FMM- 4-20mA I56-2991-002

download FMM- 4-20mA I56-2991-002

of 2

Transcript of FMM- 4-20mA I56-2991-002

  • 8/19/2019 FMM- 4-20mA I56-2991-002

    1/2

    FMM-4-20

    4-20mA Analog Input Module

    BEFORE INSTALLING

    This information is included as a quick reference installation guide. Refer tothe control panel installation manual for detailed system information. If the

    modules will be installed in an existing operational system, inform the opera-

    tor and local authority that the system will be temporarily out of service. Dis-

    connect power to the control panel before installing the modules.

    NOTICE: This manual should be left with the owner/user of this equipment.

    GENERAL DESCRIPTION

    The FMM-4-20 4-20mA Analog Input Module is intended for use in intelligent,

    two-wire systems, where the individual address of each module is selected

    using the built-in rotary switches. This module allows intelligent panels to

    interface and monitor two-wire or three-wire sensors, that produce a 4-20mA

    signal output. It transmits the status (normal, open, or alarm) of one sensor

    back to the control panel. The FMM-4-20 has a panel controlled LED indicator.

    Only one sensor can be connected to the FMM-4-20.

    COMPATIBILITY REQUIREMENTS

    To ensure proper operation, this module shall be connected to a compatible

    Notifier system control panel only (list available from Notifier). In addition,

    please refer to Notifier Device Compatibility document number 15378 for the

    list of compatible devices.

    FIGURE 1. CONTROLS AND INDICATORS:

    C0218-05

    SPECIFICATIONS

    SLC

      Normal Operating Voltage: 15 to 32 VDC

      Maximum Current Draw: 9.3 mA (LED on)

      Average Operating Current: 1 mA (LED flashing)

    External Supply

      Normal Operating Voltage: 24 VDC Nominal

      Standby Current: 10 mA

      Maximum Current: 510 mA

    Initiating Device

      Maximum Current: 500 mA

    Temperature Range: –10°C to 60°C

    Humidity: 10% to 95% Non-condensing

    Dimensions: 41/2˝ H × 4˝ W × 11/4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.)

    Accessories: SMB500 Electrical Box

    NO-460-003 1 I56-2991-002

    12 Clintonville Road

    Northford, CT 06472-1653

    Phone: 203.484.7161

    INSTALLATION AND MAINTENANCE INSTRUCTIONS

    MOUNTING

    The FMM-4-20 mounts directly to 4-inch square electrical boxes (see Figure2). The box must have a minimum depth of 21/8  inches. Surface mounted

    electrical boxes (SMB500) are available from Notifier.

    FIGURE 2. MODULE MOUNTING:

    C0449-0

    WIRING

    NOTE: All wiring must conform to applicable local codes, ordinances, and

    regulations. This module is intended for powerlimited wiring only.

    1. Install module wiring in accordance with the job drawings and appropri

    ate wiring diagrams.

    2. Set the address on the module per job drawings.

    3. Secure module to electrical box (supplied by installer), Figure 2.

  • 8/19/2019 FMM- 4-20mA I56-2991-002

    2/2

    NO-460-003 2 I56-2991-002©2008 Notifie

    Figure 3. 4-20mA Module 3-wire Configuration:

      (   +  )

      (   –  )

      (   +  )

      (   –  )

      (   +  )

      (   –  )

    TERMINAL WIRING MUSTBE POWER LIMITED.

    TO NEXTDEVICE

    FMM-4-20EMODULE SIGNAL LINE CIRCUIT (SLC)

    32 VDC MAX.TWISTED PAIR

    IS RECOMMENDED

    CONNECT MODULES TO LISTEDCOMPATIBLE CONTROL PANELS ONLY.

    FROM PANELOR PREVIOUS

    DEVICE

    SLC WIRING

    ( - )

    SENSE

    ( + ){TO 4-20mA

    3-WIREDEVICE

    DO NOT LOOP WIRE UNDERTERMINALS. BREAK ALL WIRE

    RUNS TO PROVIDE SUPERVISIONOF CONNECTIONS.

    24 VDC POWERLIMITED( + ) ( - )

    24 VDC POWERSUPPLY ISOLATED,

    REGULATED, POWERLIMITED.

    TO NEXTMODULE

    C0994-0

    Figure 4. 4-20mA Module 2-wire Configuration:

      (   +  )

      (   –  )

      (   +  )

      (   –  )

      (   +  )

      (   –  )

    TERMINAL WIRING MUST BEPOWER LIMITED.

    DO NOT LOOP WIRE UNDERTERMINALS. BREAK ALL WIRE

    RUNS TO PROVIDE SUPERVISIONOF CONNECTIONS.

    FMM-4-20EMODULE

    TO NEXTDEVICE

    SIGNAL LINE CIRCUIT (SLC)32 VDC MAX.

    TWISTED PAIRIS RECOMMENDED

    CONNECT MODULES TO LISTEDCOMPATIBLE CONTROL PANELS ONLY.

    FROM PANELOR PREVIOUS

    DEVICE

    SLC WIRING

    24 VDC POWERLIMITED( + ) ( - )

    ( – ) SENSE

    ( + )

    {TO 4-20mA

    2-WIRE DEVICE

    24 VDC POWER SUPPLYISOLATED, REGULATED,

    POWER LIMITED.

    TO NEXTMODULE

    C0995-0