Guía de Ayuda y Diagnóstico

download Guía  de Ayuda y Diagnóstico

If you can't read please download the document

description

Guía de Ayuda y Diagnóstico. TSX Premium – Mensajeria cliente Modbus TCP/IP. Centro de Competencia Técnica. 1. 5. 6. 7. 4. 2. 3. 2. 3. 2. 2. 8. Diagrama de diagnóstico 1/2. 9. 10. 5. 6. 7. 8. 11. 12. 13. Diagrama de diagnóstico 2/2. - PowerPoint PPT Presentation

Transcript of Guía de Ayuda y Diagnóstico

  • Gua de Ayuda y DiagnsticoTSX Premium Mensajeria cliente Modbus TCP/IPCentro de Competencia Tcnica

    Schneider Electric*- Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    Diagrama de diagnstico 1/2

    Schneider Electric*- Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    Diagrama de diagnstico 2/2

    Schneider Electric*- Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    1. Premium ETY (Port / 4103 /5103): leds de diagnsticoVolver al diagrama de flujoSiguiente

    Schneider Electric*- Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    2. Premium Copro: leds de diagnsticoVolver al diagrama de flujoAnterior

    Schneider Electric*- Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    3a. PingLa condicin indispensable para poder ejecutar desde un PC un comando PING para verificar la conexin TCP/IP con otro dispositivo es que ambos tengan direcciones IP compatibles.

    Los pasos a seguir para consultar o cambiar la IP de un PC son los siguientes:12Volver al diagrama de flujoSiguiente

    Schneider Electric*- Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    3b. Ping345Volver al diagrama de flujoSiguienteAnterior

    Schneider Electric*- Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    3c. PingPara ejecutar un comando PING se ha de abrir una ventana DOS:Volver al diagrama de flujoSiguienteAnterior

    Schneider Electric*- Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    3d. PingComando PING con respuesta correcta por parte del dispositivo remotoComando PING sin respuesta por parte del dispositivo remotoVolver al diagrama de flujoAnterior

    Schneider Electric*- Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    4. Software cliente/servidor Modbus TCP/IPMbTCPTest: Utilidad cliente/servidor Modbus TCP/IP. Necesita tener instalado el Framework .Net. Descargable desde: \\10.132.20.10\data$\AUT\Software_Herramientas\Utilidades AUT Imprescindibles\Utilidades Ethernet\Modbus TCPIP\MbTCPTest.zip Download details: .NET Framework Version 2.0 Redistributable Package (x86)

    Volver al diagrama de flujo

    Schneider Electric*- Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    5a. Filtro de mensajeraParmetros de configuracin de la conexin Ethernet para mensajera Volver al diagrama de flujoSiguiente

    Schneider Electric*- Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    5b. Filtro de mensajeraDnde encontrar el filtro de la mensajera en PL7?Volver al diagrama de flujoSiguienteAnterior

    Schneider Electric*- Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    5c. Filtro de mensajeraDnde encontrar el filtro de la mensajera en Unity?Volver al diagrama de flujoAnterior

    Schneider Electric*- Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    6a. Diagnstico carga PLCDiagCommSeleccionar Diagnstico > Carga Ethernet12Realizar conexinSoftware PlcDiagCommVolver al diagrama de flujoSiguiente

    Schneider Electric*- Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    6b. Diagnstico carga PLCDiagCommDatos diagnstico de Carga3Lmites y anchos de Banda Modulos EthernetVolver al diagrama de flujoAnterior

    Leeme

    El objetivo es realizar una estimacion de carga de la propia red Ethernet , el modulo Ethernet y la CPU

    Para ello hay que rellenar los campos en amarillo de las 3 primeras hojas (IOScanning , Mbus-Msg y Global Data)

    En la Hoja CALCULOS se muestran los resultados

    La hoja Performances expresa todos los limites a la hora de comunicar en Ehernet con los PLCs

    Las Hojas ETY y NOE muestra las prestaciones de las diferentes versiones de tarjetas

    The M1E as a server only

    171CCC96030 with IEC Exec v.1.27e installed

    No logic program. No I/O Scanner table entries.

    Isolated network. Only Modbus network traffic. PC M1E communications.

    14 server connections.

    Client program on PC - opening 14 modbus connections, reading 125 registers on each connection.

    M1E Transactions (query & response) per second ~ 2000. Multiple tests and Wireshark trace analysis showed packets per second = approximately 4000, no retries.

    The M1E as a client/server

    171CCC96030 with IEC Exec v.1.27e installed

    No logic program. 30 - I/O Scanner client entries.

    Isolated network. Only Modbus network traffic. PC (client) M1E (client/server) ENT/M1E (server) communications.

    14 server connections.

    Client program on PC - opening 14 modbus connections, reading 125 registers on each connection.

    M1E Transactions (query & response) per second ~ 1900. Multiple tests and Wireshark trace analysis showed packets per second = approximately 3700->3800, no retries.

    IOS_Bdw

    IO Scanner Service :TOTALTOTALMediumTOTAL

    Througput and Bandwith computationThroughputThroughputBandwidthUsed

    in Kbyte/sin Kbit/sin Mbit/sBandwidth

    001000.0%

    List of Published VariablesRequestResponseMediumUsed

    N SlaveT_RefreshRd_sizeWr_sizeFrame+IPGFrame+IPGThroughputThroughputBandwidthBandwidth

    128 maxin msin wordsin wordsin bytesin bytesin byte/sin bit/sin Mbit/sin %

    15000000001000.000%

    25000000001000.00%

    35000000001000.00%

    45000000001000.00%

    55000000001000.00%

    65000000001000.00%

    75000000001000.00%

    85000000001000.00%

    95000000001000.00%

    105000000001000.00%

    115000000001000.00%

    125000000001000.00%

    135000000001000.00%

    145000000001000.00%

    155000000001000.00%

    165000000001000.00%

    175000000001000.00%

    185000000001000.00%

    19100000001000.00%

    20100000001000.00%

    21100000001000.00%

    22100000001000.00%

    23100000001000.00%

    24100000001000.00%

    25100000001000.00%

    26100000001000.00%

    27100000001000.00%

    28100000001000.00%

    29100000001000.00%

    30100000001000.00%

    31100000001000.00%

    32100000001000.00%

    33100000001000.00%

    34100000001000.00%

    35100000001000.00%

    36100000001000.00%

    37100000001000.00%

    38100000001000.00%

    39100000001000.00%

    40100000001000.00%

    41100000001000.00%

    42100000001000.00%

    43100000001000.00%

    44100000001000.00%

    45100000001000.00%

    46100000001000.00%

    47100000001000.00%

    48100000001000.00%

    49100000001000.00%

    50100000001000.00%

    51100000001000.00%

    52100000001000.00%

    53100000001000.00%

    54100000001000.00%

    55100000001000.00%

    56100000001000.00%

    57100000001000.00%

    58100000001000.00%

    59100000001000.00%

    60100000001000.00%

    61100000001000.00%

    62100000001000.00%

    63100000001000.00%

    64100000001000.00%

    65100000001000.00%

    66100000001000.00%

    67100000001000.00%

    68100000001000.00%

    69100000001000.00%

    70100000001000.00%

    71100000001000.00%

    72100000001000.00%

    73100000001000.00%

    74100000001000.00%

    75100000001000.00%

    76100000001000.00%

    77100000001000.00%

    78100000001000.00%

    79100000001000.00%

    80100000001000.00%

    81100000001000.00%

    82100000001000.00%

    83100000001000.00%

    84100000001000.00%

    85100000001000.00%

    86100000001000.00%

    87100000001000.00%

    88100000001000.00%

    89100000001000.00%

    90100000001000.00%

    91100000001000.00%

    92100000001000.00%

    93100000001000.00%

    94100000001000.00%

    95100000001000.00%

    96100000001000.00%

    97100000001000.00%

    98100000001000.00%

    99100000001000.00%

    100100000001000.00%

    101100000001000.00%

    102100000001000.00%

    103100000001000.00%

    104100000001000.00%

    105100000001000.00%

    106100000001000.00%

    107100000001000.00%

    108100000001000.00%

    109100000001000.00%

    110100000001000.00%

    111100000001000.00%

    112100000001000.00%

    113100000001000.00%

    114100000001000.00%

    115100000001000.00%

    116100000001000.00%

    117100000001000.00%

    118100000001000.00%

    119100000001000.00%

    120100000001000.00%

    121100000001000.00%

    122100000001000.00%

    123100000001000.00%

    124100000001000.00%

    125100000001000.00%

    126100000001000.00%

    127100000001000.00%

    128100000001000.00%

    &L

    &F&C&"SchneiderPc,Regular"&36S&R

    &A

    &L&"Arial,Gras"Schneider Automation SA&"Arial,Normal"jhp &D &T&R

    page &P/&N

    MBus-Msg_Bdw

    Modbus TCP/IP Messaging Service

    TOTALTOTALMediumTOTAL

    Ancho de banda consumido como ServidorThroughputThroughputBandwidthUsed

    in Kbyte/sin Kbit/sin Mbit/sBandwidth

    001000.0%

    List of Transactions, Requests and/or ResponsesRequestResponseMediumUsed

    N SlaveT_RefreshRd_sizeWr_sizeFrame+IPGFrame+IPGThroughputThroughputBandwidthBandwidth

    128 maxin msin wordsin wordsin bytesin bytesin byte/sin bit/sin Mbit/sin %

    1100000001000.000%

    2100000001000.00%

    3100000001000.00%

    4100000001000.00%

    5100000001000.00%

    6100000001000.00%

    7100000001000.00%

    8100000001000.00%

    9100000001000.00%

    10100000001000.00%

    11100000001000.00%

    12100000001000.00%

    13100000001000.00%

    14100000001000.00%

    15100000001000.00%

    16100000001000.00%

    17100000001000.00%

    18100000001000.00%

    19100000001000.00%

    20100000001000.00%

    21100000001000.00%

    22100000001000.00%

    23100000001000.00%

    24100000001000.00%

    25100000001000.00%

    26100000001000.00%

    27100000001000.00%

    28100000001000.00%

    29100000001000.00%

    TOTALTOTALMediumTOTAL

    Ancho de banda consumido como ClienteThroughputThroughputBandwidthUsed

    in Kbyte/sin Kbit/sin Mbit/sBandwidth

    001000.0%

    List of Transactions, Requests and/or ResponsesRequestResponseMediumUsed

    N SlaveT_RefreshRd_sizeWr_sizeFrame+IPGFrame+IPGThroughputThroughputBandwidthBandwidth

    128 maxin msin wordsin wordsin bytesin bytesin byte/sin bit/sin Mbit/sin %

    1100000001000.000%

    2100000001000.00%

    3100000001000.00%

    4100000001000.00%

    5100000001000.00%

    6100000001000.00%

    7100000001000.00%

    8100000001000.00%

    9100000001000.00%

    10100000001000.00%

    11100000001000.00%

    12100000001000.00%

    13100000001000.00%

    14100000001000.00%

    15100000001000.00%

    16100000001000.00%

    17100000001000.00%

    18100000001000.00%

    19100000001000.00%

    20100000001000.00%

    21100000001000.00%

    22100000001000.00%

    23100000001000.00%

    24100000001000.00%

    25100000001000.00%

    26100000001000.00%

    27100000001000.00%

    28100000001000.00%

    29100000001000.00%

    &L

    &F&C&"SchneiderPc,Regular"&36S&R

    &A

    &L&"Arial,Gras"Schneider Automation SA&"Arial,Normal"jhp &D &T&R

    page &P/&N

    GD1_Bdw

    Global Data Service :TOTALTOTALMediumTOTAL

    Througput and Bandwith computationThroughputThroughputBandwidthUsed

    Group address :255.0.0.3in Kbyte/sin Kbit/sin Mbit/sBandwidth

    Group Name :Group_64S001000.0%

    List of Published VariablesMediumUsed

    N VarT_MastDisp_PSize_VFrame+IGPThroughputThroughputBandwidthBandwidth

    64 maxin msNbr Scanin wordsin bytesin byte/sin bit/sin Mbit/s

    110100001000.00%

    210100001000.00%

    310100001000.00%

    410100001000.00%

    510100001000.00%

    610100001000.00%

    710100001000.00%

    810100001000.00%

    910100001000.00%

    1010100001000.00%

    1150100001000.00%

    1280100001000.00%

    1380100001000.00%

    1480100001000.00%

    1580100001000.00%

    1680100001000.00%

    1780100001000.00%

    1880100001000.00%

    1980100001000.00%

    2080100001000.00%

    2180100001000.00%

    2280100001000.00%

    2380100001000.00%

    2480100001000.00%

    2580100001000.00%

    2680100001000.00%

    2780100001000.00%

    2880100001000.00%

    2980100001000.00%

    3080100001000.00%

    3180100001000.00%

    3280100001000.00%

    3380100001000.00%

    3480100001000.00%

    3580100001000.00%

    3680100001000.00%

    3780100001000.00%

    3880100001000.00%

    3980100001000.00%

    4080100001000.00%

    4180100001000.00%

    4280100001000.00%

    4380100001000.00%

    4480100001000.00%

    4580100001000.00%

    4680100001000.00%

    4780100001000.00%

    4880100001000.00%

    4980100001000.00%

    5080100001000.00%

    5180100001000.00%

    5280100001000.00%

    5380100001000.00%

    5480100001000.00%

    5510100001000.00%

    5610100001000.00%

    5710100001000.00%

    5810100001000.00%

    5910100001000.00%

    6010100001000.00%

    6110100001000.00%

    6210100001000.00%

    6310100001000.00%

    6410100001000.00%

    &L

    &F&C&"SchneiderPc,Regular"&36S&R

    &A

    &L&"Arial,Gras"Schneider Automation SA&"Arial,Normal"jhp &D &T&R

    page &P/&N

    CALCULOS

    ESTIMACIONES DE CARGA DE RED Y DE MODULO ETHERNET

    CARGA DE LA RED ETHERNET

    % CARGA DE LA RED ETHERNET DEBIDO AL IOSCANNING0.0%

    % CARGA DE LA RED ETHERNET DEBIDO AL GLOBAL DATA0.0%

    % CARGA DE LA RED ETHERNET DEBIDO A LA MENSAJERIA0.0%

    TOTAL0.0%

    CARGA DEL MODULO ETHERNET

    Peticiones/Segundo%MWs Entrada%MWs Salida

    CARGA DEL MODULO DEBIDO AL IOSCANNING1800900900

    CARGA DEL MODULO DEBIDO AL GLOBAL DATA00NO APLICA

    CARGA DEL MODULO DEBIDO A LA MENSAJERIA MODBUS TCPIP0NO APLICANO APLICA

    CARGA DE LA CPUSCAN ESTIMADO mSeg =

    Peticiones/Scan

    CARGA DEL MODULO DEBIDO A LA MENSAJERIA COMO SERVIDOR MODBUS TCPIP0

    CARGA DEL MODULO DEBIDO A LA MENSAJERIA COMO CLIENTE MODBUS TCPIP0

    Maximos :

    M340 Copro =NOM340 NOE110 = 2000Premium Copro= 2000 ETY Premium = 2000 NOE/Copro Quantum = 2000

    Maximos :

    M340 Copro = 200M340 NOE110 = 450Premium Copro= 500 ETY Premium = 450 NOE/Copro Quantum = 350

    Maximos :

    M340 Copro =NOM340 NOE110 = 800Premium Copro= 800ETY Premium = 800 NOE/Copro Quantum = 800

    Maximos :

    M340 Copro =NOM340 NOE110 = 2048Premium Copro= 4096ETY Premium = 2048NOE/Copro Quantum = ?

    Maximos :

    M340 Copro =NOM340 NOE110 = 2048Premium Copro= 4096ETY Premium = 2048NOE/Copro Quantum = ?

    Maximos :

    M340 Copro =NOM340 NOE110 = 2048Premium Copro= 2048ETY Premium = 2048NOE/Copro Quantum = 2048

    Maximos :

    M340 BMX3420 =8

    PremiumTSX570 - 1 = 4TSX572 = 8 TSX573 = 12TSX574 = 16TSX575 = 20

    Quantum = 20

    Maximos :OJO , ESTOS LIMITES SON PARA PETICIONES SIMULTANEAS HACIA EL MISMO MODULO ETHERNET COMO CLIENTE .Si no hay simultaneidad no hay limite

    M340 = ?Premium = 16Quantum = 16

    Performances

    LIMITES MODULOS Y CPUS EN LA COMUNICACIN ETHERNET

    PREMIUMM340QUANTUM

    TSXP570TSXP571TSXP572TSXP573TSXP574TSXP575ETHCoproETYPORTETY4103ETY5103WMY100BMX P3420ETHCoproNOE0100140CPU113140CPU311140CPU434/534140CPU651ETHCoproNOE77101/11NWM10000

    CPU COMO SERVIDOR

    Peticiones procesadas por scan (como server)448121620N/AN/AN/AN/AN/A8N/AN/A20202020N/AN/AN/A

    Peticiones procesadas por scan (como server) y por modulo (solo Quantum)N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A4488 NOE 16 CoproN/AN/AN/A

    CPU COMO CLIENTE

    Instrucciones de comunicacin simultaneas procesadas por el conjunto de Ports (Como cliente)161632486480N/AN/AN/AN/AN/A16N/AN/A????N/AN/AN/A

    Instrucciones de comunicacin simultaneas procesadas por cada Modulo Ethernet de comunicaciones (Como cliente)161616161616N/AN/AN/AN/AN/A16N/AN/A???16N/AN/AN/A

    MODULO ETHERNET CLIENTE/SERVIDOR

    Peticiones Modbus/Unite de Mensajeria por segundoN/AN/AN/AN/AN/AN/A500450450450450N/A200450N/AN/AN/AN/A350350350

    Lineas IOScanningN/AN/AN/AN/AN/AN/A128646464N/AN/AN/A64N/AN/AN/AN/A128128N/A

    Max %MWs IOScanning LecturaN/AN/AN/AN/AN/AN/A4096204820482048N/AN/AN/A2048N/AN/AN/AN/A40964096N/A

    Max %MWs IOScanning EscrituraN/AN/AN/AN/AN/AN/A4096204820482048N/AN/AN/A2048N/AN/AN/AN/A40964096N/A

    Transacciones Modbus IOScanning por segundoN/AN/AN/AN/AN/AN/A2000200020002000N/AN/AN/A2000N/AN/AN/AN/A20002000N/A

    N/AN/A

    Transacciones Global Data por segundoN/AN/AN/AN/AN/AN/A800800800800N/AN/AN/A800N/AN/AN/AN/A800800N/A

    Words Global Data PublicadasN/AN/AN/AN/AN/AN/A512512512512N/AN/AN/A512N/AN/AN/AN/A512512N/A

    Words Global Data SubscritasN/AN/AN/AN/AN/AN/A2048204820482048N/AN/AN/A2048N/AN/AN/AN/A20482048N/A

    MODULO ETHERNET SOCKETS

    Maximo Numero de modulos Ethernet112344N/AN/AN/AN/AN/A2N/AN/A2266N/AN/AN/A

    Maximo Numero de sockets TCP cliente abiertos simultaneamenteN/AN/AN/AN/AN/AN/A1616161616N/A1616N/AN/AN/AN/A161616

    Maximo Numero de sockets TCP Servidor abiertos simultaneamenteN/AN/AN/AN/AN/AN/A1664646464N/A1616N/AN/AN/AN/A646464

    The M1E as a server only

    171CCC96030 with IEC Exec v.1.27e installed

    No logic program. No I/O Scanner table entries.

    Isolated network. Only Modbus network traffic. PC M1E communications.

    14 server connections.

    Client program on PC - opening 14 modbus connections, reading 125 registers on each connection.

    M1E Transactions (query & response) per second ~ 2000. Multiple tests and Wireshark trace analysis showed packets per second = approximately 4000, no retries.

    The M1E as a client/server

    171CCC96030 with IEC Exec v.1.27e installed

    No logic program. 30 - I/O Scanner client entries.

    Isolated network. Only Modbus network traffic. PC (client) M1E (client/server) ENT/M1E (server) communications.

    14 server connections.

    Client program on PC - opening 14 modbus connections, reading 125 registers on each connection.

    M1E Transactions (query & response) per second ~ 1900. Multiple tests and Wireshark trace analysis showed packets per second = approximately 3700->3800, no retries.

    - Se trata del nmero mximo de peticiones Modbus y/o Unite como servidor que la CPU puede responder por cada Scan de la tarea Mast . Estas peticiones pueden llegar desde el conjunto de todos los ports de comunicacin existentes (solo ports Serie , Ethernet ,Mb+ y Fipway sin incluir buses de campo ni global data) .

    - Por tanto cuanto menor sea el scan , ms peticiones/segundo podra procesar .

    - Las peticiones como cliente no cuentan.

    - En el caso de Premium , Quantum y M340 es posible aumentar en 4 este numero (%SW90)

    - Se trata del numero mximo de instrucciones (EFs) de comunicacin que se encuentran activas simultaneamente en el programa.Una instruccion de comunicacin esta activa mientras su bit de actividad esta en estado ON o sea que esta en espera de respuesta o de time-out.

    - Incluye el conjunto de todas las vias de comunicacin

    Coincide con el maximo de equipos escrutables (Direcciones IP escrutables )

    - Maximo numero de %MWs totales IOScanning en lectura . Si por ejemplo llenamos 16 lineas IOScanning con 125 %MWs cada una , el total son 2000 %Mws leidas con lo cual estamos cerca del limite .

    - Es acumulable al de escritura

    - Maximo numero de %MWs totales IOScanning en Escritura . Si por ejemplo llenamos 20 lineas IOScanning con 100 %MWs cada una , el total son 2000 %Mws escritas con lo cual estamos cerca del limite .

    - Es acumulable al de lectura

    - Maximo numero de peticiones Modbus que el modulo puede procesar por segundo con sus respectivas respuestas -

    - Este valor representa el 100% del ancho de banda (capacidad) del modulo , por tanto llegando a este valor ya no seria posible procesar Global Data ni mensajera ya que el modulo estara saturado.

    - Por ejemplo si rellenamos 20 lineas IOScanning y el tiempo de refresco es de 10 mseg . Esto hace un total de 2000 pet/seg , que en el caso de Premium coincidiria con el mximo .

    - Maximo numero de peticiones Modbus que el modulo puede procesar por segundo con sus respectivas respuestas .

    - Este valor representa el 100% del ancho de banda (capacidad) del modulo , por tanto llegando a este valor ya no seria posible procesar Global Data ni IOScanning ya que el modulo estara saturado.

    - Por ejemplo si un supervisor (o varios) lanza este numero de peticiones por segundo , coincidiria con el mximo , y por tanto ya no seria posible procesar ningun trafico ms.

    - Maximo numero de Publicaciones/Subscripciones Global Data que el modulo puede procesar por segundo con sus respectivas respuestas

    - Este valor representa el 100% del ancho de banda (capacidad) del modulo , por tanto llegando a este valor ya no seria posible procesar IOScanning ni mensajera ya que el modulo estara saturado.

    - Por ejemplo nos subscribimos a 16 variables de 20 PLCs que son publicadas cada scan y el scan de cada PLC es de 20 mseg , esto hace un total de 800 pet/seg (50 Publicaciones/segundo por PLC ) , que en el caso de Premium coincidiria con el mximo .

    - Se trata del numero mximo de instrucciones (EFs) de comunicacin que se encuentran activas simultaneamente en el programa .

    Una instruccion de comunicacin esta activa mientras su bit de actividad esta en estado ON o sea que esta en espera de respuesta o de time-out.

    - Por ejemplo en un PLC TSXP573634 con un modulo ETYPORT + 1 ETY5103 podremos tener 16 Read_Var activos hacia el ETYPORT + 16 Read_Var activos hacia el ETY5103. En total 32 , cuando el maximo total son 48.

    Incluido el Port Ethernet integrado en la CPU si es el caso

    - Se trata de las peticiones Modbus y/o Unite que llegan al PLC desde el conjunto de todos los ports de comunicacin (solo ports serie, Ethernet y Mb+, sin incluir buses de campo ni global data) .

    - Por tanto cuanto menor sea el scan , ms peticiones/segundo podra procesar .

    - Las peticiones como cliente no cuentan.

    - Es posible aumentar en 4 este numero (%SW90)

    - Solo incluye sockets de mensajera (los de IOScanning van aparte y no cuentan)

    - Se trata de Sockets como cliente (peticiones mediante instrucciones de programa que el realiza hacia otros equipos)

    - Solo incluye sockets de mensajera (los de IOScanning van aparte y no cuentan)

    - Se trata de Sockets como Servidor (Sockets abiertos por supervisores , otros PLCs etc )

    Maximo total Cliente + Servidor = 64 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente + Servidor = 64 sockets

    Maximo total Cliente + Servidor = 64 sockets

    Maximo total Cliente + Servidor = 64 sockets

    Maximo total Cliente + Servidor = 64 sockets

    Maximo total Cliente + Servidor = 64 sockets

    Maximo total Cliente + Servidor = 64 sockets

    Para Ethernet el limite lo marca el numero de sockets maximo por cada modulo como cliente.

    Para Ethernet el limite lo marca el numero de sockets maximo por cada modulo como cliente.

    Para Ethernet el limite lo marca el numero de sockets maximo por cada modulo como cliente.

    Para Ethernet el limite lo marca el numero de sockets maximo por cada modulo como cliente.

    Incluido el Eth Copro incluido en la CPU.O sea solo es posible aadir un modulo NOE

    Logicamente coincide con el numero maximo de sockets simultaneos como cliente del modulo Ethernet

    Logicamente coincide con el numero maximo de sockets simultaneos como cliente del modulo Ethernet

    Logicamente coincide con el numero maximo de sockets simultaneos como cliente del modulo Ethernet

    Logicamente coincide con el numero maximo de sockets simultaneos como cliente del modulo Ethernet

    Logicamente coincide con el numero maximo de sockets simultaneos como cliente del modulo Ethernet

    Logicamente coincide con el numero maximo de sockets simultaneos como cliente del modulo Ethernet

    El limite lo marca la suma de modulos Ethernet por el numero mximo de sockets de cada modulo como cliente (16)

    - Maximo numero de palabras que una tarjeta Ethernet puede publicar

    Maximo numero de palabras a las que una tarjeta Ethernet puede subscribirse

    - Maximo Peticiones Modbus procesadas por scan de CPU y por Modulo NOE de comunicaciones . OJO , Solo para el caso de la peticion modbus 03 (lectura de %MWs o 40xxx) . Para el caso de lectura/escritura de bits :

    - CPU113 = 1 pet/scan- CPU311 = 1 pet/scan- CPU434 = 4 pet/scan- CPU534 = 4 pet/scan- CPU651 = 4 pet/scan con NOE 16 pet/scan Copro

    - Maximo Peticiones Modbus procesadas por scan de CPU y por Modulo NOE de comunicaciones . OJO , Solo para el caso de la peticion modbus 03 (lectura de %MWs o 40xxx) . Para el caso de lectura/escritura de bits :

    - CPU113 = 1 pet/scan- CPU311 = 1 pet/scan- CPU434 = 4 pet/scan- CPU534 = 4 pet/scan- CPU651 = 4 pet/scan con NOE 16 pet/scan Copro

    - Maximo Peticiones Modbus procesadas por scan de CPU y por Modulo NOE de comunicaciones . OJO , Solo para el caso de la peticion modbus 03 (lectura de %MWs o 40xxx) . Para el caso de lectura/escritura de bits :

    - CPU113 = 1 pet/scan- CPU311 = 1 pet/scan- CPU434 = 4 pet/scan- CPU534 = 4 pet/scan- CPU651 = 4 pet/scan con NOE 16 pet/scan Copro

    - Maximo Peticiones Modbus procesadas por scan de CPU y por Modulo NOE de comunicaciones . OJO , Solo para el caso de la peticion modbus 03 (lectura de %MWs o 40xxx) . Para el caso de lectura/escritura de bits : - CPU113 = 1 pet/scan- CPU311 = 1 pet/scan- CPU434 = 4 pet/scan- CPU534 = 4 pet/scan- CPU651 = 4 pet/scan con NOE 16 pet/scan Copro

    NOTA : En el caso de tramas UMAS la NOE soporta mximo 260 bytes de datos por trama. El copro soporta 1030 bytes.

    Para Ethernet el limite lo marca el numero de sockets maximo por cada modulo como cliente.

    Para Ethernet el limite lo marca el numero de sockets maximo por cada modulo como cliente.

    Para Ethernet el limite lo marca el numero de sockets maximo por cada modulo como cliente.

    ETY Exec.

    Exec.

    This sheet only list Premium Ethernet Unity module's firmware version and their features and fixes.

    It doesn't list Premium Ethernet PL7 modules' firmware due to the not-publish policy (explain in the ETY Upgrade Processure sheet)

    VersionTSXETY4103TSXETY5103TSX P57 1634MTSX P57 2634MTSX P57 3634MTSX P57 4634MTSX P57 5634M

    LatestV3.1V3.1V3.1V3.1V3.1V2.0V2.0

    PreviousV3.0V3.0V3.0V3.0V3.0

    ETY Module List

    SoftwareModule

    PL7TSXETY110

    TSXETY110WS

    TSXETY210

    TSXETY410

    TSXETY510

    TSXETY4102

    TSXETY5102

    TSX P57 2623M

    TSX P57 2823M

    TSX P57 3623M

    TSX P57 4823M

    UNITY PROTSXETY4103

    TSXETY5103

    TSX P571634M

    TSX P57 2634M

    TSX P57 3634M

    TSX P57 4634M

    TSX P57 5634M

    New Features & Enhancements:1. Added new Email service (SMTP component)2. Support new version of MIB(V1.2)3. Enhance I/O Scanner Timeout and Retry Transmission algorithm4. Add I/O Scanner Entry enable/disable functionality5.IO Scanner can work through a router6. Support Unity V2.0

    New Features & Enhancements:1. Added new Email service (SMTP component)2. Support new version of MIB(V1.2)3. Enhance I/O Scanner Timeout and Retry Transmission algorithm4. Add I/O Scanner Entry enable/disable functionality5.IO Scanner can work through a router6. Support Unity V2.0

    New Features & Enhancements:1. Added NTP functionnality (only in Unity V2.0 System)2. Added Email functionnality3. Added I/O Scanner Enable/Disable feature4. Dynamic allocation of Port number for the I/O scanner connection5. I/O Scanners now support routers (gateway implementation added to I/O scanner)6. Enhance I/O Scanner Timeout and Retry Transmission algorithm7. Support Unity V2.0

    Units Suitable for UpgradingAll TSXETY5103 units currently running Exec V3.0 or later.

    New Features & Enhancements:1. Added Email functionnality2. Added I/O Scanner Enable/Disable feature3. Dynamic allocation of Port number for the I/O scanner connection4. I/O Scanners now support routers (gateway implementation added to I/O scanner)5. Enhance I/O Scanner Timeout and Retry Transmission algorithm6. Support Unity V2.0

    Units Suitable for UpgradingAll TSXETY4103 units currently running Exec V3.0 or later.

    New Features & Enhancements:1. Added Email functionnality2. Added I/O Scanner Enable/Disable feature3. Dynamic allocation of Port number for the I/O scanner connection4. I/O Scanners now support routers (gateway implementation added to I/O scanner)5. Enhance I/O Scanner Timeout and Retry Transmission algorithm6. Support Unity V2.0

    Units Suitable for UpgradingAll TSX P57 1634M units currently running Exec V3.0 or later.

    New Features & Enhancements:1. Added Email functionnality2. Added I/O Scanner Enable/Disable feature3. Dynamic allocation of Port number for the I/O scanner connection4. I/O Scanners now support routers (gateway implementation added to I/O scanner)5. Enhance I/O Scanner Timeout and Retry Transmission algorithm6. Support Unity V2.0

    Units Suitable for UpgradingAll TSX P57 2634M units currently running Exec V3.0 or later.

    New Features & Enhancements:1. Added Email functionnality2. Added I/O Scanner Enable/Disable feature3. Dynamic allocation of Port number for the I/O scanner connection4. I/O Scanners now support routers (gateway implementation added to I/O scanner)5. Enhance I/O Scanner Timeout and Retry Transmission algorithm6. Support Unity V2.0

    Units Suitable for UpgradingAll TSX P57 3634M units currently running Exec V3.0 or later.

    New Features & Enhancements:1. Fix the problem of I/O Scanning and global data servers are always running without checking the status of CPU.2. Fix the problem that ETY in a high end CPUD does not receive its first configuration, ETY remains in Not conf state after downloading the application.3. Support Unity V1.0

    Units Suitable for UpgradingAll TSX ETY 4103 units with a version higher than V2.0 IE25. The required minimum level of bootrom is V2.0 IE 09

    New Features & Enhancements:1. Fix the problem of I/O Scanning and global data servers are always running without checking the status of CPU.2. Fix the problem that ETY in a high end CPUD does not receive its first configuration, ETY remains in Not conf state after downloading the application.3. Support Unity V1.0

    Units Suitable for UpgradingAll TSX ETY 5103 units with a version higher than V2.0 IE25. The required minimum level of bootrom is V2.0 IE 09

    New Features & Enhancements:1. Fix the problem of I/O Scanning and global data servers are always running without checking the status of CPU.2. Fix the problem that ETY in a high end CPUD does not receive its first configuration, ETY remains in Not conf state after downloading the application.3. Support Unity V1.0

    Units Suitable for UpgradingAll TSX P57 1634M units with a version higher than V2.0 IE25. The required minimum level of bootrom is V2.0 IE 09

    New Features & Enhancements:1. Fix the problem of I/O Scanning and global data servers are always running without checking the status of CPU.2. Fix the problem that ETY in a high end CPUD does not receive its first configuration, ETY remains in Not conf state after downloading the application.3. Support Unity V1.0

    Units Suitable for UpgradingAll TSX P57 2634M units with a version higher than V2.0 IE25. The required minimum level of bootrom is V2.0 IE 09

    New Features & Enhancements:1. Fix the problem of I/O Scanning and global data servers are always running without checking the status of CPU.2. Fix the problem that ETY in a high end CPUD does not receive its first configuration, ETY remains in Not conf state after downloading the application.3. Support Unity V1.0

    Units Suitable for UpgradingAll TSX P57 3634M units with a version higher than V2.0 IE25. The required minimum level of bootrom is V2.0 IE 09

    NOE Exec.

    Exec.

    List all Quantum Ethernet modules' firmware versions and their features and fixes.

    Not all the versions link directly to pl@net since not all of them have been pulished there yet.

    Some links may have been disconnected due to the directory change of pl@net.

    Version140 NOE 77111140 NOE 77101140 NOE 77110140 NOE 77100140 CPU 651 50140 CPU 651 60

    Unity ProConceptUnity ProConcept

    LastestV3.5V3.5V3.5V3.5V3.3V3.4V2.0V2.0

    PreviousV3.3V3.3V3.3V3.3V3.0V3.3

    V3.2V3.2V3.2V3.2V2.1V3.0

    V3.1V3.1V3.1V3.1V2.0V2.1

    V3.0V3.0V3.0V3.0V1.2V2.0

    V2.0V2.0V1.02V1.2

    V1.4V1.4V1.01V1.02

    V1.3V1.3V1.0V1.01

    V1.2V1.2V0.5V1.0

    V1.1V1.1V0.5

    V1.0.V1.0

    NOE Module List

    SoftwareModule

    Concept140 NOE 77111

    140 NOE 77101

    140 NOE 77100

    140 NOE 77110

    Unity Pro140 NOE 77111

    140 NOE 77101

    140 CPU 651 50

    140 CPU 651 60

    New Features & Enhancements:1. Priority of the IPconfig task was increased from 100 to 35. To allow the gateway to be configured before the NOE can accept requests from other devices.2. IOScanners now support routers (gateway implementation added to ioscanner) 3. Change server fast retransmission

    Units Suitable for UpgradingAll 140NOE77111 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features & Enhancements:1. Added Email functionnality2. Added NTP functionnality (only in Unity V2.0 System)3. Added IO Scanner Enable/Disable feature4. Dynamic allocation of Port number for the IO scanner connection5. Modbus Server improvments: - accept up to 8 FC 3,16 or 23 per scan - accept up to 4 other function code per scan (with Unity V2.0 CPU)6. Support Unity V2.0

    Units Suitable for UpgradingAll 140NOE77111 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features and Enhancements:1. New retransmission algorithm 2. Keep alive checksum correction3. Change server retransmission retry time from 1.2 seconds to .5msec (Vxworks bug)

    Units Suitable for UpgradingAll 140NOE77111 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features & Enhancements:1. Fixed problem with BOOTP client2. Fixed problems with Address Server configuration3. Send error to MSTR block on connection reset4. Fixed problem with I/O scanner dropping packets due to high load of traffic.

    Units Suitable for UpgradingAll 140NOE77111 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features & Enhancements:1. Added Unity Support2. Added FC23 client and server support3. Returns Incorrect ModbusTCP Function Code with Response4. Fixed the problem that Modsoft MSTR causes unexpected 4x reg to change when NOE in rack

    New Features & Enhancements:1. Added Email functionnality2. Added NTP functionnality (only in Unity V2.0 System)3. Added IO Scanner Enable/Disable feature4. Dynamic allocation of Port number for the IO scanner connection5. Modbus Server improvments: - accept up to 8 FC 3,16 or 23 per scan - accept up to 4 other function code per scan (with Unity V2.0 CPU)

    Units Suitable for UpgradingAll 140NOE77111 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features & Enhancements:1. Priority of the IPconfig task was increased from 100 to 35. To allow the gateway to be configured before the NOE can accept requests from other devices.2. IOScanners now support routers (gateway implementation added to ioscanner) 3. Change server fast retransmission

    Units Suitable for UpgradingAll 140NOE77111 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features and Enhancements:1. New retransmission algorithm 2. Keep alive checksum correction3. Change server retransmission retry time from 1.2 seconds to .5msec (Vxworks bug)

    Units Suitable for UpgradingAll 140NOE77111 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features & Enhancements:1. Fixed problem with BOOTP client2. Fixed problems with Address Server configuration3. Send error to MSTR block on connection reset4. Fixed problem with I/O scanner dropping packets due to high load of traffic.

    Units Suitable for UpgradingAll 140NOE77111 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features & Enhancements:1. Added Unity Support2. Added FC23 client and server support3. Returns Incorrect ModbusTCP Function Code with Response4. Fixed the problem that Modsoft MSTR causes unexpected 4x reg to change when NOE in rack

    Units Suitable for UpgradingAll 140NOE77111 units currently running Kernel V2.0 and Exec V2.0 or later.

    Internal/External Release of NOE 77111 Executive Code

    Internal/External Release of NOE 77111 Executive Code

    Internal/External Release of NOE 77111 Executive Code.Changes on NOE77101 apply indifferently to NOE77111

    New Fix:This version is based on the 1.1 version with the fix for the TCP user hanging problem.

    New Fix:Fix problem with ioscanner configuration on new application's download

    New Features & Enhancements:1.Added HotStandby feature2. Fix NOE module crash problem when project downloaded.3. Fix MSTR blocks are processed serially when connected to same device4.Fix Module will reboot if send an HTTP or FTP request with to many characters.5. Fix Inconsistent results when NOE771 IP address is duplicated on network.6. Fix the failure of the Modbus Client on Startup/Changeover of a Hot Standby System7. Fix Modbus FC 23 does not work with a MSTR block8. Fix Ethernet I/O scanner health block not updated 9. Fix Aborting a 984LL MSTR Block will Cause the NOE module to Reboot

    Units Suitable for UpgradingAll 140NOE77111 units below exec. V2.0. But Upgrading to V2.0 will require to update the kernel to V2.0

    New Features & Enhancements:1. Added Email functionality2. Added IO Scanner Enable/Disable feature3. Dynamic allocation of Port number for the IO scanner connection4. Modbus Server improvements: - Accept up to 8 FC 3,16 or 23 per scan - Accept up to 4 other function code per scan (with Unity V2.0 CPU)5. Support Unity V2.0

    Units Suitable for UpgradingAll 140NOE77101 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features & Enhancements:1. Added Email functionnality2. Added IO Scanner Enable/Disable feature3. Dynamic allocation of Port number for the IO scanner connection4. Modbus Server improvments: - accept up to 8 FC 3,16 or 23 per scan - accept up to 4 other function code per scan (with Unity V2.0 CPU)

    Units Suitable for UpgradingAll 140NOE77101 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features & Enhancements:1. Priority of the IPconfig task was increased from 100 to 35. To allow the gateway to be configured before the NOE can accept requests from other devices.2. IOScanners now support routers (gateway implementation added to ioscanner) 3. Change server fast retransmission

    Units Suitable for UpgradingAll 140NOE77101 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features & Enhancements:1. Priority of the IPconfig task was increased from 100 to 35. To allow the gateway to be configured before the NOE can accept requests from other devices.2. IOScanners now support routers (gateway implementation added to ioscanner) 3. Change server fast retransmission

    Units Suitable for UpgradingAll 140NOE77101 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features & Enhancements:1. New retransmission algorithm 2. Keep alive checksum correction3. Change server retransmission retry time from 1.2 seconds to .5msec (Vxworks bug)

    Units Suitable for UpgradingAll 140NOE77101 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features & Enhancements:1. Added Unity Support2. Added FC23 client and server support3. Returns Incorrect ModbusTCP Function Code with Response4. Fixed the problem that Modsoft MSTR causes unexpected 4x reg to change when NOE in rack

    New Features & Enhancements:1. Added Unity Support2. Added FC23 client and server support3. Returns Incorrect ModbusTCP Function Code with Response4. Fixed the problem that Modsoft MSTR causes unexpected 4x reg to change when NOE in rack

    Units Suitable for UpgradingAll 140NOE77111 units currently running Kernel V2.0 and Exec V2.0 or later.

    New Features & Enhancements:1. Fixed problem with BOOTP client2. Fixed problems with Address Server configuration3. Send error to MSTR block on connection reset4. . Fixed problem with I/O scanner dropping packets due to high load of traffic.

    Units Suitable for UpgradingAll 140NOE77101 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features & Enhancements:1. New retransmission algorithm 2. Keep alive checksum correction3. Change server retransmission retry time from 1.2 seconds to .5msec (Vxworks bug)

    Units Suitable for UpgradingAll 140NOE77101 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features & Enhancements:1. Fixed problem with BOOTP client2. Fixed problems with Address Server configuration3. Send error to MSTR block on connection reset4. . Fixed problem with I/O scanner dropping packets due to high load of traffic.

    Units Suitable for UpgradingAll 140NOE77101 units currently running Kernel V2.0 and Exec V3.0 or later.

    New Features & Enhancements:1.Added HotStandby feature2. NOE Module Crashes when Project Downloaded.3. MSTR blocks are processed serially when connected to same device4.Module will reboot if send an HTTP or FTP request with to many characters.5. Inconsistent results when NOE771 IP address is duplicated on network.6. Failure of the Modbus Client on Startup/Changeover of a Hot Standby System7. Modbus FC 23 does not work with a MSTR block8.Ethernet I/O scanner health block not updated (See Resolution E8085)9. Aborting a 984LL MSTR Block will Cause the NOE module to Reboot

    Units Suitable for UpgradingAll 140NOE77111 units below exec. V2.0. But Upgrading to V2.0 will require to update the kernel to V2.0

    New Fix:fix problem with ioscanner configuration on new application's download

    New Fix:This version is based on the 1.1 version with the fix for the TCP user hanging problem.

    Internal/External Release of NOE 77101 Executive Code

    Internal/External Release of NOE 77101 Executive Code

    Internal/External Release of NOE 77101 Executive Code

    New Features & Enhancements:1.A new and improved Timeout and Retry Transmission algorithm has been added to the I/Oscanner client. If the connection to a device is disturbed, the retransmission requests are now sent to the device with adaptive timing and instead of with fixed timing. 2. An error was corrected in the calculation of the Keep alive checksum.3. Change server retransmission retry time from 1.2 seconds to .5msec 4 . Priority of the IPconfig task was increased from 100 to 35. This allows the gateway to be configured before the NOE can accept requests from other devices. 5. The I/O scanner now support routers. This allows I/O scanning over different network domains that are linked by a network router (maximum TTL of 10). 6. Changed Modbus server to implement a fast retransmission algorithm This upgrade can be downloaded directly to v3.0 units. Modules with lower versions must be upgraded to V3.0 before going to V3.3

    Units Suitable for Upgrading:The existing NOE Executive version must be v3.0 or higher and kernel v3.0 or higher.

    New Features & Enhancements:1. reduces the NOE boot time significantly2. Replacement of the BOOTP server with a DHCP server, which is a superset of BOOTP server.3. allows Modbus/TCP Client and Server together to have 64 connections 4. fixes OPR 20011764 - NOE Module Crashes when Project Downloaded.5. fixes OPR 20010780 - MSTR blocks are processed serially when connected to same device6. fixes OPR 20001978 - Inconsistent results when NOE771 IP address is duplicated on network.7. fixes OPR 20010489 - Failure of the Modbus Client on Startup/Changeover of a Hot Standby System8.fixes OPR 20009207 - Modbus FC 23 does not work with a MSTR block9.fixes OPR 20014607 - Aborting a 984LL MSTR BLock will Cause the NOE module to Reboot10.fixes OPR 20017337 - Modsoft MSTR causes unexpected 4x reg to change when NOE in rack11.supports the Schneider Electric OS Loader FTP protocol12.fixes OPR 20013777 - Download causes NOE reboot13.is based on newer version of Tornado and VxWorks (Tornado V2 and VxWorks V5.4)

    Units Suitable for Upgrading:The existing NOE Executive version must be v2.xx, kernel v2.0

    New Features & Enhancements:1. OPR 20003348 - "crashing" is fixed2. OPR 20003359 - fixed when Hot-Standby is not configured(i.e. CHS not present)3. OPR 20002326 - MSTR error codes are fixed4. Fixes MB+ "Selected path does not exist" and TCP/IP "Timed-out waiting for response from controller" after Exec is downloaded by the Concept ExecLoader5. Sets the System Object ID to a value indicating Schneider's Quantum NOE to allow recognition by SNMP Managers

    Units Suitable for UpgradingAll 140NOE77100 units currently running Kernel V2.0 and Exec V2.0.NOTE:Upgrading to NOE771x0 to Version 2.1 from a pre 2.0 version will require you to update the NOE771x0 Kernel. To load the Kernel, the Executive needs to be version 2.00 or greater. If the Executive is less than 2.00 you must load the Version 2.00 Executive before you load the Kernel.

    New Features & Enhancements:1. OPR 20002266 - HotStandby run properly2. Supports Concept EXECLoader for new kernel(version >= 2.00) download and installation3. OPR 20002973 - Default gateway parameter is now set correctly4. Allows final octet IP address to the range 1-253 in HotStandby applications5. Automatic reconfiguration of IP address

    Units Suitable for UpgradingAll 140NOE77110 units currently running Exec V1.x or later.NOTE: Upgrading to NOE7710 to Version 2.0 will require you to update the NOE77110 Kernel to v2.0. To load the Kernel, the Executive needs to be version 2.00 or greater. If the Executive is less than 2.00 you must load the Version 2.00 Executive before you load the Kernel.

    New Features & Enhancements:1. is based on newer version of Tornado and VxWorks (Tornado V2 and VxWorks V5.4)2. reduces the NOE boot time significantly3. replaces the BOOTP server with a DHCP server with the role name entry hidden4. allows both I/O scanner and hot-standby to work concurrently 5. allows Modbus/TCP Client and Server together to have 64 connections 6. fixes OPR 20015082 - NOE reports corrupt data with heavy load of I/O Scanner traffic7. fixes OPR 20014702 - 77101 Returns Incorrect Modbus TCP Function Code with Response8. fixes OPR 20011764 - NOE Module Crashes when Project Downloaded.9. fixes OPR 20010780 - MSTR blocks are processed serially when connected to same device10.fixes OPR 20001978 - Inconsistent results when NOE771 IP address is duplicated on network.11.fixes OPR 20010489 - Failure of the Modbus Client on Startup/Changeover of a Hot Standby System12.fixes OPR 20009207 - Modbus FC 23 does not work with a MSTR block13.fixes OPR 20003239 - Ethernet I/O scanner health block for NOE 771 00 not updated14.fixes OPR 20014442 - Ethernet I/O scanner health block for NOE 771 x1 not updated 15.fixes OPR 20014607 - Aborting a 984LL MSTR BLock will Cause the NOE module to Reboot16.fixes OPR 20014307 - IP Address Issue - NOE Reboot17.fixes OPR 20017337 - Modsoft MSTR causes unexpected 4x reg to change when NOE in rack18.supports the Schneider Electric OS Loader FTP protocol19.fixes OPR 20013657 - TCP retransmission incorrect on the I/O Scanner20.fixes OPR 20017077 - I/O Scanner dropped packets21.fixes OPR 20013777 - Download causes NOE reboot22.fixes OPR 20015217 - Problems found during the v2.20 exec qualification

    Units Suitable for Upgrading:The existing NOE Executive version must be v2.xx, kernel v2.0

    New Features & Enhancements:1. Supports telnet sessions.2. Updates arp table when a gratitious arp is received.3. OPR 20001479 - Fixed Bug with Client and Server under heavy loads4. Adds Timestamp to the Crash Log.5. OPR 20001968 - Fixed 10.0.0.1 Problem. The NOE now uses the default IP during the Duplicate IP Addr Test.6. OPR 20001758 - Fixed the Module ID problem.7. OPR 20001480 - (Actually fixed below see #4, 1.02 release). Login will work with connection lost.8. OPR 20002271 - Fixed a miscompare after having done a cycle of power to the PLC system or after hotswapping the NOE module.9. OPR 20002125 - Fixed a limit of 4 web connections when GDE or RDE used.10.OPR 20002057 - Fixed a spontaneous reset problem. 11.OPR 20002039 - Fixed. The Executive now supports new micro rev D4.

    Units Suitable for UpgradingAll 140NOE77110 units currently running exec. V1.xx

    New Features & Enhancements:1. Changes to the Exec URL for flash formating.2. Changes to reduce the Socket timeout.3. Change to cause Exec to goto Kernel if File System can't be read.4. OPR 20001102 fixed login/logout during a disconnect

    Units Suitable for UpgradingAll 140NOE77110 units currently running exec. V1.xx

    New Features & Enhancements:Changed status bit from CPU running to NOE running

    Units Suitable for UpgradingAll 140NOE77110 units currently running exec. V1.xx

    New Features & Enhancements:1. MIB set commands timed out: Task Priority Change2. Fix 802.3 Failure: Modified MTU and HDRLEN in IP layer3. Fix several problems with the Ethernet Driver. 4. Fix Module Resets with Heavy IO Scan Load at Low CPU Scan Rates: Changed Short Stack Notification Method

    Internal/External Release of NOE 77100-10 Executive Code

    New Features & Enhancements:1. Resolved NOE reconnect issue after a com failure (log in bit for programming panel).2. Fixed NOE problem that had the NOE going to default address when cable is removed.

    Units Suitable for Upgrading:The existing NOE Executive version must be v3.0 or higher and kernel v3.0 or higher.

    New Features & Enhancements:1. OPR 20003348 - "crashing" is fixed2. OPR 20003359 - fixed when Hot-Standby is not configured(i.e. CHS not present)3. OPR 20002326 - MSTR error codes are fixed4. Fixes MB+ "Selected path does not exist" and TCP/IP "Timed-out waiting for response from controller" after Exec is downloaded by the Concept ExecLoader5. Sets the System Object ID to a value indicating Schneider's Quantum NOE to allow recognition by SNMP Managers

    Units Suitable for UpgradingAll 140NOE77100 units currently running Kernel V2.0 and Exec V2.0.NOTE:Upgrading to NOE771x0 to Version 2.1 from a pre 2.0 version will require you to update the NOE771x0 Kernel. To load the Kernel, the Executive needs to be version 2.00 or greater. If the Executive is less than 2.00 you must load the Version 2.00 Executive before you load the Kernel.

    New Features & Enhancements:1. OPR 20002266 - HotStandby run properly2. Supports Concept EXECLoader for new kernel(version >= 2.00) download and installation3. OPR 20002973 - Default gateway parameter is now set correctly4. Allows final octet IP address to the range 1-253 in HotStandby applications5. Automatic reconfiguration of IP address

    Units Suitable for UpgradingAll 140NOE77110 units currently running Exec V1.x or later.NOTE: Upgrading to NOE7710 to Version 2.0 will require you to update the NOE77110 Kernel to v2.0. To load the Kernel, the Executive needs to be version 2.00 or greater. If the Executive is less than 2.00 you must load the Version 2.00 Executive before you load the Kernel.

    New Features & Enhancements:1. Supports telnet sessions.2. Updates arp table when a gratitious arp is received.3. OPR 20001479 - Fixed Bug with Client and Server under heavy loads.4. Adds Timestamp to the Crash Log.5. OPR 20001968 - Fixed 10.0.0.1 Problem. The NOE now uses the default IP during the Dup IP Addr Test.6. OPR 20001480 - Fixed login/logout during a disconnection.7. OPR 20002271 - Fixed a miscompare after having done a cycle of power to the PLC system or after hotswapping the NOE module.8. OPR 20002057 - Fixed a spontaneous reset problem. 9. OPR 20002039 - Fixed. The Executive now supports new micro Rev D4.10.Fixed IO Scanner problem described in OPR 20002264 & 20002286.

    Units Suitable for UpgradingAll 140NOE77110 units currently running exec. V1.xx

    New Features & Enhancements:Changed meaning of status bit from CPU running to NOE running.

    Units Suitable for UpgradingAll 140NOE77110 units currently running exec. V1.xx

    New Features & Enhancements:Correct transmit lockup. When all buffers were allocated, the semaphore was not free locking all future transmits.

    Units Suitable for UpgradingAll 140NOE77110 units currently running exec. V1.xx

    New Features & Enhancements:1. MIB set commands timed out: Task Priority Change2. Fix 802.3 Failure: Modified MTU and HDRLEN in IP layer3. Fix several problems with the Ethernet Driver. 4. Fix Module Resets with Heavy IO Scan Load at Low CPU Scan Rates: Changed Short Stack Notification Method

    Internal/External Release of NOE 77100 Executive Code

    New Features & Enhancements:1.A new and improved Timeout and Retry Transmission algorithm has been added to the I/Oscanner client. If the connection to a device is disturbed, the retransmission requests are now sent to the device with adaptive timing and instead of with fixed timing. 2. An error was corrected in the calculation of the Keep alive checksum.3. Change server retransmission retry time from 1.2 seconds to .5msec 4 . Priority of the IPconfig task was increased from 100 to 35. This allows the gateway to be configured before the NOE can accept requests from other devices. 5. The I/O scanner now support routers. This allows I/O scanning over different network domains that are linked by a network router (maximum TTL of 10). 6. Changed Modbus server to implement a fast retransmission algorithm

    Units Suitable for Upgrading:The existing NOE Executive version must be v3.0 or higher and kernel v3.0 or higher.

    New Features & Enhancements:1. Added new Email service (SMTP component)2. Support new version of MIB(V1.2)3. Enhance I/O Scanner Timeout and Retry Transmission algorithm4. Add I/O Scanner Entry enable/disable functionality5.IO Scanner can work through a router6. Support Unity V2.0

    New Features & Enhancements:1. Added new Email service (SMTP component)2. Support new version of MIB(V1.2)3. Enhance I/O Scanner Timeout and Retry Transmission algorithm4. Add I/O Scanner Entry enable/disable functionality5.IO Scanner can work through a router6. Support Unity V2.0

    V3.5

    V3.5

    V3.5

    V3.5

    V3.4

    V3.1

    V3.1

    V3.1

    V3.1

    V3.0

    V3.0

    V2.0

    V2.0

    V2.1

    V2.1

    V2.0

    V2.0

    V1.2

    V1.2

    V1.02

  • Gua de Uso

    Software PLC Communications Diagnostics (PLCDiagComm)

    Centro de Competencia Tcnica

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    El software PLCDiagComm (PLC Diagnostic Communications) es una herramienta que nos permite acceder a los datos de ocupacin de recursos de los puertos ethernet de las plataformas de autmatas programables TSX Premium, TSX Quantum y BMX M340 de Schneider Electric.

    Tambin permite comparar dichos datos de ocupacin con los parmetros tericos marcados como lmites de funcionamiento de los mismos puertos ethernet.

    Qu se necesita para utilizar sta herramienta?

    El uso de sta herramienta requiere estar conectado online va ethernet al propio puerto que se quiere diagnosticar; por sta razn esta comunicacin afecta a las estadsticas que pueden observarse (es una conexin ms con un nmero de transacciones determinado) y hay que tenerla en cuenta en su estudio.

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Procedimiento de conexin:

    1- Indicar la direccin IP de conexin (activar la opcin Puerto USB si la conexin se realiza a travs de ste tipo de puerto).

    2- Conectar.

    1

    2

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Se sabe que la conexin se ha realizado correctamente si el led de conexin est verde.

    Tambin en la pantalla de diagnstico indica el estado de la conexin.

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Adems, el apartado Modo PLC indicar si la CPU asociada al puerto en estudio est en marcha (RUN) o detenida (STOP).

    Finalmente se puede verificar si la conexin es del todo correcta o hay errores de comunicacin que la dificultan.

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Informacin del PLC asociado al puerto ethernet de conexin. Se obtienen datos bsicos de la CPU (versin de frmware y hardware, modelo, ) as como de la aplicacin contenida en la misma.

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Informacin de la aplicacin contenida en el PLC: versin de software usada en la creacin del proyecto y versin usada en la ltima modificacin.

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Puesta en marcha (RUN) y parada (STOP) del PLC.

    Reinicio en fro del PLC.

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Tabla de carga del puerto ethernet:

    1

    3

    2

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Tabla de carga del puerto ethernet: carga de la CPU como servidor MB/TCP.

    Informacin a obtener:- Peticiones por ciclo de scan (valor actual, mximo y lmite mximo para sa CPU).- Peticiones por segundo (valor actual, mximo y lmite mximo para sa CPU).- Ciclo de scan de la CPU (ltimo, mximo y mnimo).- Nmero de tramas de comunicacin correctas/incorrectas

    1

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Procedimiento de conexin: tiempo de refresco.

    Gestin del tiempo de refresco de la visualizacin de datos. ste tiempo es configurable y tiene dos modos:- Automtico (Auto): se selecciona de forma automtica el tiempo ptimo de refresco de la informacin.- Manual: se puede seleccionar, mediante el selector deslizante, el tiempo de refresco de la informacin.

    Hay que tener en cuenta que a mayor tiempo de refresco ms cantidad de trfico genera el software PLCDiagComm contra el puerto al que se est diagnosticando, dato que hay que tener en cuenta a la hora de estudiar la carga de dicho puerto.

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Procedimiento de conexin: carga del mdulo ethernet diagnosticado.

    Informacin a obtener:- Cantidad de transacciones en curso gestionadas por el puerto ethernet diagnosticado; stas transacciones se separan segn los servicios a los que estn asociadas:- IOScanning.- Mensajera acclica.- Global Data.

    Acceso al Web Server del puerto diagnosticado

    2

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Procedimiento de conexin: nmero de sockets.

    Informacin a obtener: Cantidad de conexiones (sockets) establecidas por el puerto ethernet diagnosticado tanto cuando acta como servidor MB/TCP como si lo hace como cliente MB/TCP. El nmero total de sockets abiertos no puede superar el mximo indicado.

    Indicacin de si el filtro de control de acceso al puerto est configurado o no.

    3

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Tablas de comunicacin:

    1

    3

    2

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Conexiones de mensajera TCP/IP:

    Bsicamente, indica la cantidad y el tipo de transacciones de mensajera acclica que el puerto ethernet diagnosticado gestiona bien como cliente (tipo 1), bien como servidor (tipo 2).Tambin se indica la IP del dispositivo destinatario o emisor de cada transaccin, as como el puerto de envo y destino del mensaje.

    1

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Conexiones asociadas al servicio IOScanning:

    Cantidad y tipo de transacciones del servicio IOScanning que el puerto ethernet diagnosticado gestiona tanto de lectura como de escritura.Se indica la cantidad de registros de lectura/escritura configurados para cada transaccin, la direccin IP del destinatario o del origen de la informacin y el tiempo de refresco de la misma.Finalmente, se detalla si la transaccin configurada est fallando (status 2) o est funcionando correctamente (status 1).

    2

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Conexiones asociadas al servicio Global Data:

    Bsicamente, se indica la cantidad y tipo de transacciones del servicio Global Data que el puerto ethernet diagnosticado gestiona.Se separan las transacciones de registros publicados (escritos) y suscritos (ledos), as como los direcciones de origen o destino de dichos mensajes, as como el grupo de intercambio al que se asocia cada uno.

    3

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Las limitaciones en lo que se refiere a las capacidades de comunicaciones ethernet de un PLC son restricciones que vienen dadas tanto por parte de la CPU como de los propios puertos ethernet.

    CPU: La limitacin se refiere al nmero mximo de peticiones por ciclo de scan que es capaz de gestionar el dispositivo CPU; hay que tener en cuenta que, finalmente, todas las peticiones del PLC las gestiona la CPU, por lo que sta limitacin es ms restrictiva sobre otras referentes al los puertos ethernet (por ejemplo, puede darse el caso que la suma de las peticiones que son capaces de gestionar el conjunto de todos los mdulos ethernet configurados en un PLC supere al nmero de peticiones que la CPU del mismo PLC es capaz de gestionar; en ste caso, la limitacin ms restrictiva de la CPU es la que marca el lmite aceptado por el total del PLC).

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Puertos ethernet: La limitacin depende bsicamente del nmero de peticiones por segundo disponibles y utilizados para cada servicio asociado a ste puerto.- Mensajera acclica.- IOScanning.- Global data.

    Otros lmites a tener en cuenta: - Nmero de lneas de IOSCanner disponibles para el puerto.- Nmero de instrucciones/peticiones de mensajera simultneas posibles en cada puerto.- Nmero de mdulos ethernet configurados en el PLC.- Nmero de sockets (conexiones) abiertos en cada puerto.

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Existe un lmite total de transacciones para una conexin ethernet, que es diferente segn el tipo de puerto del cual se trate; ste lmite es la mxima restriccin para la totalidad de todos los servicios disponibles y viene dado por el valor de mxima capacidad en cada caso. Por ejemplo, un dispositivo (TSXETY4103) tiene los siguientes lmites:

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Para ste mdulo, y segn sus caractersticas, posibles casos pueden ser:

    - Si se configuran 2000 peticiones/segundo de IOScanning, no queda ancho de banda en el dispositivo para ningn otro servicio.

    - Si se configuran 450 peticiones/segundo MB/Unite de mensajera acclica (el mximo posible), restan 1550 para el conjunto de servicios (IOScannig y Global Data).

    - Si se configuran 700 transacciones/segundo del Global Data y 1100 transacciones/segundo de IOScanning, resta una capacidad de 200 peticiones/segundo para el servicio de mensajera.

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    El registro de estado %SW90 del PLC se puede modificar (est configurado segn un valor por defecto) para definir el nmero mximo de peticiones que la CPU puede procesar cada ciclo de scan; modificar ste valor afecta, lgicamente, al ciclo de scan.

    Schneider Electric

    *

    - Centro Competencia Tcnica - Jordi Moreno - Julio 2008 - Rev. 1

    PLCDiagComm

    Lmites de los puertos ethernet:El propio software incorpora una tabla (hoja en formato Excel) en el que se detallan los lmites que tiene cada puerto ethernet.

    Leeme

    El objetivo es realizar una estimacion de carga de la propia red Ethernet , el modulo Ethernet y la CPU

    Para ello hay que rellenar los campos en amarillo de las 3 primeras hojas (IOScanning , Mbus-Msg y Global Data)

    En la Hoja CALCULOS se muestran los resultados

    La hoja Performances expresa todos los limites a la hora de comunicar en Ehernet con los PLCs

    Las Hojas ETY y NOE muestra las prestaciones de las diferentes versiones de tarjetas

    The M1E as a server only

    171CCC96030 with IEC Exec v.1.27e installed

    No logic program. No I/O Scanner table entries.

    Isolated network. Only Modbus network traffic. PC M1E communications.

    14 server connections.

    Client program on PC - opening 14 modbus connections, reading 125 registers on each connection.

    M1E Transactions (query & response) per second ~ 2000. Multiple tests and Wireshark trace analysis showed packets per second = approximately 4000, no retries.

    The M1E as a client/server

    171CCC96030 with IEC Exec v.1.27e installed

    No logic program. 30 - I/O Scanner client entries.

    Isolated network. Only Modbus network traffic. PC (client) M1E (client/server) ENT/M1E (server) communications.

    14 server connections.

    Client program on PC - opening 14 modbus connections, reading 125 registers on each connection.

    M1E Transactions (query & response) per second ~ 1900. Multiple tests and Wireshark trace analysis showed packets per second = approximately 3700->3800, no retries.

    IOS_Bdw

    IO Scanner Service :TOTALTOTALMediumTOTAL

    Througput and Bandwith computationThroughputThroughputBandwidthUsed

    in Kbyte/sin Kbit/sin Mbit/sBandwidth

    001000.0%

    List of Published VariablesRequestResponseMediumUsed

    N SlaveT_RefreshRd_sizeWr_sizeFrame+IPGFrame+IPGThroughputThroughputBandwidthBandwidth

    128 maxin msin wordsin wordsin bytesin bytesin byte/sin bit/sin Mbit/sin %

    15000000001000.000%

    25000000001000.00%

    35000000001000.00%

    45000000001000.00%

    55000000001000.00%

    65000000001000.00%

    75000000001000.00%

    85000000001000.00%

    95000000001000.00%

    105000000001000.00%

    115000000001000.00%

    125000000001000.00%

    135000000001000.00%

    145000000001000.00%

    155000000001000.00%

    165000000001000.00%

    175000000001000.00%

    185000000001000.00%

    19100000001000.00%

    20100000001000.00%

    21100000001000.00%

    22100000001000.00%

    23100000001000.00%

    24100000001000.00%

    25100000001000.00%

    26100000001000.00%

    27100000001000.00%

    28100000001000.00%

    29100000001000.00%

    30100000001000.00%

    31100000001000.00%

    32100000001000.00%

    33100000001000.00%

    34100000001000.00%

    35100000001000.00%

    36100000001000.00%

    37100000001000.00%

    38100000001000.00%

    39100000001000.00%

    40100000001000.00%

    41100000001000.00%

    42100000001000.00%

    43100000001000.00%

    44100000001000.00%

    45100000001000.00%

    46100000001000.00%

    47100000001000.00%

    48100000001000.00%

    49100000001000.00%

    50100000001000.00%

    51100000001000.00%

    52100000001000.00%

    53100000001000.00%

    54100000001000.00%

    55100000001000.00%

    56100000001000.00%

    57100000001000.00%

    58100000001000.00%

    59100000001000.00%

    60100000001000.00%

    61100000001000.00%

    62100000001000.00%

    63100000001000.00%

    64100000001000.00%

    65100000001000.00%

    66100000001000.00%

    67100000001000.00%

    68100000001000.00%

    69100000001000.00%

    70100000001000.00%

    71100000001000.00%

    72100000001000.00%

    73100000001000.00%

    74100000001000.00%

    75100000001000.00%

    76100000001000.00%

    77100000001000.00%

    78100000001000.00%

    79100000001000.00%

    80100000001000.00%

    81100000001000.00%

    82100000001000.00%

    83100000001000.00%

    84100000001000.00%

    85100000001000.00%

    86100000001000.00%

    87100000001000.00%

    88100000001000.00%

    89100000001000.00%

    90100000001000.00%

    91100000001000.00%

    92100000001000.00%

    93100000001000.00%

    94100000001000.00%

    95100000001000.00%

    96100000001000.00%

    97100000001000.00%

    98100000001000.00%

    99100000001000.00%

    100100000001000.00%

    101100000001000.00%

    102100000001000.00%

    103100000001000.00%

    104100000001000.00%

    105100000001000.00%

    106100000001000.00%

    107100000001000.00%

    108100000001000.00%

    109100000001000.00%

    110100000001000.00%

    111100000001000.00%

    112100000001000.00%

    113100000001000.00%

    114100000001000.00%

    115100000001000.00%

    116100000001000.00%

    117100000001000.00%

    118100000001000.00%

    119100000001000.00%

    120100000001000.00%

    121100000001000.00%

    122100000001000.00%

    123100000001000.00%

    124100000001000.00%

    125100000001000.00%

    126100000001000.00%

    127100000001000.00%

    128100000001000.00%

    &L

    &F&C&"SchneiderPc,Regular"&36S&R

    &A

    &L&"Arial,Gras"Schneider Automation SA&"Arial,Normal"jhp &D &T&R

    page &P/&N

    MBus-Msg_Bdw

    Modbus TCP/IP Messaging Service

    TOTALTOTALMediumTOTAL

    Ancho de banda consumido como ServidorThroughputThroughputBandwidthUsed

    in Kbyte/sin Kbit/sin Mbit/sBandwidth

    001000.0%

    List of Transactions, Requests and/or ResponsesRequestResponseMediumUsed

    N SlaveT_RefreshRd_sizeWr_sizeFrame+IPGFrame+IPGThroughputThroughputBandwidthBandwidth

    128 maxin msin wordsin wordsin bytesin bytesin byte/sin bit/sin Mbit/sin %

    1100000001000.000%

    2100000001000.00%

    3100000001000.00%

    4100000001000.00%

    5100000001000.00%

    6100000001000.00%

    7100000001000.00%

    8100000001000.00%

    9100000001000.00%

    10100000001000.00%

    11100000001000.00%

    12100000001000.00%

    13100000001000.00%

    14100000001000.00%

    15100000001000.00%

    16100000001000.00%

    17100000001000.00%

    18100000001000.00%

    19100000001000.00%

    20100000001000.00%

    21100000001000.00%

    22100000001000.00%

    23100000001000.00%

    24100000001000.00%

    25100000001000.00%

    26100000001000.00%

    27100000001000.00%

    28100000001000.00%

    29100000001000.00%

    TOTALTOTALMediumTOTAL

    Ancho de banda consumido como ClienteThroughputThroughputBandwidthUsed

    in Kbyte/sin Kbit/sin Mbit/sBandwidth

    001000.0%

    List of Transactions, Requests and/or ResponsesRequestResponseMediumUsed

    N SlaveT_RefreshRd_sizeWr_sizeFrame+IPGFrame+IPGThroughputThroughputBandwidthBandwidth

    128 maxin msin wordsin wordsin bytesin bytesin byte/sin bit/sin Mbit/sin %

    1100000001000.000%

    2100000001000.00%

    3100000001000.00%

    4100000001000.00%

    5100000001000.00%

    6100000001000.00%

    7100000001000.00%

    8100000001000.00%

    9100000001000.00%

    10100000001000.00%

    11100000001000.00%

    12100000001000.00%

    13100000001000.00%

    14100000001000.00%

    15100000001000.00%

    16100000001000.00%

    17100000001000.00%

    18100000001000.00%

    19100000001000.00%

    20100000001000.00%

    21100000001000.00%

    22100000001000.00%

    23100000001000.00%

    24100000001000.00%

    25100000001000.00%

    26100000001000.00%

    27100000001000.00%

    28100000001000.00%

    29100000001000.00%

    &L

    &F&C&"SchneiderPc,Regular"&36S&R

    &A

    &L&"Arial,Gras"Schneider Automation SA&"Arial,Normal"jhp &D &T&R

    page &P/&N

    GD1_Bdw

    Global Data Service :TOTALTOTALMediumTOTAL

    Througput and Bandwith computationThroughputThroughputBandwidthUsed

    Group address :255.0.0.3in Kbyte/sin Kbit/sin Mbit/sBandwidth

    Group Name :Group_64S001000.0%

    List of Published VariablesMediumUsed

    N VarT_MastDisp_PSize_VFrame+IGPThroughputThroughputBandwidthBandwidth

    64 maxin msNbr Scanin wordsin bytesin byte/sin bit/sin Mbit/s

    110100001000.00%

    210100001000.00%

    310100001000.00%

    410100001000.00%

    510100001000.00%

    610100001000.00%

    710100001000.00%

    810100001000.00%

    910100001000.00%

    1010100001000.00%

    1150100001000.00%

    1280100001000.00%

    1380100001000.00%

    1480100001000.00%

    1580100001000.00%

    1680100001000.00%

    1780100001000.00%

    1880100001000.00%

    1980100001000.00%

    2080100001000.00%

    2180100001000.00%

    2280100001000.00%

    2380100001000.00%

    2480100001000.00%

    2580100001000.00%

    2680100001000.00%

    2780100001000.00%

    2880100001000.00%

    2980100001000.00%

    3080100001000.00%

    3180100001000.00%

    3280100001000.00%

    3380100001000.00%

    3480100001000.00%

    3580100001000.00%

    3680100001000.00%

    3780100001000.00%

    3880100001000.00%

    3980100001000.00%

    4080100001000.00%

    4180100001000.00%

    4280100001000.00%

    4380100001000.00%

    4480100001000.00%

    4580100001000.00%

    4680100001000.00%

    4780100001000.00%

    4880100001000.00%

    4980100001000.00%

    5080100001000.00%

    5180100001000.00%

    5280100001000.00%

    5380100001000.00%

    5480100001000.00%

    5510100001000.00%

    5610100001000.00%

    5710100001000.00%

    5810100001000.00%

    5910100001000.00%

    6010100001000.00%

    6110100001000.00%

    6210100001000.00%

    6310100001000.00%

    6410100001000.00%

    &L

    &F&C&"SchneiderPc,Regular"&36S&R

    &A

    &L&"Arial,Gras"Schneider Automation SA&"Arial,Normal"jhp &D &T&R

    page &P/&N

    CALCULOS

    ESTIMACIONES DE CARGA DE RED Y DE MODULO ETHERNET

    CARGA DE LA RED ETHERNET

    % CARGA DE LA RED ETHERNET DEBIDO AL IOSCANNING0.0%

    % CARGA DE LA RED ETHERNET DEBIDO AL GLOBAL DATA0.0%

    % CARGA DE LA RED ETHERNET DEBIDO A LA MENSAJERIA0.0%

    TOTAL0.0%

    CARGA DEL MODULO ETHERNET

    Peticiones/Segundo%MWs Entrada%MWs Salida

    CARGA DEL MODULO DEBIDO AL IOSCANNING1800900900

    CARGA DEL MODULO DEBIDO AL GLOBAL DATA00NO APLICA

    CARGA DEL MODULO DEBIDO A LA MENSAJERIA MODBUS TCPIP0NO APLICANO APLICA

    CARGA DE LA CPUSCAN ESTIMADO mSeg =

    Peticiones/Scan

    CARGA DEL MODULO DEBIDO A LA MENSAJERIA COMO SERVIDOR MODBUS TCPIP0

    CARGA DEL MODULO DEBIDO A LA MENSAJERIA COMO CLIENTE MODBUS TCPIP0

    Maximos :

    M340 Copro =NOM340 NOE110 = 2000Premium Copro= 2000 ETY Premium = 2000 NOE/Copro Quantum = 2000

    Maximos :

    M340 Copro = 200M340 NOE110 = 450Premium Copro= 500 ETY Premium = 450 NOE/Copro Quantum = 350

    Maximos :

    M340 Copro =NOM340 NOE110 = 800Premium Copro= 800ETY Premium = 800 NOE/Copro Quantum = 800

    Maximos :

    M340 Copro =NOM340 NOE110 = 2048Premium Copro= 4096ETY Premium = 2048NOE/Copro Quantum = ?

    Maximos :

    M340 Copro =NOM340 NOE110 = 2048Premium Copro= 4096ETY Premium = 2048NOE/Copro Quantum = ?

    Maximos :

    M340 Copro =NOM340 NOE110 = 2048Premium Copro= 2048ETY Premium = 2048NOE/Copro Quantum = 2048

    Maximos :

    M340 BMX3420 =8

    PremiumTSX570 - 1 = 4TSX572 = 8 TSX573 = 12TSX574 = 16TSX575 = 20

    Quantum = 20

    Maximos :OJO , ESTOS LIMITES SON PARA PETICIONES SIMULTANEAS HACIA EL MISMO MODULO ETHERNET COMO CLIENTE .Si no hay simultaneidad no hay limite

    M340 = ?Premium = 16Quantum = 16

    Performances

    LIMITES MODULOS Y CPUS EN LA COMUNICACIN ETHERNET

    PREMIUMM340QUANTUM

    TSXP570TSXP571TSXP572TSXP573TSXP574TSXP575ETHCoproETYPORTETY4103ETY5103WMY100BMX P3420ETHCoproNOE0100140CPU113140CPU311140CPU434/534140CPU651ETHCoproNOE77101/11NWM10000

    CPU COMO SERVIDOR

    Peticiones procesadas por scan (como server)448121620N/AN/AN/AN/AN/A8N/AN/A20202020N/AN/AN/A

    Peticiones procesadas por scan (como server) y por modulo (solo Quantum)N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A4488 NOE 16 CoproN/AN/AN/A

    CPU COMO CLIENTE

    Instrucciones de comunicacin simultaneas procesadas por el conjunto de Ports (Como cliente)161632486480N/AN/AN/AN/AN/A16N/AN/A????N/AN/AN/A

    Instrucciones de comunicacin simultaneas procesadas por cada Modulo Ethernet de comunicaciones (Como cliente)161616161616N/AN/AN/AN/AN/A16N/AN/A???16N/AN/AN/A

    MODULO ETHERNET CLIENTE/SERVIDOR

    Peticiones Modbus/Unite de Mensajeria por segundoN/AN/AN/AN/AN/AN/A500450450450450N/A200450N/AN/AN/AN/A350350350

    Lineas IOScanningN/AN/AN/AN/AN/AN/A128646464N/AN/AN/A64N/AN/AN/AN/A128128N/A

    Max %MWs IOScanning LecturaN/AN/AN/AN/AN/AN/A4096204820482048N/AN/AN/A2048N/AN/AN/AN/A40964096N/A

    Max %MWs IOScanning EscrituraN/AN/AN/AN/AN/AN/A4096204820482048N/AN/AN/A2048N/AN/AN/AN/A40964096N/A

    Transacciones Modbus IOScanning por segundoN/AN/AN/AN/AN/AN/A2000200020002000N/AN/AN/A2000N/AN/AN/AN/A20002000N/A

    N/AN/A

    Transacciones Global Data por segundoN/AN/AN/AN/AN/AN/A800800800800N/AN/AN/A800N/AN/AN/AN/A800800N/A

    Words Global Data PublicadasN/AN/AN/AN/AN/AN/A512512512512N/AN/AN/A512N/AN/AN/AN/A512512N/A

    Words Global Data SubscritasN/AN/AN/AN/AN/AN/A2048204820482048N/AN/AN/A2048N/AN/AN/AN/A20482048N/A

    MODULO ETHERNET SOCKETS

    Maximo Numero de modulos Ethernet112344N/AN/AN/AN/AN/A2N/AN/A2266N/AN/AN/A

    Maximo Numero de sockets TCP cliente abiertos simultaneamenteN/AN/AN/AN/AN/AN/A1616161616N/A1616N/AN/AN/AN/A161616

    Maximo Numero de sockets TCP Servidor abiertos simultaneamenteN/AN/AN/AN/AN/AN/A1664646464N/A1616N/AN/AN/AN/A646464

    The M1E as a server only

    171CCC96030 with IEC Exec v.1.27e installed

    No logic program. No I/O Scanner table entries.

    Isolated network. Only Modbus network traffic. PC M1E communications.

    14 server connections.

    Client program on PC - opening 14 modbus connections, reading 125 registers on each connection.

    M1E Transactions (query & response) per second ~ 2000. Multiple tests and Wireshark trace analysis showed packets per second = approximately 4000, no retries.

    The M1E as a client/server

    171CCC96030 with IEC Exec v.1.27e installed

    No logic program. 30 - I/O Scanner client entries.

    Isolated network. Only Modbus network traffic. PC (client) M1E (client/server) ENT/M1E (server) communications.

    14 server connections.

    Client program on PC - opening 14 modbus connections, reading 125 registers on each connection.

    M1E Transactions (query & response) per second ~ 1900. Multiple tests and Wireshark trace analysis showed packets per second = approximately 3700->3800, no retries.

    - Se trata del nmero mximo de peticiones Modbus y/o Unite como servidor que la CPU puede responder por cada Scan de la tarea Mast . Estas peticiones pueden llegar desde el conjunto de todos los ports de comunicacin existentes (solo ports Serie , Ethernet ,Mb+ y Fipway sin incluir buses de campo ni global data) .

    - Por tanto cuanto menor sea el scan , ms peticiones/segundo podra procesar .

    - Las peticiones como cliente no cuentan.

    - En el caso de Premium , Quantum y M340 es posible aumentar en 4 este numero (%SW90)

    - Se trata del numero mximo de instrucciones (EFs) de comunicacin que se encuentran activas simultaneamente en el programa.Una instruccion de comunicacin esta activa mientras su bit de actividad esta en estado ON o sea que esta en espera de respuesta o de time-out.

    - Incluye el conjunto de todas las vias de comunicacin

    Coincide con el maximo de equipos escrutables (Direcciones IP escrutables )

    - Maximo numero de %MWs totales IOScanning en lectura . Si por ejemplo llenamos 16 lineas IOScanning con 125 %MWs cada una , el total son 2000 %Mws leidas con lo cual estamos cerca del limite .

    - Es acumulable al de escritura

    - Maximo numero de %MWs totales IOScanning en Escritura . Si por ejemplo llenamos 20 lineas IOScanning con 100 %MWs cada una , el total son 2000 %Mws escritas con lo cual estamos cerca del limite .

    - Es acumulable al de lectura

    - Maximo numero de peticiones Modbus que el modulo puede procesar por segundo con sus respectivas respuestas -

    - Este valor representa el 100% del ancho de banda (capacidad) del modulo , por tanto llegando a este valor ya no seria posible procesar Global Data ni mensajera ya que el modulo estara saturado.

    - Por ejemplo si rellenamos 20 lineas IOScanning y el tiempo de refresco es de 10 mseg . Esto hace un total de 2000 pet/seg , que en el caso de Premium coincidiria con el mximo .

    - Maximo numero de peticiones Modbus que el modulo puede procesar por segundo con sus respectivas respuestas .

    - Este valor representa el 100% del ancho de banda (capacidad) del modulo , por tanto llegando a este valor ya no seria posible procesar Global Data ni IOScanning ya que el modulo estara saturado.

    - Por ejemplo si un supervisor (o varios) lanza este numero de peticiones por segundo , coincidiria con el mximo , y por tanto ya no seria posible procesar ningun trafico ms.

    - Maximo numero de Publicaciones/Subscripciones Global Data que el modulo puede procesar por segundo con sus respectivas respuestas

    - Este valor representa el 100% del ancho de banda (capacidad) del modulo , por tanto llegando a este valor ya no seria posible procesar IOScanning ni mensajera ya que el modulo estara saturado.

    - Por ejemplo nos subscribimos a 16 variables de 20 PLCs que son publicadas cada scan y el scan de cada PLC es de 20 mseg , esto hace un total de 800 pet/seg (50 Publicaciones/segundo por PLC ) , que en el caso de Premium coincidiria con el mximo .

    - Se trata del numero mximo de instrucciones (EFs) de comunicacin que se encuentran activas simultaneamente en el programa .

    Una instruccion de comunicacin esta activa mientras su bit de actividad esta en estado ON o sea que esta en espera de respuesta o de time-out.

    - Por ejemplo en un PLC TSXP573634 con un modulo ETYPORT + 1 ETY5103 podremos tener 16 Read_Var activos hacia el ETYPORT + 16 Read_Var activos hacia el ETY5103. En total 32 , cuando el maximo total son 48.

    Incluido el Port Ethernet integrado en la CPU si es el caso

    - Se trata de las peticiones Modbus y/o Unite que llegan al PLC desde el conjunto de todos los ports de comunicacin (solo ports serie, Ethernet y Mb+, sin incluir buses de campo ni global data) .

    - Por tanto cuanto menor sea el scan , ms peticiones/segundo podra procesar .

    - Las peticiones como cliente no cuentan.

    - Es posible aumentar en 4 este numero (%SW90)

    - Solo incluye sockets de mensajera (los de IOScanning van aparte y no cuentan)

    - Se trata de Sockets como cliente (peticiones mediante instrucciones de programa que el realiza hacia otros equipos)

    - Solo incluye sockets de mensajera (los de IOScanning van aparte y no cuentan)

    - Se trata de Sockets como Servidor (Sockets abiertos por supervisores , otros PLCs etc )

    Maximo total Cliente + Servidor = 64 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente = 16 sockets

    Maximo total Cliente + Servidor = 64 sockets

    Maximo total Cliente + Servidor = 64 sockets

    Maximo total Cliente + Servidor = 64 sockets

    Maximo total Cliente + Servidor = 64 sockets

    Maximo total Cliente + Servidor = 64 sockets

    Maximo total Cliente + Servidor = 64 sockets

    Para Ethernet el limite lo marca el numero de sockets maximo por cada modulo como cliente.

    Para Ethernet el limite lo marca el numero de sockets maximo por cada modulo como cliente.

    Para Ethernet el limite lo marca el numero de sockets maximo por cada modulo como cliente.

    Para Ethernet el limite lo marca el numero de sockets maximo por cada modulo como cliente.

    Incluido el Eth Copro incluido en la CPU.O sea solo es posible aadir un modulo NOE

    Logicamente coincide con el numero maximo de sockets simultaneos como cliente del modulo Ethernet

    Logicamente coincide con el numero maximo de sockets simultaneos como cliente del modulo Ethernet

    Logicamente coincide con el numero maximo de sockets simultaneos como cliente del modulo Ethernet

    Logicamente coincide con el numero maximo de sockets simultaneos como cliente del modulo Ethernet

    Logicamente coincide con el numero maximo de sockets simultaneos como cliente del modulo Ethernet

    Logicamente coincide con el numero maximo de sockets simultaneos como cliente del modulo Ethernet

    El limite lo marca la suma de modulos Ethernet por el numero mximo de sockets de cada modulo como cliente (16)

    - Maximo numero de palabras que una tarjeta Ethernet puede publicar

    Maximo numero de palabras a las que una tarjeta Ethernet puede subscribirse

    - Maximo Peticiones Modbus procesadas por scan de CPU y por Modulo NOE de comunicaciones . OJO , Solo para el caso de la peticion modbus 03 (lectura de %MWs o 40xxx) . Para el caso de lectura/escritura de bits :

    - CPU113 = 1 pet/scan- CPU311 = 1 pet/scan- CPU434 = 4 pet/scan- CPU534 = 4 pet/scan- CPU651 = 4 pet/scan con NOE 16 pet/scan Copro

    - Maximo Peticiones Modbus procesadas por scan de CPU y por Modulo NOE de comunicaciones . OJO , Solo para el caso de la peticion modbus 03 (lectura de %MWs o 40xxx) . Para el caso de lectura/escritura de bits :

    - CPU113 = 1 pet/scan- CPU311 = 1 pet/scan- CPU434 = 4 pet/scan- CPU534 = 4 pet/scan- CPU651 = 4 pet/scan con NOE 16 pet/scan Copro

    - Maximo Peticiones Modbus procesadas por scan de CPU y por Modulo NOE de comunicaciones . OJO , Solo para el caso de la peticion modbus 03 (lectura de %MWs o 40xxx) . Para el caso de lectura/escritura de bits :

    - CPU113 = 1 pet/scan- CPU311 = 1 pet/scan- CPU434 = 4 pet/scan- CPU534 = 4 pet/scan- CPU651 = 4 pet/scan con NOE 16 pet/scan Copro

    - Maximo Peticiones Modbus procesadas por scan de CPU y por Modulo NOE de comunicaciones . OJO , Solo para el caso de la peticion modbus 03 (lectura de %MWs o 40xxx) . Para el caso de lectura/escritura de bits : - CPU113 = 1 pet/scan- CPU311 = 1 pet/scan- CPU434 = 4 pet/scan- CPU534 = 4 pet/scan- CPU651 = 4 pet/scan con NOE 16 pet/scan Copro

    NOTA : En el caso de tramas UMAS la NOE soporta mximo 260 bytes de datos por trama. El copro soporta 1030 bytes.

    Para Ethernet el limite lo marca el numero de sockets maximo por cada modulo como cliente.