HOONEAUTOMAATIKASÜSTEEMID
AAR0130 2010
ÜLO KALA
OSA VI-III ATS kesk ja lisaseadmed GKS VKS
AAR0130 ÜLO KALA 201009.03.102
TULEKAHJU TEATENUPPPAIGALDATAKSE IGA VÄLJUMISUKSE JUURDE
PAIGALDATAKSE 1,5 M PÕRANDAPINNAST
NUPU KAUGUS ANTUD EVAKUATSIOONIPIIRKONNA VÄLJUMISUKSE KAUGEIMAST PINNAST EI TOHI ÜLETADA 30 m
NUPPU EI TOHI KASUTADA MILLEKSKI MUUKS KUI AINULT TULEKAHJUTEATE EDASTAMISEKS
NUPUD VÕIVAD OLLA KAS PURUSTATAVA KLAASIGA VÕI VÕTMEGA TAGASTATAVAD
NUPP VÕIB OLLA KAS ADRESSEERITAV VÕI MITTEADRESSEERITAV
NUPPE TOODETAKSE MITMES VÄRVITOONIS:
PUNANE TULEHÄIRE
KOLLANE GAASIKUSTUTUSE KÄIVITUS
HALL SUITSUÄRASTUSE KÄIVITUS
SININE TEHNILINE ALARM
Page 2
AAR0130 ÜLO KALA 201009.03.103
KONVENTSIONAALNE KESKSEADE
ESSER BMZ 80
AAR0130 ÜLO KALA 201009.03.104
ADRESSEERITAV KESKSEADE
Upright cabinetSteel sheet housing 700 x 2000 x 525 mm
Option for all Panels
Compact housing450 x 320 x 185 mm
Compact housing plus1 x Extension housing450 x 640 x 185 mm
Compact housing plus2 x Extension housing450 x 960 x 185 mm
Page 3
AAR0130 ÜLO KALA 201009.03.105
KESKSEADME JUHTIMINE
1 5432
9
8
7
6
10
Opening for Programming connector must locked with dummy plug for ESD protection
Function keys and keyboard
Operating elements
Key switch
Alphanumeric display
Common display disconnection
Common display TROUBLE
Common display PRE-ALARM
Common display FIRE
Single zone indicator unit (GEA)
AAR0130 ÜLO KALA 201009.03.106
220 V TOIDE
• ATS keskseade peab saama toite eraldi fiidri või eraldi automaadi kaudu. Eraldi automaat peab olema selgelt tähistatud ja teistest automaatidest eraldi . Hoonetes kus on maanduse kaitsereleed tuleb paigaldada eraldi relee ATS süsteemile.
• ATS toite kaitseautomaat või sulavkaitse peab olema varustatud selgepunase kirjaga ATS TOIDE.
• Alati peb olema korralik keskseadme maandus. (näiteks ESSER keskseadmed süütavad halval maandusel kollase tule teatega“ground loop fault”.
• Kasutatada tuleks alati spetsiaalset toitekaablit näit. NYM 3 x 1.5 mm2 või sarnaste tehniliste andmetega kaablit. Paigaldus peabvastama kõigile kehtivatele elektrisüsteemide ehitusele esitatavatelenõuetele.
Page 4
AAR0130 ÜLO KALA 201009.03.107
IN4
OUT5
C3
2
16
IN4
OUT5 EM2
C3
EP6 1
IN4
OUT5 EM2
C3
EP6 1Option
+
-
BR1 = n.o. (default)
BR1 = n.c.
BR1
IN4 / B -
C3 / B + A -A +
B -B +
805590 (Standard) 805590 (Standard) 805591 (Relay)
J2 J3 J4
J6 J5 J7
J2 J3 J4
J6 J5 J7
J2 J3 J4
J6 J5 J7
J2 J3 J4
J6 J5 J7
1 2 3
4 5 6
7 8 9
0
X24
BR8
BR9
max. 1000m
FACP 8000C/M, IQ8Control, 8007
Last device Last device
FAS 80001 2 3
4 5 6
7 8 9
0
FACP 8000C/M, IQ8Control, 8007
LCD-IP
GND
UBext+
BA
12 V
RS 485BA
+-
Basi
c m
odul
e X
8
RS 485
ANDURITE JA KORDUSPANEELIDE ÜHENDAMINE
AAR0130 ÜLO KALA 201009.03.108
KESKSEADME ÜHENDUS SUURSILMUSEGA
3
SUURSILMUS- MULTIFUNKSIONAALNE AHEL
max. 3,5 km
esserbus®
esserbus®
transponder
esserbus®
transponder
FDOPLISAPANEEL
SUURSILMUS
Page 5
AAR0130 ÜLO KALA 201009.03.109
AVASTUSTSOONID SUURSILMUSES
AAR0130 ÜLO KALA 201009.03.1010
SOPISTUS EHK “ SPUR”
A
B
Page 6
AAR0130 ÜLO KALA 201009.03.1011
TULETÕKKETSOON JA AVASTUSTSOON
Ground floor
1st floor
2nd floor
Stairwell
1/1 1/2 1/3 1/4
3/1 3/2 3/3 3/4
4/1 4/2 4/3 4/42/3
2/2
2/1
3 KORRUS
2 KORRUS
1 KORRUS
TREPIKODA
AAR0130 ÜLO KALA 201009.03.1012
TULETÕKKETSOON
Fire section A Fire section BTSOON A TSOON B
TULETÕKKETSOONID ON EHITUSLIKULT MÄÄRATUD PIIRKONNAD HOONES MIS ON ERALDATUD OMAVAHEL TULEPÜSIVATE VAHESEINTE, USTE JA MUUDE TÕKENDITEGA
TULETÕKKETSOON EI PEA KOKKU LANGEMA AVASTUSTSOONIGA.
TULETÕKKETSOONIS VÕIB OLLA MITU AVASTUSTSOONI AVASTUSTSOONIS EI VÕI OLLA MITUT TULETÕKKETSOONI
Page 7
AAR0130 ÜLO KALA 201009.03.1013
SUURSILMUSE LIIKMED
kustutuspaneel8010
transponder1 tsoon
transponder4 tsooni/2 releed
transponder32 LED transponder
12 Releedtransponder
FSA
TRANSPONDERRZT 8000
TEISE TOOTJA ANDURID
LED INFOPANEEL
esserbus®
LRS compact/EB
Tehnilise alarmimoodul IQ8Tam
IQ8ControlIQ8Control
AAR0130 ÜLO KALA 201009.03.1014
VÕRK (RS485)esserbus®
essernet®
FACP 8000C
FACP IQ8Control C
IAP 5008 C
Indicating and operating Panel intruder / fireGateway
FACP 3008
max. 1 km
Repeater
max. 1 km
FOC
FOC
IAP esserbus®
WINMAG
esserbus®-PLus
Fibre optical cable
Serial essernet®Interface
Page 8
AAR0130 ÜLO KALA 201009.03.1015
VÕRGUÜHENDUSED
essernet®
12
345
6
78
L1 +L1 -
L2 +
L2 -not used!
L2 +L2 -
L1 +L1 - L2 +
L2 -
L1 +L1 -
essernet® module
not used!not used!
not used!
essernet® module
AAR0130 ÜLO KALA 201009.03.1016
FIIBEROPTILINE VÕRK
TR
VccR
xD
1234
+UBext.GND
4321
+UBext.GND
Panel 1 Panel 2
essernet® moduleessernet® moduleConventional essernet® wiring orconnection via second fibre optics cable
PIN 3PIN 8
TR
Vcc
RxD
PIN 3PIN 8
Length / attenuation refer to specified optical fibre type above
FOC converter784763 / 784764
essernet®
FOC FOCFibre Optics Link
essernet®
FOC FOC
FOC FOC
Fibre O ptics Link
F ibre O ptics Link
Page 9
AAR0130 ÜLO KALA 201009.03.1017
PCPC-- NetzwerkNetzwerk
LOOPLOOPIGISIGIS
access control
videomatrix
emergency exit control
RS 485
NETNETESSERESSER
modemISDN
serial
GRAAFILINE TARKVARA
WebCamWebCam
Notifikation
InternetInternet
WebWeb--XX
AAR0130 ÜLO KALA 201009.03.1018
GRAAFILINE LIIDES• 1 EKRAANIGA
• 2 EKRAANIGA
WINMAG
Page 10
AAR0130 ÜLO KALA 201009.03.1019
STANARD LIIDES
event text and measureSÜNDMUSE TEKST JA JUHISED
PLAAN
STRUK-TUUR
AAR0130 ÜLO KALA 201009.03.1020
SÜNDMUSTE LOGI
Page 11
AAR0130 ÜLO KALA 201009.03.1021
ALARMSEADMED
ANDUR SISSEEHITATUD SIREENI VÕI VALJUHÄÄLDIGA
SPETSIAALNE ALARMSEADE
AAR0130 ÜLO KALA 201009.03.1022
HELIRÕHKEFFEKTIIVNE HLIRÕHK ON ÕHUMOLEKULIDE POOLT PÕHJUSTATUD RÕHK MIS TEKIB NENDE VÕNKUMISEL (HELILAINE)
INIMKÕRV SUUDAB VASTU VÕTTA HELISID RÕHUGA 0dB (KUULDELÄVI) KUNI 120 dB SAGEDUSEL 1000 Hz . SEE VASTAB HELIRÕHU MUUTUSELE 20N/m2 (= Pa) VÕI SIIS 1: 1,000,000 HELIRÕHU JAOKS
(Lihtsuse mõttes arvutataksegi helirõhku logaritmilistes suurustes(dB ).
130-150REAKTIIVMOOTOR 10 M110POLITSEI, TULETÕRJE JNE SIREEN 10 M 100SURUÕHU PIIKVASAR 10 M KAUGUSELT> 80TOOTMISHOONED JA LINNATÄNAV
70-75LAOHOONED DIISELTÕSTUKITEGA65-70LAOHOONED EL. TÕSTUKITEGA55-60AVATUD BÜROORUUMID
50ERALDI BÜROORUUMID< 30ELURUUMID ÖISEL AJAL
HELIRÕHU TASE dB 1)KESKKOND
Page 12
AAR0130 ÜLO KALA 201009.03.1023
MINIMAALNE HELITUGEVUS EN 54-3, OSA4.6.2 JÄRGI
82 dB
91 dB
96.0 dB
96 dB
91 dB
82 dBKÕRGE 970 Hz
80 dB
85 dB
90 dB
90 dB
85 dB
80 dB
KESKM. TOON830 Hz
81 dB
90 dB
95 dB
95 dB
90 dB
81 dB
MADAL TOON730 Hz
81 dB
89 dB
94 dB
94 dB
89 dB
81 dB
DIN SIGNAAL
165°135°105°75°45°15°KIIRGUSNURK
AAR0130 ÜLO KALA 201009.03.1024
HELIROHK KUULDEPUNKTIS92dB
72dB
1m
10m ~ -20dB
ALARMSEADMETEL ON TAVALISELT ANTUD HELIRÕHK 1 M KAUGUSEL SEADMEST. IGA KORD KUI KAUGUS SUURENEB 2 X VÄHENEB HELIRÕHK 6 Db .
HELIRÕHU MUUTUS SÕLTUVALT ALLIKA KAUGUSEST:
∆L ( dB) = 20 x log (r2 [m] / r1 [m])
KUS: r1 = 1m algne kaugus
r2 = 20m uus kaugus
Page 13
AAR0130 ÜLO KALA 201009.03.1025
Audible signals / Speech output
Audible signals (Example)
4,00FP 1063.1 Telecoms BS 5839 Pt1-Tone 2Alternating signal tone, Frequency 800 / 970 Hz @ 1Hz Tone 2 (GB)
4,00FP 1063.1 Telecoms BS 5839 Pt1-Tone 3Cyclic signal tone, Frequency 970 Hz @ 1Hz 0,5 s Tone 3 (GB)
4,00FP 1063.1 Telecoms BS 5839 Pt1-Tone 1Alternating signal tone, Fequency 800 / 970 Hz @ 2Hz Tone 1 (GB)
Duration [s]Description of signalSignal componentDemo
Speech outputs
4,46The emergency is now cancelled.We apologise for any inconvenience.Phrase 10
3,18This is a test message. No action is required.Phrase 9
4,37An incident has been reported in the building. Please await further instructions.Phrase 8
5,82Attention please. This is an emergency. Please leave the building by the nearest available exit.Phrase 7
5,27This is a fire alarm. Please leave the building immediately by the nearest available exit.Phrase 6
Duration [s]Description of signalSignal componentDemo
AAR0130 ÜLO KALA 201009.03.1026
PLAHVATUSOHT Ex VASTAVUSEU Explosion Protection Directive 94/9/EC-ATEX 100a
Page 14
AAR0130 ÜLO KALA 201009.03.1027
PLAHVATUSOHU TSOONIDTSOON 2: Alad kus plahvatusohtlik atmosfäär võib tekkida harva ja lühikeseks ajaks
TSOON 1: Alad kus plahvatusohlik kontsentratsioon tekib aeg-ajalt kindlasti
TSOON 0: Alad kus on kogu aeg plahvatusohtlik atmosfäär
AAR0130 ÜLO KALA 201009.03.1028
KUSTUTUSSÜSTEEMIDKUSTUTUSSÜSTEMID
VEEKUSTUTUSGAASKUSTUTUS PULBERKUSTUTUS
HA
LO
ON
GA
AS
ID
LO
OD
US
L.
GA
AS
ID
KE
EM
ILIS
. GA
AS
ID
VE
ES
PR
INK
LE
R
VE
EU
DU
KU
ST
UT
US
AU
RU
GA
KU
ST
UT
US
PÜ
RO
GE
EN
AE
RO
SO
OL
ID
KÄ
SIK
US
TU
TID
Page 15
AAR0130 ÜLO KALA 201009.03.1029
GAASKUSTUTUSSEADE
SUITSUANDURID
KÄSITSI RAKENDUS
SEISKAMISNUPP KESKSEADE
ALARMISEADE
KUSTUTUSAGENDI BALLOON
DÜÜSID
AAR0130 ÜLO KALA 201009.03.1030
GAASKUSTUTUSSÜSTEEM
esserbus®essernet®
8010
8010 8010
8010
801080108010
8010
Outputs
Page 16
AAR0130 ÜLO KALA 201009.03.1031
AAR0130 ÜLO KALA 201009.03.1032
HALONI ALTERNATIIVIDCO 2FM-200ArgoniteInergenFE-13VeeuduPürotehnilised
Page 17
AAR0130 ÜLO KALA 201009.03.1033
CO 2LõhnatuAtmosfääri koostisosaMinimaalne kustutusekontsentr. 34%5,800 kPa SurvestusPikk tühjenemisaeg - kuni 3 minutit
Balloonid nõavad palju ruumiVõib kasutada lokaalsetessüsteemides
AAR0130 ÜLO KALA 201009.03.1034
FM-200 HEA ASENDUS HALONILE
Kiire ja efektiivneOhutu inimestelePole elektrijuht - ohutukasutada el. seadmetelKeskkonnasõbralikPikk säilitusaeg
Page 18
AAR0130 ÜLO KALA 201009.03.1035
INERTGAASID
KUSTUTUSVIISID
AAR0130 ÜLO KALA 201009.03.1036
VAJALIK GAASI KOGUS (MAHT)
Halon 1301
CO22
Inert Gaas
Page 19
AAR0130 ÜLO KALA 201009.03.1037
ARGONITELõhnatuVajalik kontsentratsioon 40%Alati gaasiline20,000 kPa SurvestusPikk tühjenemisaeg - 60 sekunditVaja palju ballooneMärgatav ruumikuluEkspluatatsioon kallis
50% ARGON50% NITROGEN
Inert gas blend - 52% N2, 40% Argon, 8% CO2
Primarily acts by O2 dilution, to 10-12%, with some