ダイキン海上コンテナ冷凍装置Marine type Container Refrigeration Unit
LXE10E-A18CLXE10E-A18D
サービスガイド・パーツリスト
Service Manual・Parts List
オプション機能編・Optional Functions
TR07-06
PDF作成用 2008.02.20 10:36 ページ 1
-
1
Covered ModelsRegarding the features and operation of the unit, the service guidedescribes the items which are different from those of the service manualTR01-09C.
No. ItemDifferent points from service manual(Maintenance and Repair)
1 Tightening lever for control box cover Quick-lock lever type
2☆ Frozen mode Refer to the details in the following pages.
3☆ Defrosting mode Refer to the details in the following pages.
4☆ Dehumidification function Refer to the details in the following pages.
For the ☆ marked items, refer to the details in the following pages.
5☆ MODE Key (Display panel) Refer to the details in the following pages.
6☆ Operation procedure flow chart Refer to the details in the following pages.
7☆ Automatic Pump Down Refer to the details in the following pages.
8☆ Cable clamp bracket Provided.
9☆ Manual Check Selection Mode Refer to the details in the following pages.
10☆Electronic type temperature recorder(Rechargeable type)
Refer to the details in the following pages.
11☆ TransFRESH Refer to the details in the following pages.
12 Communication MODEM Provided.
13 Temperature setting range +30℃~-30℃
14☆ Appendix Refer to the details in the following pages.
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 1
-
2
CONTENTS3.5.1 Specifications .......................................3-363.5.2 Function................................................3-363.5.3 Battery check
(When using optional recargeable battery) ...3-363.5.4 Battery replacement
(Rechargeable battery) ............................3-373.6 Information interchange with personal computer...3-38
3.6.1 Data logging .........................................3-393.6.2 Software configuration..........................3-40
3.7 Inspection procedure for the electroniccontroller .....................................................3-42
3.8 Controller replacement and the initial setting...3-433.8.1 Controller replacement .........................3-433.8.2 Compatibility of controller DECOSⅢd with
Ⅲc and Ⅲb ..........................................3-443.8.3 LXE10E-1, LXE10E-A & LXE10D Initial
setting procedure (for spare controller of DECOSⅢd, DECOSⅢc & DECOSⅢb) ...................3-46
3.8.4 LXE10E-1 & LXE10E-A Initial setting tableinto spare controller DECOSⅢd ..........3-47
3.8.5 LXE10E-A Initial setting table into sparecontroller DECOSⅢc ...........................3-48
3.8.6 LXE10D Initial setting table into sparecontroller DECOSⅢb ...........................3-49
3.9 PTI (Pre-Trip Inspection) and periodic inspection ...3-503.9.1 Inspection item .....................................3-513.9.2 Automatic PTI (Pre-Trip Inspection) .....3-54
3.9.2.1 PTI selection mode........................3-553.9.2.2 Short PTI (S.PTI) ...........................3-563.9.2.3 Full PTI (F.PTI) ..............................3-573.9.2.4 Alarm list during PTI
(Pre-Trip Inspection)......................3-583.9.2.5 Manual check (M.CHECK) ............3-59
3.10 Chartless function .....................................3-613.10.1 Chart indication function.....................3-613.10.2 P code (Pull down time indication) .....3-633.10.3 Chartless code display function..........3-64
3.10.3.1 List of chartless code...................3-643.10.3.2 H-code.........................................3-653.10.3.3 d-code: ........................................3-67
3.11 Communication modem ............................3-684. SERVICE AND MAINTENANCE........................4-1
4.1 Maintenance service .....................................4-14.1.1 Collection of refrigerant ..........................4-14.1.2 Gauge manifold ......................................4-14.1.3 Automatic pump down............................4-34.1.4 Refrigerant recovery and charge............4-5
4.2 Main components and maintenance .............4-84.2.1 Scroll compressor...................................4-84.2.2 Fan and fan motor ................................4-124.2.3 PT and CT board (EC9756) .................4-134.2.4 Electronic expansion valve...................4-15
SAFETY PRECAUTIONS• Danger .................................................................3• Warning................................................................4• Caution.................................................................5
1. INTRODUCTION.................................................1-11.1 Operation range ............................................1-11.2 Basic names of components .........................1-11.3 Basic operation of refrigeration unit ..............1-2
1.3.1 Starting operation ...................................1-21.3.2 Checking during operation .....................1-31.3.3 Procedure after operation.......................1-31.3.4 Adjust the ventilation ..............................1-4
2. GENERAL DESCRIPTION.................................2-12.1 Main specifications........................................2-12.2 Names of components ..................................2-2
2.2.1 Outside ...................................................2-22.2.2 Inside......................................................2-52.2.3 Control box .............................................2-7
2.3 Set point of functional parts and protectiondevices.........................................................2-12
2.4 Operating pressure and running current .....2-132.5 Operation modes and control......................2-17
2.5.1 Frozen mode ........................................2-182.5.2 Chilled and partial frozen mode............2-202.5.3 Defrosting mode ...................................2-222.5.4 Dehumidification (Optional) ..................2-252.5.5 Common control ...................................2-26
3. ELECTRONIC CONTROLLER...........................3-13.1 Function table................................................3-13.2 Basic operation of electronic controller .........3-3
3.2.1 Control panel ..........................................3-33.3 Operation procedure .....................................3-6
3.3.1 Operation procedure flow chart ..............3-63.3.2 Mode operation procedure .....................3-9
1. Current (Operation state) indication mode ...3-92. Operation setting mode ........................3-103. Battery mode ........................................3-114. Mode operation ....................................3-125. LED display light-OFF mode ................3-146. Sensor indication mode........................3-157. Temperature record scroll mode ..........3-188. Alarm record scroll mode .....................3-219. PTI record scroll mode .........................3-23
3.3.3 Setting flow chart..................................3-2410. Optional function setting mode...........3-2611. Basic function setting mode ...............3-2712. Optional condition setting mode .........3-2913. Input data mode .................................3-3114. Controller software download mode...3-32
3.4 Alarm display and back-up function ............3-333.4.1 Alarm list...............................................3-333.4.2 Back-up operation at sensor malfunction...3-34
3.5 Back up Battery...........................................3-36
*Diffirences from standard model service manual (TR01-09C) are marked with ☆
☆
☆
☆
☆
☆
☆
☆
☆
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 2
-
3
7.10 Piping diagram ............................................7-57.11 Electric wiring pilot lamps and monitoring
circuit...........................................................7-67.12 Fuse protection table...................................7-77.13 Schematic wiring diagram (Connector type
terminal board and rechargeable battery) ...7-97.14 Stereoscopic wiring diagram (Connector type
terminal board and rechargeable battery) ...7-107.15 Schematic wiring diagram (Connector type terminal
board, temperature recorder and dry battery). ..7-117.16 Stereoscopic wiring diagram (Connector type terminal
board, temperature recorder and dry battery) .....7-127.17 Schematic wiring diagram (Screwed cramp
type terminal board, temperature recorder anddry battery) ................................................7-13
7.18 Stereoscopic wiring diagram (Screwed cramptype terminal board, temperature recorder anddry battery) ................................................7-14
8. OPTIONAL FUNCTIONS MANUAL...................8-18.1 Electronic temperature recorder....................8-2
8.1.1 Standard type .........................................8-28.1.2 Rechargeable battery type .....................8-4
8.2 Electronic controller.......................................8-58.2.1 Special operation 1.................................8-58.2.2 Special operation 2.................................8-98.2.3 Special operation 3...............................8-228.2.4 Special controller setting .....................8-268.2.5 Setting temperature and operation mode
(with Partial frozen mode).........................8-308.2.6 Defrost interval .....................................8-318.2.7 G-SET operation 1 ...............................8-328.2.8 G-SET operation 2 .................................8-328.2.9 Valve mode ..........................................8-338.2.10 Dehumidification control .....................8-358.2.11 Manual check selection mode.............8-398.2.12 F.PTI specification ...............................8-408.2.13 Rechargeable battery...........................8-42
8.3 Control box..................................................8-438.3.1 Installation of personal computer receptacle
and spare fuse in the control box .........8-438.3.2 Cable clamp bracket 1..........................8-448.3.3 Cable clamp bracket 2..........................8-45
8.4 USDA transportation.....................................8-468.4.1 Type of USDA sensor/receptacle .........8-468.4.2 Initial setting .........................................8-468.4.3 USDA sensor calibration ......................8-468.4.4 USDA transportation requirement ........8-468.4.5 USDA report required by USDA local officer...8-46
8.5 TransFRESH................................................8-488.6 Special service port ......................................8-50
8.6.1 Collection of refrigerant ........................8-508.6.2 Attaching and removing of manifold gauge...8-50
8.7 Pressure gauge............................................8-52
☆
4.2.5 Suction modulation valve .....................4-164.2.6 Drier......................................................4-174.2.7 Solenoid valve ......................................4-184.2.8 Discharge pressure regulating valve ....4-194.2.9 Check valve..........................................4-194.2.10 High-pressure switch (HPS) ...............4-204.2.11 Low pressure transducer (LPT)..........4-204.2.12 High pressure transducer (HPT) ........4-214.2.13 Air-cooled condenser and evaporator ...4-214.2.14 Fusible plug ........................................4-214.2.15 Liquid/moisture indicator ....................4-224.2.16 Evacuation and dehydrating...............4-23
5. OPTIONAL DEVICES.........................................5-15.1 Electronic temperature recorder....................5-1
5.1.1 Standard type .........................................5-15.1.2 Rechargeable battery type .....................5-3
5.2 USDA transportation .....................................5-45.2.1 Type of USDA sensor/receptacle ...........5-45.2.2 Initial setting ...........................................5-45.2.3 USDA sensor calibration ........................5-45.2.4 USDA transportation requirement ..........5-45.2.5 USDA report required by USDA local
officer......................................................5-45.3 TransFRESH.................................................5-6
6. TROUBLESHOOTING........................................6-16.1 Refrigeration system and electrical system...6-16.2 Alarm codes on electronic controller ...........6-136.3 Troubleshooting for automatic PTI (J-code)...6-176.4 Diagnosis based on the recording chart......6-196.5 Emergency operation ..................................6-22
6.5.1 Emergency operation of controller .......6-226.5.2 Short circuit operation of controller.......6-236.5.3 Opening adjustment of electronic
expansion valve....................................6-256.5.4 Opening adjustment of suction modulation
valve: ....................................................6-266.5.5 Automatic Back up for supply/ return air
temperature sensors ............................6-277. APPENDIX..........................................................7-1
7.1 Standard tightening torques for bolts ............7-17.2 Standard tightening torque for flare nut.........7-17.3 Resistance of motor coil and solenoid valve coil ...7-17.4 Standard tightening torque for electronic
expansion valve coil(EV)...............................7-17.5 HFC134a, temperature-vapor pressure
characteristics table ......................................7-27.6 Temperature conversion table and temperature sensor
(SS/RS/DSS/DRS/RSS/RRS/EIS/EOS/SGS/AMBS)characteristics table.............................................7-3
7.7 Temperature conversion table and temperaturesensor (DCHS) characteristics table..................7-4
7.8 High pressure transducer characteristics table ..7-47.9 Low pressure transducer characteristics table...7-4
☆
☆
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 3
-
4
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 4
-
5
CONTENTS1. NAMES OF COMPONENTS ……………………………………………7
1.1 Outside…………………………………………………………………71.2 Inside …………………………………………………………………8
2. FROZEN MODE……………………………………………………………92.1 Control state transition and common control ………………………92.2 Operation of magnetic contactor and solenoid valve ……………92.3 Set point temperature and control sensor…………………………102.4 Control ………………………………………………………………10
3. DEFROSTING OPERATION ……………………………………………114. DEHUMIDIFICATION CONTROL SETTING …………………………13
4.1 Description of setting ………………………………………………134.2 Dehumidification control ……………………………………………14
5. BASIC OPERATION OF ELECTRONIC CONTROLLER……………155.1 Control panel…………………………………………………………15
6. OPERATION PROCEDURE ……………………………………………166.1 Operation procedure flow chart ……………………………………16
7. G-SET OPERATION/AUTOMATIC PUMP DOWN OPERATIONMODE/DEHUMIDIFICATION ON-A・OFF SETTING ………………17
8. SETTING FLOW CHART ………………………………………………198.1 Controller initial setting………………………………………………208.2 Optional function setting mode ……………………………………218.3 Initial setting & operation procedure ………………………………23
9. TEMPERATURE SENSOR………………………………………………249.1 Sensor calibration……………………………………………………24
10. AUTOMATIC PUMP DOWN ……………………………………………2511. CABLE CLAMP BRACKET ……………………………………………2612. MANUAL CHECK SELECTION MODE ………………………………2713. ELECTRONIC TEMPERATURE RECORDER ………………………2814. APPENDIX ………………………………………………………………29
14.1 Refrigerant piping diagram ………………………………………2914.2 Schematic wiring diagram…………………………………………3014.3 Stereoscopic wiring diagram………………………………………31
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 5
-
6
CAUTION
RSV DSV BSVHSV ESV ISV
Temperature recorder box cover
Quick-lock lever
Control box cover
Before starting the unit, run the generator.
Securely close the control box cover and the temperaturerecorder box cover (optional).Otherwise, It will cause water entry.
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 6
-
7
Trans FRESH
RSV DSV BSVHSV ESV ISV
1
1. NAMES OF COMPONENTS
1.1 Outside
q Reheat coil solenoid valve (RSV)
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 7
-
8
1.2 Inside
1
3
2
q Reheat coilw USDA Receptaclee Personal computer port receptacle
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 8
-
9
2. FROZEN MODE
2.1 Control state transition and common control
Sol
enoi
dva
lve
Mag
netic
cont
acto
r
Component name Thermostat ON Pump down Thermostat OFFCompressor CC ON ON OFFEvaporator fan. High speed EFH OFF OFF OFFEvaporator fan. Low speed EFL ON ON ONCondenser fan CF ON / OFF※1 ON / OFF※1 OFFLiquid solenoid valve LSV ON OFF OFFEconomizer solenoid valve ESV ON(OFF※3) ON(OFF※3) OFFInjection solenoid valve ISV OFF(ON※2) OFF(ON※2) OFFHot-gas solenoid valve HSV OFF OFF OFFDefrost solenoid valve DSV OFF OFF OFFDischarge gas by-pass solenoid valve BSV OFF OFF OFFSuction modulating valve SMV 100%Electronic expansion valve EV 10 to 100%
Note) ※1: High pressure control※2: Injection control (Refer to Page 2-25 of Service manual)※3: Economizer control (Refer to Page 2-26 of Service manual)
RS > SP + 0.5˚C
LPT< 0kPa
RS : Return air temperature LPT : Low pressure transducerSP : Setting point temperature
Thermostat OFF●Compressor Stop●Evaporator fan Low speed
Pump down●Compressor Running●Evaporator fan Low speed
Thermostat ON (Pull-down range)●Compressor Running●Evaporator fan Low speed (L)
≤≤Continuous compressor running for 2 minutes or more and RS SP - 0.5˚C
2.2 Operation of magnetic contactor and solenoid valve
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 9
-
10
2.3 Set point temperature and control sensorWhen the set point temperature (referred to as SP hereafter) is –10.1˚C(+13.8˚F) or lower, thecompressor is operated ON and OFF, in response to return air temperature.
2.4 Control
- 10℃
SP
SP-0.5℃ A
C
SP+0.5℃
SP-1.0℃ SP-1.5℃
qWhen the control temperature reaches SP-0.5˚C (point A),the compressor and condenser fan are turned off after theliquid solenoid valve has been de-energized and the pumpdown operation has been completed.
wWhen the control temperature exceeds SP+0.5˚C, the compressor,liquid solenoid valve and condenser fan are turned on.However, the compressor runs for at least 2 minutes everytime once it is turned on. Even if the control temperaturebecomes SP-0.5˚C or lower (point C) within 2 minutes afterthe compressor is turned on, the compressor, condenser fanand liquid solenoid valve are not turned off. (2 minutescompressor forced operation)
EV
Receiver
EV:Elec.Exp.Valve HSV:Hot Gas Solenoid ValveLSV:Liquid Solenoid Valve ISV:Injection Solenoid ValveDSV:Defrost Solenoid Valve BSV:Discharge gas Bypass Solenoid ValveESV:Economizer Solenoid Valve LPT:Low Pressure TransducerDPR:Discharge pressure regulator HPT:High Pressure TransducerSMV:Suction Modulation Valve HPS:High Pressure Switch.
FROZEN (Return air < 5˚C)
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 10
-
11
3. DEFROSTING OPERATION(1) Defrosting system
A hot-gas defrost system is adopted in the units; i.e. the high temperature and high pressure refrigerant(hot gas) from the compressor is sent to the evaporator and drain pan for defrosting. Since the evaporatoris heated directly by the hot gas (refrigerant), defrosting can be performed effectively.
(2) Defrosting initiationDefrosting is initiated by the timer or the manual defrost key.However, defrosting is not initiated when frosting on the evaporator can not be detected.
¡Evaporator inlet temperature : 5˚C or higher (during chilled operation)¡Evaporator outlet temperature : 20˚C or higher
qInitiation by timer (Timer is set at the electronic controller, refer to section 3.3.2 of service manual for itsoperating method.)
※1. On-demand defrost selection (12 hours for Frozen mode and 6 hours automatic for Chilled mode)※2. 6 hours when the control temperature is –20˚C or below.
wStarting by MANUAL DEFROST key (on the operation panel sheet key)Press the MANUAL DEFROST key, then press the ENTER/ESC key while indicate "ON" on the LEDdisplay. The manual defrosting operation starts.
eInitiation by frost detectionIf the suction air temperature does not drop at the speed of 0.2˚C/1hr during frozen pull-downoperation, defrosting will be initiated because it is judged that frost is formed on the evaporator.However, if the suction temperature is –20˚C or lower, defrosting will not be initiated. (activated)
(3) On demand defrost settingWhen "99" in long timer is selected, defrosting is activated upon the condition of frost on evaporatorcoil. This function is only for Frozen setting (SP < –10.1 deg C). and starting with 12 hours.(If this function is selected for chilled setting, defrost initiates every 6 hours automatically.)
Procedure:Step 1: After defrost, the controller records compressor running time for 1st 1 hour. (T1)Step 2: When 12 hours passed after defrost, controller records compressor running time for last 1
hour (T2). And the controller check whether the below condition is satisfied.
Step 3: If the above condition is satisfied, defrost is activated.If above condition is not satisfied, defrost is postponed another one hour.After counting up 13 hours, then repeat "Step 2".Defrost will be postponed every one hour until the above condition (Step 2) is satisfied.(Max. 24 hours)
T2 > T1×1.15
Type of timer Defrosting interval set Function
Long timer
3, 6, 9, 12, 24 and 99※1 hours areselectableOptional function setting mode:If the"AUT-INT"is set to ON, the set timemay be changed. For details, refer toinformation in"defrosting interval automaticchanging function"(on page 10).
Regardless of the control temperature,defrosting is initiated according to theselected interval.
Short timer 4 hours※2Defrosting is initiated every 4 hours until thecontrol temperature comes within the in-range after pull-down.
Out-range timer 30 minutes
After the control temperature comes withinin-range once, defrosting will be started 30minutes later if the control temperaturerises out of the in-range.
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 11
-
12
(4)Defrosting Interval Automatic Changing Function
What is the Defrosting Interval Automatic Changing Function?
This is a function to measure the time required for defrosting operation with the "long timer"and,according to the measurement, changes intervals of the defrosting operation. If a lapse of time afterturning OFF the power supply is less than 48 hours, the intervals of defrosting operation immediatelybefore turning OFF the power supply and elapsed time after the completion of defrosting operationwill be maintained. If a lapse of time after turning OFF the power supply is 48 hours or more, theintervals of defrosting operation will be reset to the default value of 6 hours and the elapsed timeafter the completion of defrosting operation will be reset to zero, respectively.
*CautionIf the defrosting operation is performed according to any timer other than the long timer (e.g. shorttimer or out-range timer), the defrosting operation counter will be reset to zero.
Conditions to use the Defrosting Interval Automatic Changing Function:
In order to use the defrosting interval automatic changing function, the following conditions should beboth satisfied.
¡The defrosting interval automatic changing function is set to "ON" while in optional functionsetting mode.For details of the optional function setting, refer to information on page 19.
¡The set temperature falls within the range of -2.0˚C ≦ +6.0˚C.
Details of Defrosting Interval Automatic Changing Function
To make the interval shorter:If defrosting operation for a period of 40 minutes or more is performed consecutively two times ordefrosting operation for a period of 60 minutes or more is performed once, make the defrostingoperation interval shorter by 1 step with the "long timer".
Example:・6-hour interval before change → 3-hour interval after change・12-hour interval before change → 9-hour interval after change
To make the interval longer:If defrosting operation for a period of 20 minutes or less is performed consecutively two times,make the defrosting operation interval longer by 1 step with the "long timer".
Example:・3-hour interval before change → 6-hour interval after change・9-hour interval before change → 12-hour interval after change
Resetting of Contents of Defrosting Interval Automatic Changing Function
If a lapse of time after turning OFF the power supply is 48 hours or more, the intervals of defrostingoperation will be reset to the default value of 6 hours and the elapsed time after the completion ofdefrosting operation will be reset to zero, respectively.
Procedure for counting a period of time during when the power supply is kept OFF
The period of time during when the power supply is kept OFF is counted in increments of 30 minutes.Example: When a lapse of time after the completion of defrosting operation is 5 hours and 29minutes and the interval of defrosting operation is set to 6 hours, if the power supply is turned OFFonce and ON again after a lapse of 47 hours and 59 minutes, counting of a period of time will berestarted by taking the lapse of time as 5 hours (discarding the time less than 30 minutes) to startdefrosting operation 1 hour after the power supply is turned ON.
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 12
-
13
4. DEHUMIDIFICATION CONTROL SETTINGThis unit features the dehumidification function. Therefore, it is necessary to set whether thedehumidification control is to be executed or not according to the cargo to be transferred.
You can set whether the dehumidification control is to be executed or not by operating the displaypanel of controller.
4.1 Description of settingWhether the dehumidification control is to be executed or not is switched over according to the settingof dehumidification control parameter "dHu" under the "7. G-SET operation / Automatic pump downoperation mode / Dehumidification ON-A・OFF setting"
CAUTION1.ON/OFF of the reheating coil and DE-HUMID LED lit/unlit are not
synchronous.2.To apply the humidification control, be sure to set "ON-A".
Dehumidificationcontrol
Setting ofdehumidification
control "dHu"DE-HUMID LED Remarks
To execute ON-A (Applied) ON
Case of the unit without thehumidity sensor
Note) If the following conditionsare both satisfied, thedehumidification controlwill automatically be set to"OFF" (dehumidificationcontrol clearing function).
¡ The "dHU-CAN" is set to ON.¡ 48 hours or more lapsed after
the main unit power supplyturned OFF.
Not to execute off (Not applied) OFF
Note) The dehumidification control clearing function is a function to automatically change thesetting of dehumidification control to OFF if the main unit power supply turns OFF for aperiod of 48 hours or more. The ON/OFF setting of the dehumidification control clearingfunction "dHU-CAN" is made while in optional function setting mode. For details of settingprocedure, refer to information (on page 15). The setting of dehumidification control "dHU"can also be made while in optional function setting mode.
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 13
-
14
4.2 Dehumidification control※If reheat coil (Optional) is equipped:
The unit have dehumidification control by a reheat coil, which is under the evaporator coil.In dehumidification, the Reheat Solenoid Valve (RSV) opens to give high pressurized refrigerant toreheat coil. The "DEHUMID" LED lamp will light up.
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 14
-
15
5. BASIC OPERATION OF ELECTRONIC CONTROLLER
5.1 Control panel
Name and function of each components
q
ty
u
i
w
e
r
o
!0
Operation key
3
1
2
b
– 1 2 – 1 0 – 8 – 6 – 4 – 2
– 2– 3– 4– 5– 6 – 1
S P – 5
O V E R
2
I N R A N G E
H O U R S
D A Y S
1
U N D E R
A L A R MR . H .
S U P P L YR E T U R N ˚C / ˚F
%R H
D E F R O S T I N R A N G E D – H U M I DC O M P .
˚C
˚C
S P + 5
D E C O SD A I K I N E L E C T R O N I C C O N T A I N E R O P E R A T I O N S Y S T E M
① SUPPLY LED (Lights when "supply air temperature" is indicated.)② RETURN LED (Lights when "return air temperature" is indicated.)③ ALARM LED (Lights alarm is generated.)④ R.H.LED (Lights when "relative humidity" is indicated.)⑤ COMP.LED (Lights when the compressor is running.)⑥ DEFROST LED (Lights when the unit is under the defrosting operation.)
⑦ IN RANGE LED (Lights when the control temperature is in range.)⑧ DE-HUMID.LED (Lights when the controller is the
dehumidification control optional.)⑨ Temperature base (Used for the graphic chart indication
on the LCD.)⑩ Time base (Used for the graphic chart indication on the LCD.)
Function of operation key
●MODE Key
Shift from "Current indication mode" G-SET operation." / Automatic pump down mode /
Dehumidication ON-A・OFF setting.
Note: When the dehumidification ON-A・OFF is set to ON, G-Set operating mode will be skipped.
MODE
M
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 15
-
16
6. OPERATION PROCEDURE
6.1 Operation procedure flow chart
S
S
S
I/O ON I/O OFF
I/O
SI/O Unit On / Off key S key Select key
Enter key 8 / Chart key
CHART
CHART
CHART
Difference from
standard model
Difference fromstandard model
Power OFF
Unit OFF
All indicationlight on
(for 3 sec.)
Startingpreparation(for 18 sec.)
※ 1Current
indication(Operation state)
When no power supply
Non operation for 30 sec.
Circuit Breaker ON
Circuit Breaker OFFafter setting change
( OFF when no settig change)
※ 3 Battery mode, Operation Condition Setting with back-up battery (Set Point Temperature˚C / Humidity %, / Defrost Internal)
for 3 sec. for 3 sec. for 3 sec. for 3 sec.
※ 12 ※ 13
※2 Operation Setting (Set Point Temperature˚C, Humidity %, Defrost Internal)
※9 Sensor Indication
※7 Chart Indication
※ 10 Temperature Record Scroll
※ 11 AlarmRecord Scroll
※ 15※ 14 ※ 16
or non operation for 5 min.
or non operation for 5 min.
※G-SET operation (The energy consumption reducing operation)
※4 Dehumidification ON-A・OFF setting
※4 Automatic pump down
F. PTIS. PTIM. CHECK
※17 Logging data can be down loaded even when the power supply OFF, the unit OFF or the unit in operation.
To down load the data during the power supply OFF, press the key for using
the wake-up battery.
OptionalFunctionSetting
BasicFunctionSetting
OptionalConditionSetting
ContainerI.D & TimeSetting
for 3 sec.
MODE
MMODE
M
MODE
M
MODE
M
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 16
-
17
7. G-SET OPERATION/AUTOMATIC PUMP DOWN OPERATIONMODE/DEHUMIDIFICATION ON-A・OFF SETTING
The energy consunption reducing operation during G-SET operation, automatic pump down operationcollecting refrigerant to the liquid receiver and dehumidification ON-A・OFF setting are executed.
Press the key in current indication mode to go to G-SET operation /Automatic pump down operation / Dehumidification ON-A・OFF setting.※ After the automatic pump down is completed, the pump down status is
maintained until the power supply is turned off.
Pressing the key changes the mode between G-SET operation and automatic pump down /Dehumidification ON-A・OFF setting.The set point can be set by using key or key.
Note: When the dehumidification ON-A・OFF is set to ON, G-Set operating mode will be skipped.
MODE
M
MODE
MMODE
M
All indicationlight on
(for 3 sec.)
Startingpreparation(for 18 sec.)
Currentindication
(Operation state)
※1
G-SET operation /Automatic pumpdown operation / DehumidificationON-A•OFF setting.
MODE
M
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 17
-
18
Setting item LED panel LCD panel Setting method
–– –– ––
ON, OFF diSPOFF Select ON by using
or key, and press
the key to determine
the setting.
ON, OFF P down Select "ON" by using
key and key,
and press the key to
determine the setting.
Currentindication mode
G-SEToperation
Automatic pumpdown operation
DehumidificationON-A・OFF setting
MODE
M
MODE
MMODE
M
MODE
M
Note) Refer to the detail of automotic pump down function in the "8.3, (2)" of Service manual.
CAUTION1.To apply the humidification control, be sure to set "ON-A".2.ON/OFF of the reheating coil and DE-HUMID LED lit/unlit are not
synchronous.3.When the dehumidification ON-A・OFF is set to ON, G-Set
operating mode will be skipped.
OFF, ON-A dHu Select "ON-A" by using
key and key,
and press the key to
determine the setting.
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 18
-
19
I/O ON
I/O
Power OFF
Unit OFF
All lights on(for 3 sec.)
Preparation(for 18 sec.)
Circuit Breaker ON
Circuit Breaker OFFafter setting change
( OFF when no setting changed)
for 3 sec. for 3 sec. for 3 sec. for 3 sec.
CASE 2CASE 1
CASE 3 (Refer to 3.8.2 of Service manual)
OptionalFunctionSetting
BasicFunctionSetting
OptionalConditionSetting
ContainerI.D & TimeSetting
PTI
for 3 sec.for 3 sec.
DECOS3: D (C or B or A) SLog. Interval: 30 (or 15 or 60 or 120) SREC SEN: ON (or OFF) SOC-SET: Sing (or Dual) S HP: 10 (or 5) SDISP: OFF (or ON) SCOMP: 100 (or 33) SREHEAT: OFF (or ON) SFA-SEN: OFF (H or L)(DECOS3d only)
Container I.D SController Time
CHARTLS: OFF (or ON) SUSDA 1/2: 2 (or 1) SH001~H006 Sd-1**~d-2** SC/F : C (or F)
USDA: OFF (or 3 or 4) SdHU: OFF (or ON) SAUT-INT: ON (or OFF) SdHU-CAN: ON (or OFF)
8. SETTING FLOW CHARTThis configuration setting flow shall be utilized, when
Case 1) Where USDA cool transportation setting, defrosting interval automatic changing function, ordehumidification control clearing function is required. (Optional function setting)
Case 2) Where an urgent change of container ID to other ID should be made. (Setting of container ID and calendar)
Case 3) Where a new controller is installed for replacement. (Settings of optional function, basicfunction, optional conditions, and input data should be made.)
NOTE 1 : All initial settings are pre-setted, when the unit is delivered. 2 : In case to complete the setting change, CIRCUIT BREAKER shall be turned off
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 19
-
20
8.1 Controller initial setting
Optional function mode
P 19●USDA sensor setting ●Defrosting interval automatic changing
function on/off setting
Basic function setting mode
TR01-09A
Service manual
P 3-27
P 3-28
●Controller type ●Logging interval
●Indication (LED section) light
off function on/off
●FA-SEN
●Data recorder sensor on/off●Power supply
Optional condition setting modeTR01-09A
Service manual
P 3-29
P 3-30
●Chartless function setting ●H001
●H006
●H002
●H005
●H003●H004
Input data mode TR01-09AService manual
P 3-31
P 3-32
lContainer I.D. (No.)
●d1--●d2--●d3--●d-1-●d-2-
Personal computer and controller
Data logged in a personal computer and controller is exchangable.For the details, refer to the "Operation manual for personal computer software".
Controller software download mode TR01-09AService manual
P 3-32
●Dehumidification control on/off setting
●Compressor unload●Reheat coil
●Compressor horse power
●Type of USDA sensor●°C/°F set
●Dehumidification control clearingfunction on/off setting
lController time
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 20
-
21
8.2. Optional function setting modeFollowing functions can be set up.With/Without setting of USDA sensor, With/without setting of cargo temperature, With/Without setting ofdehumidification control, ON/OFF setting of dehumidification control clearing function, and ON/OFFsetting of dehumidification control clearing function
I/O ON I/O OFF
I/O
Power OFF
Unit OFF
All indicationlights on
(for 3 sec.)
Startingpreparation(for 18 sec.)
※ 1Current
indication(Operation state)
Circuit Breaker ON
Circuit Breaker OFFafter setting change
( OFF when no setting changed)
for 3 sec.
Optional Function SettingF. PTIS. PTIM. CHECK
for 3 sec.
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 21
-
22
To set the USDA ON/OFF and CARGO TEMPERATURE SENSOR ON/OFF:Select "OFF (not in use)", "3 (3 USDA probes are in use)", or "4 (3USDA probes and 1 cargo temperature sensor are in use)" on the LEDwhile the LCD displays "USdA".Whenever the or key is pressed, the indication of "OFF" or "3"or "4" is changed.Press the key to determine the setting.Note: When two USDA probes are connected, the setting will bedetermined automatically to "3" (3 USDA probes are in use).
To set the DEHUMIDIFICATION CONTROL:Select "ON" (conducting dehumidifying with humidity sensor) or "OFF"(conducting no dehumidifying) on the LED while the LCD indicates"dHU". Whenever the or key is pressed, the indication of "ON" or"OFF" is changed.
Press the key to determine the setting.
Note : This setting can be changed by key. (Refer to 3-12)
ON/OFF setting of defrosting interval automatic changing function
In order to make ON/OFF setting of the defrosting interval automatic
changing function, when the "AUT-INT" is displayed on the LCD
screen, select ON (Use the defrosting interval automatic changing
function) or OFF (Not use the defrosting interval automatic changing
function) displayed on the LED screen.
Every time the "ON" or "OFF" key is pressed, the display will change.
To determine the setting, press the Enter key.
For the contents of the defrosting interval automatic changing function,
refer to information on page 10.
ON/OFF setting of dehumidification control clearing function
In order to make ON/OFF setting of the dehumidification control
clearing function, when the "dHU-CAN" is displayed on the LCD
screen, select ON (Use the dehumidification control clearing function)
or OFF (Not use the dehumidification control clearing function)
displayed on the LED screen.
Every time the "ON" or "OFF" key is pressed, the display will change.
To determine the setting, press the Enter key.
For the contents of the dehumidification control clearing function, refer
to information on page 19.
M
USDA SENSOR ON/OFF, CARGO TEMPERATURE SENSOR ON/OFF SETTING
DEHUMIDIFUCATIONCONTROL ON/OFF SETTING
S
S
S
S
DEFROSTING INTERVAL AUTOMATIC CHANGING FUNCTION ON/OFF SETTING
DEHUMIDIFICATION CONTROLCLEARING FUNCTION ON/OFFSETTING
Whenever the key is pressed, the display changes.
Turn the power breaker OFF after the setting.
S
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 22
-
23
: Sel
ect k
ey
: Man
ual a
ctio
n: S
key
: E
nter
key
: Con
trolle
r ope
ratio
n
IN
ITIA
LSE
TTIN
Gfo
r4
MO
DES
※13
. Opt
iona
l Fun
ctio
n Se
tting
Mod
e※
14. B
asic
Fun
ctio
n Se
tting
Mod
e※
15. O
ptio
nal C
ondi
tion
Setti
ng M
ode
※16
. Inp
ut D
ata
Mod
eU
SDA
: OFF
(or 3
or 4
)
DEC
OS3
: C
(or b
or a
*1)
CH
ARTL
S :
OFF
(or O
N *5
) S
ET I.
d (C
onta
iner
I.D
)
Pr
ess
for
3 se
cond
s
Circ
uit
Brea
ker
OFF
Circ
uit
Brea
ker
ON
Uni
t Sw
itch
OFF
Uni
t Sw
itch
ON
Pres
s fo
r3
seco
nds
dH
U
: OFF
(or O
N)
USD
A 1/
2 : 1
(or 2
*6)
i.d.-C
REC
SEN
: O
N (o
r OFF
)H
001
: 3H
005
: 3d3
: 1
Set 4
alp
habe
ts
OC
-SET
: Si
ng (o
r dU
AL)
H00
2 : 2
H00
6 : 1
d-1
: 1i.d
-n
'---N
ote
1---
HP
: 10
(or 5
)H
003
: 2d
: 1d-
2 : 1
Afte
r mov
ing
to s
ettin
g ite
m w
ith S
key
,se
lect
the
initi
al s
ettin
g va
lue
with
△ o
r ▽
key
and
dete
rmin
e it
with
Ent
er k
ey.
Key
oper
atio
n1.
Und
erlin
ed fi
gure
s sh
ow th
e va
lue
of th
e m
ost u
sual
set
ting
case
. Act
ually
all
the
setti
ng h
ave
been
set
follo
win
g 3.
8.3
INIT
IAL
SETT
ING
TAB
LE a
t fac
tory
.2.
Whe
n th
e se
tting
cha
nge
is re
quire
d, s
elec
t the
des
ired
setti
ng u
sing
or
k
ey a
nd p
ress
key
to c
onfir
m, a
nd th
en tu
rn c
ircui
t bre
aker
off.
3.W
hen
cont
rolle
r is
repl
aced
from
the
spar
e pa
rts, c
onfir
m th
e m
odel
nam
e fir
st, a
nd th
en s
et a
item
s by
follo
win
g 3.
8.3
INIT
IAL
SETT
ING
TAB
LE
Set 7
num
bers
(num
eral
)
DIS
P :
OFF
(or
ON
*2)
H00
4 : 2
d2 :
1C
/F :
CSE
T I.d
CO
MP
: 100
(o
r 33
*3)
SET
TIM
E
REH
EAT
: OFF
(or O
N *4
)Se
t yea
r, m
onth
& d
ay
Set h
our a
nd m
inut
e
Pres
s fo
r 3 s
econ
dsAl
l Ind
icat
ion
light
ON
(fo
r 3 s
econ
ds)
Star
ting
prep
arat
ion
(f
or 1
8 se
cond
s) T
RIP
STA
RT
SET
TIN
G
in 1
8 se
cond
s※
6. P
TI s
elec
tion
mod
e (fo
r Trip
Sta
rt Se
tting
) 1
. Sel
ect 「
Man
ual C
heck」
with
△ o
r ▽ k
ey a
nd
det
erm
ine
it w
ith E
nter
key
. 2
. Sel
ect T
rip S
tart 「T
S H」
with
△ o
r ▽ k
ey a
nd
set
it to
"0" b
y pr
essi
ng E
nter
key
for 3
sec
onds
.Al
l Ind
icat
ion
light
ON
(fo
r 3 s
econ
ds)
Star
ting
prep
arat
ion
(f
or 1
8 se
cond
s)
All I
ndic
atio
n lig
ht O
N (
for 3
sec
onds
)St
artin
g pr
epar
atio
n
(for
18
seco
nds)
※2.
Ope
ratio
n se
tting
mod
e
OPE
RAT
ION
CO
ND
ITIO
NSE
TTIN
G
Set C
ontro
l Tem
pera
ture
Alar
m F
301
: Non
set
ting
of [C
ontro
l Tem
pera
ture
] E3
03 :
Non
set
ting
of [C
ontro
l Hum
idity
]Se
t Con
trol H
umid
ityif
dHU
is s
et to
ON
if dH
U is
set
to O
N.
E3
05 :
Non
set
ting
of [D
efro
st In
terv
al]
Set D
efro
st In
terv
al.
Ope
ratio
n
Circ
uit B
reak
er :
ON
Uni
t Sw
itch
: ON
Uni
t Sw
itch
: OFF
Uni
t Sw
itch
: ON
Log.
Inte
rv :
30 (o
r 15,
60
or 1
20)
Pres
s fo
r3
seco
nds
SS S S S S S S
SS
SS
S
S
SS
S
SS
S
S
Not
es*5
. Set
ON
for t
he u
nit n
ot e
quip
ed re
cord
er.
*6. S
et 2
for B
lack
rece
ptac
les
of U
SDA
sens
ors.
(
Fact
ory
set 1
is fo
r Gra
y re
cept
acle
s.)
*1. T
he s
oftw
are
of D
ECO
S3d
is in
tech
agea
ble
to D
ECO
S3c,
b.
The
refo
re, m
ake
sure
to re
cogn
ize
the
cont
rolle
r typ
e "d
" or "
c" o
r "b"
at t
he in
itial
se
tting
.
i.e.:
set t
o "d
" for
DEC
OS3
d
set
to "C
" for
DEC
OS3
c
set
to "b
" for
DEC
OS3
b*2
. Set
ON
for t
he u
nit r
eque
sted
"Pan
el L
ED D
ispl
ay L
ight
OFF
" fun
ctio
n.*3
. Set
33
for t
he u
nit L
XE10
D-A
10C
~A10
G in
stal
led
reci
proc
atin
g ty
pe c
ompr
esso
r with
un
load
ing
valv
e.*4
. Set
ON
for t
he u
nit e
quip
ed R
EHEA
T C
oil f
or d
efum
idifi
catio
n co
ntro
l (op
tion)
.
SS S
S S
△ ▽
USD
A : O
FF (o
r ON
)
dH
U
: OFF
(or O
N)
SS
FA-S
EN :
OFF
(or H
or L
)(D
ECO
S3d
only
)
S
8.3
Init
ial s
etti
ng
& o
per
atio
n p
roce
du
re
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 23
-
24
9. TEMPERATURE SENSOR
9.1 Sensor calibration
● Supply and Return air sensor(SS/RS/DSS/DRS)
q Prepare the ice bathw Cut the binding of each sensor and put
them into the ice bathe Turn on the unit and display "Sensor
calibration (CAL)" in "Manual Check" modein 3.9.2.5
r Press the key to calibrate 4 sensors*Be sure to check the ice bath temperatureis 0 degC.
t Controller LED segments display the resultof calibration
1st : Supply air sensor (SS)2nd : Return air sensor (RS)3rd : Data recorder sensor for Supply air4th : Data recorder sensor for Return air
: Sensor accuracy is normal; The readingof the sensor is within 1.0deg C.Offset figure is memorized in order torecord accurate control/recording.
: Sensor accuracy is out of +/-1.0deg C.The sensor shall be malfunction.(Replacement is required.)
1st 2nd 3rd 4th
(Example)
· SS : Normal· RS : Normal
(DSS) · DSS : Abnormal(DRS) · DRS : Abnormal
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 24
-
25
10. AUTOMATIC PUMP DOWNAn automatic pump down system is applied to the unit to prevent the unit operation from extradecreasing of low pressure due to pump down operation or burning of scroll compressor due to closestop valve.(1) Controller operation
Press the key twice to select the pump down mode, then, the LCD indicates "P down".Select "ON" by using key or key, and press the key to start the automatic pump downoperation.
MODE
M
™Controller indication
COMP. DEFROST IN RANGE DE-HUMID.
SUPPLYRETURNALARMR.H.
DISPLAY SELECT G SET G SETMANUAL UNIT
UPSELECTSET
DEFROST ON/OFF
˚C F8
CHERT/ / I/O
SDOWN ENTER/ESC
Pump down mode Pump down completed
COMP. DEFROST IN RANGE DE-HUMID.
SUPPLYRETURNALARMR.H.
DISPLAY SELECTMANUAL UNIT
UPSELECTSET
DEFROST ON/OFF
˚C F 8CHERT/ / I/O
SDOWN ENTER/ESC
DISPLAYON/OFF
DISPLAYON/OFF
•When the pump down operation is ended abnormally, "E201" (pump down malfunction) will be indicated.
•When the pump down operation is completed, the unit becomes stop state.
Presskey to startpump down
Fig. 2
Fig. 1
Current indication mode(Operation condition ndication)
G-set mode(Energy saving setting) ※1
Pumpdownoperation
DehumidificationON-A•OFF setting
MODE
MMODE
MMODE
M
MODE
M
※1: When the dehumidification ON-AoOFF is set to ON, G-Set operating mode will be skipped.
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 25
-
26
11. CABLE CLAMP BRACKETWhen it is operated on the trailer or railway chassis, be sure to fasten the power cable with .cable clamp
CABLE CLAMP
LOOSE
CLAMP
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 26
-
27
12. MANUAL CHECK SELECTION MODEThe LED indicate the values of following items.Compressor operating time, Evaporator fan motor high-speed running current, Evaporator fan motorlow-speed running current, Condenser fan motor running current, Battery life, Horse power, Elapsedtime after trip start, Evaporator fan motor running time, Condenser fan motor running time, Controllersoftware version and sensor calibration.
To indicate the compressor operating time:Press the key while the LCD indicates "CC ✕10H".The operating time is [the value indicated on the LED] ✕10 hours.Pushing the key for 3 seconds sets compressor operating time to 0 (hour).
To indicate the current value of evaporator fan motor high-speed operation:Press the key while the LCD indicates "EFH A", then the LED indicatesthe current value. (Unit: Ampere)
To indicate the current value of evaporator fan motor low-speed operation:Press the key while the LCD indicates "EFL A", then the LED indicates thecurrent value. (Unit: Ampere)
To indicate the current value of condenser fan motor running current:Press the key while the LCD indicates "CF A", then the LED indicates thecurrent value. (Unit: Ampere)
To indicate the elapsed time after trip start:Press the key while the LCD indicates "TS H", then the LED indicates theelapsed time. (Unit: Hours).When the key is depressed for 3 seconds while the elapsed time is indicated,the TRIP START is set, and the elapsed time display is reset to "0" (hour).
To indicate the evaporator fan motor-1 operating time:Press the key while the LCD indicates "EF1 ✕10H".The operating time is [the value indicated on the LED] ✕10 hours.When the key is depressed for 3 seconds while the evaporator fan motor-1operating time is indicated, the evaporator fan motor-1 operating time is reset to"0" (hour).("EF1" stands for the right hand side fan motor seeing from the inside of the container.)
To indicate the evaporator fan motor-2 operating time:Press the key while the LCD indicates "EF2 ✕10H".The operating time is [the value indicated on the LED] ✕10 hours.If the key is depressed for 3 seconds while the evaporator fan motor-2operating time is indicated, the evaporator fan motor-2 operating time display isreset to "0" (hour)."EF2" stands for the left hand side fan motor seeing from the inside of the container.
To indicate the condenser fan motor operating time:Press the key while the LCD indicates "CF ✕10H".The operating time is [the value indicated on the LED] ✕10 hours.If the key is depressed for 3 seconds while the condenser fan motor operating timedisplay is indicated, the condenser fan motor operating time display is reset to "0" (hour).
To indicate the controller software version:Press the key while the LCD indicates "SOFTVER".The value on the LED is the software version.
To calibrate the temperature sensor SS,RS,DSS or DRS ;Press the key while the LCD indicates "CAL".(Refer "5.1 sensor calibration" for more detail.)
COMPRESSOROPERATINGTIME
EVAPORATOR FANMOTOR HIGH-SPEEDRUNNING CURRENT
EVAPORATOR FANMOTOR LOW-SPEEDRUNNING CURRENT
EVAPORATORFAN MOTOR-1OPERATING TIME
CONDENSER FANMOTOR RUNNNINGCURRENT
ELAPSED TIMEAFTER TRIPSTART
CONTROLLERSOFTWAREVERSION
EVAPORATOR FANMOTOR-2OPERATING TIME
CONDENSER FANMOTOROPERATING TIME
SENSORCALIBRATION
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 27
-
28
13. ELECTRONIC TEMPERATURE RECORDER●Temperature record with power supply turned off
When the power supply is turned off, the pen will move to the outer circumference of recording sheetsimultaneously.
Record on the outer circumferencePower supplyis turned off.
Frostin
g record
●Rechargeable batteryThe rechargeable battery is equipped on the electronic temperature recorder.
(Application of rechargeable battery)①Drive of chart②Pen swings up when the main power is turned off (+25˚C is recorded.)
(Specifications of rechargeable battery)・Charge type nickel cadmium battery (7.2V, 600mA)・Model:6N-600AA-2
(Replacement reference)・As reference, 2 to 4 years have elapsed.・Replace the battery if the pen does not swing up to +25˚C when the breaker is turned off.・Confirm the life of rechargeable battery and make sure the internal gear rotating properly
through the rotation check window when the battery was replaced.
P001-028_S/G-A4_LXE10E-A18C,D 2008.02.19 17:40 ページ 28
-
14. APPENDIX
14.1 Refrigerant piping diagram
29
P029-032_S/G-A3_LXE10E-A18C,D 2008.02.18 13:45 ページ 31
-
14.2 Schematic wiring diagram
※ 11
CN2
WHT
RECORDER
SUPPLY
AIRSENSOR
BS4
※ 12
EOS
LIGHT-EM
ITTING
DIODE(D
E-HUM
ID)
TrC
(WHT)SGS
SS (GRN)
CONDENSERFANMO
TOR
BS8
Fu1-6
PT
127128
SERVICE
MONITOR-GREEN(EC6)
UR3 USDA3
174
122121 ES
V
5WH
T
LD6
TrC
155
RRPP
133
3 T2
2
S
(COOL):BLU,(HEAT):RED
SS
106
SMV
LD3
表面
105
BS9
EFH
11WH
T
CFC
34WHT
UCFM
V
35BLK
33RED
W
DF-BLK CABLE
116
HSV115
※ 8
109
CN10
T/FA2-5
Fu
RPP
SCC3
HSV
SUCTIONMO
DULATIN
GVALVE
RECORDER
RETURN
AIRSENSOR
104
HIGHSPEEDE
VAPORATORF
ANCONTACTOR
Ry1-19
WIRING
OFSCC1,2,3
CONTROLTRANSFORMER
LIGHT-EM
ITTING
DIODE(IN
RANGE)
Trans
FRESH,
A2-5
CABLE
※ 6
(BLU)RS
POWERSUPPLY
BOARD(RECORDER)
SCC2
BLK (RED)HPTWHTRED
※ 6
FUSE(250V,5
A)(EC
6)
RRS
PHOTOCOUPLER
EFM1
EFM2
43WHT
EFL
U1V1
U1
V2
39BRN
W1
U2
V1
U2
40YLW
42RED
W1
41BLU
W2
44BLK
V2
EFH
W2
RELAY
CN32
EC1
COMPRESSOR
CONTACTOR
・ LX
E10E-A1
8:NO.1
&2
P+RED
COMPRESSOR
MOTOR
LIQUID
CRYSTALDISPLAY
USDA
SENSOR
・ LXE10E-A3
0:NO.1
&2&3&4
P-BLK
EC6
PCC1,2
EC4
LIGHT-EM
ITTING
DIODE
CFC139 MTP140
171
SCC1-1,-2
EC8
SCC1-2(RED)
PPR1
EC8
EIS (BRN)
※ 5
(HEAT)
※ 11
BS1
POTENTIAL
TRANSFORMER
EC6
EMERGENCY
LIQID
SOLENOID
VALVE
※ 12
RECORDER
CC
RS
BS1-10
BS2
EVAPORATOR
OUTLET
SENSOR
P+RED
PPR1,2
LPT
SERVICE
MONITOR-GREEN(EC1)
CN9
PHASECORRECTIO
NCONTACTOR
EV
LED1
LIGHT-EM
ITTING
DIODE(E
C6)
INJECTION
SOLENOID
VALVE
DATA
RECORDER
RETURN
AIRSENSOR
87
23
15
64
EC5
LIGHT-EM
ITTING
DIODE(D
EFROST)
173
LEDA
BS3
BS6
BAT1
BACK
SID
E
CN8
EC2
※ 8
RETURN
AIRSENSOR
※ 7
REMO
TECOMM
UNICA
TION
DEVIC
E(RTE)
LD-A
LD2
DATA
RECORDER
SUPPLY
AIRSENSOR
※ 9
REMO
TEMO
NITORIN
GRECEPTACLE
SUCTIONGASSENSOR
※ 9
42
id
3
b
8j
6
ag
h
51
7
c
1OPTIO
NAL
SPECIFICATIO
N
SCC3(WHT)
EFH
B
BSV
CT1,2
CN1RECORDER
BOX
CN4
1
CN2
CN5
CN32
CN6
RRS
REC
RSSCN8
RRS
BAT2
RSS
EC7
EC8
FRONT
SID
E
(+)
CN20
PHC
RY
1
PHC
9RY
26
87
RY
CN25
23
RYRY
64
RY4
RYRY
1016
3
1
92
21
3
611
CN22
15RY
CN24
415
RY6
10
CN23
79
175
PHC
RY13
813
RY
5
CN26
8
EC2
712
RY
414
RY
PHC
18RY
75
RYRY
34
19RY 23
RY
CN21
81
NORMAL
POSITION
・ SCC1,2:BEHIND
THECONTROLLER
・ SCC3:CN-C1(TB1)
TB2
A
PC.PO
RTRECEPTACLE
EC1
138 EFL
EFH137 152
CFC
LIGHT-EM
ITTING
DIODE(R
ETURN)
129
HPS130
UR1-3
DISPLAYBOARD(DECOS)
USDA1-3
21
26
51
47
83
PRINTED
CIRCUIT
BOARD
(PT,C
T)
SHORTCIR
CUIT
CONNECTOR
(BLU,BLU)
注意
DSS
RSS
21e
f
SCC2
101
DCHS
EC4
Fu1
EVAPORATOR
FANMO
TOR
CTP
HIGH
PRESSURE
TRANSDUCER
RSV
裏面
LD5
2
LD1
3
(BLU)WHTRED
LPTBLK
BS7
DF+WHT
LIGHT-EM
ITTING
DIODE(A
LARM)
RSV
AMBIE
NTTEMP.SE
NSOR
LD7
COMPRESSOR
THERMALP
ROTECTOR
a
9
TeS1-4
3216
123
7
40
k
1
17
1
Fu6
1
5
3
41
Fu4
CN5
103
35
8
14
j
910
189
47
24
Fu3
3445
4
421
6
d
19
ib
2
22
83
1131
CN2
156
2937
5
Fu1
g
30
CN3
3
7
c
24
2
1
1
5
e
68 33
TB1
h
2
2613
220
3612
43
Fu2
7
36
25
CN-C2
CN4
46
CN-C1
3
CN1
4
Fu5
5
4239
384
2
844
28
f
27
ELECTRONIC
EXPANSIONVALVE
4WH
T
P-BLK
TB1,2
T/F
1B
C
SHORTCIR
CUIT
CONNECTOR
BAT1
CN17
LD-A
CN12
1
CN16
CN14
CN10
CN18
5CN15
3
CN11
CN19
3
A2
HOTGASSOLENOID
VALVE
PUSH
BUTTON
SWITC
H
EV
CONTAINER
REFRIGERATION
UNIT
WIRINGDIAGRAM
C
BATTERY
HPT
113 DSV114
380V
50HZ
400V
415V
440V
60HZ
460V
PCC2
1
154PCC146
145
CM
CN13
COND.M
OTOR
THERMALP
ROTECTOR
EC4COMPRESSOR
DISCHARGESENSOR
10WH
T
※ 10
A5CABLE
T/F
FUSE(250V,1
0A)(TB1)
EISEFL
OPTIO
NALITE
MNO.
EFL
DF+WHT
EC2
ISVDRS
REVERSEPHASEPROTECTOR
151135136 EF
H
EFL
EC3
EC3
注意
1.操作回路(線番号100以降)および、リモ
ートコミニュケーションデバイスには絶
縁試験を行わぬこと。
2.※
1~8は、操作回路(裏面)に接続されてい
ます。
CA
UTI
ON
1. D
O N
OT
AP
PLY
INS
ULA
TIO
N T
ES
T O
N
THE
CIR
CU
IT(O
N W
IRE
No.
100
AN
D
AFT
ER
)AN
D T
HE
RE
MO
TE
CO
MM
UN
ICA
TIO
N D
EV
ICE
.
2. ※
1~8
AR
E C
ON
NE
CTE
D T
O C
ON
TRO
L C
IRC
UIT
(BA
CK
SID
E)
1.主回路(線番号100以降)および、リモート
コミニュケーションデバイスには絶縁試験
を行わぬこと。
2.※
1~8は、主回路(裏面)に接続されています。
CA
UTI
ON
1. D
O N
OT
AP
PLY
INS
ULA
TIO
N T
ES
T O
N
THE
CIR
CU
IT(O
N W
IRE
No.
100
AN
D
AFT
ER
)AN
D T
HE
RE
MO
TE
CO
MM
UN
ICA
TIO
N D
EV
ICE
.
2. ※
1~8
AR
E C
ON
NE
CTE
D T
O M
AIN
C
IRC
UIT
(BA
CK
SID
E)
EC5
※ 2
165
※ 3
5
164
4
※ 1
※ 4
1※ 5
3 1 753171 56RCD(R
TE)
106
101
166
32
SCC1-1(BLU)
CN84
CN81
CN83 LED1
CN82
Fu1
LEDA
EC6 SMV
CONDENSERFANCONTACTOR
117118
ISV
HPS
AMBS
24BLKV CM
CT2
U
CC
22RED23WHT
W
DF-BLK
CB
LD5
EC3 C
N31
LD1
LD2
LCD
LD3
LD7
LD4
LD8
LD6
LD9-12
110
RM
112111 BS
V
172
LOWSPEEDE
VAPORATORF
ANCONTACTOR
POWERPLUG
DRS (BLU,RED)
※ 1
Fu6
173
MTP
BS10
CURRENTT
RANSFORMER
3314
1816
3
23
212
401
31
514
1521
17
G
1
11G
G
34
42
298
6
DC5V
37
DC24V
G1
16
6
17
8
G
1915
24
20
259
9
6
TB1
54
7
32
13
22
CN7
2
2836
7
3018
3
3
382
2019
CN6
10
TeS5
1
1327
12
41110
TeS6
35
G5
397
26
EVAPORATOR
INLETSENSOR
SGS
P REC
e
2k
1USDA2
UR2
CFM
※ 3
BS5
EC1
ESV
172
CN13
CPUBOARD(DECOS)
TB1
RCD
PPR2
TB2
CTP
131132
CFC
144 PCC1
143 PCC
153
2
CONTROLBOX
LD9-12
※ 2
AC
123
126
124
D
125
B RM
119 LSV120
DEFROSTSOLENOID
VALVE
EC7
REHEAT
COIL
SOLENOID
VALVE
ADAPTERBOARD
(PPL)DCHS
RPP CC134
133 155
LIGHT-EM
ITTING
DIODE(R
.H.)
SHEETKEY(DECOS)
PCC1,2
CIRCUIT
BREAKER(30A)
(COOL)
(YLW)EOS
102
LD4
RED
LIGHT-EM
ITTING
DIODE(S
UPPLY)
USDA
RECEPTACLE
DSV
A4CABLE
UR1 USDA1
4
174
※ 10
CT1
RPP
EACH
MODELT
OEQUIP
FOLLOW
INGOPTIO
NS.
SUPPLY
AIRSENSOR
AD
BC
NOTES
1.SCREWTERMINAL
CONNECTOR
TABTERMINAL
OPTIONAL
PARTS
2.()MEANS
DISTINGUISHING
TAPE
COLORAT
ENDFORSENSOR.
3.MO
NITORING
PLUG
CONNECTEDAS
FOLLOW
(FRONT
VIEW)(RM)
A:Earth
B:Compressor
C:Defrost
D:In
range
BAT1,2
CN1
LSV
(-)
A3CABLE
(BLK)AMBS
LCD
21
31 32PCC2
PCC1
T/FFu
※ 7
I/OBOARD(DECOS)
CB
CC
(GRN,GRN)
TERMINAL
BOARD
6WH
T
CN2
CT1
CN11
4EC
5CT2 PT
SHORTCIR
CUIT
CONNECTOR
101
W1W2
E
0V
W3
16224V
U2
104
TrC
24VW U2 160
U1
0V
415V U3U1
0V
163
161
13VGAS
BYPASS
SOLENOID
VALVE
CB
Trans
FRESH,
FUSEA
SSYIN
LINE(2
50V,2A
)
※ 4
LIGHT-EM
ITTING
DIODE(C
OMP)
10WH
T
12WH
T11
WHT
EFM1,2
RCD
DSS (GRN,RED)
ECONOM
IZERSOLENOID
VALVE
HIGH
PRESSURE
SWITC
H
A
LOWPRESSURE
TRANSDUCER
BACK
LIGHT
POWERB
OARD
(DECOS)
PHC
LD8
S
4REDR
5WHT
T BLK
30
P029-032_S/G-A3_LXE10E-A18C,D 2008.02.18 13:45 ページ 32
-
14.3 Stereoscopic wiring diagram
C
C
1 1 9
32
7★
101
C N 5
155
101
E V
T e S 1
T e s 6
11
( B L U , R E D )
42
E F M 1
4143RED
BRN
YLW
BLU
44BLK
3940
WHT
1 2 232
136
TB2.17
3
U 2
BRN
6
4
RED
GRY
C C
24
WHTYLW
22131
RED
23
C M
BLK
C T P
W
U
VH
132
172
C
BLK
1
EC1.CN
15-5
C
B L K
C T 1
( 4 0 0 V )
1 3 0
CN10
EMERGENCY(HEAT)
3
TB1.CN
5-3
※ 5
10
154
1 1 5
T B 1
31
1
★
T e S 3
★
41
A
BLK
R S V
10A
C
C N 8 3
11
3 2 A
151
BRN
0V
31A
P C C 1
I S V
T e S 4
C C
42
5
C N 8 1
6
138
( B R N )
C M
UR3 USDA3
162
W 2
★
S
TB1
1 2 1
C
21 3
4 64 44 24 03 83 63 43 23 02 8
2 62 42 22 01 81 61 41 21 08654
1 2 9
U 1
31
34
T B 1
B
TB1
T r c
C
13V
1
D C H S
※ 4
TB1.CN
5-2
S G S
105
E
CH P S
C T 2
152
C
E C 1B A T 1
7
RED
P C C 2
U 2
C N 8 2
C N 8 4
H S V
153
39
1 1 1
PPR1
4
E C 5
160
( Y L W )E O S
400V
UR1 USDA1
11
D S V
172
1 0 2
1 1 8
A
USDA2UR2
22C
(GRN,G
RN)
24V
5WHT
153
44
5
T e s 5
0V
10
2
TB2.17
3
BAPPR2
C
TB2.17
4
TB2.17
2
1 2 0
3
C N 2 5C N 2 1
1
C N 2 03
C N 2 2
C N 2 6
106
TB2
11C
161
H P T ( R E D )
U 1
T r c
C N 2 3
4 5
※ 5
C B6
140
D R S
11A
1
W H T
★
EMERGENCY(COOL)
B L K
1
W
A 1
V
S
W 1 4U
R T 1 3
A 2
3 1
3 2
★
CN-C1
P + R E D
2
C N 3
TB2.17
4
144
32C
C N 9
2
4
C N 210
C
SMV
143
32A
35
C
W 3
11
2
C N 2
24V
E F H
1 1 6
32C
(注 18)
40
1 1 3
( G R N )S S
※ 3
31C
RCD(RTE)
E C 6
173
※ 1
C
※ 1
R E D
P T
A
1
3
T e S 2
P C C 1
134
146
EC5
A
104
C N 1 C N 2E C 3
T B 1
E C 8C N 3 2
L C D C N 3 1T B 1
3
1
E C 4
(注 18)
R E D
A M B S
EC8CN
11
137
23C
154
T /F Fu
174
B
P T、 C Tボ - ド
E C 2 . C N 2 6 - 3
R E DR R S R S S
RRS
RSS
R R S R S S+-
C N 1
R E CC N 8E C 2 . C N 2 6 - 1
E C 2 . C N 2 6 - 2
E C 2 . C N 2 6 - 4
E C 7B A T 2
2
C N 6
43
1
C N 5
C N 421
C N 3
E C 7
C N 2
EC2.CN
26
W H T
( G R N , R E D )
EC1.CN
15-1
E C 2
RPP133
B S V
TB1.CN
5-4
E I S
0V
W
T A 1S 3 1R
A 23 2VU
139
C F M
BRN
BRN
33WH
T35
BLK
34 171R
ED
T r c
P
EC1.CN
15-3
( B L U )R S
0V
D F - B L K
B
PT-CT
C N 4
5
P+RED
DF+WH
TA5
CABLE
T/F
P-BLK
DF-BLK
A4CABLE
A3CABLE
A2 CABLE
A
★
C
T r c
D F + W H T
24C
C
1 1 4
C
★
151
33
C T位 置
WHT
12C
BLK
1 1 0
★
U 3
T r C
173
C
C F C
123TB
1TB
1
126
TB1
TB1
125
R MDA CB
124
※ 4
B
4
W H T
3 1 AA
31C
1 1 7
145
171
YLW
C N 7
3
155
4 03 93 83 73 63 53 43 33 23 13 02 92 82 72 62 52 42 32 22 12 01 91 81 71 61 51 41 31 21 11 0987654321
BRN
BLK
3940
WHT
44
YLW
41RED
43 42BLU
E F M 2
C B
R
11C
C N 1
10
(BLU,B
LU)
BLU
EC8CN
13
165C N 1 3C N 1 2
C N 1 6
5
C N 1 7C N 1 0
※ 6
3C N 1 9
C N 1 4166
C N 1 5
E C 1
C N 1 8C N 1 1
1
164
CN-C2
L S V
T r c
W 1
※ 3
104
C
RCD
D S S
L P T ( B L U )
12
10
C N 8
( P P L )
32 152
E C 1 . C N 1 5
4 54 34 13 93 73 53 33 12 92 7
2 52 32 11 91 71 51 31 197321
32C
1 0 9
5
E F L
1 1 A
C N 2 4
1 1 2
※ 2
31C
WHT
RED
( W H T )
C N 1
12
11C
174
2 4
A 1S 2 3
A 2V
R T
W 1 4U
1 3
C
※ 2
★
6
E S V
TB2.17
2
U
S
1 4
3 1 A 1
W A 23 2V
R 1 3T
P-BL
K
B
TB1.CN
5-1
B
C N 6
1 0 1
T
S A 1R
3 2 A 2V
3 1
U
T
W
C
163
43
A 2
R
W
S 3 1T A 1
U V 3 2
135
12A
31
B
C T 2C T 1
165
101
164 ※ 6
166
106
E C 1 . C N 1 6
31
P029-032_S/G-A3_LXE10E-A18C,D 2008.02.18 13:45 ページ 33
-
32
P029-032_S/G-A3_LXE10E-A18C,D 2008.02.18 13:45 ページ 34
-
33
掲載機種このサービスガイドは本ユニットの特長及び取扱いについてサービスガイド(サービス編TR01-08B)と異なる事項のみ掲載しております。
NO. 項 目 サービスガイド(サービス編)と異なる点1 コントロールボックス蓋締め付け金具 ワンタッチレバータイプ
4☆ 除湿制御運転 次ページ以降の詳細説明を参照下さい
5☆ モードキー(表示パネル) 次ページ以降の詳細説明を参照下さい
6☆ 設定フローチャート 次ページ以降の詳細説明を参照下さい
☆印の項目については次ページ以降に詳細説明を掲載しています。
2☆ フローズン運転 次ページ以降の詳細説明を参照下さい
3☆ デフロスト運転 次ページ以降の詳細説明を参照下さい
7☆ 自動ポンプダウン 次ページ以降の詳細説明を参照下さい
8☆ ケーブルクランプ金具 装備しています
9☆ マニュアルチェック選択モード 次ページ以降の詳細説明を参照下さい
10☆ 電子式温度記録計 次ページ以降の詳細説明を参照下さい
11☆ TransFRESH 次ページ以降の詳細説明を参照下さい12 通信モデム 装備しています13 温度設定範囲 +30℃~-30℃
14☆ 付図 次ページ以降の詳細説明を参照下さい
P033-060_S/G-A4_LXE10E-A18C,D 2008.02.19 17:43 ページ 33
-
34
目 次3.5.3 バッテリチェック………………………3-363.5.4 バッテリ交換(充電式電池)…………3-37
3.6 パソコンとの情報交換………………………3-383.6.1 データロギング…………………………3-393.6.2 パソコンソフトの構成…………………3-40
3.7 コントローラの点検方法……………………3-423.8 コントローラの交換および初期設定………3-43
3.8.1 コントローラの交換……………………3-433.8.2 コントローラDECOSⅢdとⅢc & Ⅲbとの互換性 ………………………3-443.8.3 LXE10E-1,LXE10E-A & LXE10D スペアーコントローラ
DECOSⅢd,DECOSⅢc & DECOSⅢb交換時のイニシャル設定手順…3-463.8.4 LXE10E-1 & LXE10E-A スペアーコントローラDECOSⅢdの初期設定表…3-473.8.5 LXE10E-A スペアーコントローラDECOSⅢcの初期設定表…3-483.8.6 LXE10D スペアーコントローラDECOSⅢbのイニシャル設定表 …3-49
3.9 PTI(使用前点検)と定期点検 ……………3-503.9.1 点検項目…………………………………3-513.9.2 自動PTI …………………………………3-54
3.9.2.1 PTI選択モード ……………………3-553.9.2.2 S.PTI ………………………………3-563.9.2.3 F.PTI ………………………………3-573.9.2.4 PTI(使用前点検)中のアラーム一覧 …3-583.9.2.5 M.CHECK …………………………3-59
3.10 チャートレス機能 …………………………3-613.10.1 チャート表示機能 ……………………3-613.10.2 Pコード(プルダウンタイム表示)……3-633.10.3 チャートレスコード …………………3-64
3.10.3.1 チャートレスコード一覧 ………3-643.10.3.2 H-コード …………………………3-653.10.3.3 d-コード …………………………3-67
3.11 通信モデム …………………………………3-684.サービスとメンテナンス …………………………4-1
4.1 サービスの方法 ………………………………4-14.1.1 冷媒の回収 ………………………………4-14.1.2 ゲージマニホールドの取付け、取外し …4-14.1.3 自動ポンプダウン ………………………4-34.1.4 冷媒の回収および充填 …………………4-5
4.2 主要機器とメンテナンス ……………………4-84.2.1 スクロール圧縮機 ………………………4-84.2.2 ファンおよび電動機……………………4-124.2.3 PT/CTボード(EC9756) ………………4-134.2.4 電子膨張弁………………………………4-154.2.5 吸入比例弁………………………………4-164.2.6 ドライヤ…………………………………4-174.2.7 電磁弁……………………………………4-184.2.8 吐出圧力調整弁…………………………4-194.2.9 逆止弁……………………………………4-194.2.10 高圧圧力開閉器(HPS)………………4-204.2.11 低圧圧力センサ(LPT)………………4-204.2.12 高圧圧力センサ(HPT)………………4-214.2.13 空冷凝縮器、蒸発器 …………………4-214.2.14 可溶栓 …………………………………4-214.2.15 リキッド/モイスチャーインジケータ …4-224.2.16 真空乾燥 ………………………………4-23
取扱上の注意
・危険…………………………………………………4・警告…………………………………………………5・注意…………………………………………………7
1. 概要 …………………………………………………1-11.1 運転範囲 ………………………………………1-11.2 各部の名称 ……………………………………1-11.3 運転操作 ………………………………………1-2
1.3.1 運転準備と操作 …………………………1-21.3.2 運転中の点検 ……………………………1-31.3.3 停止後の処置 ……………………………1-31.3.4 ベンチレータの開閉 ……………………1-4
2.製品データ …………………………………………2-12.1 主仕様 …………………………………………2-12.2 部品名称 ………………………………………2-2
2.2.1 庫外側 ……………………………………2-22.2.2 庫内側 ……………………………………2-52.2.3 コントロールボックス …………………2-7
2.3 機能部品・保護装置の設定値………………2-122.4 運転圧力と電流値……………………………2-132.5 運転モードと制御……………………………2-17
2.5.1 フローズン運転…………………………2-182.5.2 チルド、パーシャルフローズン運転…2-202.5.3 デフロスト運転…………………………2-222.5.4 除湿制御運転(オプション)…………2-252.5.5 共通制御…………………………………2-26
3.電子式コントローラ ………………………………3-13.1 機能 ……………………………………………3-13.2 電子式コントローラの基本操作 ……………3-3
3.2.1 コントロールパネル ……………………3-33.3 操作方法 ………………………………………3-6
3.3.1 操作方法フローチャート ………………3-63.3.2 各表示モード操作方法 …………………3-9
1.カレント(運転状態)表示モード …………3-92.運転設定モード …………………………3-103.電池モード ………………………………3-114.モード運転 ………………………………3-125.表示(LED部)消灯モード…………………3-146.センサ表示モード ………………………3-157.温度記録スクロールモード ……………3-188.アラーム記録スクロールモード ………3-219.PTIレコードスクロールモード…………3-23
3.3.3 設定フローチャート……………………3-2410.オプション機能設定モード……………3-2611.基本機能設定モード……………………3-2712.オプション条件機能設定モード………3-2913.インプットデータモード………………3-3114.コントローラソフトダウンロードモード…3-32
3.4 アラーム表示とバックアップ機能…………3-333.4.1 アラーム一覧表…………………………3-333.4.2 センサ異常時のバックアップ運転……3-34
3.5 バックアップ用電池…………………………3-363.5.1 仕様………………………………………3-363.5.2 機能………………………………………3-36
☆が付いている項目は、標準サービスガイド(TR 01-08B)と内容が異なることを示しています。
☆
☆
☆
☆
☆
☆
☆
☆
P033-060_S/G-A4_LXE10E-A18C,D 2008.02.19 17:43 ページ 34
-
35
目 次8.2.8 ジーセット運転2 ………………………8-328.2.9 バルブモード……………………………8-338.2.10 除湿制御 ………………………………8-358.2.11 マニュアルチェック選択モード ……8-398.2.12 F.PTI仕様………………………………8-408.2.13 リチャージャブルバッテリ …………8-42
8.3 コントロールボックス………………………8-438.3.1 パソコンレセプタクル、
予備ヒューズのコントロールボックス内装備………8-438.3.2 ケーブルクランプ金具1 ………………8-448.3.3 ケーブルクランプ金具2 ………………8-45
8.4 USDA低温処理輸送 …………………………8-468.4.1 USDAセンサ、レセプタクルの型式…8-468.4.2 初期設定…………………………………8-468.4.3 USDAセンサカリブレーション………8-468.4.4 USDA低温処理輸送要件………………8-468.4.5 USDA事務所要求の書類作成…………8-46
8.5 TransFRESH…………………………………8-488.6 特殊サービスポート…………………………8-50
8.6.1 冷媒の回収………………………………8-508.6.2 ゲージマニホールドの取付け、取外し …8-50
8.7 圧力計…………………………………………8-52
5. オプション…………………………………………5-1
5.1 電子式温度記録計 ……………………………5-15.1.1 標準型 ……………………………………5-15.1.2 リチャージャブルバッテリ型 …………5-3
5.2 USDA低温処理輸送 …………………………5-45.2.1 USDAセンサ、レセプタクルの型式……5-45.2.2 初期設定 …………………………………5-45.2.3 USDAセンサカリブレーション…………5-45.2.4 USDA低温処理輸送要件…………………5-45.2.5 USDA事務所要求の書類作成……………5-4
5.3 TransFRESH …………………………………5-66.故障診断 ……………………………………………6-1
6.1 冷媒システム・電気システム ………………6-16.2 アラームコードの診断………………………6-136.3 自動PTIのトラブルシューティング(Jコード)…6-176.4 記録紙による診断……………………………6-196.5 緊急運転の方法………………………………6-22
6.5.1 コントローラの緊急運転………………6-226.5.2 コントローラの短絡運転………………6-236.5.3 電子膨張弁の緊急運転…………………6-256.5.4 吸入比例弁の緊急運転方法……………6-266.5.5 吹出センサ・吸込センサ緊急運転……6-27
7.付図 …………………………………………………7-17.1 ボルトの標準締付トルク ……………………7-17.2 フレヤナットの標準締付トルク ……………7-17.3 モータコイル及び電磁弁コイルの抵抗値 ……7-17.4 電子膨張弁コイルの標準締付トルク(EVコイル)……7-17.5 HFC134a、温度一蒸気圧特性表 ……………7-27.6 温度換算表と温度センサ(SS/RS/DSS/DRS/RSS/RRS/EIS/EOS/SGS
/AMBS)特性表 ……………………………………�