Generator Details: :CalculatGenerator Voltage (VL) 11 KV Phase to N
Maximum Over Voltage 14.3 KV % of ForceFrequency 50 Hz Phase to N
Generator Transformer Details: CapacitiveTransformer Primary Vo 33 KV Total Capa
Transformer Secondary 11 KV Rating of N
Capacitance Per Phase: Neutral EartGenerator Winding Cap 0.22 Farad Size of Neu
Generator Connection C 0.001 Farad Residual Ca
Generator Transformer 0.006 Farad Required R
Generator Transformer 0 Farad Required G
Transformer Cabale Ca 0.0003 Farad Neutral Eart
Surge Arrestor Capacita 0.25 Farad Neutral Eart
Other Capacitance / Ph 0.2 Farad Neutral Eart
Total Zero Sequence 0.67730 Farad Neutral Eart
Total Zero Sequence 4702.07 /Phase Neutral Ear
Neutral Earthing Transformer Size: Fault curre
Primary Voltage of the 11 KV :Results:Secondary Voltage of th 240 Volt RatingTurns Ratio of the Grou 45.83 Short time
Neutral Earthing Transf 4% 0.04 Ratio of Ne
Neutral Earthing Transf 0.04 PU Neutral Eart
Neutral Earthing Transf 0.24 KV Required G
MaxSecRes 2.23834172
Trafo Pr/Sec cap 0.1 uf
resistance 2929.115407 ohms
pri imp volt 45 kv
sec effect 13863.71668
-
8/10/2019 NGT rexcel
2/3
Size of Neutral Earthing Transformer: utral Voltag 6.35 KV VL/1.732
ield conditio 30% 1.3 utral Voltag 8.26 KV Vf=Vp1x 1.3
harging cur 1.76 Amp Ic=Vf / Xc
itive charg 5.27 Amp It=3xIc
eutral Earthi 57.94 KVA Pr=VpxIt
hing Transf 2.6
tral Earthin 22 KVA P=Pr/ 2.6
pacitive rea 1567.36 Xct=Xc / 3
esistance 0.746 Rsec=Xct / (NxN)
rounding R 1567.36 Rp=Xct
hing Transf 92.86 Amp
hing Transf 313.87 Amp
hing Transf 2.58
hing Transf 0.10 X=Xpu x Base X
thing Tran 0.14
nt through 4.05 Amp If=Vp1/Rp
f Neutr 22 KVA ating of Ne 58 KVA
tral Earthin 11000 /240 Volt
hing Transf 92.86 Amp
ounding Re 1567.36
-