  • 8/17/2019 Gangguan Di PLTM

    1/1

    Location:

    Engineer:Study Case:  SM

    12.6.0HPage: 1

    SN:

    Filename: Kandibata 1_rev01

    Project: ETAP

    Contract:  

    Date: 28-04-2016 

    Revision: Base

    Config.: Terhubung

     Sequence-of-Operation Event Summary Report

    ID If (kA)Time (ms)

    Symmetrical Line-to-Line Fault at BUS PLTM.

    T1 (ms) T2 (ms) Condition

    50.0 Relay1 2.586 50.0 Phase - OC1 - 50

    60.0 Relay2 2.586 60.0 Phase - OC1 - 50

    60.0 CB9 10.0 Tripped by Relay1 Phase - OC1 - 50

    70.0 CB8 10.0 Tripped by Relay2 Phase - OC1 - 50

    100 VR1 100 Undervoltage - 27

    110 CB9 10.0 Tripped by VR1 Undervoltage - 27

    2000 VR1 2000 Undervoltage - 27

    Koordinasi Relay Saat Gangguan di PLTM