MULTI TRANSDUCERtransducer.co.kr/uploaded/board/data1/Multi_transducer.pdf · 2017. 7. 6. · MULTI...
Transcript of MULTI TRANSDUCERtransducer.co.kr/uploaded/board/data1/Multi_transducer.pdf · 2017. 7. 6. · MULTI...
Voltage input AC 110 / 220 / 380VCurrent input AC 5A or 1AInput loss/element V: 0.3VA, C: 0.5VA
Max. inputoverload
Voltage(PT) 150% for 10secCurrent(CT) 1000% for 10sec
Frequency 50 / 60Hz
IndicatorLED(Red)
Fault OnNormal Off
LED (Green) Flicker at the load input
Aux. power supply AC110/220V±15V 50/60HZ 1.5VADC Volt ±10% 1W
pulse output specification계기정수(Pulse/Kwh) : 10000외부출력 펄스 : 1Pulse=0.1Wh(Ic<10mA, Vcc<30V, 펄스폭 70mS)
Communication Modbus
TemperatureRange
Storage -20~70
Operating -10~60
Operating humidity 20~90%RH (Non-condensing)
Accuracy(at 25) ±0.5%
Temp. influence ±0.01% /
Insulation resistance 100MΩ more with DC500V
Dielectric test AC 2000V / 1minute
Mounting Wall or DIN Rail(35mm)
Size 150(W) × 75(H) × 112(D)mm
Case material ABS Resin
Weight Approx. 500g
P×W PT ratio CT Cal.Watt Code
1×2110V 5A 550W A220V 5A 1100W D
Others Others Others S
3×3220V 5A 2200W D380V 5A 3800W G
Others Others Others S
3×4190/110V 5A 1650W K380/220V 5A 3300W L
Others Others Others S
통신 Type Pulse output Type
1 2Modbus(RS-485)
모든 전기량
계기정수(Pulse/Kwh) : 10000외부출력 펄스 : 1Pulse=0.1Wh
DT-CWH SERIES는 AC 전기량의 검침 값을 데이터 통신을
통해 외부로 전송할 수 있는 인터페이스를 지원하는 변환기
입니다.
DT - CWH- - 1) 2) 3) 4) 5) 1) CONNECTION 12 : 1Phase 2Wire 33 : 3Phase 3Wire
34 : 3Phase 4Wire
2) INPUT
3) OUTPUT
4) AUX. POWER A : AC 110/220V B : AC 115/230V C : AC 120/240V D : DC 24V E : DC 48V F : DC 110V G : DC 115V H : DC 220V
MULTI TRANSDUCER (RS485 Modbus Communication) DT - CWH Series
Specifications
MODEL CODE
Characteristics
교류전용 CPU를 채택하여 전기 계측에 신뢰성과 정밀성
을 높였습니다.
다양한 통신방식이 가능한 유연한 시스템방식인 ModBus
(RS-485)통신방식을 수용하여 실시간으로 모니터링이
가능합니다.
유.무효 누적량은 최대 6digit(999,999kWh)까지 가능하고
자동 Reset됩니다.
검침 데이터 보존 기능 - 비휘발성 메모리를 채택하여 정전
시에도 데이터를 영구 보존합니다.
정밀 sensor 사용으로 0.5% 이하로 정밀측정이 가능합니다.
전압은 PT 없이 AC 380V까지 가능하며 전류는 CT 2차측
AC 5A까지 입력 가능합니다.
1
계측항목 요 소 계측항목 요 소
전 압 R,S,T - 상전압 전 류 R,S,T
송전유효전력 (-역방향) R,S,T,⅀ 수전유효전력 (+정방향) R,S,T,⅀송전무효전력 (-역방향) R,S,T,⅀ 수전무효전력 (+정방향) R,S,T,⅀
송전유효전력량 (-역방향) ⅀ 수전유효전력량 (+정방향) ⅀송전진상무효전력량 (-역방향) ⅀ 수전진상무효전력량 (+정방향) ⅀송전지상무효전력량 (-역방향) ⅀ 수전지상무효전력량 (+정방향) ⅀
역 율 R,S,T 주 파 수 -
※ 상기 표시 범위는 CT, PT 2차측 기준이므로 배율을 곱하여 사용하여야 하며 아랫방법을 참고 하시기 바랍니다.
1) 전압
- 데이터 통신을 통해 계측된 전압을 사용하면 됩니다. - 기본 상전압이기 때문에 3P4W에서 선간전압으로 표시를 원하실 경우 PT비율을 곱해서 사용 합니다. ex) PT가 380/220V일 경우 PT비는 1.727 이므로 220V × 1.727 = 380V가 됩니다.
2) 전류
- 데이터 통신을 통해 계측된 전류에 CT비율을 곱해서 사용하면 됩니다. ex) 계측된 전류 : 2A, CT비 : 200/5A일 경우 - 계측된 전류 × CT비 = 2A × 40 = 80A가 됩니다. 3) 유효전력•전력량 및 무효전력•전력량
- 데이터 통신을 통해 계측된 유효전력에 승율(CT비 × PT비)을 곱해서 사용합니다. ex) 측정된 유효전력: 825W, CT비 : 200/5A, PT비 : 380/190V일 경우
유효전력값 × CT비 × PT비 = 825W × 40 × 2 = 66KW로 표시가 되도록 프로그램을 작성하여 사용
하십시오.
- 유효전력량 또한 계측된 유효전력량에 승율(CT비 × PT비)을 곱해 사용하십시오. ex) 측정된 유효전력량: 2500WH, CT비 : 200/5A, PT비 : 380/190V일 경우
유효전력량값 × CT비 × PT비 = 2500WH × 40 × 2 = 200KWH로 표시가 되도록 프로그램을 작성
하여 사용 하십시오.
4) 역율
- 데이터 통신을 통해 계측된 값을 사용하면 됩니다.
5) 주파수
- 데이터 통신을 통해 계측된 값을 사용하면 됩니다.
Data setting
Measurement
2
2 4 6 8
1 3 5 7 9 11
P1 P3P2
1S
P0
2S1L 3S2L
16
3L
141210
171513
-+-+
~
~
+
DC Volt
AC 110V
-
AC 220V
KwhFault
21
N3
LOADLINE
3P4W
PULSE 통신출력
42
1
6
3 119
P3P2P1
1L1S
16
3L3S
10 12 14
15 1713
-+-+
~
~
-+
DC Volt
AC 220V
AC 110V
Fault Kwh
21
3
3P3W
LOADLINE
PULSE 통신출력
42
31
P1 P2
1L1S
14 1610 12
13 15 17
+ -+-
~DC Volt
~
-+
AC 220V
AC 110V
KwhFault
21LINE
통신출력
1P2W
LOAD
PULSE
Connection diagram
Dimensions
3
Full Scale inputDC Voltage (0 ~ 300V)
DC Current (0~50mA)
TemperatureRange
Storage -20°C ~ 70°C
Operating -10°C ~ 60°C
Operating humidity 20~90%RH (Non-condensing)
Accuracy(at 25) ±0.5%
Temp. influence ±0.01%/°C
Linearity ±0.02% F.S
Response time 0.4sec(0~90%)
Communication Modbus RS-485
Aux. power supply 110/220VAC ±15V,50/60Hz,4VADC Volt ±10% 2W
Operating humidity 20~90%RH (Non-condensing)
Insulation resistance 100MΩ more with DC500V
Dielectric test AC 1500V / 1minute
Isolation Input/Output/Power/Case
Mounting Wall or DIN Rail(35mm)
Size 150(W) × 75(H) × 112(D)mm
Case material ABS Resin
Weight Approx. 500g
Code Input Input ResistanceA DC 4~20mA 250Ω
B DC 0~1mA 1.5KΩ
C DC 0~50mV 1MΩ
D DC 0~100mV 1MΩ
E DC 0~1V 1MΩ
G DC 0~5V 1MΩ
H DC 0~10V 1MΩ
S Specify current : less than 50mASpecify voltage : less than 300V
통신 Type 1 RS-485(Modbus)
Specifications MODEL CODE
Characteristics
Data Setting
DT-MT-SC SERIES는 다양한 DC 전압 및 전류의 입력값을
테이터 통신을 통해 외부로 전송할 수 있는 인터페이스를
지원하는 변환기입니다.
DT-MT-SC- 1) 2) 3) 1) INPUT
2) OUTPUT
3) AUX. POWER A : AC 110/220V B : AC 115/230V C : AC 120/240V D : DC 24V E : DC 48V F : DC 110V G : DC 115V H : DC 220V
- DC입력에 관계없이 모든 계측값은 최소값 0 , 최대값 1 로 계측 됩니다. - 계측된 데이터 값에 표시하고자 하는 값을 곱해서 사용하면 됩니다. ex) 인버터 주파수 0~10KHz일 때 발생되는 0~10VDC를 변환기(DT-MT-SC)에 연결시켜 RS485(Modbus) 로 0 ~ 1의 계측값이 측정됨. 최소값 = 0Hz × 0(계측값) = 0 Hz 중간값 = 10000Hz × 0.5(계측값) = 5000 Hz 최대값 = 10000Hz × 1(계측값) = 10000 Hz입니다. 그러므로 측정치 = 입력최대치 × 계측값 공식으로 계산하면 됩니다.
4-CHANNEL SIGNAL CONVERTER MULTI TRANSDUCER (RS485 Modbus) DT-MT-SC Series
입력받는 DC전압 ⋅ 전류의 값을 0.5%이하로 정밀하게
측정하여 신뢰성과 정밀성을 높였습니다.
다양한 통신방식이 가능한 유연한 시스템방식인 RS-485
(Modbus) 통신방식을 수용하여 실시간으로 모니터링이
가능합니다.
1
Dimensions
Connection diagram
2
ACMax. Voltage input 0 ~ 520VMax. Current input 0 ~ 5A Input loss V: 0.3VA, C: 0.5VA
DCVoltage input 0 ~ 300V
Current Input 0 ~ ±100mVFrequency 50/60Hz
Aux. power supply 110/220VAC ±15V,50/60Hz,4VADC Volt ±10% 2W
Communication RS-485(Modbus)
TemperatureRange
Storage -20 ~ 70
Operating -10 ~ 60
Operating humidity 20~90%RH (Non-condensing)Accuracy(at 25) ±0.5%
Temp. influence ±0.01% /
Insulation resistance 100MΩ more with DC500V
Dielectric test AC 1500V / 1minute
Mounting Wall or DIN Rail(35mm)Size 150(W) × 75(H) × 112(D)mmCase material ABS ResinWeight Approx. 700g
CodeINPUT
AC V AC A DC V DC A DC AA 150V 5A 150V 50mV ±50mVB 520V 5A 150V 50mV ±50mVC 150V 5A 300V 50mV ±50mVS Others
통신 Type 1 RS-485(Modbus)
Data Setting
DT-MT-REC SERIES는 정류기반의 AC, DC 전압 및 전류의
검침 값을 데이터 통신을 통해 외부로 전송할 수 있는
인터페이스를 지원하는 변환기입니다.
DT-MT-REC-
1) 2) 3) 4)
1) INPUT
2) OUTPUT
3) AUX. POWER A : AC 110/220V B : AC 115/230V C : AC 120/240V D : DC 24V E : DC 48V F : DC 110V G : DC 115V H : DC 220V
1) 전압
- AC 전압 입력에 관계없이 모든 계측값은 최소값 0 , 최대값 1 로 계측 됩니다. - 입력이 0~520V일 경우
최소값 = 0V × 계측값 0 = 0V 최대값 = 520V × 계측값 1 = 520V입니다. 그러므로 측정값 = 입력최대값 × 계측값 공식으로 계산하면 됩니다.
2) 전류
- 데이터 통신을 통해 계측된 최소값 0 , 최대값 1 에 전류 CT비율을 곱해서 사용하면 됩니다. ex) 계측된 전류 : 2A(2차측), CT비 : 200/5A일 경우 데이터 측정값은 0.4가 측정이 됩니다. 그러므로 전류값 = 200A(1차값) × 0.4(데이터 측정값) = 80A가 됩니다.
DCA : DC Current with shunt
RECTIFIER PANEL MULTI TRANSDUCER (RS485 Modbus Communication) DT-MT-REC Series
Specifications
MODEL CODE
Characteristics
입력받는 AC전압 전류 및 DC전압 전류의 값을 0.5%이하
정밀하게 측정하여 신뢰성과 정밀성을 높였습니다.
다양한 통신방식이 가능한 유연한 시스템방식인 RS-485
(ModBus)통신방식을 수용하여 실시간으로 모니터링이
가능합니다.
1
3) DC전압
- 데이터 통신을 통해 계측된 최소값 0 , 최대값 1 에 DC전압을 곱해서 사용하면 됩니다. ex) 입력이 DC 0~150V일때
- 입력전압 : DC 110V일 경우 데이터 측정값은 0.7333가 측정이 됩니다. 그러므로 전압값 = 150V(최대값) × 0.7333(데이터 측정값) = DC 110V가 됩니다.
4) DC전류(단방향) - 데이터 통신을 통해 계측된 최소값 0 , 최대값 1 에 DC전류를 곱해서 사용하면 됩니다. ex) 입력이 DC 0~150A일때
- 입력전류 : DC 50A일 경우 데이터 측정값은 0.3333가 측정이 됩니다. 그러므로 전류값 = 150A(최대값) × 0.3333(데이터 측정값) = DC 50A가 됩니다.
5) DC전류(양방향) - 데이터 통신을 통해 계측된 최소값 -1 , 최대값 1 에 DC전류를 곱해서 사용하면 됩니다. ex) 입력이 DC 0~150A일때
- 입력전류 : DC 50A일 경우 데이터 측정값은 0.3333가 측정이 됩니다. 그러므로 전류값 = 150A(최대값) × 0.3333(데이터 측정값) = DC 50A가 됩니다. - 입력전류 : DC -50A일 경우 데이터 측정값은 -0.3333가 측정이 됩니다. 그러므로 전류값 = 150A(최대값) × -0.3333(데이터 측정값) = DC -50A가 됩니다.