lec7.pdf

download lec7.pdf

of 21

Transcript of lec7.pdf

  • Power System Dynamics

    Prof. M. L. Kothari

    Department of Electrical Engineering

    Indian Institute of Technology, Delhi

    Lecture - 07

    Transient Stability Analysis of a Multi Machine System

    (Refer Slide Time: 00:55)

    Friends, today we will study the transient stability analysis of a multi machine system

    using a classical approach.

    (Refer Slide Time: 01:06)

  • We shall address to some of the important issues related to the transient stability analysis

    of a multi machine system, I shall discuss the node elimination by matrix algebra,

    classical model of the system using that model we will develop the power output equations of generators in the multi machine system, then we will write down the swing

    equations in a multi machine system and then for transient stability analysis whatsoever

    preliminary computations are required to be made then we will discuss those.

    (Refer Slide Time: 01:41)

    (Refer Slide Time: 02:24)

    One of the requirements while pursuing the multi machine stability problem is the

    elimination of some nodes in the system where there is no current injection that is if you

  • have a system right and at some nodes in the system if there is no injection then these

    nodes can be eliminated okay.

    Now to understand how these nodes can be eliminated we start with the general system

    and the mathematical model of the system is expressed as I is equal to Y bus into V

    where I is the current vector and V is the voltage vector that is I are the currents which

    are injected at the buses and V are the bus voltages okay, Y bus is a matrix which is a

    square matrix okay and this is symmetric matrix you all know about it.

    Now to understand how the nodes can be eliminated what we will do is that we will

    partition this equation that is the current vector I can be partitioned into two sub vectors

    similarly, the voltage vector will be appropriately partition and then Y bus matrix is also

    partitioned, after partitioning this matrices we can write down IA IX this is the I vector and

    IA is a vector, IX is also a vector.

    (Refer Slide Time: 03:48)

    It can be partitioned as the sub matrix Y matrix is partitioned as K, L, L transpose M,

    VA, VX that is we are when we are doing the partitioning right of the system then when I

    partition this current vector then the Y bus matrix is also appropriately partitioned and

    bus voltage that is also appropriately partitioned. After this partitioning we can write

    down the equations, the two basic equation in the form, IA equal to K times VA plus L

    times VX and IX can be written as L transpose VA plus M times VX that is this is simply

    obtained by multiplying the uh this two matrices on the right hand side of this equation

    okay therefore, I get IA is equal to K times VA plus L times VX, IX is equal to L transpose

    VA plus M times VX.

  • (Refer Slide Time: 04:37)

    Now in case in case this IX is a null vector in the sense all elements are 0, okay in that

    case what we can do is that we can write down VX in terms of VA and other elements of

    this equation, what we do is that you subtract both the sides of the equation by L

    transpose VA IX is anyway 0 and multiply by M inverse. Now when you do this two

    operations that is you are subtracting both sides by this L transpose VA right and then you

    multiply by M inverse, you will get an equation in the form minus M inverse L transpose

    VA it is wrong it is L transpose VA.

    (Refer Slide Time: 06:01)

  • Okay this is equal to VX, now we have obtained the expression or equation for VX in

    terms of other non-quantities okay. So that what we do is that we substitute the

    expression for VX in equation 7.3 right. So that this VX is eliminated and the moment we

    eliminate this VX you can write down the equation in the form IA is equal to K times VA

    minus LM inverse L times VA. Okay and therefore this equation can be put in the form IA

    equal to K minus LM inverse L transpose into VA right that is if I write the equation in

    this form, IA equal to K minus LM inverse L transpose this is L transpose into VA.

    (Refer Slide Time: 07:13)

    Here, I and V have the same dimensions and this is a matrix is going to be square matrix

    have the same dimensions as that of the K and therefore now I can say that the my model

    becomes IA equal to Y bus reduced Y bus reduced into VA. Therefore, this reduced Y bus

    this you can say this is Y bus reduced okay and this reduced Y bus can be written in the

    form as K minus LM inverse L transpose. Therefore, here the network which initially had

    certain number of nodes and those nodes where there was no current injection okay.

    These nodes have been eliminated and therefore this is now a reduced order model and

    there are no nodes where there is no injection. Actually I will just illustrate this with the

    help of a example

    Now, let us consider that we have a simple system is the third order system let us say

    okay and the Y bus matrix as original system is minus 3.330, 3.330 minus 7.5, 2.5, 3.333

    and in, I can put 3 here also 2.5 and minus 10.833. This is let us say is Y bus of a system

    which has 3 nodes okay. Now let us assume that the node number 3 is 1where there is no

    current injection and I want to eliminate that node, what we do is that we partition this

    matrix because there are 3 nodes 1 and 2 and 3, okay therefore we partition it in the

    fashion.

  • (Refer Slide Time: 09:17)

    So that K becomes now matrix minus 3.3300 minus 7.5 okay. L is a vector in this

    particular case 3.33, 2.5, j will be there in all the cases okay and M is minus j times

    10.833. Okay now you substitute the value of KL and M in the expression, K minus L M

    inverse L transpose.

    (Refer Slide Time: 11:03)

    Now we make the substitution here this is a column column matrix this is simply a scalar

    quantity this is a row where when you multiply this 2 it will be a 2 by 2 matrix and then

    subtract this form the elements of K matrix and the resultant matrix which comes out to

    be j times 2.308, 0.769, 0.769 minus 6.923.

  • Now I have illustrated through a very a you know small example but this is applicable to

    any system which may have ah any number of nodes to be eliminated and this simplifies

    the process to a great extent okay. Now our next step will be in solving the multi machine

    problem, we have to develop the classical model.

    (Refer Slide Time: 12:20)

    When I say it is a they are using the classical approach we will have to develop the

    model. Now in the classical approach for transient stability analysis we make all those

    assumptions which are made earlier. These 5 assumptions which we made earlier I will

    just reiterate them, first was that mechanical input power remains constant, second was

    all asynchronous powers or dumping torques were assumed to be 0, third assumption was

    asynchronous generator can be represented by a constant voltage behind direct axis

    transient reactance, fourth was that synchronous power can be computed from the steady

    state solution of network and the fifth was the phase angle of the voltage behind transient

    reactance coincides with the total position with respect to the synchronously rotating

    reference plane.

    These were the 5 assumptions which we had made, the next assumption which we will

    make here is all loads because in any power system we will have loads at various buses

    all loads may be considered as shunt impedances to ground with values determined with

    values determined by conditions prevailing immediately prior to the transient conditions

    that is in the system we have loads connected and we will convert the loads loads by

    equivalent shunt impedances okay and while calculating the shunt impedances, we will

    consider the condition prevailing prior to the transient.

    Okay whatsoever are the condition before the occurrence of transient or steady state

    condition, okay using that condition we will find out the equivalent load admittances or

    load impedances. Okay this is very important next assumption which is made

  • Now for analyzing the transient stability or for any a stability problem we always require

    the initial operating condition or the steady state operating condition prior to the

    occurrence of disturbance.

    (Refer Slide Time: 14:57)

    Now for a multi machine system the steady state pre fault conditions for the for the

    system are computed using load flow, there is a mistake by mistake I did not write. The

    steady state pre fault conditions for the system are computed using a load flow.

    Therefore, a load flow for the system becomes a pre condition for starting the solution of

    any stability problem in a multi machine system. Okay now the model for the system.

    (Refer Slide Time: 15:32)

  • Okay now the model of the system actually with this all the assumptions which we have

    made it looks like this. The transmission network is shown here, to this transmission

    network we have generators connected at certain nodes. We can, so that these are the

    points at which the generators are connected. There are certain points in the network

    where the loads are connected. Okay now these loads are represented by constant

    impedances connected to the reference bus.

    Now this generators are replaced by ah voltage behind transient reactance direct axis

    transient reactance. Now here, here we will not neglect the armature resistance of the

    synchronous machine okay. Once we account for the armature resistance then we are

    representing the generator by a impedance r1 plus j times xd1 prime r2 plus j times xd2

    prime and we find out the voltage behind this impedance, if you neglect this resistance

    then it becomes simply the voltage behind direct axis transient reactance but here when

    we do the transient stability analysis there is no need to ignore the resistance and we can

    account for it.

    Once you account for this then these are the voltages behind the transient reactance.

    Therefore, now if you see here the network which is enclosed in this rectangle is a

    passive network it does not have any source now, okay all the sources have been taken

    out that is at this nodes we have connected the voltage sources and all the loads have

    been replaced by constant impedances and therefore what we exactly do when solving

    this problem is that initially you will perform a load flow analysis okay and once you

    perform the load flow analysis you will find out the voltages at all these nodes and all the

    nodes where the all the nodes where the loads are connected.

    Okay then using using this information the loads will be converted into equivalent

    impedances and we will replace the generators by equivalent voltage in series with

    impedance. Okay then then this becomes my model which is going to be used for

    transient stability analysis.

    Now in this case what we have done is that I have shown n generators okay and there

    may be ah r nodes where the loads are connected. Okay therefore the system may have

    originally n plus r nodes. Now when you perform this load flow analysis you will, you

    will find out that the Y bus matrix considering only the line parameters. Okay therefore

    now when you perform the transient stability analysis the Y bus matrix will be modified

    and it will be obtained considering the machine impedances and this load impedances.

    Okay once you obtain this Y matrix accounting for this machine impedances and the load

    impedances, the load buses can be eliminated okay and therefore you will be left with

    only these n buses where the generators are connected okay all the load buses you

    eliminated and the the buses where this generators are connected they are also eliminated

    because there is no injection here also but ultimately you will need or you will get a

    model which will have the n nodes, where the generators are connected and these are the

    constant voltages that is the voltages of constant magnitude their phase angles will very

    during the dynamic conditions okay.

  • (Refer Slide Time: 20:05)

    Now for this network we can write down the equations in the from I equal to Y bus E,

    where I is the current vector are or current injected at all the n buses and Y bus is the

    admittance matrix obtained after eliminating all the nodes. Okay therefore using this we

    shall be in a position to obtain the equations for for electrical power output from all the

    machines because we know actually that where we have to obtain or we have to analyze

    the transient stability analysis we need the expressions for electrical power output from

    the generators, okay. Therefore using this model which is having only the n nodes where

    the generators or internal voltage of the generators are connected and this exercise is a

    important exercise for which I have already the explained the methodology.

    (Refer Slide Time: 21:23)

  • Now here, we will represent the uh diagonal elements of the Y bus matrix which are

    called Yii will be equal to magnitude Yii angle theta ii, which will have real and

    imaginary parts Gii plus j times Bii. Similarly, the diagonal elements will be shown as Yij

    magnitude Yij angle theta ij, Gij plus j times Bij and these voltages, Ei will be written as Ei

    angle delta i.

    (Refer Slide Time: 22:37)

    (Refer Slide Time: 22:59)

    Now here I am not writing this prime right because once we understand that this is the

    voltage behind the direct axis transient reactance and the state of resistance included.

  • Okay then there because writing every time E prime is little what inconvenient okay

    therefore we consider that these are the internal voltages and the magnitudes of these

    voltages will remain constant. Now we can find out the electrical power output Phi by

    this basic equation that is the real part of Ei Ii star real part of Ei Ii star this is very

    important.

    Now here you look like this that this is the bus at which the voltage source is connected

    say Ei this is i th bus, this Ii is the current which is injected by this voltage source. Okay

    and we know actually the the complex power injected is equal to Pi Si equal to Pi plus j

    times Qi and this can be obtained by the formula formula always and in this particular

    system Ei into Ii conjugate, this star stands for conjugate. Okay and therefore when I take

    the real part of this Ei Ii star that becomes the electrical power output from the I th

    generator.

    (Refer Slide Time: 24:28)

    Now you we make the we substitute the expression for Ii, the expression for Ii is we have

    the vector Ii can be obtained as Yi1 Yi2 Yin multiplied by this vector E1 up to that is you

    have this is this is the I th row of the Y bus matrix and when you multiply this with the

    voltage vector, bus voltage vector you will get actually this Ii as Yi1 plus Yi2 E2 plus Yin En that is we can write down this Ii as summation of Yij Ej where j varies from 1 to n, this

    is the way we will be writing the expression for Ii .

    Now when you make this substitution here for the expressions for Ii that is you have to

    the conjugate of this current and then perform simplifications you will get the expression

    Pei that is electrical power output of I th machine as Ei square Gii plus j equal to 1 to n Ei

    Ej cosine of theta ij minus delta i plus delta j and j will not take the value equal to i and

    this equation is valid for i varying from 1 to n for all the machines that is you put i equal

    to 1, 2, 3, 4. You will find that you will be in a position to get the expression for electrical

    power.

  • This is a very important expression and for n machine system we will get n such

    equations. Now you can if you just look this look at this expressions carefully, you will

    find actually that this depends upon the magnitudes of all the voltages which are known

    to us, they remain constant during the transient stability analysis that is during the

    transient period. These are the Gii there is one term which is missing here actually just

    please correct it. It is Yij it is there will be Ei Ej, Yij will also be there.

    Okay cosine of theta ij minus delta i plus delta j therefore this, Yij is also known to us

    only thing which is not known will be the quantity which vary the delta i delta ij

    therefore, what happens is that these angles will be computed by using the numerical

    technique and at the end of each step of computation these angles will be known.

    Therefore, you substitute the value of these angles which are computed when you solve

    the swing equations right and you get the expression for Pei at each step. Now, once we

    know the expressions for electrical power output of the machines for all the n machines

    then we can write down the n swing equations okay.

    (Refer Slide Time: 28:10)

    The swing equations for each machine will be 2 times Hi upon omega s, d omega i by dt

    equal to Pmi, that is the mechanical input to i th machine minus the electrical output of the

    i th machine again here. Yij term is missing. Okay that is what we have done is that this

    expression is same as I have computed this is the expression for electrical power output

    from i th machine okay then this is the main equation and we write down this d delta i by

    dt equal to omega I, which is equal to the actual speed of the rotor minus synchronous

    speed because d delta i by dt is the access speed of the rotor right and this it is access over

    synchronous speed. Therefore, I am writing d delta i by dt equal to omega i which is

    equal to d theta i by dt minus omega s.

  • Okay therefore what we see here is that we have written 2 equations, 2 first order

    equations for one machine and therefore, if you have n machines in the system then you

    will get total 2 n such first order equations. Now we need the information of what is the

    mechanical power input to the machines Pmi and we assume that this Pmi is constant over

    the transient period that is mechanical power input to all the machines are assumed to be

    constant right. Therefore, there is a necessity to find out what will be the mechanical

    power input initially okay.

    Now how to do it because under steady state conditions the electrical power output is

    equal to the mechanical power input and the system is in steady state condition that is the

    derivative terms on the right left hand side of the equations are all 0 okay.

    (Refer Slide Time: 30:48)

    Therefore, with this condition we can write down the expression for mechanical power

    input as Pmio equal to Ei square Giio, I am putting o here means this is the this is the

    element of the Y bus matrix before the occurrence of transient again here you have Yij

    okay, that is the complete expression of wherever actually ah angles were delta i, I put

    delta io, delta j, delta jo, now theta ijo here you will find actually that when the system is

    subjected to disturbance.

    Okay therefore during fault conditions the Y bus matrix of the system will be different,

    during post fault condition it is again going to be different right and therefore we will

    have 3 different ah Y bus matrices one pre fault condition, one during fault condition,

    third post fault condition. Now here to compute the mechanical power input initial

    mechanical power input Pmio right. We use the conditions which are prevailing the in the

    system before the occurrence of disturbance and this is, I am denoting by putting a further

    subscript o, okay.

  • (Refer Slide Time: 32:26)

    Now the equations which we have written were 2n equations, these 2n equations can be

    written in the general form as X dot equal to a function a non-linear function X, Xo, t

    where, X is a vector of dimensions 2n into 1X is a vector of dimension 2n into 1 where, n

    is the number of machines and these are all first order nonlinear differential equations or

    we can say a set of 2n first order couple non-linear differential equations they are all

    couple.

    Now X transpose is actually the X is the state vector the state variables are omega 1, delta

    1, omega 2, delta 2, omega n, delta n right and let me just summarize here, how we obtain

    the mathematical model of the system. The first step is therefore a given system you

    perform a load flow study and find out the initial steady state operating condition okay,

    once you have done this the next step will be to replace all the loads by constant

    impedances.

    Then next step will be to knowing the information which you have obtained in the steady

    state ah condition you replace all the generators by constant voltage behind a impedance r

    plus j times Xd prime okay. Once you have done this thing, you can illuminate all those

    nodes where they are no current injections or no source is connected okay using the

    matrix algebra.

    Once you have done this thing you can find out the set of non-linear coupled differential

    equations for the machine okay. Once these equations are there our task is to solve these

    equations using numerical technique and plot the graph relating delta versus time that is

    the, we have to plot swing curves for all the machines and then we examine the swing

    curves to see whether the system is stable or not okay this is what is step.

  • (Refer Slide Time: 35:10)

    Now here before we do all the transient steady analysis one has to perform some

    preliminary computations. The preliminary preliminary computations to be computed

    done are, all system data are converted to a common base this is a pre important

    requirement that when you assemble the system data you will find actually that data are

    given on the basis of there name plate ratings. Suppose you have a generator of 5hundred

    MVA, okay then the generator parameters will be given on the basis of name plate rating

    of the machine.

    Okay but once you are consoling a system you have to convert all the data on a common

    base and the common base generally chosen is hundred MVA, okay 100 MVA is

    common because it looks to be little convenient for computations okay. Otherwise there

    is no such hard and fast rule you choose the common base and when you say the one is

    MVA base another is the voltage voltage in a particular circuit you will choose and then

    you will compute the per unit values of all the system parameters on common base.

    The second step is the loads are converted into equivalent impedances or admittances the

    needed for this is obtained from the load flow study, okay this is what I have already told

    you. Now how do we convert actually the loads into constant admittances these steps are

    also important this we can write down here, that at suppose the load is represented as PL plus j times QL at any bus as load is a PL plus j times QL.

  • (Refer Slide Time: 36:45)

    This load can be written as VL into IL star because this is the complex complex load right

    and with this can be written as the bus voltage , of the load bus, the voltage of the load

    bus into the conjugate of the current drawn by the load IL star. Okay using this expression

    we will compute the value of elements of the admittance which is going to replace the

    load by a constant admittance. Now the admittance will be written as YL plus j times YL equal to GL plus j times BL, okay.

    (Refer Slide Time: 38:43)

    This can be simply obtained that in this expression in this expression you can substitute

    the value of IL, we know that the current drawn by an admittance is equal to admittance

  • into the voltage and admittance load admittance multiplied by the voltage that will be the

    current and admittance is given by this formula, load voltage is VL therefore IL star is

    going to be VL star into YL star IL star is VL star into therefore VL into VL star becomes

    VL square and IL then YL will become GL minus times j times BL, YL star.

    So that we can write down this load as VL square into GL minus j times BL right and

    therefore, using this expression equation 7.8 right, we can say that the load admittance is

    equal to PL minus VL square minus j times QL by VL square that is you can say that the ah

    real part is PL divided by VL square and reactive part is BL divided QL minus VL square

    okay and the proper sign is to be consider.

    Therefore, this is one important step and this voltage is VL which are substituting in this

    expression are the obtained by load flow analysis. Okay another computation which is

    required to perform is the voltage behind the transient reactance. Okay now here you can

    use this expression Ei prime equal to Vti plus j times Xdi prime into Ii.

    (Refer Slide Time: 40:17)

    Now here I have not considered the armature resistance right but you can modify this by

    putting here instead of j times Xdi prime, we can put here Ri plus j times Xdi prime okay

    and since the all information is are known, current is known, terminal voltage is known,

    you can find out the while finding out this internal voltage we will use this expression,

    the current injected by the generator is Pi minus j times Qi divided by Vti star.

    This is very standard equation which can be used to compute the value of current and this

    current is required in the equation 7.10 to compute the internal voltage. The internal

    voltage which you compute, the internal voltage which you compute right will have its

    magnitude and phase angle right and this phase angle which you get become the initial

    value of deltas, okay and the magnitudes will remain constant during the transient.

  • Now once you have done these preliminary calculations okay we obtain using this

    information, the swing equations. Now you know that we require swing equations under

    3 different conditions, one is the pre fault operating condition, second is the during fault

    and third is the post fault and therefore when you solve the swing equations suppose I

    start solving the equations at time t equal to 0, okay now if the perturbation or

    disturbances occur at time t equal to 0 right then immediately from that initial steady state

    condition I will be using the swing equations, I will be solving the swing equations which

    are applicable during the during the fault on period.

    Then once I know that okay after this much time the fault is cleared right it means the

    movement I reach that particular point i will change over from the fault on period swing

    equations to post fault swing equations and continue to solve it right. Now one should

    know actually that suppose the fault occur in the system, how to obtain the ah the swing

    equations which will be applicable during fault conditions, pre fault conditions we have

    already obtained.

    Now the faults can be ah symmetrical faults or unsymmetrical faults. Now in case it is a

    symmetrical fault then the problem is bit simple, if it is unsymmetrical then also it is not

    difficult because we have already seen how to account for the unsymmetrical fault. Now

    if it is suppose I take fault at a particular bus, let us say that fault occurs at a particular

    bus then voltage of that bus will collapse it will become 0. Therefore, the occurrence of

    fault at the particular bus is accounted by considering or by is by setting that voltage of

    that bus to 0.

    Okay then once the voltage of that bus becomes 0 we have to modify the Y bus matrix

    which will be applicable to this period, this particular fault on condition. This

    modification are not difficult one can, once you see that a particular bus is grounded okay

    looking into that condition you can modify the Y bus matrix. Now simplest way is that if

    you have Y bus matrix for the pre fault condition then if suppose at a particular bus let us

    say ah bus number five bus number five if suppose there is a 3-phase short circuit then

    the row and column corresponding to the bus number 5 can be deleted from the pre fault

    Y bus matrix and the remaining, the remaining Y bus matrix right will become the Y bus

    matrix applicable to post fault condition.

    In fact actually suppose one particular bus is grounded or since it is sorted it gets get

    grounded it they the number of buses which remain now will become less by one right

    therefore Y bus matrix also reduce in dimension. Similarly, once you consider the post

    fault condition right then, you can obtain the Y bus matrix during the post fault condition

    because under post fault condition what happens one line may be out therefore for the

    remaining system you have to find out the Y bus matrix.

    Now this Y bus matrix will not be assembled fresh one can be modify the existing Y bus

    matrix by modifying the elements of Y bus matrix some elements will be affected, for

    example actually if suppose there is a Y bus matrix and if the line connecting the node

    one and two that is tripped.

  • Okay then what is that is going to affect the or which elements of the Y bus matrix will

    be affected that is Y11 will be affected because that line is out, Y22 will be affected and

    Y12 will be affected others will not be affected, right. Therefore once we know that

    particular type of line element has been removed right you can easily find out the Y bus

    matrix applicable during the post fault period and once we know the Y bus matrix which

    are applicable during post fault, during fault and during pre-fault conditions that you

    already known because our equations that is the equations for electrical power output are

    written using the reduced Y bus matrix therefore this reduction process has to be done for

    all the 3 conditions pre-fault fault on condition and post fault condition.

    (Refer Slide Time: 46:48)

    Now I will suggest you to refer to these problems or these two examples which are given

    in here, one example is given in the book written by P. M. Anderson and Fouad, power

    system control and stability volume one, example 2.6 and 2.7, these two examples this is

    example which is very very commonly used for illustrating the transient stability

    analysis. It is a 9 bus system, it has total 3 generators, 9 buses okay and in these two

    examples all the step by step computations have been carried out to illustrate the steps

    involved in solving the transient stability problem.

    One more simple example which is given in the ah basic book on power system analysis

    that is elements of power system analysis by Stevenson, everybody is aware of this book

    Stevenson here he has solved 5 bus system. Okay and in this 5bus system he has

    illustrated all the steps which are required to obtain the complete transient stability

    solution. Now once the model is obtained and you solve the swing equations, couple a set

    of the coupled swing equations, you will get the swing curves.

    Okay the swing curves will plot actually as delta one delta two delta three as function of

    time. Now to examine whether the system remains stable or not we have to see the

  • relative variation of the swing curves that is not the absolute values of delta 1, delta 2

    delta n that is important what is the relative value that is more important.

    Suppose the two machines may accelerate simultaneously okay but the angles may

    remain very close to each other or angle difference may remain very close then system is

    not losing synchronism therefore, when you examine the stability of the multi machine

    system we have to examine the ah the plots of relative ah angles that is we plot actually

    delta 12 that is delta 1 minus delta 2.

    You plot delta 1 minus delta three suppose there is a three machine system they are only

    a 3angles involved and once this curves are plotted in case actually the curves or we can

    say delta 12 reaches the maximum value and decreases it shows the stability condition,

    in case delta 12 increases continuously it shows unstable condition. Okay with this let me

    conclude what we have done today.

    We have an we have given or we have studied the basic steps involved in analyzing the

    transient stability of a multi machine system. Here we have used a classical model for

    analyzing the stability I have mentioned that how do we obtain the required required

    models for pre-fault, fault on and post fault operating conditions. Okay and the swing

    equations which we obtained for the system are solved by using numerical techniques

    and the stability of the system is understood by examining the swing curves which we

    plot and particularly the is the swing curves are relating the relative relative angles of the

    machines, okay thank you very much.