LMV-322-IOM_0603

download LMV-322-IOM_0603

of 53

Transcript of LMV-322-IOM_0603

  • 8/10/2019 LMV-322-IOM_0603

    1/53

    Visit our website at www.sundyne.com

    02.09.02E, 06/03

    Effective: June 2003

    Supersedes: 10/00

    SUNDYNE LMV 322 Pump

    Installation & Operation Manual

  • 8/10/2019 LMV-322-IOM_0603

    2/53

    DESCRIPTION

    WARRANTY

    USING THIS MANUAL (ICONS USED)

    i INTRODUCTION TO THE SUNDYNE PUMP

    ii SAFETY PRECAUTIONS

    iii CRITICAL START-UP CHECKLIST

    INSTALLATIONINSPECTION

    STORAGE

    SUCTION AND DISCHARGE PIPING

    SEAL ENVIRONMENTAL CONTROL SYSTEM

    GEARBOX HEAT EXCHANGER

    BASEPLATE AND MOUNTING

    DRIVER AND COUPLING

    PIPING CONNECTIONS

    LUBE SYSTEM

    DESCRIPTION

    LUBRICATING OIL SYSTEM

    OPTIONAL LUBE OIL SYSTEM AUXILIARIESOIL PRESSURE

    STARTUP

    START-UP PROCEDURES

    PUMP CONTROL DURING START-UP

    SERVICING

    GEARBOX OIL LEVEL

    OIL PRESSURE

    GEARBOX OILAND FILTER CHANGE

    SEAL LEAKAGE

    ANTIFRICTION BEARINGSDRIVER

    COUPLING

    GEARBOX LUBRICANT RECOMMENDATIONS

    OPERATION AND CONTROL

    FLEXIBLE COUPLING INSTALLATION AND SERVICING

    MAINTENANCE

    DISASSEMBLY/INSPECTION AND REASSEMBLY OF THE PUMP

    DISASSEMBLY/INSPECTION AND REASSEMBLY OF THE GEARBOX

    PARTS LIST

    GENERAL

    RECOMMENDED SPARES

    GEARBOX EXCHANGE

    REPAIR KITS

    ORDERING REPLACEMENT PARTS

    CROSS-SECTIONAL ASSEMBLY DRAWING

    TROUBLESHOOTING

    Page 2 Visit our website at www.sundyne.com 02.09.02E, 06/03

    PAGE

    4

    5

    6

    6

    7

    88

    8

    8

    8

    9

    9

    9

    9

    10

    10

    10

    1011

    13

    13

    14

    15

    15

    15

    15

    15

    15

    15

    15

    16

    17

    19

    23

    23

    30

    41

    41

    41

    41

    41

    41

    42

    50

    TABLE OF CONTENTS

  • 8/10/2019 LMV-322-IOM_0603

    3/53

    Page 3Visit our website at www.sundyne.com02.09.02E, 06/03

    Sundyne Corporation 2000 All Rights Reserved

    DESCRIPTION

    ILLUSTRATIONS

    FIGURE 1. SEAL PORT IDENTIFICATION

    FIGURE 2. SERVICE CHECK POINTS

    FIGURE 3. LMV-322 LUBE OIL SCHEMATIC

    FIGURE 4. HEAT EXCHANGER MOUNTING

    FIGURE 5. LUBE OIL SPECIFICATIONS

    TABLES

    TABLE 1 FALK COUPLING SPECIFICATIONS

    TABLE 2 THOMAS COUPLING SPECIFICATIONS

    TABLE 3 PUMP AND GEARBOX TROUBLESHOOTING

    TABLE 4 MECHANICAL SEAL TROUBLESHOOTING

    PAGE

    10

    10

    11

    12

    16

    20

    21

    50

    52

  • 8/10/2019 LMV-322-IOM_0603

    4/53Page 4 Visit our website at www.sundyne.com 02.09.02E, 06/03

    WARRANTY

    Sundyne Corporation warrants to Buyer for a period of twelve (12) months from thedate of being placed in service (but not to exceed eighteen (18) months after thedate of shipment) that the equipment at the time of shipment will be free fromdefects of design, material and workmanship. If any defects or malperformance occurduring the warranty period, Sundyne's sole obligation shall be limited to alteration,repair or replacement at Sundyne's expense, F.O.B. Factory, of parts or equipment,which upon return to Sundyne and upon Sundyne's examination prove to bedefective. Equipment and accessories not manufactured by Sundyne are warrantedonly to the extent of and by the original manufacturers' warranty. Sundyne shall notbe liable for damage or wear to equipment caused by abnormal conditions, vibration,failure to properly prime or to operate equipment without flow or caused bycorrosives, abrasives or foreign objects. THE FOREGOING WARRANTY IS EXCLUSIVE

    AND IN LIEU OF ALL OTHER WARRANTIES, WHETHER EXPRESSED OR IMPLIEDINCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANYPARTICULAR PURPOSE. In no event shall Sundyne be liable for consequential orincidental damages.

    COPYRIGHT

    All rights reserved. No part of this publication may be reproduced, stored in a retrievalsystem or transmitted in any form or by any means, electronic, mechanical,photocopying, recording or otherwise without the prior permission of SundyneCorporation.

    1999 Sundyne Corporation

  • 8/10/2019 LMV-322-IOM_0603

    5/53Page 5

    ICONS USED IN THIS MANUAL

    The following icons (symbols) are used to indicate specif

    types of information.

    It is important to recognize the meaning of these symbol

    because danger to personnel or damage to equipment ma

    occur, if cautions are not heeded

    .

    Good ideas to use. A reminder to do something

    Equipment use alert. Unless you follow thes

    procedures correct ly, the equipment may b

    damaged.

    Safety alert. Failure to follow these procedure

    can endanger the safety of you or o thers.

    E lec t r i ca l hazard. Fai lu re to fo l l ow thes

    procedures can endanger the safety of you o

    others.

    USING THIS MANUAL:

    This manual is part of the final data package for your

    Sundyne LMV centrifugal pump. This manual explains

    procedures for the Sundyne pump, including how to:

    install it, maintain it, service it, troubleshoot problems

    and order parts. In addition to this manual, the final data

    package includes: drawings, Sundyne specification

    sheet with test performance curves, test data, inspection

    data, material certificates if required, driver, coupling and

    auxiliary equipment information.Information that may be required regarding

    performance, alterations, or detailed technical data

    which is not included herein, may be found in the

    specification sheet and parts list accompanying the unit,

    or may be obtained from your Sundyne representative.

    Custom-made auxiliary equipment cannot be shown in

    this manual. Refer to the outline drawing for specifics.

    Al ways re fe rence th e pump se ri al num ber in any

    communication with the factory.

    All dimensions are provided in English units followed by

    SI units in parenthesis.

    Figures and item numbers: parenthetical numbers

    included in the text correspond to item numbers on the

    illustrated figures. The item number of a part is based

    on the part's function, and the correct spare part can be

    ordered for any generation pump even if the component

    parts do not appear the same as presented in this

    revision of the Instruction Manual.

    NOTES:

    LMV = Line Mounted Vertical Pump

    Visit our website at www.sundyne.com02.09.02E, 06/03

  • 8/10/2019 LMV-322-IOM_0603

    6/53

    safety shoes shall be worn. When testing the

    equipment, hearing protection is highly recommended

    if noise levels exceed 85 dB during an eight (8.0) hour

    period. Chemical resistant gloves shall be used if

    chemical use is required (see Chemical Use below for

    additional information). If chemicals have warnings

    regarding fumes and/or dust/mists, a dust mask

    respirator shall be worn as a minimum.

    When selecting one piece of PPE to be used with

    another, consider the compatibility between them. For

    example, safety glasses should not interfere with the

    seal from hearing protection. Be sure to clean the PPE

    after each use.

    Use of Forkl i f ts: Al l forkli ft drivers must have a

    current recognized license. If using a forklift, first

    ensure that the lift is in a safe operating condition.

    Electrical Safety: During installation, service, or

    repair ensure all electrical sources are off and it is safe

    to operate on the equipment. A recognized Lock-

    out/Tag-out program should be followed - Locks and/or

    tags should be provided warning employees that theequipment is being installed, serviced, and/or repaired.

    Once the work is complete, the person installing the

    lock and/or Tag shall remove it following your

    company's procedure for Lock-out/Tag-out and inform

    others of start-up.

    Testing Equipment: Persons in the immediate area

    shall be warned when a test is to be performed.

    Tools: Tools shall be insulated from electrical shock.

    Ensure all tools are clean and free of oil and the

    insulation is not damaged in any way.

    Chemical Use: Any chemicals to be used shall be

    accompanied by a relevant material safety data sheet

    (MSDS), in accordance with your government

    legislation. If applicable, chemical proof gloves shall

    be used. An eye wash station (or equivalent) should be

    available in the event of injury. Should any hazardous

    or flammable chemicals have passed through the

    equipment a complete decontamination of the

    equipment is required.

    Fall Protection: When working over six feet from the

    ground, fall protection is required.

    Machine Guards: Guards shall remain in place on all

    equipment. Only during maintenance/repair can the

    guards be removed, and prior to start-up, the guard

    must be replaced.

    Lock-out/Tag-out Guidelines:Follow Your Company's Lock-Out / Tag-Out

    Procedure When Servicing Sundyne Pumps.

    02.09.02E, 06/03

    i. INTRODUCTION TO THE SUNDYNE

    PUMPThe Sundyne LMV pump has a single stage, with an

    integral gearbox. It 's purpose is to increase the

    pressure of a continuous flow fluid by applying

    centrifugal action. Sundyne LMV Pumps are most

    commonly used in HPI, CPI, and Boiler Feed

    applications. They are also used in refineries,

    petrochemical plants, and power generation plants.

    Within these facilities, Sundyne Pumps are used in

    high head, low to medium flow processes.

    Sundyne LMV Pumps offer industrial quality in a

    compact unit that is simple to maintain. It provides

    high-energy performance and competitive efficiencies.

    For detailed specifications of Sundyne LMV Pumps,

    see the specification sheet and bill of material or

    consult Sundyne Corp. For the primary components,

    reference the Pump and Gearbox section. For more

    information about additional custom equipment for the

    basic Sundyne LMV Pump product, see the brochure

    that accompanies this manual.

    ii. SAFETY PRECAUTIONS

    Safety Warning

    Sundyne Corporation manufactures centrifugal pumps

    to exacting International Quality Management System

    Standards (ISO 9001) as certified and audited by

    Lloyd's Register Quality Assurance Limited. Genuine

    parts and accessories have been specifically designed

    and tested for use with these products to ensure

    continued product quality and performance. As

    Sundyne Corp. cannot test all parts and accessories

    sourced from other vendors, incorrect design and/orfabrication of such parts and accessories may

    adversely affect the performance and safety features

    of these products. Failure to properly select, install or

    use authorized Sundyne pump parts and accessories

    is considered misuse, and damage or failure caused

    by misuse is not covered by Sundyne's warranty.

    Addi tional ly, modification of Sundyne products or

    removal of original components may impair the safety

    of these products and their effective operation.

    Suggested Safety Instructions:

    During installation, maintenance, or repair operations

    of a Sundyne pump, systems for safety shall be

    applied before the commencement of work. Failure to

    take responsibility for safety may lead to injury of

    operator or others.

    Personal Protective Equipment (PPE): Safety

    glasses with side shields, as a minimum, shall be

    worn by all personnel install ing or performing

    maintenance or repair on the equipment. If equipment

    is over 15 pounds (7 kg) and is to be manually lifted, or

    if pallet jacks or forklifts are to be used, steel-toed

    Visit our website at www.sundyne.comPage 6

  • 8/10/2019 LMV-322-IOM_0603

    7/53

    iii . CRITICAL STARTUP CHECKLIST

    Know Your Machine:

    Before servicing and starting up the Sundyne LMV

    pump, carefully review the specification sheet, the

    outline drawings, performance curves, and this

    instruction manual. It is important you become familiar

    with the pump configuration before starting and

    operating the pump.

    Driver Instructions :Carefully follow the installation and starting instructions

    provided by the manufacturer of the driver. This is

    included in the final data package.

    Auxi liaries:

    1. Check the utility connections.

    2. Verify that the auxiliary piping conforms to

    Sundyne's drawings.

    3. Verify the connections of the switches, the

    instruments, and their settings.

    4. Calibrate all measurement equipment (Flow meters,

    Current or Ampere meters, Pressure meters, etc.).

    Environmental Control System:

    Install a system to control the environment of the seal,

    if required.

    Pressurized Fluid Loop:

    Pressurize double seal buffer loop or external seal

    flush, if required, prior to admitting fluid into pump

    casing.

    Check Driver Rotation:

    Rotation must be in the opposite direction as the arrow

    stamped or cast on the pump casing. Pump rotation iscounterclockwise, while motor rotation is clockwise.

    Gearbox Servicing:

    Fill gearbox within 1/4 inch (6.4 mm) from top of oil

    level sight glass with lube oil which conforms to the

    specification in figure 5. Where applicable, operate

    auxiliary lube pump to fill heat exchanger and filter.

    Add oil as necessary through fill fitting until oil level

    stabilizes in sight glass. The gearbox alone requires

    approximately four and one-half U.S. quarts (4.25

    liters).

    Starting Pump:

    Start pump with suction valve completely open while

    throttling discharge valve, to bring pump to design

    operating point.

    Heat Exchanger:

    If a heat exchanger for the gearbox is installed, adjust

    the cooling flow to keep the temperature of the

    gearbox sump at 140-160F (60-71C).

    Checks:

    Check total head, flow rate, and power consumption

    against pump specification sheet. Power consumption

    should not exceed the maximum shown on the pump

    specification sheet. Check that specific gravity

    viscosity and NPSH are in accordance with

    specification sheet. These conditions will significantly

    alter performance of the pump.

    Process Conditions:

    Do process conditions; suction pressure, suction

    temperature, discharge pressure, agree with

    specification sheet information? Check with you

    Sundyne representative if you must test or run a

    different fluid/specific gravity than shown on the

    specification sheet.

    Auxi liary Lube Pump:

    If you have an auxiliary lubrication pump, unlock the

    electrical circuit and start it in the "hand" position

    Check for oil leaks and recheck the oil level.

    Piping Connections:

    Are the following bolted/threaded connections tight:

    1. Pump flange bolts?

    2. Seal environment piping and port connections?3. Cooling water connections to heat exchanger (i

    applicable)?

    4. Gearbox oil drain plug?

    5. Pump case drain plug?

    Page 7Visit our website at www.sundyne.com02.09.02E, 06/03

  • 8/10/2019 LMV-322-IOM_0603

    8/53Page 8 Visit our website at www.sundyne.com 02.09.02E, 06/03

    Inspection

    Upon receipt of Sundyne equipment, check for any

    damage which may have occurred during shipment.

    Notify the carrier and Sundyne promptly if damage has

    occurred.

    The input shaft may not turn freely due to seal drag

    and speed increasing gear meshes; however, if

    rotation is "bumpy", this would indicate some disorderor damage and requires investigation for cause.

    Storage

    If the pump is not to be installed immediately, it should

    be protected from exposure to moisture and dust.

    Shipping covers installed at the factory (for casing

    flanges and seal ports) must be kept securely in place.

    Storage instructions provided by the driver (motor or

    turbine) manufacturer should be observed.

    Long-Term Storage

    Certain long-term storage considerations should

    be met for any Sundyne pump which will not be

    operating for a period of time exceeding six months

    from date of factory shipment. This action will ensure

    minimum corrosion damage to the gearbox and fluid-

    end components. Because of storage location and

    other unknown site factors beyond our control,

    Sundyne will not accept any liability for damage to the

    equipment during the storage period, nor does

    Sundyne guarantee the quality of the equipment

    during and after the storage period.

    To ensure the original quality of the Sundynepump prior to commissioning after storage, all

    components must be inspected by an authorized

    Sundyne service engineer. Any components not of

    Sundyne manufacture (except mechanical seals) must

    be inspected by that particular submanufacturer's

    authorized service personnel. The cost of such

    service personnel and any component replacement

    will be at the purchaser's expense.

    Factors which affect the quality of an uninstalled

    Sundyne pump are the humidity/temperature and the

    chemicals in the atmosphere surrounding theequipment. The method employed for long-term

    storage should prevent the humidity/temperature and

    airborne chemicals from making contact with the

    internal components of the equipment.

    When the equipment is to be stored in strong chemical

    environments or near salt water, protection should be

    executed immediately upon receipt of the equipment.

    Following are the Sundyne recommended long-term

    storage procedures:

    1. Indoor, climate controlled building (maintains

    constant temperature and humidity).

    2. Inert gas purging of component internals.

    3. Oil flooding of gearbox internals.

    4. Desiccant bags.

    Because long-term storage of equipment is of ahighly critical nature, it is recommended that Sundyne

    be contacted to provide more details on the above

    procedures.

    Suction and Discharge Piping

    1. The suction line should be clean and a strainer

    should be installed to protect the impeller from

    damage by mill scale, welding slag, or other foreign

    particles during initial startup.

    2. All piping must be supported independently of the

    pump. The piping should always line up with the pumpflanges. Never draw the piping into place by the use

    of force at the f langed suction and discharge

    connections as this may impose excessive strains on

    the unit.

    3. The piping, both suction and discharge, should have

    no unnecessary elbows, bends, and fittings, as they

    increase friction losses in the piping. The size of pipe

    and fittings should be selected carefully and be

    sufficient to keep the friction losses as low as practical.

    4. The use of elbows near the suction flange should be

    avoided. When used, elbows should be long radius.

    A straight pipe run of at least ten times the pipe

    diameter is desirable between an elbow and the

    suction flange.

    5. Suction pipe should never be of smaller diameter

    than the pump suction inlet.

    6. Block valves (both suction and discharge) are

    recommended to isolate the pump during shutdown, to

    minimize process leakage during the shutdown

    condition and to prevent possible reverse rotation due

    to back- flow through the pump.

    SEAL ENVIRONMENTAL CONTROLSYSTEM

    1. For the seals used with the Sundyne LMV pump,

    always maintain the environment shown on the

    specif ication sheet for your unit. For some

    arrangements and applications, you may need a buffer

    system to control the seal environment. For many

    applications, you can obtain a standard system from

    the factory. Make sure that the system is installed

    properly and that the ports are open or plugged, as

    INSTALLATION

  • 8/10/2019 LMV-322-IOM_0603

    9/53Page 9Visit our website at www.sundyne.com02.09.02E, 06/03

    applicable. Always be sure to leave port 1 free to drain

    leakage from the gearbox oil seal and vent the

    process seal, otherwise oil could contaminate the

    outboard seal or allow process seal leakage into the

    gearbox. This port can be attached to a flare line, but

    should not have back pressure in excess of 5 psi (34.5

    kPa).

    2. A liquid buffer system is used with double and

    tandem liquid seals. The buffer liquid is introduced into

    port 2, allowed to flow through the seal cavity, and out

    of port 7.

    3. Buffer flow should be 0.5 to 3.0 GPM (1.9 to 11.6

    Liters/min) with an inlet temperature of 60 to 120F

    (16 to 49C) and inlet pressure as indicated on the

    specification sheet.

    4.The buffer liquid may require cooling prior to

    returning to port 2. Otherwise, heat generated by seal

    friction will build up in the buffer, resulting in shorter

    seal life.

    GEARBOX HEAT EXCHANGER

    1. The standard heat exchanger is a shell and tube

    water-cooled type.

    2. Cool water should be provided at 150 psig (11

    kg/cm2) maximum pressure. Coolant flow should be

    controlled to maintain a gearbox sump temperature

    between 140F to 160F (60C to 71C).

    3. The optional air cooled heat exchanger should be

    controlled to maintain the same gearbox sump

    temperature as above.

    NOTE:

    Refer to the outline drawing in the LUBE SYSTEM

    section for heat exchanger mounting configuration.

    The assembly should not be rearranged without

    consulting the factory. THE HEAT EXCHANGER

    IS NEVER MOUNTED HIGHER THAN THE

    GEARBOX MANIFOLD.

    A inch socket head pipe plug in the filter

    manifold is required when using the gearbox heat

    exchanger. (See figure 4.) This plug is omitted

    when the heat exchanger is not used.

    4. For more detail refer to the appropriate section onLUBE SYSTEM.

    BASEPLATE MOUNTING & GROUTING

    NOTE: The installation should provide clearance on

    either side for removal and service. Overhead

    clearance must be provided for lifting out the driver

    or gearbox assembly.

    1. A rigid concrete mounting base is recommended for

    all installations. The concrete foundation should have

    minimum deflections and freedom from resonan

    frequencies in the operating range of the equipmen

    being supported. The flanged base shall be secured in

    position by 7/8" diameter bolts. The bolts shall be

    installed in the foundation per the Installation Drawing

    with sufficient length to protrude 1/4 inch (6.4mm

    above the nut.

    2. The baseplate, if used should be leveled prior to

    grouting. Grout shall set for a minimum of forty eigh

    (48) hours before tightening the foundation bolts, o

    set for the minimum time suggested by the

    manufacturer of the grout.

    DRIVER AND COUPLING

    1. Drivers are normally shipped separately from the

    gearbox and pump. When a splined interconnecting

    shaft is supplied, this shaft must be lubricated at each

    end with one tube (5cc) of antifretting compound

    (Sundyne Part Number MP01AA10). Also available

    are solid shaft drivers coupled to the gearbox with a

    flexible coupling. See appropriate Section fo

    SERVICING the coupling.

    2. Spline driven units do not require alignment.

    Lock-out starting switch on driver prior to working on

    coupling. You should review and know you

    company's Lock-out / Tag-out procedure prior to

    working on energized equipment.

    PIPING CONNECTIONS

    Drain lines from the seal housing ports may be

    necessary. Refer to the outline drawing for port usage.

  • 8/10/2019 LMV-322-IOM_0603

    10/53Page 10 Visit our website at www.sundyne.com 02.09.02E, 06/03

    PORT

    1

    2

    5

    6

    7

    DIRECTION

    OF DRIVER

    ROTATION

    DIRECTION

    OF IMPELLER

    ROTATION

    TOP VIEW OF PUMPDESCRIPTION

    SEAL DRAIN

    SEAL DRAIN SINGLE SEAL

    OR BUFFER FLUID IN

    (DOUBLE OR TANDEM SEAL)

    SEAL FLUSH

    SEAL FLUSH

    SEAL DRAIN SINGLE SEAL

    OR BUFFER FLUID OUT

    (DOUBLE OR TANDEM SEAL)

    Figure 1. Seal Port Ident ification

    PUMPDRAIN

    DIRECTION OF DRIVER ROTATION

    CAUTION PLATE

    REMOVE COVER AND OBSERVE DRIVER SHAFT

    ROTATION- MUSTBE SAME AS THATSHOWN BY

    ARROW ON PLATE ON TOPOF GEARBOX

    HOUSING (DRIVER AND PUMPROTATION INOPPOSITE DIRECTION)

    VISUALLYCHECK OILHERE. ALSO

    CHECK OILTEMPERATURE HERE

    PORTS 2 & 7

    CHECK ELECTRICALCONNECTIONS

    HERE

    LUBE PRESSURE GAGE PORT

    FILL-VENTFITTING AND

    CAP(ADD GEARBOX OIL

    HERE)

    EALFLUSH

    ORTS 5 & 6

    GEARBOX OIL

    FILTER

    SHAFT

    SEALVENT

    PORT

    SUCTION DISCHARGE

    Figure 2. Service Check Points

  • 8/10/2019 LMV-322-IOM_0603

    11/53Page 11Visit our website at www.sundyne.com02.09.02E, 06/03

    between 140F to 160F (60C to 71C)

    Approximately one hour may be required to stabilize

    temperature. See Figure 4.

    The oil filter is a disposable pleated paper elemen

    type. Gearbox oil and filter should be changed every

    six months. See Figure 5 for oil specifications.

    LUBRICATING OIL SYSTEM

    INCLUDING REMOTE SKID MOUNTED

    SYSTEMS

    The oil used in Sundyne gearboxes must meet the

    specif ications presented in Gearbox Lubrican

    Recommendations (see Bulletin 40.2.04). In general

    an ISO viscosity grade 32 oil will meet these

    specifications. Before using any oil, you should verify

    its properties by consulting its manufacturer. Failure to

    use the proper gearbox lubricant will void the warranty

    No other additives are recommended.

    OPTIONAL LUBE OIL SYSTEM AUXILIARIES

    1. Lube Oil Priming Kit

    This prelube system is optional on LMV-322 pumps

    The kit consists of a motor driven posit ive

    displacement pump, check valve, gauges, and

    necessary piping. To start pump, operate the prelube

    DESCRIPTION

    The integral Sundyne lube oil system consists of the

    following major components: gearbox sump, main

    lube pump, oil heat exchanger and oil filter. Oil is

    taken from the sump by the lube pump, then passed

    through internal passages to an externally mounted

    manifold through the heat exchanger, then through the

    filter, and back into the gearbox to the bearings. After

    passing through the bearings, the oil drains back to thesump.

    The gearbox sump holds approximately four and one-

    half U.S. quarts (4.25 liters) of oil, not including

    auxiliary piping and heat exchanger. The oil level

    should always be maintained within the black circle in

    the sight glass. DO NOT overfill gearbox, as this will

    cause excessive foaming and overheating.

    The main lube pump is a constant displacement gear

    type pump directly driven by the input shaft. The lube

    pump includes a relief valve plate supported by a

    spring under the input shaft.

    The standard heat exchanger is a shell and tube water

    cooled type mounted on the gearbox manifold. Cold

    water should be provided at 150 psig (11 kg/cm2)

    maximum pressure. See the specification sheet for

    cooling water requirements. Coolant flow should be

    controlled to maintain a gearbox sump temperature

    Figure 3 LMV-322 Lube Oil Schematic

    LUBE SYSTEM

    Pressure Gage

    Filter

    Optional Heat

    Exchanger

    Internal Lube Pump

    Temperature Gage

    High Speed Bearing

    High Speed BearingLow Speed Bearing

    Low Speed Bearing

    NOTE: WHEN GEARBOX HEAT EXCHANGER

    IS REQUIRED, THE OIL PASSES THROUGH

    THE HEAT EXCHANGER BEFORE IT IS

    FILTERED.

    Sump

  • 8/10/2019 LMV-322-IOM_0603

    12/53Page 12 Visit our website at www.sundyne.com 02.09.02E, 06/03

    pump at least 30 seconds with a minimum of 5 psig

    (0.35 kg/cm2) indication prior to starting the main

    driver. (If oil piping has been drained, several minutes,

    operation is suggested to allow trapped air to bleed

    from the system.)

    The prelube pump is to shut down only after main

    driver is at full operating speed. Do not operate the

    prelube pump continuously when the main pump is

    running.

    2. REMOTE HEAT EXCHANGER

    Some large water cooled and all air cooled heat

    exchangers are mounted away from the gearbox.

    Except for packaged units, the interconnecting piping

    is the purchaser's responsibility. The heat exchanger

    MUST be mounted lower than the oi l manifold;

    otherwise, air pockets may be present in the lube oil

    lines at start-up, causing oil starvation at the bearings.

    Equivalent length of piping and fittings must not

    exceed 20 feet (6 m), using a minimum of inch (18

    mm) I.D. tubing or pipe. If greater pipe lengths are

    required, pipe diameter must be increased accordingly.

    3. GEARBOX SUMP HEATER

    A sump heater is required when ambient temperatures

    may fall below the temperature at which the gearbox

    oil becomes too viscous for proper lube pump

    operation. Both steam and electric sump heaters are

    available. The lube oil priming kit MUST be operated

    to circulate oil around the heater when the main drive

    motor is not running.

    OIL PRESSURE

    Depending upon the bearing configuration and the

    characteristics of the lube oil used. The gearbox

    internal lube pump will maintain oil pressure between

    45 and 60 psig (3.2 and 4.2 kg/cm2) during normal

    operation. The gearbox should never be operated with

    less than 10 psig oil pressure.

    Figure 4. Heat Exchanger Mounting

    A 1/4 INCH SOCKET-HEAD PIPE PLUG IN THE

    FILTER MANIFOLD IS REQUIRED WHEN USING

    THE GEARBOX HEAT EXCHANGER. THIS PLUG

    MUST BE REMOVED WHEN THE HEAT

    EXCHANGER IS NOT USED.

    THE HEAT EXCHANGER INSTALLATION IS A

    SUNDYNE CORP. ASSEMBLY AND SHOULD NOT

    BE REARRANGED. THE HEAT EXCHANGER IS

    NEVER MOUNTED HIGHER THAN THE FILTER.

    GEARBOX MOUNTED

    HEAT

    EXCHANGER

  • 8/10/2019 LMV-322-IOM_0603

    13/53Page 13Visit our website at www.sundyne.com02.09.02E, 06/03

    c) On units with an auxiliary lubrication pump

    operate the pump for a few minutes to remove

    trapped air. Vent any high points to assure

    complete fill. Add more oil to maintain the

    proper level. Adjust the relief valve on the

    auxiliary pump to provide 25 psi (1.76

    kg/cm2)oil pressure to the system.

    d) The auxiliary lubrication system should be

    operated for at least 5 seconds before startingthe main pump driver. Pressure switches and

    time delays can be used if automatic star

    sequences are desired.

    e) After the start of the main pump driver, oi

    pressure is supplied by the internal gearbox

    lube pump. An increase in oil pressure should

    be observed.

    7. Turn on the cooling water to the lubrication system

    heat exchanger. Adjust cooling to maintain oi

    temperature in the sump to 140F - 160F (60C

    71C).

    Start-up sequence

    1. Start the auxiliary oil pump, if provided.

    2. Pressurize the seal buffer system, if provided.

    3. Open the pump suction valve 100%.

    4. Open the seal vent port, either #5 or #6 to vent air.

    5. Open the pump discharge valve 25%.

    6. Start the main pump motor and observe the flow

    rate and discharge pressure.

    7. Adjust the discharge valve for pump operation

    within the recommended flow limits.8. Shut down the auxiliary oil pump within two

    minutes of main motor start-up.

    Never start or operate the pump against a closed

    discharge valve. Always check to ensure tha

    the d ischarge va lve i s open to des ign

    conditions.

    9. On units with heat exchangers, once the gearbox oi

    temperature has stabilized, adjust the cooling wate

    flow until the oil sump temperature is 140F-160F(60C-71C). Maximum recommended temperature

    is 180F (82C ). Recommended sett ing fo

    temperature switches are alarm at 180F (82C

    and shut down at 200F (93C).

    STARTUP

    Refer also to the Critical Startup Checklist in

    this manual.

    If a Sundyne supplied control panel is to be used with

    the Sundyne LMV Pump, use the control panel

    recommended start-up procedure in addition to the

    steps below. Before starting the LMV Pump, complete

    the following procedure in the order in which the steps

    are provided herein.

    Run-In of the Pump: If the pump(s) is to be run-in

    under conditions which are considerably different from

    those that the unit is designed for (such as type of

    liquid, suction pressure, flow rate, etc.) Sundyne

    should be consulted to insure that the run-in conditions

    are compatible with the pump.

    Preparation for unit start-up

    1. Make sure that the driver has been serviced as

    recommended by the manufacturer.

    2. Install a suction strainer to protect the pump fromdebris. After start-up, verify that the strainer is not

    clogged, reducing suction pressure. A suction

    pressure gage is recommended for this purpose.

    Clean the strainer as required.

    3. If a buffer fluid, or an external seal flush is required,

    this system should be commissioned prior to

    admitting process fluid into the pump. This is

    required to flush contaminants from the seal

    chamber and to lubricate the seals.

    4. For double seal configurations, the buffer system

    must be pressurized to the pressure specified onthe Sundyne Specification Data Sheet prior to

    pressuring the pump with process fluid. Failure to

    do so can result in reverse pressurization of the

    primary seal, contamination of the buffer system,

    and malfunction of the primary seal.

    5. Vent the seal cavity through port #5 or #6.

    6. Fill the gearbox with clean lubricating oil through the

    fill and vent fitting. Use oil conforming to the

    specifications in Figure 5. The capacity of the

    gearbox is approximately 4.5 quarts (4.25 liters).

    a) On units without an auxiliary lubrication pump,

    remove the oil filter, fill it 50% full and reinstall.

    Remove the heat exchanger, fill it and the

    piping 100% and reinstall. Fill the gearbox to

    the top of the maximum line on the sight glass.

    b) Jog the main drive until oil pressure is

    observed on the pressure gauge. This should

    occur by the second or third jog of 2-3

    seconds duration.

  • 8/10/2019 LMV-322-IOM_0603

    14/53Page 14 Visit our website at www.sundyne.com 02.09.02E, 06/03

    PUMP CONTROL DURING START-UP

    Refer to the Section on "OPERATION AND

    CONTROL" for basic instruction. Also refer to the

    Sundyne Pump Control Bulletin (01.09.07E) for

    additional information on pumps operating in parallel

    and series.

    SINGLE UNITS

    1. Start pump with the suction valve open whilethrottling the discharge valve to bring the pump to the

    design flow operating point.

    2. If the process fluid is near boiling, a seal cavity vent

    back to the supply vessel may have to be opened to fill

    the pump with liquid.

    PARALLEL OPERATION

    1. Check valves must be placed in the discharge

    piping of each pump to prevent back-flow.

    2. An individual pump minimum flow bypass loop witha control valve should be installed between the pump

    discharge and the check valve. The bypass loop

    should either be cooled or routed back to the suction

    vessel.

    3. Start first unit as described above for single units.

    4. Start second unit on bypass and maintain flow.

    Open discharge valve on second unit and maintain the

    design flow of both units. It is preferable that the units

    not operate at their peak head capability.

    5. Separate f low controls on each pump arerecommended and provide a lower minimum flow

    range than can be achieved by pressure control.

    NOTE

    If an on-line spare pump is started while the main

    pump is running, this is considered parallel

    operation. This condition could result in the spare

    pump dead heading if the bypass loop is not

    available. Catastrophic pump failure could result

    from operation in a dead headed condition!

  • 8/10/2019 LMV-322-IOM_0603

    15/53Page 15Visit our website at www.sundyne.com02.09.02E, 06/03

    Driver: Inspect the driver to make sure that it performs

    according to the manufacturer's specifications.

    Coupl ing: Inspect the coupling according to the

    manufacturer's specifications.

    Never operate the pump without first checking the

    coupling guard.

    A pump wit h a miss ing or inco rr ec tl y ins ta lled

    coupling guard could cause serious or fatal injury.

    GENERAL REQUIREMENTS

    To increase the operating life of your pump and keep it

    in good operating condition, you should inspect and

    service it regularly. See figure 2 for check points.

    Measure all of the operating parameters documented

    in the specific maintenance procedures and log your

    measurements. Make sure that all major equipment,

    such as lubricating pumps, heat exchangers, and

    instrumentation, perform according to themanufacturer's recommendations. Whenever you find

    a deviation from specifications, identify its source

    immediately, and take any corrective steps that are

    required to bring the unit into manufacturer's

    specifications.

    Regular Maintenance

    Gearbox Oil: Check the level of the oil in the gearbox

    immediately before and after initial start-up, and

    regularly while the pump is running. Be sure to keep

    the level of the oil within the design limit. You can add

    oil while the pump is running.

    DO NOT OVER FILL THE GEARBOX. This can

    cause damage to the internal components.

    Oil Pressure: The correct oil pressure from the main

    pump of the gearbox depends on the configuration of

    the bearings and the characteristics of the lubricating

    oil used. In the normal operation, the oil pressure

    supplied to the gearbox should be between 18-60 psig

    (124-413 kPa). Recommended limits are 15 psig (103

    kPa) decreasing alarm and 10 psig (69 kPa)

    decreasing shutdown.

    Changing the Gearbox Oil and Filter: Change the oil

    in the reservoir and the oil filter elements every 6

    months. Sundyne recommended synthetics may go for

    one year maximum before an oil change is required.

    Seal Leakage: Check the seal ports regularly.

    Excessive leakage is dependent on process liquid, but

    considered as approximately one pint per day. If

    persistent excessive leakage is present, consider the

    use of a double or tandem seal configuration with a

    buffer fluid.

    Anti -Fri ct ion Bearings: Antifriction ball bearings on

    the gearbox low speed shaft should be replaced after

    three years, or whenever the unit is being overhauled.

    Care must be exercised to ensure that the correct

    replacement bearings are installed. Incorrect

    replacement bearings will jeopardize mechanical

    integrity of the unit. Replacement bearings should be

    purchased from Sundyne to ensure proper quality and

    fit.

    SERVICING

  • 8/10/2019 LMV-322-IOM_0603

    16/53Page 16 Visit our website at www.sundyne.com 02.09.02E, 06/03

    Figure 5 Recommended gearbox lube oil specifications

    The lubricant chosen must be compatible with gearbox elastomers, Viton and Buna N. Any oil that contains an inert

    additive such as PTFE, molybdenum disulfide or silicon should not be used in Sundyne gearboxes.

    USE OF LUBRICANTS CONTAINING INERT ADDITIVES WILL VOID THE PRODUCT WARRANTY.

    Sequence 3 25/0 max.

    Sequence 2 50/0 max.

    Sequence 1 25/0 max.

    Foam Limits, ASTM D 892

    at 82 C (180F) after 60 minutes Pass

    at 54 C (130F) after 30 minutes Pass

    Time to 0 emulsion

    Demulsibilty, ASTM D 1401

    Rust Protection, ASTM 665 A & B Pass

    Neutralization Number, Maximum 0.20

    Color, ASTM D 1500 1 to 5

    Viscosity Index 95 min.

    ISO Viscosity Grade 32

    Viscosity, Index 95 Minimum

    Viscosity cST at 100C 5.2 (44 min. SSU @210 F)

    Viscosity cST at 40C 28.8 to 35.2 (150/180SSU @ 100F)

    Flash point, C (F) 204 (400) min.

    Pour point, C (F) -7 (20 max.)

    Gravity, API 28-37

  • 8/10/2019 LMV-322-IOM_0603

    17/53Page 17Visit our website at www.sundyne.com02.09.02E, 06/03

    OPERATION AND CONTROL

    OPERATIONRefer to the Sundyne Pump Control Bullet in

    (01.09.07E) for addit ion information on pumps

    operating in parallel and series.

    While the application of the pump in any particular

    system is not within the scope of this instruction

    manual, the importance of proper operation cannot be

    ignored. Several factors must always be considered.

    The experienced operator will be aware of the effects.

    1.SUCTION CONDITIONS: The most common

    reasons for improper centrifugal pump operation are

    those relating to proper flow of liquid into the impeller.

    To avoid turbulence at the eye of the impeller, the

    suction pipe should be straight for a minimum of ten

    pipe diameters beyond the suction flange. Another rule

    of thumb is that suction piping should be at least one

    pipe size larger than the pump suction flange.

    It is essential that liquid reaching the impeller eye have

    enough vapor pressure to prevent it flashing to a gas

    in the impeller. The result of the liquid flashing iscavitation, a phenomenon which can cause damage to

    the impeller and inducer. Cavitation is noticeable as a

    "pumping gravel" noise in centrifugal pumps. In high

    speed single stage pumps this sound may not be

    discernible. The way to prevent cavitation is to

    maintain suction pressure at a high enough level and

    suction temperatures low enough to maintain Net

    Positive Suction Head available (NPSHa) greater than

    Net Positive Suction Head required (NPSHr) by the

    pumps (See Sundyne Specification Sheet).

    2. MINIMUM FLOW CONDITIONS: Centrifugal

    pumps can also experience vibrations from internal

    f low separations and re-circulation at low f low

    conditions. The operator should be aware of the

    minimum flow recommendations of the manufacturer.

    While a pump can operate with some noise due to

    recirculation without harm to the pump, excessive

    noise and vibration are signs that the pump may be

    subject to damage if operation continues. Noise and

    vibration may be accentuated by resonance in the

    discharge line, especially when a control valve is

    located well down stream from the pump.

    3. ENTRAINED GASES: Entrained gases in the fluid

    will reduce the head and capacity of the centrifuga

    pump. Normally it is considered that two to three

    percent entrainment is limiting. The pump has beenfound to operate very well under adverse conditions o

    gas entrainment. However, the operator should expec

    a reduction in performance.

    4. SYSTEM HEAD CURVE: The flow at which a

    centrifugal pump operates depends upon the point o

    intersection of the system (head) curve with the pump

    characteristic (head versus flow) curve. In order fo

    control to be steady, the system curve must intersec

    the pump characteristic curve at a significant angle

    Examples of satisfactory and unsatisfactory angles o

    intersection are shown on the following diagram.

    NOTE: The curve for pump A has a significant angle o

    intersection with system curves D and E. The system

    curve D could represent a system with the contro

    valve wide open while system E could represent the

    same system but with the throttle valve partially closed

    to reduce flow from flow 1 to flow 2. Pump curve B, on

    the other hand, will provide only flow 2, even with the

    control valve wide open (curve D). When the contro

    valve is partially closed to create system curve E, the

    curve E and the lower pump curve B are nearly

    parallel. The lack of significant angle of intersection

    means that the pump flow is likely to drift aimlessly

    and not respond to control valve position.

    CONTROL

    Proper operation of the Sundyne LMV pump (as with

    any other centrifugal pump) requires that the pump be

    SYSTEM (HEAD)

    CURVES VALVE PARTIALLY CLOSED

    VALVE

    WIDE

    OPENGOOD ANGLE

    OF INTERSECTION

    AD

    B

    E

    12

    HEAD

    FLOW

  • 8/10/2019 LMV-322-IOM_0603

    18/53Page 18 Visit our website at www.sundyne.com 02.09.02E, 06/03

    operated in a range where:

    (1) the system head curve and pump performance

    curve intersect at a significant angle (2) the pump does

    not operate below the minimum flow recommended

    and (3) the pump does not operate "in the break" or

    beyond the maximum capacity recommended. Rule of

    thumb would establish the maximum capacity as 10%

    beyond the design flow.

    It is recommended that flow control rather than

    pressure control always be used with the LMV.Pressure and flow controls both operate by throttling

    the discharge flow. However, flow control devices are

    much more sensitive to the changes in the point of

    intersection of the performance curve with the system

    head curve.

    Minimum flow is determined by the larger of either:

    (1) the amount of flow necessary to prevent damaging

    low flow recirculation (2) the amount of flow necessary

    to prevent excessive temperature rise in the pump

    casing due to low flow recirculation, or (3) in the case

    of pumps operated in parallel the minimum flow that

    will prevent one from dead-heading the other.

    The minimum flow necessary to prevent excessive low

    flow recirculation has been found to be largely a

    function of the system design. The operation of a

    control valve downstream can produce a resonant

    condition which can accentuate recirculation vibration

    to damaging proportions.

    It has been found through experience that the greater

    the distance the control valve is located from the pump

    discharge flange the more severe the effect of this

    vibration.

    If the pump is not operated below minimum flow

    recommendations, temperature rise within the pump is

    unlikely to be a problem. However, if operation at low

    flows becomes mandatory, or if the system causes the

    pump discharge line to be blocked for any period of

    time, a means of maintaining a minimum flow must be

    provided. This can be accomplished by use of either a

    continuous bypass or by a flow controlled bypass. Any

    bypass arrangement must return liquid to the suction

    tank or to a location with similar heat sink capacity.

    Various devices to protect the pump and system are

    available. Devices that monitor vibration, temperature

    or pressure changes can be installed. Consult the

    manufacturer for recommendations.

  • 8/10/2019 LMV-322-IOM_0603

    19/53Page 1902.09.02E, 06/03 Visit our website at www.sundyne.com

    General Information

    (1) If other than Sundyne supplied couplings are used,

    they must be flexible disc or gear type couplings

    capable of tolerating reasonable amounts of parallel

    and angular misalignment, and axial end float. Refer to

    coupling manufacturer's recommendations for

    installation and maintenance.

    Lock out starting switch on driver prior to working

    on coupling.

    (2) Coupling installation for turbine drivers is identical

    to that for motors.

    (3) The gearbox coupling hub will normally be

    mounted at the factory. The driver coupling hub will be

    mounted on all motors and turbines shipped from the

    Sundyne factory.

    Flexible Disc or Grid Type couplings

    (4) If the driver coupling hub is not mounted, the

    following procedure should be used:(a) Measure the distance from the top surface of the

    gearbox hub to the datum face of the driver adapter

    (Figure 6). This will be called the "X" dimension.

    (b) From Table 1 or 2, determine the end gap

    (distance between coupling hubs) for the size of

    coupling provided.

    (c) Subtract the end gap values from the "X"

    dimension to determine the distance from the driver

    datum face to the coupling hub face ("Y" dimension -

    Figure 7). Scribe the shaft to show the "Y" dimension.

    (d) Make sure the coupling hub bore, keyways, and

    shaft are clean, free from burrs, and that the key will fi

    in the keyways. Heat the hub in an oil bath or oven to

    approximately 250F (121C), or more if necessary, so

    the hub will slide onto the motor shaft. Position the

    hub at the scribed line on the shaft and tighten the hub

    key set screw.

    On flexible disk couplings, before the hub is installed

    check to see if it is possible to assemble the coupling

    bolts and washers (Figure 9) from the motor side othe hub when installed. If this is not possible

    assemble the short bolts with bevel washers into the

    hub flange before fitting in onto the shaft.

    (5) Grid Type Coupling Installation Instructions

    (a) The driver adapter has coupling guard plates which

    must be removed and stored while installing coupling.

    The coupling seals should have a light coating of

    grease before installation and assembly. When

    mounting or remounting the coupling hub, for any

    reason, always put the seal ring on the gearbox ordriver shaft first. Then install the coupling hub. The

    coupling will not seal properly if these rings are

    omitted (Figure 8).

    (b) Mount the driver on the driver adapter and tightenthe attaching bolts.

    (c) From Table 1, determine the end gap (distance

    between coupling hubs) for the size of coupling

    provided.

    (d) Using a feeler gauge, check the actual end gap

    (Figure 9) to verify that it is within the limits given in

    Table 1. If it is not, loosen the hub key set screw and

    move the hub up or down until the end gap is within

    limits. Retighten the set screw.

    FLEXIBLE COUPLING

    Figure 6

    Figure 7

    Figure 8 Grid

    Type CouplingDatum Face

    Driver

    Adaptor

    Coupling

    Guard

    Coupling

    Guard

    Screw

    Datum

    Face

    Hub Key Screw

    Gasket

    Lug Up

    Vertical

    CouplingsSeal

    Seal

    Grid

    Cover

  • 8/10/2019 LMV-322-IOM_0603

    20/53Page 20 02.09.02E, 06/03Visit our website at www.sundyne.com

    Figure 9 Grid Disassembly

    Figure 10 Coupling Disassembly

    Table 1 Falk Coupling Specifications

    (e) It is good practice to coat the coupling assembly

    and shafts with grease or some form of protection in

    order to minimize the chance of corrosion.

    (f) Replace the coupling guards and secure them with

    the screws provided.

    Servicing the Grid Type Coupling

    (a) Couplings should be lubricated at least once ayear. Lubricate more often when the coupling is

    exposed to excessive moisture or extreme

    temperatures.

    Remove both lube plugs and insert one grease fitting.

    Fill with grease until excess appears at opposite hole.

    Remove fitting and replace plugs.

    (b) For operation in ambient temperatures of 0 to

    150F (-18 to 66C), grease with the following

    specifications should be used:

    DROPPING POINT - 300F (149C) or higher.

    CONSISTENCY - NLGI #2 with worked penetration

    value in the range of 250 to 300.

    Falk Coupling Size End Gap Cover Bolt Torque

    40T10 0.062 in. (1.57mm) 0.125 in. (3.17mm) 0.188 in. (4.77mm) 100 lb/in (1.15 kg-m)

    50T10 0.062 in. (1.57mm) 0.125 in. (3.17mm) 0.188 in. (4.77mm) 200 lb/in (2.30 kg-m)

    End

    Gap

  • 8/10/2019 LMV-322-IOM_0603

    21/53Page 2102.09.02E, 06/03 Visit our website at www.sundyne.com

    SEPARATION AND RESISTANCE - Low oil separation

    rate and high resistance to separation from

    centrifuging.

    LIQUID CONSTITUENT - Good lubricating properties

    equivalent to a high quality, well refined, petroleum oil.

    INACTIVE - Must not corrode steel or cause swelling

    or deterioration of neoprene.

    CLEAN - Free from foreign inclusions.

    For ambient down to -30F (-34C), a grease with

    worked penetration value of 310-340 should be used.

    For ambients above or below those given, consult the

    Falk Corporation.

    (c) If it should be necessary to disassemble the

    coupling, the following procedure should be followed.

    Remove the cover halves from the coupling. Use a

    round rod (for screwdriver) that will fit into the open

    loop ends of the grid. Begin at the open end of grid

    and pry the grid radially in even, gradual stages,

    proceeding alternately from side to side. See Figure

    10.

    If other than Sundyne supplied couplings are used,

    refer to manufacturer's recommendations for

    maintenance and lubricating procedures.

    Falk Freedom or Thomas Type DBZ Installation

    Instructions.

    (a) The driver adapter has coupling guard plates tha

    must be removed and stored while installing coupling.

    The coupling is shipped with the center assembly

    assembled as shown in Figure 11 (initial view). If it is

    necessary to completely disassemble the cente

    assembly, tie a wire through the bolt holes to maintain

    the order of the disc packs. Be careful to note the

    arrangement of the parts so that the coupling can be

    reassembled with the parts in the same order.

    Figure 11. Flexible Disk Coupling Alignment

    Figure 12

    Figure 13. Final Assembly

    Thomas Coupling Size End Gap Cover Bolt Torque

    Minimum Normal Maximum163 0.876 in. (22.24mm) 0.938 in. (23.81mm) 1.005 in. (25.41mm) 156 lb/in (1.80 kg-m)

    201 0.876 in. (22.24mm) 0.938 in. (23.81mm) 1.005 in. (25.41mm) 300 lb/in (3.46 kg-m)

    Table 2. Coupling Specifications (Thomas Type DBZ)

    End

    Gap

    Initial View

    Note that coupling

    is in alignment.

    Final View

    Bolt

    Nut

    Washe

    Center

    Assembly

  • 8/10/2019 LMV-322-IOM_0603

    22/53Page 22 02.09.02E, 06/03

    (b) Mount the driver on the driver adapter and tighten

    the attaching bolts.

    (c) From Table 2, determine the end gap (distance

    between coupling hubs) for the size of coupling

    provided.

    (d) Using a proper gauge, check the actual end gap

    (Figure 12) to verify that it is within the limits given in

    Table 2. If it is not, reposition the hub up or down until

    the end gap is within limits.

    Generally, the gearbox hub is easier to adjust

    than the driver hub. If the hub does not move

    easily, use a bearing puller and heat the hub.

    DO NOT heat hub any more than is absolutely

    necessary to loosen it.

    (e) Assemble the center assembly to the hubs using

    the bolts, nuts, and washers provided keeping the

    proper order of parts as noted in step (a). (See Figure

    13).

    (f) It is good practice to coat the coupling assemblyand shafts with grease or some form of protection in

    order to minimize the chance of corrosion.

    (g) Replace the coupling guard plates.

    (h) Removal for Maintenance - It may not always be

    possible to remove or install the center disk pack after

    the driver is installed. For easy removal, loosen the

    four lower bolts holding the lower disc pack to the

    gearbox coupling hub. Remove the mounting bolts

    holding the driver adapter to the gearbox. Remove the

    driver, the driver adapter and upper coupling as a total

    assembly. For assembly, follow this procedure inreverse.

    Visit our website at www.sundyne.com

  • 8/10/2019 LMV-322-IOM_0603

    23/53Page 2302.09.02E, 06/03 Visit our website at www.sundyne.com

    STEP 1

    Remove the driver from the gearbox.

    UNITS WITHOUT A FLEXIBLE COUPLING (Shown

    here) - Remove attaching bolts. Lift the driver from the

    gearbox. Remove the interconnecting shaft (110). Removethe old lubricant from the male and female spline areas of

    the interconnecting shaft. Before reassembly, apply 5 cc of

    antifrett ing compound (Sundyne Part Number

    MP01AA100) to each end of the splined interconnecting

    shaft (110).

    UNITS WITH A FLEXIBLE COUPLING - (Ref. figure 21)

    Remove the coupling housing cover plate (116) by

    removing screws (904A). Disengage the input coupling

    (117). Remove hex head cap screws (905J). Lift the

    driver from the gearbox. Remove the coupling housing

    (118) by removing attaching bolts. Remove the coupling

    hub (119) from the gearbox low speed shaft (120). Thecoupling hub is installed with a light press fit and may

    require a puller to remove it.

    The following replacement parts will be required as a result

    of pump disassembly and seal housing removal:

    PART ITEM NO. QUANTITY

    Impeller Tab washer 5 1

    O-Ring Repair Kit -- 1

    Chemical Barrier Gasket 106 1

    (Optional)

    The following procedures apply to all configurations of the Sundyne LMV-322 process pump. Refer to the

    specification sheet to determine your specific pump configuration and optional equipment included.

    Disassembly should be done only to the extent necessary for repair. Parenthetical numbers included in the text

    correspond to item numbers in the parts list section.

    MAINTENANCE

    1. PROCEDURE FOR DISASSEMBLING AND INSPECTING LMV-322 PUMP

    Shown here

    completely

    assembled with

    gearbox and driver.

  • 8/10/2019 LMV-322-IOM_0603

    24/53Page 24 02.09.02E, 06/03Visit our website at www.sundyne.com

    STEP 2

    Remove nuts (914A) from the pump casing studs.

    STEP 3

    Lift the gearbox and seal housing assembly from the

    pump casing. Exercise care not to damage the

    inducer (9) if one is installed. Lay the assembly on its

    side.

    STEP 4

    Bend tab washer (5) to allow inducer (9) or impeller nut

    to be removed.

  • 8/10/2019 LMV-322-IOM_0603

    25/53Page 2502.09.02E, 06/03 Visit our website at www.sundyne.com

    STEP 5

    Prevent impeller (2) from turning.

    Inducer or impeller bolt assembly will loosen by turning

    CW (LEFT-HAND thread)

    During reassembly install a new impeller tab washer

    (5). Fit tabs into the slot of the inducer or impeller bolt.

    STEP 6

    Hold impeller (2), remove impeller bolt assembly (3) or

    inducer (9), inducer stud (10) and tab washer (5).

    STEP 7

    Pry impeller (2) from high speed shaft and remove

    impeller key (4).Caution:

    An induce r or impell er that ha s rubb ed ag ai ns

    surrounding surfaces may be out of balance and could

    result in high speed shaft bearing failure if re-used in

    this condition.

    The impeller and inducer are balanced at the factory

    to less than 0.01 inch-ounces in two planes.

  • 8/10/2019 LMV-322-IOM_0603

    26/53Page 26 02.09.02E, 06/03Visit our website at www.sundyne.com

    STEP 8

    Turn gearbox up side down.

    Remove two 1/2 pipe nipples from seal housing.

    STEP 9

    Remove cap screws (905A).

    Lift seal housing (30) from gearbox.

    STEP 10

    Lift out seal rotating face (51A).

  • 8/10/2019 LMV-322-IOM_0603

    27/53Page 2702.09.02E, 06/03 Visit our website at www.sundyne.com

    STEP 13

    Lift out mechanical seal (60A single) and seal spacer

    (52).

    Note the position of the chamfer on the seal spacer(against the mechanical seal). Oring (936H) is

    positioned against the seal housing.

    See figure 17 for cross-sectional drawing and parts list

    for single seal arrangement.

    O- ring 936H here and on mechanical seal (60A)

    Chamfer side (52) toward mechanical seal (60A).

    Single Seal arrangement shown here.

    Double and Tandem Seal arrangement shown later

    STEP 11

    Flip seal housing over and remove cap screws (905F),

    washers (916B) and throttle bushing (21B).

    Remove thermal barrier gasket (87A).

    STEP 12

    Lift out throttle bushing (21B) and seal retainer space

    (19A).

  • 8/10/2019 LMV-322-IOM_0603

    28/53Page 28 02.09.02E, 06/03Visit our website at www.sundyne.com

    STEP 14

    Flip mechanical seal over carefully inspect the sealing

    surfaces for abrasive particles, excessive seal face

    wear and binding action of the seal face washer.

    Seal repair kits are available for most seals.

    Replace or rebuild faulty mechanical seals. A seal may

    be rebuilt by replacing the seal face washer, wedge ring

    or o-ring, retaining ring, and springs. See specific

    information on seals contained in the data package

    accompanying the pump.

    Replace the seal rotating face (51A) if the wear track isrough or is worn to a depth greater than 0.0002-inch

    (0.005mm).

    Reassemble as shown in STEPS 12 & 13.

    CAUTION:

    A combined to tal of 0.010- inch (0 .25mm) may be

    removed from the surfaces of the pump rotating seal

    face (51A) and gearbox rotating seal face (51D).

    Proceed to STEP 20

    Reassembly

    Insert O ring (936H), seal spacer (52) as shown in

    step 13, followed by lower mechanical seal (60A) face

    side up, with another O ring (936H) on the face side.

    Chamfer side of seal spacer (52) faces the mechanicalseal.

    Align parts and install seal retainer spacer (19A).

    Double Seal Arrangement STEPS 15 and 16STEP 15 Disassembly

    Remove upper mechanical seal (60B), seal rotating face

    (51C), (not shown) seal retaining spacer (19A), seal

    spacer (52) and lower mechanical seal (60A).

    Inspect all parts using step 14 as a guideline.

    See figure 18 for double seal arrangement.

    STEP 16

    Position seal rotating face( 51A)

    Align upper mechanical seal (60B).

    Proceed to STEP 20.

  • 8/10/2019 LMV-322-IOM_0603

    29/53Page 2902.09.02E, 06/03 Visit our website at www.sundyne.com

    STEP 19

    Install seal rotating face (51B).

    STEP 18

    Install seal retaining spacer (19A)

    Tandem Seal Arrangement STEPS 17 THRU 19

    STEP 17 Disassembly not shown

    Remove upper mechanical seal (60B), seal retaining

    spacer (19A), seal rotating face (51B), lower mechanical

    seal (60A), seal spacer (52) and lower shaft sleeve

    (50A).See figure 19 for Tandem Seal arrangement and parts

    list.

    Reassembly is shown here:

    Install lower mechanical seal (50A) rubbing face down.

    O-rings (936H) applied to both sides of seal (50A).

  • 8/10/2019 LMV-322-IOM_0603

    30/53Page 30 02.09.02E, 06/03Visit our website at www.sundyne.com

    STEP 20 ALL SEALARRANGEMENTS

    Install mechanical seal (60B tandem & double) or (60A

    single).

    Install washers (916B) and cap screws (905F); evenly

    tighten and torque per figure 15.

    PROCEDURE FOR DISASSEMBLING INSPECTION AND REASSEMBLY OF THE GEARBOX

    The following replacement items will be required as a result of gearbox disassembly:

    PART ITEM NO. Quantity

    5 cc Tube Antifretting Compound --- 2

    Gearbox Oil Filter 185 1

    Shaft Lip Seal 115 1

    Housing Gasket 105 1

    O-ring Packing(interconnecting shaft) 936M 2

    O-ring Packing(oil seal) 936P 1

    O-ring Packing(lower housing oil passage) 936T 1O-ring Packing(slinger sleeve, outer) 936J 1

    STEP 21 (after disassembly of pump)

    Position gearbox up-side down.

    Remove O-ring (936J) and slinger sleeve (50).

    Remove high spots from shaft (130) and slinger sleeve

    faces (50) so that the seal rotating face will not be

    distorted by the clamping force of the inducer stud or

    impeller bolt.

  • 8/10/2019 LMV-322-IOM_0603

    31/53Page 3102.09.02E, 06/03 Visit our website at www.sundyne.com

    STEP 24

    Remove gearbox seal rotating face (51D).

    Replace or lap the seal rotating face if the wear track is

    rough or is worn to a depth greater than 0.0002-inch

    (0.005mm). Lapped surface to be flat within 0.000020-inch (0.0005mm) and parallel to the back surface within

    0.0002-inch (0.005mm).

    NOTE:

    When installing a new or reworked seal rotating face, be

    sure that the side with a large chamfer on the inside

    diameter is inserted toward the gearbox to clear the

    radius on the shaft shoulder.

    STEP 22

    Remove hex head screws (905L), washers (916K) an

    gearbox mechanical seal (60C).

    Carefully inspect the mechanical seal and sealing surface

    for abrasive particles on the fluid and leakage sides of th

    mechanical seal, excessive seal face wear and bindin

    action of the seal face washer.

    Replace or rebuild faulty mechanical seals. A seal may b

    rebuilt by replacing the seal face washer, O-ring, retainin

    ring, and springs. See specific information on seal

    contained in the data package accompanying the pump

    Seal repair kits are available for most seals.

    Replace the seal rotating face if the wear track is rough o

    is worn to a depth greater than 0.0002-inch (0.005mm).

    CAUTION:

    A combined total of 0.010-inch (0.25mm) may be remove

    from the surfaces of the gearbox rotating faces.

    STEP 23

    Remove O-ring (936K) from high speed shaft (130).

  • 8/10/2019 LMV-322-IOM_0603

    32/53Page 32 02.09.02E, 06/03Visit our website at www.sundyne.com

    STEP 26

    From the inside of the input housing (101B), tap out

    the old shaft seal (115) with a punch or screwdriver.

    Exercise care to avoid damaging the aluminum

    gearbox housing or the low speed shaft.

    NOTE:

    If the housing bore is scratched, apply a light coat of

    oil-proof gasket cement to the outside diameter of the

    new shaft seal.

    STEP 25

    Support the gearbox on blocks.

    Remove screws (909B), washers (916H) and nuts

    (914E).

    Separate input gearbox housing (101B) by insertingprybars into the pry slots at the parting flange.

    STEP 27Remove the high speed shaft (130) from the output

    gearbox housing (101A).

  • 8/10/2019 LMV-322-IOM_0603

    33/53Page 3302.09.02E, 06/03 Visit our website at www.sundyne.com

    STEP 29

    Remove cap screws(905M) and journal bearing (151A)

    from the output gearbox housing (101A).

    STEP 28

    Remove the input shaft (120) from the output gearbox

    housing (101A).

    Inspect radial ball bearings (125C and 125D) for smooth

    rotation, worn outside diameter of the outer race and

    snugness of the inner race on the shaft. Replace if the

    bearing has been in operation for more than one year, if

    rotation is not smooth, or if the outside or inside

    diameter is worn.

    Radial ball bearings should be pressed onto the shaft

    using a press that contacts only the inner race. Bearingdamage will occur by pressing or pulling on the outer

    race. No gap should exist between bearings (125C and

    125D), spacers (123A), gear (122A), and shaft

    shoulders.

    Inspect radial ball bearing contact areas of the input

    shaft (120). If the outside diameter of either shaft

    bearing surface is less than 1.5748-inches (40.00mm)

    install a new shaft.

    STEP 30

    Drive locating pins (918M) flush with the input gearbox

    housing (101B).

  • 8/10/2019 LMV-322-IOM_0603

    34/53Page 34 02.09.02E, 06/03Visit our website at www.sundyne.com

    STEP 33Inspect the inside of bearing liners. If the bearing liner

    inside diameter is more than 3.5460-inches (90.07mm),

    replace the input gearbox housing (101B) or output

    gearbox housing (101A), whichever contains the worn

    liner. Bearing liners are not replaceable in the field.

    STEP 32

    Remove and inspect the upper and lower thrust

    washers (155B and 155A). If metal is smeared into the

    radial lube grooves of the washer face, install a new

    washer.

    When replacing upper thrust washer (155B) apply

    petroleum jelly to the under side to hold the thrust

    washer in place when the input gearbox housing is

    installed.

    STEP 31

    Remove cap screws(905N) and journal bearing (151B)

    from input gearbox housing (101B).

    Inspect the upper and lower journal bearings (151B and

    151A). Replace the bearings if the inside diameter of

    the upper bearing is more than 0.9418-inch (23.92mm)

    or the inside diameter of the lower bearing is more than

    1.5020-inches (38.15mm). Refer to Figure 14.

    Also , if the bear ings show signs of metal pickup,galling, or overheating they should be replaced.

  • 8/10/2019 LMV-322-IOM_0603

    35/53Page 3502.09.02E, 06/03 Visit our website at www.sundyne.com

    LOW SPEED SHAFT AND BEARING LINER CLEARANCES

    UPPER JOURNAL BEARING AND HIGH SPEED SHAFT CLEARANCES

    LOWER JOURNAL BEARING AND HIGH SPEED SHAFT CLEARANCES

    Figure 14 Bearing and Shaft Clearances

    TYPICAL CLEARANCES AT BEARING

    125C AND 125D AND BEARING LINERS

    103C AND 103D

    MINIMUM OUTSIDE DIAMETER

    OF LOW SPEED SHAFT: 1.5748

    INCHES (40.00mm)

    RADIAL BALL

    BEARING

    BEARING LINER

    LOW SPEED SHAFT

    MAXIMUM INSIDE DIAMETER OF

    BEARING LINER: 3.5460 INCHES

    (90.07mm)

    MAXIMUM INSIDE DIAMETER

    OF UPPER JOURNAL BEARING:

    0.9418 INCH (23.92mm)

    MINIMUM OUTSIDE DIAMETER OF

    HIGH SPEED SHAFT AT UPPERJOURNAL BEARING: 0.9368 INCH (23.79mm)

    UPPER

    JOURNAL BEARING

    UPPER

    THRUST WASHER

    THRUST RUNNER

    HIGH SPEED SHAFT

    HIGH SPEED SHAFT

    LOWER

    JOURNAL BEARING

    LOWER

    THRUST WASHER

    MINIMUM OUTSIDE DIAMETER OF

    HIGH SPEED SHAFT AT

    LOWER JOURNAL BEARING:

    1.4960 INCHES (38.00 mm)

    MAXIMUM INSIDE DIAMETER OF

    LOWER JOURNAL BEARING:

    1.5020 INCHES (38.15mm)

  • 8/10/2019 LMV-322-IOM_0603

    36/53Page 36 02.09.02E, 06/03Visit our website at www.sundyne.com

    STEP 34

    Inspect the high speed shaft thrust runner (133B). If it

    shows signs of wear or overheating, it should be

    replaced. The thrust runner is shrunk on the shaft;

    therefore, use a 10-ton hydraulic press or equivalent for

    removal. Inspect the pinion gear before replacing the

    thrust runner.Install a new thrust runner by heating it to 375 - 400F.

    (191 - 205C) and cooling the shaft to about 0F. (-

    18C). The thrust runner should be slipped into place

    rapidly to avoid heating the shaft. No more than 0.001-

    inch (0.02mm) gap should exist between the shaft

    shoulder and the thrust runner.

    STEP 36Inspect the high speed shaft at the lower journal

    (minimum of 1.4960-inches (38.00mm).

    Check for bearing or washer materials on its surfaces. If

    there are signs of overheating or wear to a depth

    greater than 0.001-inch (0.02mm), install a new gear

    and shaft assembly.

    STEP 35Inspect the high speed shaft at the thrust runner and

    journal bearing contact areas. If the outside diameter of

    the shaft is less than 0.9368-inch (23.79mm) at the

    upper journal or if the shaft has bearing or washer

    materials on its surface, or shows signs of overheating

    or wear to a depth greater than 0.001-inch (0.02mm),

    install a new gear and shaft assembly.

    Inspect the spur gear (122A) and pinion gear (132B) for

    pits, chips, gear tooth wear, or excessive wear between

    the gear and shaft. The gears are shrunk onto the

    shafts. A 10-ton hydraulic press or equivalent is required

    for removal. Install a new gear by heating the gear to

    375 - 400F. (191 - 205C.), and cooling shaft to about0F (-18C). The gear should be slipped rapidly into

    place to avoid heating the shaft. No more than 0.001-

    inch (0.02mm) gap should exist between the shaft

    shoulder, gear and bearings.

  • 8/10/2019 LMV-322-IOM_0603

    37/53Page 3702.09.02E, 06/03 Visit our website at www.sundyne.com

    STEP 37

    Check the high speed shaft runout by holding the shaft

    in V-blocks on the journal bearing locations and

    measure the runout on the keyed end of the shaft using

    a dial indicator. The shaft runout must not exceed

    0.001-inch (0.02mm).

    STEP 38

    Remove the lube jets (174C shown and 174D). Clean

    all lube passages with solvent and blow-dry with clean

    air. Clean all other parts thoroughly and lubricate with

    clean turbine oil. Immediately reinstall jets into the

    housings.

    STEP 39

    The lube pump (160) is bi-directional and will provide

    lubrication to the bearings regardless of the direction ofrotation.

    Installation of the pump requires that the 180 recessed

    portion of the lower corner of the bottom stationary plate

    be positioned over the roll pin (918N) in the lower

    gearbox. In the event that the pump is inadvertently

    driven in the wrong direction, the entire lube pump

    assembly will rotate 180 and will continue to function to

    prevent damage to the bearings.

  • 8/10/2019 LMV-322-IOM_0603

    38/53Page 38 02.09.02E, 06/03Visit our website at www.sundyne.com

    STEP 41

    The lube pump is driven by the input shaft. A roll pin in theouter rotating part of the pump fits into a slot in the lower

    end of the input shaft. The pump relief spring (23A) is

    inserted between the pump and input shaft. The correct

    engagement of these parts can be checked by pushing

    downward on the input gear. The input shaft assembly

    should bounce up and down on the relief spring.

    STEP 40

    Insert the pump relief spring (23A) between the lube

    pump and input shaft.

    NOTE: Using an O-ring repair kit, replace all O-rings

    disturbed by disassembly. Tighten bolts and nuts as

    specified in figure 15. Fill the gearbox sump and oil filter

    with clean turbine oil as specif ied in "STARTING"

    procedures of the "INSTALLATION" section. Check for

    freedom of rotation after the pump is completelyassembled.

    GearboxItem No. Location Size Torque Value

    905H Oil Filter Manifold 3/8 - 16 x 1/2 22 - 25 ft-lbs (30 - 34 N-m)

    905L Gearbox Seal 1/4 -20 x 1/2 75 - 80 in-lbs (8.5 - 9.0 N-m)

    905M, N Journal Bearings #10 - 24 x 1 35 - 40 in-lbs (4.0 - 4.5 N-m)

    905T Chemical Barrier Gasket 1/4 - 20 x 5/8 75 - 80 in-lbs (8.5 - 9.0 N-m)

    909B Gearbox Halves 3/8 - 16 x 2 1/2 40 - 45 ft-lbs (54 - 60 N-m)

    --- Sight Glass #8 - 32 x 1/2 20 - 22 in-lbs (2.3 - 25. N-m)

    Pump

    Item No. Location Size Torque Value*3 Impeller Bolt/Inducer 1/2 - 20 36 - 40 ft-lbs (49 - 54 N-m)

    905E Mechanical Seal No. Spacer 1/4 - 20 x 12 95 - 102 in-lbs (11 - 12 N-m)

    905F Throttle Bushing/Mechanical Seal 1/4 - 20 x 12 95 - 102 in-lbs (11 - 12 N-m)

    905G Double Seal with Spacer 1/4 - 20 x 3/4 95 - 102 in-lbs (11 - 12 N-m)

    914A Case Nuts 3/4 - 10 250 - 275 ft-lbs (340 - 370 N-m)

    914A Case Nuts 7/8 - 9 300 - 330 ft-lbs (410 - 450 N-m)

    --- Seal Housing to Gearbox 3/8 - 16 x 1 3/4 35 - 40 ft-lbs (48 - 54 N-m)

    905P Separator 1/2 - 20 x 5/8 95 - 102 in-lbs (11 - 12 N-m)

    *When using PTFE o-rings, allow 30 minutes between repeated torquing for the PTFE to cold flow.

    Figure 15. Torque Values

  • 8/10/2019 LMV-322-IOM_0603

    39/53

    Page 39Visit our website at www.sundyne.com02.09.02E, 06/03

    STEP 43

    Assemble the input housing to the output housing.

    Reseat locating pins (918M).

    Torque cap screws (909B) and nut (914E) per Figure 15

    STEP 42

    Install the input shaft (120) then the output shaft (130)

    into the output gearbox housing (101A).

    Apply a new housing gasket (105) to the parting flange,

    and a new O-ring (936T) to the oil port.

    STEP 44Install a new shaft seal (115) using a special too

    available from the factory. (Tool P/N TO06AA47).

    During reassembly lubricate the lip of the new shaft sea

    (115) and the outside diameter of the input shaft with

    grease or oil.

  • 8/10/2019 LMV-322-IOM_0603

    40/53Page 40 Visit our website at www.sundyne.com 02.09.02E, 06/03

    STEP 46

    Install rotating face (51D), o-ring (936P), gearbox seal

    (60C), washers (916K) and hex head screws (905L).

    Tighten cap screws evenly and torque per Figure 15.

    STEP 45

    Lightly tap the new shaft seal into place. If the lip seal

    tool is not available, tape the keyway of the shaft prior toinstallation of the lip seal. Use caution to prevent

    damage to the seal.

    Reassemble the pump to the gearbox in the reverse

    order to disassembly.

  • 8/10/2019 LMV-322-IOM_0603

    41/53Page 4102.09.02E, 06/03 Visit our website at www.sundyne.com

    GENERAL

    Assemblies, subassemblies and components of the

    Sundyne LMV-322 Process Pump are illustrated in the

    following exploded drawings and cross-sectional

    views. Refer to your Sundyne specification sheet for

    those options applicable to your pump. The

    corresponding parts lists, keyed to each part by item

    number, identify detailed parts by part name, quantity

    and location.

    RECOMMENDED SPARES

    Recommended spares are indicated in the quantity

    column by an asterisk (*) to the specific quantity. A

    double asterisk (**) designates recommended spare

    components of a mechanical seal, which may be

    stocked other than, or in addition to, the entire

    assembled seal. The quantity column and the

    indicated spares recommended are based on support

    of one pump unit.

    The type and quantity of spare parts may vary with

    each application, depending upon equipment location,

    operating conditions, and the type of liquid being

    pumped. An available supply of recommended spares

    provides immediate replacement parts without costly

    downtime and keeps inventory requirements to a

    minimum. You can obtain assistance for planning an

    adequate supply of recommended spare parts from

    your Sundyne representative.

    GEARBOX EXCHANGE

    A gearbox exchange can be arranged for a fixed price.

    A replacement gearbox, completely tested and with a

    full one-year warranty, can be shipped from Sundyne

    to anywhere in the Continental United States within 48

    hours after receipt of order in Arvada.

    REPAIR KITS

    Seal and o-ring repair kits are not illustrated herein

    but may be purchased directly from the factory. The

    use of these kits reduces maintenance time, prevents

    assembly mistakes, simplifies stocking and inventory

    and reduces delivery time.

    ORDERING REPLACEMENT PARTS

    When ordering replacement parts, give the pump

    serial number and list each part by part number as

    shown on the PARTS LIST which is included with each

    pump shipment (preferred method), or list each part by

    item number (as listed in this manual), part name and

    pump model. Specify quantities desired.

    Order parts from your local Sundyne representative o

    directly from Sundyne Corporation at the address on

    the back cover.

    PARTS LIST

  • 8/10/2019 LMV-322-IOM_0603

    42/53

    (920F) KEY

    (120) LOW

    SPEED SHAFT

    (920A) KEY

    (920A)KEY

    (160) LUBE

    PUMP

    (23A) LUBEPUMPSPRING

    (125D)

    RADIAL BALL

    BEARING

    (120) LOW

    SPEED SHAFT

    (122A) SPUR

    GEAR

    (123A)SHAFT SPACER

    (123A) SHAFT

    SPACER

    (123A) SHAFTSPACER

    (125C) RADIAL

    BALL

    BEARING

    (193C) PRESSUREVALVE

    (177) VALVE

    (98) DUST COVER(FOR USE ON

    COUPLED SHAFTONLY)

    *(936M) O-RING

    PACKING (2)

    (115) SHAFTSEAL

    (GEARBOX)*

    (110) INTERCONNECTINGSHAFT

    (186) FILLAND VENT FITTING

    (909B) BOLT (6)

    (916H) WASHER (12)

    (174C) LUBE JET

    (101B) GEARBOXHOUSING (INPUT)

    (918M) PIN (2)

    (905M) HEX HEAD CAP SCREW (2)

    (916AA) WASHER (2)

    (918N) PIN

    (101A) GEARBOX HOUSING (OUTPUT)

    (971A) NIPPLE

    *(185) OIL FILTER (FRAM PH-16)

    (105)HOUSINGGASKET

    (916H) WASHER (6)

    (914E) NUT (6)

    (906B) SOCKET HEAD CAPSCREW (4)

    (191) SIGHT GLASS

    (193) TEMPERATURE GAGE

    (151A) JOURNAL BEARING, LOWER

    (51D) SEAL ROTATING FACE

    (936P) O-RING PACKING*

    (60C) GEARBOX SEAL*

    (916K) WASHER (3)

    (905L) HEX HEAD CAP SCREW (3)

    (174D)

    LUBEJET

    (924G) PIPE PLUG (2)

    (INSTALL ONLY IF OIL

    COOLER IS USED)

    (936T) O-RINGPACKING*

    (916Z)

    WASHER

    (905N)HEX HEAD

    CAP

    SCREW

    (151B) JOURNAL

    BEARING, UPPER

    (155B) THRUST

    WASHER, UPPER

    (133B) THRUST

    RUNNER

    (132B) PINION GEAR

    (920B) KEY (130) HIGH SPEED SHAFT

    (155A)

    THRUST WASHER,LOWER

    (951W)

    NIPPLE

    (943A)

    CAP

    (936K) O-RINGPACKING

    (87A) HOUSING

    GASKET

    BA

    02.09.02E, 06/03 visit our website at www.sundyne.com

    * Recommended Spare Parts

  • 8/10/2019 LMV-322-IOM_0603

    43/53Page 43 02.09.02E, 06/03Visit our website at www.sundyne.com

    Sundyne LMV-322

    Figure 16 Pump and Gearbox Cross Section

    Single Seal Arrangement

    Optional

    Dual Pressurized

    (Double) Seal

    Optional

    Dual Pressurized

    (Tandem) Seal

    Optional

    Internal Centrifugal

    Separator

    Optional

    Inducer

    Note:

    1. Item numbers listed above identify only part location

    and must be used with parts list for specific pump.

    2. A combination of options may be used in a specific unit.

    Refer to instruction manual.

    3. A solid shaft and flexible coupling is used on some units

    instead of splined interconnecting shaft.

  • 8/10/2019 LMV-322-IOM_0603

    44/53Page 4402.09.02E, 06/03 Visit our website at www.sundyne.com

    Figure 17 SIngle Seal Arrangement

    Item Name Part Name Qty. Item Name Part Name Qty.

    19A Seal Retaining Spacer 1 63A - Seal Spring Backup Disc 1**

    21B Throttle Bushing 1 64A - Seal Retaining Ring 1**

    50 Slinger Sleeve 1* 65A - Seal Spring 6**

    51A Seal Rotating Face 1* 68A - Seal Wedge Ring*** 1**

    52 Seal Spacer 1 905F Hex Head Cap Screw 3

    60A Mechanical Seal (Pump Lower) 1* 916B Washer 3

    61A - Retainer & Drive Sleeve Assembly 1 936H O-Ring Packing 3*

    62A - Seal Face Washer 1** 936G O-Ring Packing 1*

    936H O-Ring Packing 3*

    ** Recommended Spare Parts 936J O-Ring Packing 2*

    ** Recommended Seal Space Component Parts 936K O-Ring Packing 1**** Specific to Type 9AB Seal Design

  • 8/10/2019 LMV-322-IOM_0603

    45/53Page 45 Visit our website at www.sundyne.com 02.09.02E, 06/03

    Figure 18 Double Seal Arrangement

    Item Name Part Name Qty. Item Name Part Name Qty.

    19A Seal Retaining Spacer 1 61B - Retainer & Drive Sleeve Assembly 1

    50A Shaft Sleeve (Lower) 1 62B - Seal Face Washer 1**

    50B Shaft Sleeve (Upper) 1* 63B - Seal Spring Backup Disc 1**

    51C Seal Rotating Face 1* 64B - Seal Retaining Ring 1**

    52 Seal Spacer 1 65B -Seal Spring 6**

    60A Mechanical Seal (Lower) 1* 68B - Seal Wedge Ring*** 1**

    61A - Retainer & Drive Sleeve Assembly 1 905F Hex Head Cap Screw 3

    62A - Seal Face Washer 1** 916B Washer 3

    63A - Seal Spring Backup Disc 1** 936G O-Ring Packing 1*

    64A - Seal Retainer Ring 1** 936H O-Ring Packing 3*

    65A - Seal Spring 6** 936J O-Ring Packing 2*

    68A - Seal Wedge Ring*** 1** 936K O-Ring Packing 1*

    60B Mechanical Seal (Upper) 1*

    * Recommended Spare Parts

    ** Recommended Seal Space Component Parts

    *** Specific to Type 9AB Seal Design

  • 8/10/2019 LMV-322-IOM_0603

    46/53

    Page 46Visit our website at www.sundyne.com02.09.02E, 06/03

    Figure 19 Tandem Seal Arrangement

    936G936H

    936J

    936K

    Item Name Part Name Qty. Item Name Part Name Qty.

    19A Seal Retaining Spacer 1 63A - Seal Spring Backup Disc 1**

    50A Shaft Sleeve (Lower) 1 64A - Seal Retainer Ring 1**

    50B Shaft Sleeve (Upper) 1* 65A - Seal Spring 6**

    51A Seal Rotating Face 1* 68A - Seal Wedge Ring*** 1**

    51B Seal Rotating Face 1* 60B Mechanical Seal (Upper Alternate Gas) 1*

    51C Seal Rotating Face 1* 61B - Seal Retainer 1**

    52 Seal Spacer 1 62B - Seal Face Washer 1**

    60A Mechanical Seal (Lower) 1* 65B - Garter Spring 1**

    61A - Retainer & Drive Sleeve 1 68B - Backing Ring 2**

    62A - Seal Face Washer 1** 69B - O-Ring Packing or Tec Seal 1**

    63A - Seal Spring Backup Disc 1** 905F Hex Head Cap Screw 364A - Seal Retainer Ring 1** 916B Washer 3

    65A - Seal Spring 6** 936G O-Ring Packing 1*

    68A - Seal Wedge Ring*** 1** 936H O-Ring Packing 3*

    60B Mechanical Seal (Upper) 1* 936J O-Ring Packing (2 pc. seal requires 3) 2*

    61B - Retainer & Drive Sleeve Assembly 1** 936K O-Ring Packing 1*

    62B - Seal Face Washer 1**

    * Recommended Spare Parts

    ** Recommended Seal Space Component Parts

    *** Specific to Type 9AB Seal Design

    ALTERNATE GAS SEAL (UPPER 60B)

    ALTERNATE TWO PIECE UPPER SEAL

    ROTATING FACE (REPLACING 51B)

  • 8/10/2019 LMV-322-IOM_0603

    47/53Page 47 Visit our website at www.sundyne.com 02.09.02E, 06/03

    Figure 20 Inducer and Inducer Stud

    Figure 21 Flexible Coupling Adapter

    Item Name Part Name Qty.

    9 Inducer 1

    10 Inducer Stud 1

    Item Name Part Name Qty.

    116 Coupling Housing Cover 1

    117 Input Coupling 1

    118 Coupling Housing 1

    119 Hub 1

    904A Screw 4

    905J Hex head Cap Screw 4

    909D Bolt 4

    914D Nut 4914H Nut 4

    916E Washer 4

    916M Washer 4

    916R Washer 4

    916Y Washer 4

    920E Key 1

    101A (REF)

    2 (REF)

    10

    9

    5 (REF)

    30 (REF)

  • 8/10/2019 LMV-322-IOM_0603

    48/53

    Page 48Visit our website at www.sundyne.com02.09.02E, 06/03

    Figure 22 Chemical Barrier Gasket

    Figure 23 Discharge Orifice

    93 Discharge Piping

    Item Name Part Name Qty.

    106 Chemical Barrier Gasket 1*

    107 Seal Spacer 1

    905T Hex Head Cap Screw 3

    916V Seal Washer 3*

    * Recommended Spares

    Item Name Part Name Qty.

    93 Discharge Orifice 1

    916V 905T107 106

    101A (REF)

    130 (REF)

  • 8/10/2019 LMV-322-IOM_0603