the refrigerant tank.

    PREPARING THE VACUUM PUMP

    The Va cuMast er®  vacuum pump is

    shipped with out oil in the reservoir.

    Be for e sta r t i ng th e sta t i on , you m us t 

    f i l l t h e p um p w i t h o i l a n d r emo ve t h e  

    exhau st p l ug f r om the end o f t he 

    pum p ’ s han d l e.

    Note: The Iso-ValveTM isolation va lve on

    th e side of the pump mus t remain open

    (the position shown in the illustration)

    for t he sta tion to opera te.

    CAUTION! D o no t at tempt to run thevacuum pump when the ma nifold gauge

    set shows pressure rea dings a bove 5 psi.

    In the vacuum mode, positive pressure

    will:• High pressure — not a l low the

    vacuum solenoids t o open.

    • Low pressure — blow oil out of the

    pump handle when the va cuum

    solenoids do open.

    Running t he vacuum pump with posit ive

    pressure locks high pressure between the

    tw o solenoids a nd prevents operat ion of

    the pump.

    Follow th ese procedures to prepare t hevacuum pump for use with t he cha rging

    sta t ion.

    1. Remove an d discar d the exhaust plug

    from the end of the pump’s handle.

    2. Remove and reta in the black plug on

    the oil fill port.

    3. P our vacuum pump oil into the oil fill

    port until oil appear s in t he sight

    glass on th e reservoir. The a pproxi-

    ma te oil ca pacity of th e pump is 13

    ounces (384 millilit ers).4. Close both t he high side an d low side

    valves on t he sta tion’s ma nifold.

    Di agram of Vacuum Pump Components 

    Set Up Instructions 

    EXHAUST PLUG

    OIL FILL PORT

    SIGHTGLASS

    OILDRAINVALVE

    ISO-VALVEˇ 

  • 8/9/2019 Robinair Mod 10324

    5/163R-134a Smart Cart ®  Automatic A/C Charging Station

    INSTALLING A REFRIGERANT TANK

    Follow these steps to insta ll a r efrigerant

    tank on the charging station.

      WARNING

    Always wear safety goggles whenworking with refrigerants. Read and

    follow a ll wa rnings at the beginning ofthis ma nua l before operat ing the unit .

    Connecting hoses to the wrong portsmay cause personal injury or maydamage the equipment. Read and follow all wa rnings at t he beginning of this

    ma nua l before operating the unit .

    Use only with refrigerant type R-134a!Cross-conta mina tion w ith other refriger-

    an t t ypes will cause severe da ma ge to the

    sta tion and t o tools an d equipment.

    Do not mix refrigerant types through a

    system or in the sa me conta iner!

    1. Att ach the sta tion’s yellow charging

    hose to a full refrigerant ta nk, as

    follows:

    • Disposab le ta nks — Connect t he

    yellow hose, open the t a nk’s valve,

    an d place the inverted tan k (wit h its

    valve down) on the scale platform.

    B e sure to center th e tan k over the

    stud w elding point. U se only ta nks

    designed for use w ith R-134a, includ-

    ing Acme threa ds on the fit t ings.

    5. P lug the sta tion into the proper

    voltage outlet , an d tur n on the MAIN

    POWER switch.

    6. Simulta neously press the ENTER

    a nd zero keys on th e keypad to a ccess

    the ma nua l diagnostic mode.

    7. P ress “1” on the keypad t o star t the

    pump.

    8. While the pump is running, add

    enough va cuum pump oil so tha t t he

    oil level is even wit h t he line on t he

    reservoir’s sight glass.

    9. P ress “1” or the RES ET CYCLE key

    on the keypad t o stop th e pump.

    10. Replace the black plug on th e oil fill

    port .

    IMPORTANT!  For maximum perfor-ma nce, change th e vacuum pump oil

    frequently (approximately after every

    four hours of running time). We recom-

    mend using our Premium H igh Vacuum

    Pump Oil; it is specifically blended to

    mainta in ma ximum viscosity a t normal

    running t empera tures a nd to improve

    cold weather starts (see the “Replace-

    ment P ar t s Lis t ”).

    Read a nd follow the deta iled instructions

    in the Vacu-Master ®  Vacuum P ump

    Opera ting Ma nua l. You do not need to

    return the wa rranty regis tra t ion card

    contained in the Vacu-Master ®  VacuumPump Operating Manual — return only

    the wa rranty regis tra t ion card a t ta ched

    to the s ta t ion to va lidate your w arra nty .

    Di agram of Di sposable Tan k I nstal lat i on 

    Set Up Instructions 

    Bulk Refrigerant Tank(Not Included)

    TankValve Handle

    Ball

    Valve

    Yellow Hose ToRefrigerantSolenoid

    Dual PurposeHold-Down

    Bracket

      ! !

    (Continued) 

  • 8/9/2019 Robinair Mod 10324

    6/164 © 1991 Robinair Division, SPX Corporation

      WARNING

    Disconnect hoses with extreme caution!All hoses may contain liquid refrigerantunder pressure. Read a nd follow a llwa rnings a t t he beginning of this manual

    before operating the unit.

    2. Disconnect th e hose from the tank.

    3. Release the retaining stra p buckle.

    4. Loosen the wing nut on the hold-

    down bra cket a nd remove the empty

    ta nk from the platform.

    USING THE HEATER BLANKET

    A heat er blanket speeds the t ra nsfer of

    refrigera nt a nd a ssures a complete

    charge by raising the pressure with in the

    refr igerant ta nk.

    1. Wrap the heater blanket a round the

    refrigerant ta nk, secure it wit h theVelcro®  s tra p, and plug its power cord

    into the heater outlet on the bottom

    of the control box (right receptacle).

    2. Turn on the MAIN P OWER sw itch

    on t he front of the sta tion.

    The heater blanket is on whenever the

    sta tion’s MAIN P OWER switch is on,

    elimina ting t he need for ma nua l control.

    You can extend the life of the heater

    blanket by unplugging the heat er when

    it’s not being used or tu rning off th e

    MAIN P OWER switch.

    • Re f i l l a b l e ta nks — Leave the tank

    upright, at tach the yellow charging

    hose to the blue LIQUI D va lve on th e

    ta nk, an d open the blue valve.

    2. Open th e ball valve on the yellow 

    char ging h ose (th e open position ru ns

    par a llel to the hose).

    Note: Use a ma ximum ta nk size of 50pounds (23 kilograms) with this charging

    sta t ion.

    3. Fas ten the tank securely with the

    ta nk hold-down bra cket. P lace the

    heater bla nket a round the center of

    the ta nk, an d fast en it securely (see

    “Using the Heater Blanket”).

    4. Secure the reta ining s t rap a round

    the tank.

    Note: Adjust the stra p so that it comes in

    contact w ith the ta nk, b u t i s n ot t i g h t  a r ou n d t h e t a n k  .

    5. I f the tank wa s changed a f ter press-

    ing the HOLD key to interrupt the

    cycle, press the CONT key or RES ET

    CYCLE key, depending on the

    operation you require next.

    REMOVING AN EMPTY TANK

    Follow t hese steps to remove an empt y

    refrigerant tank from the charging

    sta t ion.

    1. If the stat ion is opera ting, press theHOLD key. You do not need to turn

    off the MAIN POWER switch.

    Di agram of Refi l lable Tank I nstal lat i on 

    PlatformMountRing

    Blue LIQUID Valve

    Ball Valve

    YellowHose To

    RefrigerantSolenoid

    BulkRefrigerant

    Tank(Not Included)

    Set Up Instructions 

      ! !

  • 8/9/2019 Robinair Mod 10324

    7/165R-134a Smart Cart ®  Automatic A/C Charging Station

    Operating Procedures 

    Summar y Char t of Operat in g Procedur es 

    TO DIAGNOSE SYSTEM PROBLEMS

    1. Sta r t the A/C sys tem and w atch the

    gauge pressures (refer to the

    manufacturer’s specifications for

    proper opera ting pressures).

    2. P er form any other visual and diag-

    nostic inspections recommend ed by

    the ma nufacturer .

    3. If t he A/C sy stem is operat ing prop-

    erly, disconnect t he h ose couplers

    from the A/C syst em. To recha rge or

    ma ke necessary repairs, see the

    appropriate sections that follow.

    TO ADD REFRIGERANT TO PARTIALLYCHARGED SYSTEMS

    1. In t he progra m mode, press ADD .2

    lbs. REF RIG . The messa ges “AU TO-

    MATIC” an d “RE FRIG ERANT”

    appear on the display.

    2. Open t he low side valve. The sta tion

    dispenses .2 pounds (.1 kilograms) of

    refrigeran t, th en displays t he mes-

    sage “CP L.” Close the low side valve.

    3. Monitor the A/C syst em opera ting

    pressures. Correct a ny low cha rge

    indicat ions by pressing RE SE T

    CYCLE ; repeat S tep 1 as n ecessary.

    N ote: There a re oth er A/C s yst em pr ob-

    lems which cause symptoms similar t o a

    low refrigerant charge — refer to youroperat or’s ma nua l or a relia ble A/C

    troubleshooting cha rt . I f a dding one

    pound of refrigerant does not correct the

    low charge symptoms, you ma y need to

    recover a nd/or recharg e refrigeran t, a s

    described next.

    B efore opera ting th e 220V 50Hz m odel,

    plug th e short power cord from t he upper

    cont rol box into th e outlet on th e lower

    power box. Plug the main power cord

    into a 220V 50Hz power source tha t is

    free from transients and electrical noise.

    The chart below summarizes the steps in

    each of th e following sections.TO ATTACH HOSES TO THE SYSTEM

    1. Be sure a l l va lves on the manifold are

    closed.

      WARNING

    Connecting hoses to the wrong portsmay cause personal injury or maydamage the equipment. Check your A/Csystem operat ing ma nua l for the correct

    hook-up.

    Use only with refrigerant type R-134a!Cross-conta mina tion w ith other refriger-

    an t t ypes will cause severe da ma ge to the

    sta tion and t o tools an d equipment.

    Do not mix refrigerant types through a

    system or in the sa me conta iner!

    2. Att ach th e red high side hose’s

    coupler to t he h igh side of t he A/C

    system.

    3. Att ach t he blue low side hose’s

    coupler to t he low side of t he A/C

    system.

    N ote: The ma nifold is ported so tha t t hegauges indicate pressure wh ether or not

    the valves are open.

      ! !

    SUMMARY

    1. Attach hoses to the A/C system.

    2. Start the A/C system and compare operating pressures to

    manufacturer’s specifications.

    3. Add a partial charge, if necessary.

    4. Discharge the A/C system, if required.

    5. Program the vacuum/recharge cycles.

    6. Start the A/C system and perform final operating check.

    7. Disconnect the hoses from the A/C system.

  • 8/9/2019 Robinair Mod 10324

    8/166 © 1991 Robinair Division, SPX Corporation

    TO RECOVER REFRIGERANT

    IMPORTANT! U se a recovery unit . Dono t vent refrigera nt t o the at mosphere.

    1. B e sure the A/C syst em is turn ed off,

    then connect t he yellow hose from

    the m a nifold’s center port to your

    recovery un it’s inlet port.

    2. Open th e manifold’s red high side

    valve, blue low side valve, and center

    valve, and sta rt t he recovery unit .

    Follow the recovery unit’s instruc-

    tions to recover refrigerant.

    TO PROGRAM VACUUM/ CHARGING CYCLE

    Vacuum is programmed in minutes a nd

    refrigera nt is programmed by w eight. If

    no quant ity for an y particular cat egory is

    required, enter zeros.

    1. I f the message “PROGRAM” is not

    displayed, press RES ET CYCLE.

    2. The message “VACU UM” should

    appear on the display. If it does not,

    press the RE VIEW PROG RAM key

    repeatedly until it does.

    Note: Follow the A/C sys tem m a nufa ctur-

    er’s recommenda tions for t he proper

    vacuum and refrigerant requirements.

    3. P ress the appropriate number keys

    until the desired vacuum t ime

    appears on the display. E ntervacuum time in w hole minutes.

    For example, to program 20 minutes,

    press two and zero — the display

    shows “20.00.” P ress ENTER an d th e

    display flashes once indicat ing t he

    progra mmed da ta is accepted.

    4. P ress the REVIEW P ROGRAM key.

    The message “REFRIGERANT”

    appears on the display. Ent er the

    am ount of refrigerant to be recha rged

    to hundredths of a pound.

    For example, to program 23/4 pounds,

    press two, seven, five and ENTER.

    The display sh ows “2.75” a nd fla shes

    once, indicating the programmed

    data is accepted. To program 21/2

    pounds, press t wo, five, zero a nd

    ENTER — be sure to add t he last

    zero.

    Note: U se th e convenient conversion

    chart on t he back cover of this ma nua l if

    you need help convertin g ounces to

    hundredths of a pound.

    TO USE AUTOMATIC VACUUM/ CHARGING CYCLE

    IMPORTANT! Before start ing the

    va cuum pump, be sur e tha t a ll A/Csystem pressure is discharged.

    1. Close the SYSTEM D ISCH ARGE

    valve, and open the appropriat e high

    side a nd/or low side va lves on th e

    station.

    2. P ress the START key on t he keypad.

    The display shows the message

    “AUTOMATIC” followed by the

    message “VACU UM.”

    3. After a s l ight delay the vacuum

    pump start s . The display shows theam ount of t ime program med and

    begins a countdown to zero.

    4. At the end of the automa tic vacuum

    cycle, the display shows the message

    “HOLD.” C lose the high and low side

    valves a nd m a ke sure the A/C syst em

    holds a vacuum (if it doesn’t, perform

    a ny n ecessa ry r epairs). Then open

    the high a nd low side valves, and

    press CONT to cont inue cha rging.

    Note:  Consu lt y our A/C sy st em service

    guide for the proper chargingprocedure.

    5. During the cha rging cycle, the

    message “REFRI G ERANT” appears

    on the display. The display shows the

    progra mmed a mount of refrigeran t,

    counts d own to zero as the char ging

    process proceeds, a nd indica tes t he

    end of the char ging process by

    showing the message “CP L.”

    6. If the refrigerant t ran sfer is too slow,

    the sta tion emits an a udible signal,

    the display countdown st ops, and the

    message “CHE CK REFRIG ERANT”

    appears on the display. P ress the

    HOLD key and close the high side

    valve, but leave the low side valve

    open. St a rt t he A/C syst em, a nd press

    the C ONT key to pull the rema inder

    of the cha rge into th e low sid e of the

    A/C sy st em.

    Operating Procedures 

  • 8/9/2019 Robinair Mod 10324

    9/167R-134a Smart Cart ®  Automatic A/C Charging Station

    2. Compare the gauge pressure read-

    ings to the system ma nufacturer’s

    specifications.

    3. Check the cool air vent discharge

    temperature to be sure that the

    syst em cooling is a cceptable.

    TO DISCONNECT THE SYSTEM

    1. Turn off the A/C syst em.

     WARNING

    Disconnect hoses with extreme caution!All hoses may contain liquid refrigerantunder pressure. Read a nd follow a llwa rnings a t t he beginning of this manual

    before operating the unit.

    2. Disconnect the blue an d red hose

    couplers from t he A/C s yst em.

    3. Replace the caps on all fit t ings. Store

    the hoses on the cart , a nd store thecouplers by connecting t hem t o the

    coupler ra ck.

      !

    If the signal continues and t he

    display does not count down, press

    the HOLD key an d replace the tank

    as described in “Insta lling a Refriger-

    an t Tan k.” P ress the CONT key to

    complete th e au toma tic cycle, or

    press RESET to access the program

    mode.

    7. When th e aut omatic cycle is com-

    pleted, the sta tion beeps once, an d

    the message “CPL” appears on the

    display , followed by the “H OLD”

    message. Pr ess any key to a ccess the

    program mode.

    TO CHECK FINAL SYSTEM OPERATION

    B efore disconn ecting t he A/C sy st em

    from the sta tion, you should check tha t it

    is operating properly.

    CAUTION! B efore st a rt ing t he A/Csystem, be sure both valves on the

    station’s manifold are closed.

    1. Run th e A/C system unt il the gauge

    readings sta bilize.

    Operating Procedures 

      !

    Follow t hese instru ctions to properly

    ma inta in your a utomat ic A/C charging

    sta tion. Be sure to wipe up any spills

    immediately a nd keep the sta tion clean.

    STORING THE STATION1. Turn off the MAIN P OWER switch,

    and unplug the station.

    2. St ore the hoses on the car t , an d store

    the couplers by connecting them to

    the coupler rack.

    3. Close all valves when the sta tion is

    not in use.

    MAINTAINING THE VACUUM PUMP

    1. Check the vacuum pump oil daily,

    a nd a dd oil as necessary. The proper

    level is at the midpoint of the sight

    glass w hen the vacuum pump is

    runn ing a nd t he A/C syst em is under

    vacuum.

    N ote: Use only our P remium High

    Vacuum P ump Oil (see “Repla cement

    P ar ts Lis t ”).

    2. For maximum efficiency a nd longer

    pump life, change the vacuum pump

    oil frequently (approximately after

    every four hours of running time).

    Read a nd follow the deta iled instructionsin the vacuum pump operat ing man ual

    to chan ge oil.

    CHECKING THE SCALE ACCURACY

    You should routinely check the accuracy

    of the scale platform a nd calibrat e the

    scale, if necessary, to assure th at the unit

    charges accurately.

    1. While in the P ROGRAM mode,

    simultan eously press the E NTER an d

    zero keys on the keypa d to clea r th e

    display.

    2. P ress the “6” key on the keypad to

    display the a pproximate scale

    platform weight.

    3. Remove the ta nk from the scale

    platform. The empty platform weight

    display ed should range from + tw o

    pounds. If it does not, contact the

    factory.

    Maintenance Instructions 

  • 8/9/2019 Robinair Mod 10324

    10/168 © 1991 Robinair Division, SPX Corporation

    USING MANUAL DIAGNOSTICS

    The s ta t ion has internal and m anua l

    dia gnostic modes. The int erna l or self-

    dia gnostic mode checks for entr ies or

    pressures outside of normal limits and

    for cert a in electrical conditions. The

    ma nua l diagnostic mode allows you to

    check major components for properoperation.

    The station’s safety features include a

    check valve which prevents high side

    pressure from entering t he refrigera nt

    tank. Also, any operating problems

    resulting in an error message on the

    display prevent opera tion until th e

    problem is corrected.

     WARNING

    Be sure to discharge any system pres-sure before performing any manualdiagnostics.

    1. I f the message “PROGRAM” is not

    displayed, press the RES ET CYCLE

    key.

    2. Simulta neously press the ENTER

    a nd zero keys. The display should be

    blan k except for the decimal point.

    3. P ress the following keys to perform

    these functions:

    Pr ess “1”  — The VACU U M displa y

    segment comes on, the vacuumsolenoid opens, and the pump starts.

    P ress “1” aga in to turn off.

    Pr ess “3”  — The REF RIG ERANT

    display segment comes on and the

    solenoid opens. This is a momenta ry

    conta ct switch w hich turns off when

    released. C lose the high an d low side

    valves to perform this test.

    Pr ess “5”  — All display segments

    light up. Pr ess “5” a gain t o turn off.

    Pr ess “6”  — The display shows t he

    approximat e weight on t he scale. See

    “Checking the Scale Accuracy” for

    dia gnostic procedures.

    4. P ress the RESET CYCLE key to

    return t o the program mode.

    CALIBRATING THE SCALE

    You should also routinely calibrate the

    scale, if necessary, to a ssure that the

    compressor shuts off when t he ta nk is

    full. You can a utomat ically calibrat e the

    scale through the keypad.

     WARNING

    Proper operation of the scale is essen-tial to safety features built into thestation. If you have any questions aboutscale accuracy, call the factory.

    1. P ress ENTER a nd the zero key on

    the keypad to access the diagnostic

    mode, then press 8-7-8-7. The display

    will sh ow “A1.”

    Note: If you press a ny other key before

    the 8-7-8-7 sequence, you cannot enter

    the a utomat ic calibration routine.

    2. B e sure the scale is empty of all

    weight (e.g. ta nk). P ress “0” a nd t hen

    press ENTER on the keypa d. The

    display shows “0.00” and then

    chan ges to the messa ge “A2.”

    3. P lace a known weight (between 10

    a nd 80 pounds) in th e cent er of the

    scale platform. Enter tha t w eight on

    the display using the keypad, t hen

    press ENTER . The display r eturn s to

    the VACU UM mode.

    4. To re-enter th e diagnostics mode a ndverify t he calibrat ion, simulta neously

    press ENTER and the zero key on the

    keypad. Then press “6.” The display

    shows the known w eight on th e scale

    platform.

    5. Remove the known weight , and the

    display r eturn s to “0.00.”

    Maintenance Instructions 

      ! !

      ! !

  • 8/9/2019 Robinair Mod 10324

    11/169R-134a Smart Cart ®  Automatic A/C Charging Station

    HOW TO USE THE CONTROLS

    The charging station has various compo-

    nents t ha t control its opera ting func-

    tions.

    CAUTION! D o no t operate t he stat ionuntil you ha ve filled the vacuum pump

    wit h oil and removed th e exha ust plug

    from the pump’s handle, as outlined in“Preparing the Vacuum Pump.”

    1. SYSTEM DISCHARGE Valve — Letsyou depressu rize t he A/C sy st em.

    Connect to a refrigerant recovery

    unit — do no t vent refrigerant t o the

    atmosphere.

    2. LOW Side Valve — When closed,isolat es th e low sid e of the A/C

    system from t he sta tion controls.

    N ote: The ma nifold is ported so tha t t he

    gauges indicate pressure wh ether or notthe valves are open.

    3. LOW Side Compound Gauge — Whenconnected t o the low side of a n A/C

    system, indicates the system’s low 

    side pressure.

    4. HIGH Si de Va lve — When closed,isolat es th e high side of th e A/C

    system from t he sta tion controls.

    5. HIGH Side P ressure Ga uge — Whenconnected t o the h igh side of a n A/C

    system, indicates t he system’s highside pressure.

    6. Display — Shows the t ime pro-

    gram med for vacuum, the w eight of

    refrigeran t programm ed for charg-

    ing, the control sta tus, a nd t he cycle

    of operation. Detailed instructions for

    program ming th e display follow the

    next section.

    7. Keypa d — Accomplishes specific

    operating functions, as described in

    the next section.

    8. MAIN POWER Switch — Supplieselectrica l power t o the cont rol panel.

    9. ACCESSORY Outlet — Pr ovides anelectrica l outlet for a ccessory equip-

    ment, such as a thermistor vacuum

    ga uge. This outlet is energized w hen

    the sta tion is plugged in, an d it is

    loca ted on t he side of the control box.

    N ote: There is no accessory outlet on the

    220V 50Hz m odel.10. HEATER Outlet — Provides a n

    electrical outlet for the refrigerant

    tank’s heater blanket. This outlet is

    contr olled by th e MAIN P OWER

    switch a nd is energized when the

    pow er is on.

    11. PUMP Outlet — Provides an electri-cal outlet for th e vacuum pum p. This

    outlet is controlled by t he logic board.

    Additional Operating Guidelines 

    Di agram of Contr ol Components 

  • 8/9/2019 Robinair Mod 10324

    12/1610 © 1991 Robinair Division, SPX Corporation

    Additional Operating 

    Guidelines 

    USING THE KEYPAD

    The cha rging sta tion also has a unique

    keypad for da ta entry. It uses only six

    keys for sequence control, and the LCD

    display indicat es the opera ting m ode.

    CAUTION! Do no t operate t he sta tionuntil you ha ve filled th e vacuum pump

    with oil an d removed th e exha ust plugfrom the pump’s handle, as outlined in

    “Preparing the Vacuum Pump.”

    START — P ress to begin the a utomat iccycle after t he charging st at ion is pro-

    grammed.

    CONT — Pr ess to resume (or cont inue)operations a fter pressing the H OLD key

    (described below).

    HOLD — P ress to interrupt t heaut oma tic cycle.

    REVIEW PROGRAM — P ress to review the existing programmed data.

    ENTER — P ress to enter program da tainto t he computer’s memory.

    RESET CYCLE — Press t o accessprogram mode.

    ADD .2 LB. REFRIG. — P ress to partia llycha rge t he A/C sy st em.

    USING THE DISPLAY PANEL

    The charging sta tion a lso displays

    various messages on the display pa nel.

    CAUTION!  Do no t operate t he sta tionuntil you ha ve filled th e vacuum pump

    with oil an d removed th e exha ust plug

    from the pump’s handle, as outlined in

    “Preparing the Vacuum Pump.”

    Segment A — Indicat es in wh ich modethe sta tion is operating:

    PROGRAM — The sta tion is in t heprogra mming m ode, which a llows

    you to program va cuum time and

    refrigerant weight or to review th e

    existing program.

    HOLD — The evacuation process iscomplete a nd t he vacuum pump is

    off, or no refrigerant is being

    charged; also HOLD is used whilechanging a refr igerant ta nk or to

    interr upt t he vacuum /char ging

    cycles.

    AUTOMATIC — Eith er the vacuumor refrigerant charging cycle is in

    process.

    Segment B — Indicates th e stat ion iseither eva cuat ing t he A/C sy stem or 

    charging refrigerant or the sta tion is

    rea dy t o be program med for one of these

    tw o functions:

    VACUUM

      • Wi t h PR O GR AM, ind ica t e s t h e

    sta tion is ready t o be programmed for

    evacuation.

      • With AUTOMATIC, indicates the

    vacuum pump is running; the num-

    ber displayed counts down in sec-

    onds, showing the a mount of t ime

    remaining for evacuat ion.

      • With HOLD, indica tes the vacuum

    cycle is complete (if t he displa y sh ows

    “0.00”), or if you pressed the H OLD

    key to interrupt the vacuum cycle,

    indicat es the rema ining t ime the

    pump runs when you press the

    CONT key.

    Di agram of K eypad 

  • 8/9/2019 Robinair Mod 10324

    13/1611R-134a Smart Cart ®  Automatic A/C Charging Station

    Qu i ck Refer ence Cha r t 

    Segment B Messages

    VACUUM + PROGRAM = Program station for vacuumVACUUM + AUTOMATIC = Vacuum pump is runningVACUUM + HOLD = Evacuation complete or

    interrupted vacuum cycle

    REFRIGERANT + PROGRAM = Program station for chargeREFRIGERANT + AUTOMATIC = Station is charging A/C systemREFRIGERANT + HOLD = Interrupted charging cycle

    REFRIGERANT (POUNDS)

      • Wi t h PR O GR AM, ind ica t e s t h e

    sta tion is ready to be programmed

    for t he am ount of refrigera nt to be

    char ged int o the A/C system ;

    on the keypad enter th e charge in

    pounds (or kilogram s, depending on

    th e model you ha ve).

      • With AUTOMATIC, indicat es the

    sta tion is charging refrigerant into

    th e A/C sy stem; t he num ber shown

    on the display counts down, showing

    the remaining a mount of refrigerant

    to be dispensed.

      • With HOLD, indica tes the HOLD key

    wa s pressed to interrupt the charging

    cycle; the number shown on the

    display is the a mount of refrigerantremaining t o be charged into the

    syst em. To cont inue cha rging, press

    CONT.

    Use the quick reference chart above to

    interpret Segment B messages.

    Segment C — Shows a number or acoded error m essage on the display tha t

    indicat es the sta tion’s operating sta tus or

    a ny specific problems.

    NUMBER

    Indicates the vacuum time in min-

    utes or the refrigerant weight in

    pounds (or kilogram s, depending on

    th e model you ha ve).

    MESSAGE CODES

      • C PL — I n dica t e s t h e r ef ri ger a n t

    char ging cycle is complete.

      • ERR5 — Indica tes an over loaded or

    broken scale.

    Segment D — Indicat es the tra nsfer ofrefrigerant is slow or has stopped.

      • I f th e d i sposab l e ta nk i s emp ty or 

    t h e r ef i l l a b l e t an k i s l ow  , replace

    the t an k following the instr uctions in

    “Insta lling a Refrigerant Tan k.” A

    small amount of refr igerant a lwaysremains in a refillable ta nk.

    • I f t h e r e i s adequa t e r ef r i g er an t i n  

    t h e t a n k  , you need to pull the

    remainder of the program med charge

    int o the low si de of the A/C sy st em,

    a s outlined in S tep 7 of “To Use

    Automa tic Vacuum /Cha rging Cycles.”

    Additional Operating Guidelines 

    Di agram of Di splay Panel 

  • 8/9/2019 Robinair Mod 10324

    14/1612 © 1991 Robinair Division, SPX Corporation

    Replacement Parts List 

    The followin g is a list of replacement

    part s you ma y need to service or ma in-

    tain your automatic charging station.

    Because of ongoing product improvements, we 

    reserve the right to change design, specifications,

    or materials without notice.

    Our P remium High Vacuum P ump Oil is

    also available in handy quart containers

    or in convenient gallon containers:

    Qua rt (shipped 12 qua rt s per case) 13203

    G a llon (shipped 4 gallons per case) 13204

    This oil ha s been specifically blended t o

    mainta in ma ximum viscosity and to

    improve cold w eather st ar ts .

    Description 115V 60 Hz 220V 50 Hz

    Handle (Red) 40448 40448

    Handle (Blue) 40447 40447

    Gauge, Blue Low Side Compound 11741 11726

    Gauge, Red High Side Pressure 11742 11727

    High Side Coupler 18191 18191

    Low Side Coupler 18190 18190

    Vacuum Pump RA15427 RA15428120” Blue Hose 62120 62120

    120” Red Hose 63120 63120

    60” Yellow Hose 37160 37160

    9” Blue Hose 37059 37059

    Tank Hose 37024 37024

    Black Vacuum Hose 40586 40586

    Main Power Switch RA40994 RA40994

    Scale Assembly RA19008 RA19008

    Tank Platform RA14967 RA14967

    Heater Blanket 10994 45605

    Vacuum Solenoid Assembly RA19020 RA19020

    Refrigerant Solenoid RA19006 RA19006

    Main Board RA18761 RA19092

    Keypad RA18751 RA18751

    Check Valve RA17112 RA17112

    Tank Strap RA19056 RA19056

    Cover 17495 17495

    Wheel & Nut RA10751 RA10751

    Transformer N/A RA19091

    High Vacuum Grease 13033 13033

  • 8/9/2019 Robinair Mod 10324

    15/1613R-134a Smart Cart ®  Automatic A/C Charging Station

    Symptom Cause Cure

    • Station unplugged • Plug station into power

    source

    • No power at wall outlet • Locate problem with outlet or

    change outlets

    • Vacuum pump unplugged • Plug pump into power source

    • Vacuum time not entered • Program required vacuum

    time

    • Defective vacuum pump • Remove and replace pump

    • Faulty components • Call factory

    • Transfer stopped or • Start A/C system and pulltoo slow rest of refrigerant into system

    (Step 6 in “To Use Automatic

    Vacuum/Charge Cycle”)

    • Tank safety strap too tight • Loosen the safety strap

    • Refrigerant supply empty • Replace the refrigerant tankor call factory

    • Refrigerant supply empty • Replace the refrigerant tank

    • Discharge valve open • Close discharge valve

    • Low side valve closed • Open low side valve

    • Pump oil contaminated • Flush and change pump oil

    • Hose gasket damaged • Replace gasket or hose

    • Charging line loose • Check connections

    • Manifold leaking • Check connections

    • Pump’s Iso-valve closed • Open Iso-valve

    • Overloaded or broken • Check tank weight, recali-

    scale brate if necessary, or callfactory

    Trouble- Shooting Tips 

    No power when 

    POWER switch is on — no display showing 

    Vacuum pump does not start 

    Audible tone sounds and “  CHECK REFRIG- ERANT ”   message 

    displays during refrigerant transfer 

    Refrigerant doesn ’ t flow 

    or “  REFRIGERANT ”  message doesn ’ t 

    display 

    Vacuum pump runs, but 

    low side gauge does not register an appropriate 

    vacuum 

    ERR5 

  • 8/9/2019 Robinair Mod 10324

    16/16

    For assistance in servicing or using theAutomatic A/C Charging Station, call thetoll-free Service Line, 800-822-5561, inside

    the continental U.S. In Canada, call 419-485-5561, Ext. 300. In all other locations,contact your local distributor. To help usserve you better, please be prepared toprovide the model number, serial number,and date of purchase.

    To validate your warranty, you must com-plete the warranty card attached to yourstation and return it within ten days fromdate of purchase.

    Ounce Pound

    1 .062 .123 .19

    4 .255 .31

    6 .387 .44

    8 .509 .5610 .62

    11 .6912 .75

    13 .81

    14 .8815 .9416 1.00

    PSI(oF) R-34a

    -20 -1.8-15 0

    -10 2.0-5 4.1

    0 6.55 9.1

    10 12.0

    15 15.120 18.4

    25 22.130 26.1

    35 30.4

    40 35.045 40.1

    50 45.455 51.3

    60 57.465 64.0

    70 71.175 78.580 86.7

    85 95.390 104.3

    95 113.9100 124.1

    105 134.9110 146.3

    115 158.4120 171.1125 184.5

    130 198.7135 213.5

    140 229.2

    Note : Gauge pressures are approximationsrounded to the nearest 1/20 PSI.

    Temperature — Pressure RelationR-134a Refrigerant

    Conversion ChartOunces to Hundredths of a Pound