RELAI FREKUENSI ( FREQUENCY RELAY )
description
Transcript of RELAI FREKUENSI ( FREQUENCY RELAY )
DOK - IBA
RELAI FREKUENSI
BESARAN INPUT DARI RELAI FREKUENSI ADALAHTEGANGAN YANG DIAMBIL DARI TRAFO TEGANGAN [ PT ]
RELAI INI MEMONITOR BESARNYA FREKUENSI SISTEM .
1. RELAI FREKUEN SI KURANG [ UFR ] MEMBANDINGKAN FREKUENSI SISTEM DENGAN FREKUENSI SETTINGNYA . BILA FREKUENSI SISTEM LEBIH KECIL ATAU SAMA DENGAN FREKUENSI SETTING MAKA RELAI AKAN KERJA
2. RELAI FREKUENSI LEBIH BILA FREKUENSI SISTEM LEBIH BEAR ATAU SAMA DENGAN FREKUENSI SETTING MAKA RELAI AKAN KERJA .
DOK - IBA
FUNGSI / APLIKASI UFR
1. DIPASANG PADA PENYULANG TM , UNTUK LOAD SHEDDING SECARA OTOMATIS BILA TERJADI PENURUNAN FREKUENSI SIATEM , AKIBAT KEHILANGAN DAYA PEMBANGKIT . ADA 6 TAHAP PENYETELAN RELAI UFR DI PENYULANG 20 KV PLN YAITU 48,8 – 48,3 Hz
2. DIPASANG DI PEMBANGKIT ,UNTUK MEMISAHKAN PEMBANGKIT DARI SISTEM INTERKONEKSI, BILA TERJADI GANGGUAN PADA SISTEM [ ISLANDING SYSTEM ] DILENGKAPI DENGAN UVR .
FUNGSI / APLIKASI OFR
DIPASANG DI PEMBANGKIT SEBAGAIPENGAMAN KECPATAN LEBIH [ OVERSPEED ]
DOK - IBA
R1
R2
C
f
f
Prinsip kerjaelektrodinamik
Relai frekuensi dengan asas induksi
50
48 52
V
DOK - IBA
T1
T2
T1
T2
T T1
T T2
1
2
T1
T2
V
V
DOK - IBA
sec.0.0.0.0.0.0T1 HzT
1f
11
MFVU
sec.0.0.0.0.0.0T2 Hz2
2 T
1f
0,050.10,20,20,5
1225
10
0000000000
0.050,10,20,20,5
1225
10
0000000000
f1 f1
f2f2f1 ON OFF
ON OFF Pu:do 1:1
f2:f1
Vx=110V=
MFVU210CA00045
f1 f2 Reset Test
sec
)(0,1
t1
sec
)(0,1
t2
DOK - IBA
T1
T2
T1
T2
T T1
T T2
1
2
T1
T2
V
V
RESETSET
SETRESET
SETRESET
RESET
PU DOt2
t1
&
&
V>
TEST
f2:f1
f2:f2
2
2R L
2
1R L
26
27
28
1
3
5
6
4
2
9
11
10
13
12
14RL2-2
RL1-1
RL1-2
RL2-1
f2
f1
>>
>>
+
-0V
17
18V
V=
1
2
DIAGRAM INTERNAL RELAI FREKUENSITIPE MFVU 21 GEC
DOK - IBA
V=
52TC 52TC
52a52a
110V+
-
27
28
17 +
18 -
PT
BUS 20 KV
1
3
9
11
MFVU 21
TRIP PMT 1
TRIP PMT 2
t1
t2
f1
f2
PT
PENGAWATAN
DOK - IBA
250V125V
48VOFF
VA
NORM. FREQ.
FAULT FREQ.
+
-CONTACT
ON
OFF OUTPUTSUPPLY220V
FTS 300 EIL
PORTABLE TESTSET TIPE FTS 300 EIL
6
321
4
5
7
8
910
1112
13
15
14
1. Power Input Connection2. Main Power Switch3. Function Switch4. AC signal Output5. Output Voltage Control6. Output Voltage Meter7. Frequency Range Switch8. Frequency adjust Control9. Frequency meter / Timer10. Contact / DC power
terninal11. DC Power Supplay Control12. Contact mode select
switch13. Contact status Indicator14. Target current control /
range switch15. DC Ammeter
Keterangan Gambar :
DOK - IBA
FUNGSI ALAT KONTROL PADA PANEL DEPAN ALAT UJI FTS 300
1. Power Input Connection Menghubungkan power cord untuk mendapatkan power input pada
alat uji ( suplai 220V).2. Main Power switch Mengontrol input power dan juga sebagai pemutus dalam hal
hubung singkat atau gangguan. Untuk menunjukan bahwa alat uji dienergis maka lampu akan menyala.
3. Function Switch Memilih kondisi kerja dari alat uji4. AC signal Output Memberikan output AC signal dari alat uji5. Output Voltage control Mengatur besarnya AC output signal. Knob “Output control” terdiri
dari dua potensio konsentris, knob luar mengatur besarnya tegangan normal, dan knob dalam mengtur besarnya tegangan gangguan. Tombol Read Fault Voltage memungkinkan tegangan gangguan ada dalam kondisi Set Fault sebelum diswitch ke posisi Test
6. Output Voltage meter Memonitor besarnya tegangan AC signal yang ada pada signal
output.DOK - IBA
7. Frquency range switch Untuk memilih output rentang frekuensi 40 – 70 Hz atau 360 – 440 Hz 8. Frequency Adjust control Potensiometer dengan 15 posisi yang mana mengatur frekuensi
normal dan gangguan9. Frequency meter / Timer Untuk menampilkan frekuensi normal / frekuensi gangguan atau
waktu , tergantung pada kondidsi kerja / mode dari alat uji. Dibawah meter ditunjukan 2 buah lampu Led yang ditandai dengan “Hertz” dan “Second”.
10. Contact DC power supplay terminals Terminal merah dan kuning digunakan untuk memonitor status dray
contact atau scr dalam kondisi Normal ,Set Fault dan Test. Penutupan contact ditandai oleh Led dari kontak closed. Dalam kondisi Test penutupan kontak dapat digunakan untuk menyetop Timer.
11. Dc Power Supplay Control Memilih tegangan output Dc yang ada pada terminal merah dan
hitam. Tiga jenis tegangan yang tersedia yaitu 48V, 125V dan 250V sesuai kebutuhan relai. Indikator On/Reset adalah suatu Led oranye akan menyala bila tegangan ada. Supplay diproteksi terhadap beban lebih,dan dapat direset dengan menekan tombol tekan (Led).
DOK - IBA
12. Contact Mode Select Switch Untuk menentukan apakah timbul atau tidak hubung pendek pada
terminal merah dan kuning, dan akan menyetop timer dalam kondisi Test. Dengan memilih salah satu kontak normally open atau close untuk memonitor test penundaan waktu.
13. Contact status Indicator Led yang menyala untuk menunjukan suatu hubung pendek pada
terminal merah dan kuning.14. Target Current Control/Range Switc Knob luar adalah suatu saklar yang memilih range dari Ammeter
DC yang diinginkan yaitu 0,3 atau 3 A. Knob dalam adalah suatu potensio yang mengtur besarnya arus DC dalam kondisi Target.
15. DC Ammeter Memonitor arus dari internal DC supplay dalam kondisi Normal ,
Set Fault dan Test ,dan mengukur besarnya arus DC pada terminal merah dan kuning dalam kondisi Target.
DOK - IBA
PENGUJIAN INDIVIDUAL RELAI FREKUENSI KURANGTIPE MFVU 21 GEC – TEST SET FTS 300
1. TUJUAN Setelah melaksanakan pengujian siswa diharapkan dapat mengukur: 1. pickup / drop off frequency 2. waktu kerja relai frekuensi
2. ALAT UJI / RELAI 1. Frequency Test Set model FTS 300 (EIL) 2. Relai frekuensi tipe MFVU 21 GEC
3. RANGKAIAN PENGUJIAN 1. Rangkai lah rangkaian pengujian ( lihat gambar pengujian ) 2. Hubungkan sumber tegangan 220V ke alat uji 3. Posisikan kontrol ( tombol, saklar, alat ukur ) dari alat uji FTS 300 sebagai berikut :
DOK - IBA
250V125V
48VOFF
VA
NORM. FREQ.
FAULT FREQ.
+
-CONTACT
ON
OFF OUTPUTSUPPLY220V
FTS 300 EIL
2726
28
18
1
3
17+
-
RANGKAIAN PENGUJIAN RELAI FREKUENSI TIPE MFVU 21 GEC
MFVU 21 GEC
PORTABLE TESTSET TIPE FTS 300 EIL RELAI YANG DIUJI
9
11
DOK - IBA
Kontrol Posisi
Main Power switch . . . . . . . .. . . . . . Off Function Switch . . . . . . . . . . . . . NormalOutput Voltage adjust control . . . . . . . Putar penuh kekiriFrequency range switch . . . . . . . . . . 40 – 70 HzFrequency adjust control . . . . . . . . . Mid rangeContact mode select switch . . . . . . . . NO (open)Target current range switch . . . . . . . . Sesuai yang diinginkanTarget current control . . . . . . . . . . . Putar penuh kekiriDC power supply . . . . . . . . . . . . . . Sesuai yang diinginkan
4. PENGUJIAN PICK UP / DROP OFF FREQUENCY 1. Hidupkan alat uji ( Main power switch pada posisi on ) 2. Putar Output Voltage control ke kanan sampai Voltmeter menunjuk tegangan input nominal relai (100V) 3. Atur normal frequency control sampai frekuensi meter menunjuk harga rated dari normal frekuensi 4. Atur normal frequency control sampai relai mulai pick up ( indikator kontak menyala ) dan naikan frekuensi sampai indikator kontak padam ( reset ) 5. Cata kedua besaran ini , dan ulangi percobaan ini untuk output tegangan yang laian .
DOK - IBA
5. PENGUJIAN WAKTU KERJA RELAI 1. Atur nominal frequency control sehingga frekuensi meter menunjuk harga rated dari normal frekuensi (50Hz) 2. Putar Function swicth ke posisi set fault 3. Atur Fault frequency control sehingga frekuensi meter menunjuk frekuensi yang diinginkan 4. Tekan tombol read voltage control dan atur tegangan gangguan dengan mengatur output voltage control 5. Putar Function switch pada posisi Test maka frekuensi meter akan berubah menjadi Timer (akan mencatat waktu kerja relai ) 6. Ulangi pengujian diatas untuk setting waktu yang lain atau frekuensi gangguan yang lain. 7. Matikan alat uji dan lepas kabel kontrol .
DOK - IBA
A1
6
2345
78
12
910
111211
10987
6
5
1
23
Trip 2
Trip 2Trip 1
Trip 1
PT 110V+
+ _
+
NF921 11
333513
7 7 7
999
UE--UE+
UE+UE--
UE+UE--
33
45 45
45 45 45
4137
3939
37
41
37
3941
29
3131 31
29293333
FC 95 - 22
E
110V DC
AUX. SUPPLY
FCN 950 - 22
INTERNAL DIAGRAM UFRTIPE FCN 950ABB
DOK - IBA
1
0
+_
MODEf(Hz)
dF/dt
t(s)
SAVE
1
2
DC U<
CARA SETTING UFR TIPE FCN 950 MERK ABB
1. Tekan tombol Mode + enable s/d f(Hz) menyala, kemudian tekan tombol Mode + enable s/d lampu 1 (Freq 1) menyala.
2. Untuk menambah / mengurangi nilai setting freq. / waktu dengan cara menekan tombol enable dan tombol + / - .
3. Untuk menyimpan data setting tekan tombol mode + enable s/d lampu save menyala, kemudian tekan tombol enable dan +/- sampai dengan display muncul angka.
Catatan : 1. Untuk merubah fungsi f(Hz) t(sec) Save 2. Tripping freq. 1 muncul indikasi angka 1. Tripping freq 2 muncul angka 2.
Tombol enable ditekan terus dan dengan menekan tombol mode maka fungsi akan berubah
DOK - IBA
ENABLE
PENGUJIAN INDIVIDUAL RELAI FREKUENSI KURANGTIPE FCN 950 ABB – TEST SET FTS 300
1. TUJUAN Setelah melaksanakan pengujian siswa diharapkan dapat mengukur: 1. pickup / drop off frequency 2. waktu kerja relai frekuensi
2. ALAT UJI / RELAI 1. Frequency Test Set model FTS 300 (EIL) 2. Relai frekuensi tipe FCN 950 ABB
3. RANGKAIAN PENGUJIAN 1. Rangkai lah rangkaian pengujian ( lihat gambar pengujian ) 2. Hubungkan sumber tegangan 220V ke alat uji 3. Posisikan kontrol ( tombol, saklar, alat ukur ) dari alat uji FTS 300 sebagai berikut :
DOK - IBA
250V125V
48VOFF
VA
NORM. FREQ.
FAULT FREQ.
+
-CONTACT
ON
OFF OUTPUTSUPPLY220V
FTS 300 EIL
3
1
UE
7
6
UE+
-
RANGKAIAN PENGUJIAN RELAI FREKUENSI TIPE FCN 950 ABB
FCN 950 ABB
PORTABLE TESTSET TIPE FTS 300 EIL RELAI YANG DIUJI
9
8
2
DOK - IBA
Kontrol Posisi
Main Power switch . . . . . . . .. . . . . . Off Function Switch . . . . . . . . . . . . . NormalOutput Voltage adjust control . . . . . . . Putar penuh kekiriFrequency range switch . . . . . . . . . . 40 – 70 HzFrequency adjust control . . . . . . . . . Mid rangeContact mode select switch . . . . . . . . NO (open)Target current range switch . . . . . . . . Sesuai yang diinginkanTarget current control . . . . . . . . . . . Putar penuh kekiriDC power supply . . . . . . . . . . . . . . Sesuai yang diinginkan
4. PENGUJIAN PICK UP / DROP OFF FREQUENCY 1. Hidupkan alat uji ( Main power switch pada posisi on ) 2. Putar Output Voltage control ke kanan sampai Voltmeter menunjuk tegangan input nominal relai (100V) 3. Atur normal frequency control sampai frekuensi meter menunjuk harga rated dari normal frekuensi 4. Atur normal frequency control sampai relai mulai pick up ( indikator kontak menyala ) dan naikan frekuensi sampai indikator kontak padam ( reset ) 5. Cata kedua besaran ini , dan ulangi percobaan ini untuk output tegangan yang laian .
DOK - IBA
5. PENGUJIAN WAKTU KERJA RELAI 1. Atur nominal frequency control sehingga frekuensi meter menunjuk harga rated dari normal frekuensi (50Hz) 2. Putar Function swicth ke posisi set fault 3. Atur Fault frequency control sehingga frekuensi meter menunjuk frekuensi yang diinginkan 4. Tekan tombol read voltage control dan atur tegangan gangguan dengan mengatur output voltage control 5. Putar Function switch pada posisi Test maka frekuensi meter akan berubah menjadi Timer (akan mencatat waktu kerja relai ) 6. Ulangi pengujian diatas untuk setting waktu yang lain atau frekuensi gangguan yang lain. 7. Matikan alat uji dan lepas kabel kontrol .
DOK - IBA
KESIMPULAN ; BANDINGKAN HASIL UJI DENGAN DATA TEKNIK SEHINGGA DIPEROLEH KESIMPULAN BAHWA KONDISI RELAI MASIH STANDAR / NORMAL ATAU MENGALAMI PENURUNAN KUALITAS / CONDONG TIDAK NORMAL DAN PERLU PENGGANTIAN .
DOK - IBA
DOK - IBA