Gangguan Di GI
1
Location: Engineer: Study Case: SM 12.6.0H Page: 1 SN: Filename: Kandibata 1_rev01 Project: ETAP Contract: Date: 28-04-2016 Revision: Base Config.: Terhubung Sequence - of - Operation Event Summary Report ID If (kA) Time (ms) Symmetrical Line-to-Line Fault at Bus_TD1. T1 (ms) T2 (ms) Condition 100 VR1 100 Undervoltage - 27 110 CB9 10.0 Tripped by VR1 Undervoltage - 27 766 Relay1 0.940 766 Phase - OC1 - 51 766 Relay2 0.940 766 Phase - OC1 - 51 776 CB8 10.0 Tripped by Relay2 Phase - OC1 - 51 776 CB9 10.0 Tripped by Relay1 Phase - OC1 - 51 2000 VR1 2000 Undervoltage - 27 Koordinasi Relay Saat Gangguan di GI
Transcript of Gangguan Di GI
Location:
Engineer:Study Case: SM
12.6.0HPage: 1
SN:
Filename: Kandibata 1_rev01
Project: ETAP
Contract:
Date: 28-04-2016
Revision: Base
Config.: Terhubung
Sequence - of - Operation Event Summary Report
ID If (kA)Time (ms)
Symmetrical Line-to-Line Fault at Bus_TD1.
T1 (ms) T2 (ms) Condition
100 VR1 100 Undervoltage - 27
110 CB9 10.0 Tripped by VR1 Undervoltage - 27
766 Relay1 0.940 766 Phase - OC1 - 51
766 Relay2 0.940 766 Phase - OC1 - 51
776 CB8 10.0 Tripped by Relay2 Phase - OC1 - 51
776 CB9 10.0 Tripped by Relay1 Phase - OC1 - 51
2000 VR1 2000 Undervoltage - 27
Koordinasi Relay Saat Gangguan di GI