Electrical Machines

179
ФЕДЕРАЛЬНОЕ АГЕНТСТВО ПО ОБРАЗОВАНИЮ Государственное образовательное учреждение высшего профессионального образования «Томский политехнический университет» ___________________________________________________________________________________________ Ш.С. Ройз, В.М. Игнатович, Н.Г.Новикова ELECTRICAL MACHINES Учебное пособие Издательство ТПУ Томск 2006

description

Учебное пособиеИздательство ТПУТомск

Transcript of Electrical Machines

  • ___________________________________________________________________________________________

    .. , .. , ..

    ELECTRICAL MACHINES

    2006

  • 621.313 31 .., .., .. 31 ELECTRICAL MACHINES: . : -

    , 2006. 176 .

    ISBN , ,

    . . 3-

    621.313

    -

    , .

    , ..

    , 2006

    ISBN : , 2006

  • 3

    PREFACE Electrical Engineering is a dynamic profession, which provides the expertise to meet technical challenges facing the nation. Electrical Engineering concerns generation, supply, distribution, application and their automation. The electrical engineer is often a key figure in different industries. Electrical machine is the main type of converter of mechanical energy into electric, and electric into mechanical, one, as well as one form of electric energy into another one, different in voltage, current and sometimes in frequency. It has played, during the entire historic period of electrical engineering development, a leading role, which has mapped out progress in different fields and, particularly, in the branch termed heavy-current engineering. Continuous improvements in the design of electrical machines have made many new practical applications possible and have become strong impulses for further progress and more diverse use of electric energy. This account for fact that electrical machine was given great attention to by scientists and engineers and that electrical machines attained technical perfection of design so soon. This textbook is intended for studying the course Electrical Machines for students, who go through the Bachelor Degree Program in Electrical Engineering. Students study this course in the fifth semester. The course is based on the higher mathematics, physics, engineering graphics knowledge, mechanics and measurement. The textbook is intended mainly for students, who have already taken courses TEE 201, 202 Electric Circuit Theory, INCABE 202 Electrical Engineering Materials. All important concepts of magnetism, electricity and electromagnetic conversion theory are explained. The mathematical language is as simple as possible. The textbook is based on the classical series of the textbooks on Electrical Machines by A.I. Voldek, M.P. Kostenko and L.M. Piotrovsky, B.F. Tokarev, M.M. Katsman and it consists of the following topics:

    1. Transformers. 2. Induction Machines. 3. Synchronous Machines. 4. Direct Current Machines.

    The topic "Transformers" includes the following questions: elements of construction; basic voltage equations; schemes and group of transformers winding coupling; distribution of load between transformers and etc. The topic "Induction Machines" includes the following questions: elements of construction; rotating magnetic field, voltage equations of induction motor; energetic diagrams of active and reactive power, induction motor torques, starting and regulation of rotation frequency three-phase induction motor and etc.

  • 4

    The topic '' Synchronous Machines' includes information about construction and basic principle of a synchronous machine operation, magnetic field of excitation winding, reaction of armature, voltage vector diagrams of synchronous generators, synchronous motors and compensators. The authors welcome yours suggestions for improvements of future editions of this textbook. The topic '' Direct Current Machines' includes information about basic elements of D.C. Machine construction and principle of their action; the process of commutation in D.C. Machines; characteristics of direct current generators and motors. The authors welcome your suggestions for improvements of future editions of this textbook.

  • 1. TRANSFORMERS

    Transformer is a static electromagnetic device with two (or more)

    inductively linked windings intended for transforming one (primary) an

    alternating current system to another (secondary) one by means of

    electromagnetic induction. Power transformers are widely used in

    electrotechnical installations as well as in power transmission systems which

    change only the values of alternating voltage and current (Fig. 1.1). While

    studying the given section attention is focused on general-purpose power

    transformers.

    1 - pole core, 2, 3 - windings, 4 - case, 5 - cooling pipes, 6 - voltage switch handle, 7, 8 - terminals, 9 expander.

    Fig. 1.1

    5

  • 1.1. Design and Operation Principle of Transformers

    A single-phase transformer consists of a pole core and two windings. One

    winding called primary is cut in to alternating current supply at voltage .

    Load is cut in to another winding called secondary. Primary and secondary

    windings of power transformer are not electrically linked and power is

    transmitted from one winding to another by electromagnetic way.

    1U

    Zload

    Transformer operation is based on electromagnetic induction principle. When

    cutting in primary winding to a. c. supply at frequency f alternating current

    flows in the turns of this winding producing alternating magnetic flux in the

    pole core. Being closed in the pole core this flux is linked with both windings

    and induces self-induction e.m.f. in primary winding

    1i

    1

    ( )dtdwe 111 = , mutual induction e.m.f. in secondary winding is ( )dtdwe 122 = , where is turns number in primary and secondary windings. 21 , ww

    When cutting in the load to the terminals of secondary winding current

    is produced under the effect of e.m.f. in the winding turns and voltage is

    induced across the terminals of secondary winding. Step-up transformer shows

    and step-down transformer offers

    Zload 2i

    2e U 2

    12 UU > 12 UU < . The second alternating magnetic flux 2 is produced when current flows

    across the turns of secondary winding. Direction of this flux depends on the

    character of transformer load and may be in opposition or concordant to the flux

    of primary winding. Besides, the fact that current appears in secondary winding

    causes current change in primary winding but resultant magnetic flux in the

    pole core is not changed and depends only on magnitude and the rate of primary

    winding voltage. Thus, one may assume that joint flux

    equals flux . 1Modern power transformers are of similar design circuit consisting of 4

    main systems, i.e. 1. closed magnetic system - pole core, 2. electrical system - 6

  • two or more windings, 3. cooling system - air, oil, water or combined systems,

    4. mechanical system providing mechanical durability of the construction and

    possibility of transformer transportation.

    The pole core is intended to increase inductive coupling between the

    windings. It forms magnetic circuit along which resultant magnetic flux of

    transformer is closed. The pole core is made of iron laminations, which are

    isolated from one another by a very thin coat of varnish or oxide on one side of

    each lamination. Such pole core construction makes it possible to reduce eddy

    currents induced by alternating magnetic flux and to minimize energy losses in

    the transformer.

    Power transformers are produced with pole cores of three types, i.e. core-

    type, shell-type and shell-core-type constructions.

    A single-phase transformer of core-type construction [Fig. 1.2(a)] consists of

    four areas, they are two limbs ( L ) and two yokes ( Y ). A limb is considered to

    be an area of the pole core which is enclosed by turns per coil, an yoke being an

    area of the pole core connecting limbs and closed pole core.

    (a) (b) (c)

    Fig. 1.2

    In a single-phase two-winding transformer of core-type construction each

    of two windings consists of two parts situated on two limbs connected either in

    series or in parallel. Such winding arrangement brings to inductive linking

    increase.

    7

    Cross-sectional area of the limb is step-shaped circle inscribed. An yoke is of

    cross-sectional area with less number of steps and four angles which are beyond

  • 8

    the circle. Yoke cross-section is larger than that of the limb that allows, in

    particular, to improve the parameters of no-load transformer.

    In a single-phase transformer of shell-type pole core [Fig. 1.2(b)] there is one

    limb and two yokes which partly cover windings like a shell from diametrically

    situated sides. Magnetic flux in the limb of such pole core is twice larger than

    that in the yokes, therefore each yoke possesses twice less cross-section than

    that of the limb. In single-phase transformer pole core of shell-core type

    construction [Fig. 1.2(c)] there are two limbs and two yokes as is the case with

    core-type transformer and two more lateral yokes as in shell-type transformer.

    Such pole core construction requires larger amount of electric steel but makes it

    possible to reduce pole core height that is important for transformer

    transportation by railway.

    Three-phase transformer pole core of core-type construction [Fig. 1.3(a)]

    consists of three limbs and two yokes located in one plane if the pole core is flat.

    In spatial pole core the limbs are located in different planes. Flat pole core of

    core-type construction is not quite symmetrical as pole core length for the mean

    phase is somewhat shorter than for the marginal ones. However, it does not

    influence.

    The pole core of shell-type three-phase transformer [Fig. 1.3(b) may be

    schematically represented by three single-phase shell-type pole cores which are

    superimposed. The mean phase of such a transformer has reverse switching

    relative to marginal phases. In this case fluxes are geometrically added in

    contacting areas of the next phases of the pole core instead of being subtracted

    that allows to reduce the cross-section of these pole core segments.

    In three-phase transformer pole core of shell-core type construction

    [Fig. 1.3(c)] there are three limbs and two yokes like in a core-type transformer

    and two more lateral yokes like in a shell-type transformer. Advantages and

    drawbacks of such pole core design are similar to the like single-phase

    transformer design.

  • For three-phase voltage conversion one can use not only a three-phase

    transformer with any type of pole core mentioned above but three single-phase

    transformers as well. Such device is called three-phase transformer bank.

    (a) (b) (c)

    Fig.1.3

    Three-phase transformers with the pole core common for all phases are often

    used. They are more compact and cheaper. Transformer bank is used in case of

    transportation problems and for decreasing stand-by power in case of emergency

    repair.

    Transformer windings are important elements owing to two reasons, i.e.

    1. The cost of materials used for manufacturing makes up about a half of

    transformer cost.

    2. Transformer durability often depends on winding durability.

    In two-winding transformers the winding to which ceiling voltage is applied

    is called high-voltage ( HV ) winding and the winding with very low voltage is

    called low-voltage ( LV ) winding.

    9

  • 10

    According to the pole core arrangement on the limb the windings are

    classified as concentric and sandwich winding constructions. Concentric

    windings are designed in the form of hollow cylinders placed concentrically on

    the limbs. LV winding is placed closer to the limb as less isolation distance is

    required and HV winding is placed outside.

    Sandwich (disc) windings are made in the form of separate HV and LV

    sections (discs), which are sandwiched on the limb. They are used only in

    special-purpose transformers.

    According to engineering design the windings are classified as

    1. Cylindrical single- or multilayer windings made of rectangular or round

    wire

    2. Spiral simplex and multiple windings of rectangular wire

    3. Continuous disc windings made of rectangular wire

    4. Windings made of foil.

    Single- and two-layer cylindrical windings of rectangular wire are used as

    LV windings at nominal current up to 800A. The turns of each layer are wound

    closer to each other in a spiral manner. Interlayer isolation is made by two layers

    of electroisolating 0.5 mm cardboard or by the channel.

    Multilayer cylindrical windings made of rectangular wire are used as HV

    windings (up to 35 kW). These windings are used in 110 kW transformers and

    above.

    Spiral simplex and multiple windings are used as LV windings at the current

    over 300 A. Turns are wound in the form of one or several movements spiral.

    Channels are made between turns and parallel branches.

    Continuous-disc windings consist of disk coils connected in series and

    wound in continuous spiral without breaking wire between separate coils. The

    coils are separated by the channel. They are used as HV and LV windings.

  • 1.2. Basic Transformer Equations

    It can be supposed that resultant alternating magnetic flux in the transformer pole core is sinusoidal time function.

    Whereas instantaneous e.m.f. value induced in the primary winding equals

    ( ) ( )2sincos max1max111 === twtwdtdwe where f 2= .

    By analogy for the secondary winding this leads to the following

    ( )2sinmax22 = twe Thus, e.m.f. and lag resulting flux 1e 2e in phase through an angle 2 .

    Effective e.m.f. value may be written as

    ,44.42 max1

    max11 fw

    EE == ,

    max22 44.4 fwE =

    E.m.f. ratio of HV and LV windings is called transformation ratio

    21

    21

    21

    UU

    ww

    EEk ==

    Currents and in transformer windings besides resultant magnetic

    flux induce magnetic leakage fluxes

    1I 2I

    1 and 2 (Fig. 1.4). Each flux is linked with the turns of only inherent winding and induces e.m.f. leakage in it.

    Effective e.m.f. leakage values are proportional to the currents in the

    corresponding windings

    ,xIjE ;xIjE 2 22111 == &&&

    11

  • where are inductive leakage reactances of primary and secondary

    windings accordingly. The sign minus in this expression points to leakage e.m.f.

    reactance.

    21 , xx

    Fig. 1.4

    If the primary transformer winding with ohmic resistance cut into the

    voltage main, voltage equation is

    1r

    1U

    ( ) 111111 rIxIjEU ++= &&&&

    In power transformer inductive and active voltage drop is not significant,

    therefore one can assume that ( )11 EU && . For secondary transformer winding the voltage drop at the load equals

    terminal voltage of secondary winding and voltage equation results is

    load2222222 ZIrIxIjEU == &&&&&

    where is ohmic resistance of secondary winding. 2r

    If a transformer runs at primary winding cut into the voltage main and

    broken secondary winding we deal with no-load duty. Current in primary

    winding under these conditions is called no-load duty.

    1U

    0I

    12

  • Magnetomotive force (m.m.f.) 10 wI produced by this current induces magnetic flux in transformer pole core with the amplitude

    10max 2 RwI = where is pole core magnetic resistance. mR

    When secondary winding is closed to load current develops. As

    for the primary winding the current increases up to the value . Now magnetic

    flux in pole core develops under the effect of two m.m.f. and .

    loadZ 2I

    1I

    11 wI & 22 wI &Thus, it may be considered that resultant magnetic flux value at stable

    voltage does not practically depend on transformer load if its value does not

    exceed the nominal value. The considered approach leads to the following

    transformer m.m.f. equation

    1U

    221110 wIwIwI += &&& 221110 wIwIwI += &&&

    and transformer currents equation is ( )2012112210 ,/ IIIIIwwIII +=+=+= &&&&&&&& , where is secondary winding current brought to the primary

    winding turn number.

    1222 / wwII = &&

    13

  • 1.3. Transformer Equivalent Circuit

    Parameters of primary and secondary transformer windings differ

    resulting in marked transformation ratio that makes difficult plotting vector

    diagrams.

    14

    2

    This problem is eliminated by bringing secondary parameters and the load

    to the form of primary winding, they are converted per turn number of primary

    winding . As a result, instead of a real transformer with transformation ratio

    we get the equivalent transformer with

    1w

    k w w= 1 / 121 == wwk , where . Such transformer is called the idealized transformer. 12 ww =

    Secondary parameters referred above should not influence energetic

    transformer values, i.e. all voltages and phase shifts in secondary winding

    remain the same as in a real transformer. As a result, turns number of secondary

    winding changes into kwwww == 2122 // times and as a consequence

    22 EkE && = , . 22 UkU && =If electromagnetic voltages of real and idealized transformer secondary

    winding are equal then the expression for the secondary winding current is

    obtained

    kIIIEkIEIE / , 22222222 &&&&&&&& === Referring to the losses equality in the secondary windings effective

    resistance of both real and idealized transformers the expression for idealized

    effective resistance of a secondary winding is obtained

    ( ) ( ) 222222222222 ,/ krrrkIrIrI === &&& Referred inductive leakage reactance of secondary winding is determined

    from the equality condition of secondary winding reactive power of real and

    idealized transformers

    ( ) ( ) 222222222222 ,/ kxxxkIxIxI === &&& .

  • Referred impedance of transformer secondary winding 2

    2222 kZxjrZ =+=

    Voltage equations for idealized transformer may be written as ( ) 111111 rIxIjEU ++= &&&& , 222222 rIxIjEU = &&&&

    Currents equation is ( )201 III += &&& These equations show analytical relation between transformer parameters

    in the range between no-load and nominal duties.

    Lets consider transformer equivalent circuit [Fig. 1.5(a)]. This diagram shows

    Fig. 1.5

    that ohmic and inductive resistances are conventionally taken out by convention

    from the corresponding windings and are energized in series. 15

  • As 1=k in the idealized transformer then is obtained. As a result points A and a, X and x in the diagram are of similar potentials, that makes its

    possible to connect them electrically and to obtain T-shape electric equivalent

    circuit of the idealized transformer [Fig. 1.5(b)]. Magnetic linking between the

    windings is substituted for electric linking in this equivalent circuit.

    21 EE = &&

    T-shaped electric equivalent circuit of the idealized transformer makes

    investigation of electromagnetic processes and transformer calculations easier.

    The circuit is a complex of three branches. The first branch contains impedance

    and current . The second branch (magnetizing) contains

    impedance and current , where , are the parameters of a

    magnetizing branch. The third branch contains impedances of secondary

    winding , load

    111 jxrZ += 1I&

    mmm jxrZ += 0I& mr mx

    222 xjrZ += loadloadload xjrZ = and current 2I&. All the parameters of electric equivalent circuit but loadZ are constant and may be determined either by calculation or experimentally (no-load and short-circuit

    duties ).

    1.4. No-Load Duty

    No-load duty is considered to be transformer duty at closed secondary

    winding , . =loadZ 02 =IVoltage and current equations take the form ( ) 101011 rIxIjEU ++= &&&& ;

    220 EU = && ; . 01 II && =Magnetic flux 1 in the transformer is alternating one, therefore the pole

    core is being steadily remagnetized, there arise magnetic losses from hysteresis

    and eddy currents induced by alternating magnetic flux in iron laminations.

    Open-circuit current is of two components, namely, active component

    owing magnetic losses and reactive one showing magnetizing current

    0I& aI0&

    I0&

    16

  • 20

    200 a III +=

    Fig. 1.6

    Active component of open-circuit current usually is not significant, it does not

    exceed 10% of the current and therefore it does not significantly influence

    open-circuit current.

    0I

    As net power of transformer while running

    under no-load conditions equals zero active

    power consumed under this conditions is

    spent for magnetic losses in the pole core

    and electric losses in primary winding .

    0P

    mP

    120 rI

    Taking into consideration the fact that open

    circuit current does not usually exceed 2-

    10% of primary winding nominal current

    electrical losses can be neglected and

    magnetic losses in the iron core can be

    0I

    nomI1

    Fig. 1.7 considered to be open-circuit losses.

    Electric equivalent circuit and transformer vector diagram are shown in Fig. 1.6

    and Fig. 1.7.

    17

    Angle through which vector of magnetic flux & 1 lags behind from current is called magnetic loss angle. This angle increases with the growth of open-

    0I&

  • circuit current active component i.e. with the growth of magnetic losses in

    the transformer core.

    aI0&

    1.5. Short-Circuit Duty

    Short circuit is the transformer duty at short-circuited secondary winding

    , . 0load =Z 02 =UUnder operating conditions when nominal voltage is applied short

    circuit is considered to be emergency duty and a serious hazard to the

    transformer. Only steady short-circuit current exceeds the nominal current 10-20

    times.

    nomU1

    Short-circuit duty is not a hazard to the transformer as step-down voltage

    is supplied to the primary winding, in so doing currents in both windings being

    equal to nominal currents.

    This step-down voltage is called nominal short-circuit voltage and is

    usually expressed as a percentage of nominal voltage

    ( ) %1051001scsc == nomUUu

    As we have found before the resultant magnetic flux in the transformer pole core

    is approximately proportional to primary winding voltage. Consequently, at

    short-circuit duty resultant magnetic flux in

    the pole core is small, magnetizing current

    is required to induce it and it may be

    neglected, therefore equivalent circuit does

    not posses magnetizing branch.

    Equations of voltages and currents take the form

    ( ) ( ) sc1sc111211211sc ZIxIjrIxxIjrrIU scscscscsc &&&&&& =+=+++= , scsc II 21 = && ,

    18

  • where is transformer impedance under

    short circuit conditions,

    scZ

    scsc , xr are active and reactive components of

    resistance . scZ

    Electric equivalent circuit and vector

    diagram are shown in Fig. 1.8 and Fig. 1.9.

    Rectangular triangle AOB is called short-circuit triangle, its legs being active and

    reactive components of short circuit

    voltage

    scaU&

    scrU&

    scasc12211 )( UrIrIrIOB scscsc &&&& ==+= , scrsc12211 )( UxIjxIjxIjBA scscsc &&&& ==+= .

    As at short circuit duty the resultant flux is too small compared with its

    value at nominal primary winding voltage pole core magnetic losses may be

    neglected. It follows that active power , consumed at this duty is spent for

    electric losses in transformer windings

    scP

    sc2

    122

    112

    1sc rIrIrIP scscsc =+= & .

    19

  • 1.6. Transformer Vector Diagrams under Load Conditions

    For plotting vector

    diagrams of electric

    equivalent circuit of the

    idealized transformer and

    the basic equations of

    voltage and currents are

    used. Vector diagrams

    clearly show relations and

    phase shifts between the

    currents, e.m.f. and

    voltages of the

    transformer.

    For determination of

    phase shift angle between

    and one should

    know the load character.

    At active-inductive load (Fig. 1.10) vector lags in phase through an angle

    2 & 2I &

    2I & 2 &( ) ( )[ ]n2n212 /tan rrxx ++=

    At active-capacitive load (Fig. 1.11) vector advances through an angle 2I & 2 &( ) ( )[ ]n2n212 /tan rrxx +=

    At marked capacitive load component the voltage U may be larger than

    e.m.f. at open circuit (no-load) duty . Besides, reactive component of

    secondary winding is in phase with reactive component of the

    open circuit current , showing magnetizing effect on the pole core. It causes

    2&

    2 &

    222 sin= II r &&rI0&

    20

  • primary winding current decrease compared with its value at active-inductive

    load when the component shows

    demagnetizing effect.

    1I&

    rI 2&

    The above vector diagrams of a loaded

    transformer cannot be used for practical

    calculations as being complex. By

    analogy with short- circuit duty in the

    transformers running at the load close to

    the nominal one open-circuit current is

    neglected and it is considered to be

    . 21 II = &&As a result, transformer equivalent

    circuit takes a simplified form, it lacks

    magnetizing branch. The circuit consists

    of connected in series elements r [Fig. 1.12(a)].

    sc

    21

  • Simplified vector diagram is plotted according to nominal voltage values of

    primary winding nomU 1.

    , nominal current of primary winding , power factor nomI1&

    nom2cos and short circuit triangle parameters , , . scU& scaU& scrU&Lets explain plotting simplified transformer vector diagram at active-inductive

    load [Fig. 1.12(b)]. In an arbitrary way for example, one constructs a current

    vector is constructed on Y-axis from its origin. A line is drawn at an

    angle , where voltage vector

    21 II = && 2 ( )2U & is located on it according to the load

    character. One constructs - short-circuit triangle is constructed. The leg

    BC being equal to active component of short-circuit voltage is in phase with

    vector current. The leg AB being equal to reactive component of short circuit

    voltage advances current vector by .

    ABC

    90o

    One shifts the triangle without changing the legs of an angle orientation

    so that the vertex C could be found on the line directed at an angle to the current vector until the distance from coordinates origin to the vertex A equals

    .

    ABC2

    nomUU 11 && =Then phase shift angle between the primary winding current and its

    voltage as well as vector value

    1 1I&

    1U& ( )2U & are determined. All vector constructions are carried out at the usual scale.

    1.7. External Transformer Characteristics

    Current change of transformer load causes the changes of its secondary

    voltage and efficiency due to the change of voltage drop and active power losses

    in the windings.

    Secondary voltage change is usually expressed in percent and is

    determined as follows

    22

  • 10010020

    220

    20

    220 ==

    UUU

    UUUU &

    &&&

    &&&

    where are ordinary and referred voltages (e.m.f.) of secondary

    winding open circuit at nominal voltage of primary winding, are

    ordinary and referred voltages across transformer secondary winding terminals

    at primary winding rated voltage.

    2020 , UU &&

    22 ,UU &&

    Using simplified transformer vector diagram the expression for calculation of

    secondary voltage change is obtained

    ( ) ( ) ,%200/sincossincos 22sca2scr22scr2sa ++= UUUUU &&& , where is load factor. nomIIII 22nom22 // == &&&&

    10010020

    220

    20

    220 ==

    UUU

    UUUU &

    &&&

    &&&

    From the given expression it follows that secondary voltage change

    depends on amount and character of the load.

    Dependences at ( )fU = & const=2cos shown in Fig. 1.13(a) are

    23

  • practically linear as the first addend changes proportionally the load and the

    second one being insignificant does not practically influence U value. The second addend is neglected in most cases due to its rather small value

    and a simplified formula for U calculation is used ( )2scr2sca sincos += UUU &&&

    Dependences ( 2 )fU = at const= are of more complicated form [Fig. 1.13(b)]. At sc2 U 0 U== this leads to the following result at

    . The largest

    voltage change occurs at

    sc0

    2 90 UU == sc =2 and is

    equal to scUU = max .

    24

    At ( ) 0 ,90 sc020 == U . Dependence of secondary winding

    on load current or on load factor

    2U&

    2I& at rated voltage and primary winding frequency

    under stable load conditions is called external transformer characteristic.

    For plotting external characteristic the following formula may be used

    ( ) ,100/1202 UUU = where [ . ] %U =External characteristics (Fig. 1.14) due to linearity dependence ( )fU = are also linear.

  • 1.8. Transformer Voltage Regulation

    Voltages at different sections of energy transmission line where step-

    down transformers can be cut in differ from each other and as a rule, from

    transformer rated primary voltage. Besides, these voltages change owing to load

    changes. Taking into consideration the fact that terminal secondary winding

    voltage of the transformer should correspond to State Standard requirements it is

    possible to provide these requirements, in particular, by changing transformation

    ratio.

    HV windings of step-down transformers have regulating shunts with the

    help of which one can obtain transformation ratio that differs from the nominal

    one may be obtained.

    Regulating shunts are designed in each phase either close to zero point or

    in the middle of the phase. In the first case three or five branches are made in

    each phase, in so doing medium shunt corresponds to rated transformer ratio and

    two ( four ) other shunts correspond to transformation ratio that differs by 5% ( and ) from the rated one. In the second case each phase is divided

    into two parts and six shunts are formed, that makes its possible to get except for

    rated transformation ratio four additional values that differ and

    2 5. % 5%

    2 5. % 5% from the rated one.

    Two kinds of power transformer voltage regulation are provided, i.e.

    voltage regulation by switching winding branches without excitation (SWE)

    after cutting out all transformer windings and voltage regulation without load

    break (LBR), without cutting out transformer windings. Branch switches LBR

    compared with SWE are of more complex design because each phase is

    provided with special switching devices. LBR equipment is located in the

    common tank with active transformer part and its switching is automatized or

    done at a distance (from switchboard). Transformers with LBR are usually

    intended for voltage regulation within the range of 6-10%. 25

  • At higher transformer voltages

    LBR equipment seems to be too

    complex. In this case one uses

    voltage regulation is used with of an

    injector transformer consisting of ST

    transformer connected in series and

    regulating autotransformer (RA) with

    switching device (SD) (Fig. 1.15).

    Transformer secondary winding voltage ST U& is summarized with line voltages and changes it up to the value . The value L1U& UUU &&& = L1L2 U& may be changed by the regulation autotransformer (RA) and U& may be changed through by a pitch regulation switch (PRS). 180o

    1.9. Transformer Losses and Efficiency

    In the process of electric energy transformation some energy is lost in the

    transformer in the terms of electric and magnetic losses.

    Electric losses cause heating the transformer windings when electric current

    flows across them. Power of electrical losses is proportional to current square

    and is equal to the sum of electric losses in primary and secondary

    windings

    eP

    1eP 2eP

    22

    212

    121 )( rImrImPPP eee +=+= where m is phase number in transformer windings.

    This expression for transformer electric losses is used only at the stage of

    designing. When manufacturing transformer electrical losses are determined by

    26

  • the results of short circuit duty taking the voltage at rated currents in the

    windings scnomP

    scnome PP = 2 , where is load factor.

    As electrical losses depend on transformer losses they are called

    alternating.

    Magnetic losses occur mainly in the transformer pole core. Magnetic

    losses of hysteresis are in direct proportion to pole core frequency of magnetic

    reversal, i.e. to a.c. frequency (

    mP

    fph ). Magnetic losses from eddy currents are proportional to the square of this frequency ( ). Total magnetic losses

    are considered to be proportional to current frequency by the power 1.3. The

    amount of magnetic losses also depends on magnetic induction square in limbs

    and yokes of the pole core. If

    2fpec

    constU =1 and constf = magnetic losses do not depend on transformer load, they are called constant. For the manufactured

    transformer magnetic losses are determined by the results of open-circuit duty,

    measuring open-circuit power at rated primary voltage. nomP0

    Thus, active power released to primary transformer winding is partly

    spent for electrical losses in this winding , for magnetic losses in the pole

    core respectively. The remainder is called electromagnetic power and it is

    released to secondary winding where it is partly spent for electrical losses in this

    winding . Active power released to the load of a three-phase transformer

    (net power) may be determined as follows

    1P

    1ep mP

    2ep 2P

    == PPpppPP eme 12112 or 22222 coscos3 == nomSIUP

    where are total losses in the transformer, += scnomnom PPP 20 nomS is rated transformer power,

    27

  • 2I , are linear current and voltage values of secondary winding. 2U

    Transformer efficiency is determined as active power ratio of secondary

    winding output to active power of primary winding input 2P 1P

    ( ) === 11

    11

    2 1 PPPPP

    PP ,

    scnomnomnom

    nom

    PPSS

    ++= 2

    02

    2

    coscos

    .

    The analysis of the above expression shows that transformer efficiency

    depends both on the value ( ) and the character ( 2cos ) of the load. Maximum efficiency value corresponds to the load at which magnetic losses are

    equal to electrical losses

    scnomnom PP = 20 , i.e. at scnomnom PP /0= .

    Transformer efficiency usually is of maximum value at = and decreases slightly at load increase.

    0 45 0 65. .

    1.10. Diagrams and Connection Groups of Transformer Windings

    Marking the initial and final windings is done in the following way. In a

    single-phase transformer HV winding is denoted by Latin capital letters (A-

    origin, X- end). LV winding is denoted by Latin small letters (a - origin, x

    end). When the third winding with medium voltage is available its origin and

    end is denoted as Am and Xm accordingly. In three-phase transformer HV

    winding is denoted by capital letters (A, B, C origins, X, Y, Z ends). LV

    winding is denoted by Latin small letters a, b, c origins, x, y, z ends. It is

    common practice to consider phase alternation A, B, C from left to right if the

    transformer is examined as viewed from HV tapped winding.

    28

  • In most cases three-phase transformer windings are star- (Y), delta- () or seldom zigzag (Z)-connected. The first two diagrams of three-phase winding

    connection are denoted by Russian capital letters , accordingly.

    Zero terminals of star- and zigzag-connected three-phase winding are

    denoted in HV windings by capital letter O and in LV winding by small

    letter o. In so doing index N (Yn, Zn) is added to letter designation of winding

    connection diagrams.

    While connecting a transformer in parallel with other transformers phase

    shift between primary and secondary winding e.m.f. is of prime importance. The

    notion connection group of winding to characterize this shift is applied.

    Consider the fragment of core-type construction pole core of a single-

    phase two-winding transformer (Fig. 1.16). Both windings are wound along the

    left spiral line and are of similar wind direction.

    In both windings origins A and a are arranged

    above and ends X and x below respectively, i.e.

    they are marked in a similar way.

    E.m.f. induced in the winding is considered to

    be positive if it acts from initial to final

    windings. In both windings e.m.f. is induced by

    the same main magnetic flux. Similar wind

    direction and marking makes its possible to hold

    that the above mentioned e.m.f. of these

    windings acts in a similar direction at every

    instant, i.e. coincidentally positive or negative.

    E.m.f. AE.

    and aE.

    are in phase. The angle between e.m.f. vectors of

    primary and secondary windings equals zero. Conventional symbol is I/I-0 (zero

    group).

    29

  • If the marking in one winding is reversed (Fig. 1.17) or wind direction is

    changed opposite in sign e.m.f. will act in the windings at every instant. The

    angle between e.m.f. vectors of primary and secondary windings is 180. When determining the connection group of the winding this angle should be divided

    into 30. Conventional symbol is I/I-6 (the sixth group). Thus, in single-phase transformers two groups of winding connection

    zero and the sixth groups are available.

    Lets consider three-phase two-winding transformer with HV and LV

    star-connected windings under the following conditions:

    1. Windings are of similar wind direction

    2. Windings are similarly marked

    3. Like winding phases are placed on common limbs.

    Firstly, vector diagram for HV winding is

    plotted, choosing arbitrarily the direction of the first

    phase e.m.f., conforming phase alternation with the

    others. When plotting vector diagram for LV winding

    it should be remembered that the direction of each

    vector depends on vector diagram of HV winding.

    Then, all the vectors of phase e.m.f. in pairs

    AE.

    and aE.

    , BE.

    and bE.

    , CE.

    and cE.

    as well as all

    linear e.m.f. vectors in pairs ABE.

    and abE.

    , BCE.

    and

    bcE.

    , CAE.

    and caE.

    are in phase at every instant, i.e. the

    angle between them equals zero (Fig. 1.18).

    30

  • In three-phase transformers the group of winding connection is defined by

    the angle between like linear e.m.f. In the case considered conventional symbol

    is Y/Y-0 ( zero group ).

    What will be the result if we change LV winding marking per one pitch

    around? E.m.f. vector diagram representation for HV winding remains

    unchanged. E.m.f. vector diagram of LV winding will be another. The phase a-x

    of LV winding is located on a common limb with phase B-Y of HV winding. As

    phases possess similar wind direction and are similarly marked core magnetic

    flux induces e.m.f. similar in the direction in these phases. Vector aE.

    of LV

    winding is represented as being in phase with vector BE.

    of HV winding.

    The same reasoning is provided concerning vector bE.

    and cE.

    directions.

    As a result e.m.f. vector diagram of LV winding is clockwise displaced 120 compared with the previous vector diagram. The angle between like linear e.m.f.

    is determined clockwise from e.m.f. vector of HV winding up to e.m.f. vector of

    LV winding. The angle is 120, the fourth group. Conventional symbol is Y/Y- Thus, when changing marking of one winding per one pitch around connection

    31

  • grouping of winding varies to four as linear e.m.f. vectors are clockwise

    displaced 120.

    Fig.1.19

    Similar results may be obtained if HV and LV windings have another but

    similar winding connection - diagram - delta.

    If connection diagrams of HV and LV windings of a three-phase

    transformer are similar one can get six even groups are formed: 0, 4, 8, 6, 10, 2

    by changing the marking of one winding.

    Consider three-phase two-winding transformer with different connection

    diagrams (Fig. 1.20) following the conditions mentioned above. LV winding is

    delta-connected. E.m.f. vector diagram of HV winding is plotted as shown

    above.

    E.m.f. vector diagram of LV winding is a triangle, each side being equal

    to phase and linear e.m.f. in magnitude and phase. The angle between like linear

    e.m.f. is 330, the eleventh group. The symbol is Y/-11. Marking the change of LV winding per one pitch around marking in

    changing connection group of windings to four, it will be the third group. If LV

    32

  • winding marking is changed again per a pitch around connection group of

    winding will change to four again, it will be the seventh group.

    It is not difficult to confirm that marking change of one winding in a

    three-phase transformer of different winding connection diagrams makes its

    possible to get six odd groups: 11, 3, 7, 5, 9, 1.

    According to Russian State Standard there are transformers with the

    following connection diagrams and connection groups of windings for using:

    1. Y/Yn-0

    2. /Yn-11 3. Y/-11 4. Yn/-11 5. Y/Zn-11.

    In zigzag-connected circuit each winding phase is divided into two parts

    which are placed on different limbs (one part is placed on the main limb, the

    second one is arranged on the limb of the neighbouring phase in the order of

    alternation). In so doing the second half of each phase is switched on in

    opposition to the first half. This makes its possible to get phase e.m.f. 3 times

    higher than in the matched switching.

    33

  • However, at matched switching of phase halves e.m.f. of each phase is

    1.15 times less than when phase halves are placed on one limb. Therefore wind

    wire consumption in zigzag connection increases 15%. This connection is used

    only when non-balanced phase load with zero currents is available.

    1.11. Parallel Transformer Operation

    Parallel operation of two or several transformers is operation at parallel

    connection of both primary and

    secondary windings. In parallel

    connection like terminals of

    transformer windings are

    connected to the same conductor

    (Fig. 1.21) in the mains.

    Parallel operation of

    transformers instead of one

    transformer of total voltage is recommended owing to the following reasoning:

    1. to provide regular power supply of consumers in case of emergency

    when one of the transformers is under repair,

    2. to provide transformer operation with high performance indices

    (efficiency, cos2) changing the number of transformers under optimum load conditions,

    To distribute the load between parallel transformers proportionally to their

    nominal voltages three conditions should be fulfilled.

    Firstly, primary and secondary voltages of transformers should be equal

    accordingly, i.e. transformers should be of equal transformation ratios

    ( ). K=== 321 kkkSecondly, transformers should be of the same connection group of

    windings. 34

  • Thirdly, rated short-circuit voltage of transformers should be equal

    ( K=== 321 scscsc UUU ). When the first condition is not fulfilled even at no-load duty phasing

    current Iph develops in parallel transformers. It is due to secondary

    e.m.f. difference of the transformers U& (Fig. 1.22)

    21 scsch ZZ

    UI += &&

    where are short-circuit transformer 21 , scsc ZZ

    impedances.

    When the load is energized phasing current is superimposed

    on load current. In transformers with higher secondary e.m.f. ( in step-down

    transformers - transformers possessing less transformation ratio) phasing current

    is added to load current. The transformer of similar rating but with larger

    transformation ratio is underloaded as phasing current is opposed to load

    current.

    Continuous transformer overload is impermissible as it requires reducing total

    load at different transformation ratios. At marked difference of transformation

    ratios proper transformer operation is impractible. It makes possible to operate

    parallel transformers with unlike transformation ratios if their difference does

    not exceed 0.5% geometric mean %5.0100

    21

    21 =

    kkkkk .

    When the second condition is not fulfilled secondary linear transformer

    voltage is phase-shifted relative to each other. In transformer the voltage

    difference in a circuit arises causing marked phasing current. U&Let us consider, for example, energizing two parallel transformers with

    equal transformation ratios, one being of zero (Y/Y-0) and another being of the

    35

  • eleventh (Y/-11) connection group of windings. Firstly, linear voltage of the first transformer will be

    21U&

    3 times higher than linear

    voltage of the second transformer. Secondly, the vectors

    of these voltages will be phase-shifted relative to each other by

    30 (Fig. 1.23)

    22U&

    2/3 22UOA = as 3/2122 UU = then 2/21UOA = and 22UU = .

    Such voltage difference U& results in the phasing current in secondary transformer circuit, the current exceeding

    nominal load current 15-20 times, i.e. emergency conditions

    occur. The highest U& value appears when energizing parallel transformers with zero or the sixth connection group of

    windings ( 22UU = ) as in this case the vector of linear secondary windings is in reverse phase.

    When the third condition is not fulfilled neglecting short-circuit currents

    parallel transformers [Fig. 1.24(a)] are changed for short-circuit resistances

    [Fig. 1.24(b)]. 21 , scsc ZZ

    As the currents in parallel branches are inversely related to their

    resistances relative voltages (loads) of parallel transformers are inversely related

    to their short-circuit voltages as well. As a result, it causes transformer overload

    with less U value and underload with high U . sc sc

    36

  • Therefore, State Standard allows parallel transformers energizing at different

    short-circuit voltages if their difference does not exceed arithmetic mean 10%

    ( ) %101005.0 2121 +

    =scsc

    scscsc UU

    UUU

    The greater is short-circuit voltage difference the more significant is transformer

    difference by voltage. State Standard recommends nominal voltage ratio of

    parallel transformers to be not more than 3:1.

    Besides, it is necessary to control the order of phase alternation before

    energizing three-phase parallel transformers. Phase alternation order should be

    similar in all transformers.

    aintenance of these

    regulations is checked by

    transformer phasing (Fig.

    1.25). In so doing each

    pair of opposite terminals

    of a closing switch is

    connected by a conductor

    (it is not shown) and

    voltage is taken with zero

    voltmeter between the

    remaining pairs of

    terminals. If secondary

    transformer voltages are

    equal and connecting

    groups of their windings

    are similar zero voltmeter reading is zero if there is similar order of phase

    sequence. In this case parallel transformers may be energized. If voltmeter

    37

  • shows some voltage it is necessary to clear out what parallel performance

    condition is not fulfilled and eliminate it.

    1.12. Non-Balanced Load of Three-Phase Transformers

    The reasons of non-balanced load are considered to be uneven distribution

    of single-phase receivers by load, emergency conditions that occur at single-

    phase, two-phase short circuit or at one phase of wiring line failure.

    Non-balance of transformer secondary voltages has a detrimental effect on

    both the consumers and the transformer. For example, in a.c. motors permissible

    load voltage decreases, durability of filament lamps is reduced at high voltage

    and luminous intensity is decreased at low voltage. Overload of separate

    transformer phases, excessive phase voltage increase and pole core saturation

    occur.

    For investigation of transformer operation at non-balanced load the

    method of balanced components studied in the course Theoretical fundamentals

    of electrotechnics is widely used. While considering three-phase step-down

    transformer non-balanced currents of LV may be represented as the sum of three

    balanced systems of positive, negative and zero sequence differing by sequence

    of current passing through

    ++=++=++=

    021

    021

    021

    cccc

    bbbb

    aaaa

    IIIIIIIIIIII

    &&&&&&&&&&&&

    (*)

    The currents forming positive sequence system reach maximum

    successively in phases a, b, c. The currents forming negative sequence system

    reach maximum successively in phases a, b, c. Zero sequence currents in all

    three phases are of one direction (zero shift).

    After coefficients a, a2 are entered into the equations (*) they will be

    written as follows

    38

  • ++=++=

    ++=

    022

    1

    0212

    021

    IIaIaIIIaIaI

    IIII

    aac

    aab

    aaa

    &&&&&&&

    &&&&

    (**)

    Multiplying any vector into coefficient a does not change its absolute

    value, but changes 3/2 its argument, i.e. rotates vector through 120 towards vector rotation.

    From (**) currents of positive, negative and zero sequence may be

    obtained through non-balanced ones

    ( )( )( )

    ++=

    ++=

    ++=

    cbaS

    cbaa

    cbaa

    IIII

    IaIaII

    IaIaII

    &&&&

    &&&&

    &&&&

    31

    3131

    22

    21

    (***)

    On the basis of the latter equality in (***) it follows that given the

    currents of zero sequence currents sum of three phases is not equal to zero.

    The advantage of the method of balanced components includes the fact

    that balanced system of each sequence can be transformed regardless of the

    systems of other sequences using conventional methods of mathematical and

    graphical analysis. However, the method of balanced components suggests

    application of superposition method, which is valid only for linear systems.

    Therefore, as applied to the transformer one makes assumption taking into

    account the lack of pole core iron saturation ( constZ m = ) or neglecting open-circuit current ( =mZ ).

    Besides, the transformer at non-balanced load is considered to possess

    equal number of secondary and primary winding turns ( 21 ww = ) that does not allow to use reference procedure.

    39

  • At balanced load when transformer phase currents make up a balanced

    system one can put down . Substituting these values in

    (***) we obtain

    acaba IaIIaII &&&& == , , 2

    ( )( )( ) .01 ;1 as ,0

    31

    ;031

    ;31

    232

    242

    331

    =++==++=

    =++=

    =++=

    aaaIaIaII

    IaIaII

    IIaIaII

    aaaS

    aaaa

    aaaaa

    &&&&

    &&&&

    &&&&&

    Thus, at balanced load there are currents of only positive sequence.

    Therefore, all facts considered above regarding balanced load match transformer

    operation with positive sequence currents.

    What will happen if the position of two terminals of HV windings (for

    example B and C) and LV winding (b and c) is interchanged in the transformer

    under balanced load condition? Vector alternation of transformer phase currents

    will change to reverse, i.e. it corresponds to negative sequence current

    alternation. The duty of the transformer and consumers will not change.

    Thus, negative sequence currents are converted from one winding to

    another as well as positive sequence currents. Transformer operation regarding

    positive and negative sequence currents is similar. Above equivalent circuits are

    valid both for positive and negative sequence currents, transformer resistance

    relative to these sequence currents is similar and equal to short-circuit

    resistance . scZ

    Currents of zero sequence in star-connected windings may develop only

    with zero wire. In delta-connected windings zero sequence currents make up

    current flowing across the closed circuit and linear currents as current

    differences of adjacent phases do not contain zero sequence currents. Therefore

    zero sequence currents in delta-connected winding may develop only as a result

    of inducing them by another transformer winding.

    40

  • Zero sequence fluxes are induced by zero sequence currents and therefore

    they are in phase in time domain. Let us see how zero sequence fluxes influence

    the transformer with different types of pole cores.

    In three-phase transformers of shell-type, core-shell-type design and

    transformer bank zero sequence fluxes S& are closed across the pole cores. Magnetic resistance for the fluxes S& is slight, therefore even small currents of zero sequence are able to develop large fluxes 000 cba III &&& == S& . If the current

    equals short-circuit transformer current magnetic flux equalling

    nominal running transformer flux is induced. The similar reasoning refers to

    e.m.f. induced by e.m.f. flux .

    0aI& S&

    S&In a core-type three-phase transformer zero sequence fluxes of all the

    phases tend to close from one yoke to another ( for example, in oil transformer

    through oil and transformer tank. In this case magnetic resistance for the flux

    is rather high and eddy currents are induced in tank walls and losses occur.

    Therefore, magnetic flux and induced e.m.f. are small.

    S&S&

    Physical conditions of transformer operation at non-balanced load.

    Case 1. Zero sequence currents are missing. At non-balanced load

    voltage drop U in transformer phases is different. If currents of separate phases do not exceed nominal values U is rather small due to small resistance

    of the transformer. scZ

    Thus, non-balanced transformer load in missing of zero sequence currents

    does not distort phase and linear voltage balance at secondary winding

    terminals.

    As for the case considered primary and secondary currents of positive

    sequence in each phase are equal in magnitude and opposite in sign. It is valid

    for the currents of negative sequence as well and for the current sum of positive

    41

  • and negative sequences. Therefore the simplifications taken before ( and

    neglecting magnetizing current) make it possible to put down, thus

    21 ww =

    cCbBaA IIIIII &&&&&& === ; ; . As a result, one may state that magnetizing forces and currents of primary

    and secondary windings are balanced in each phase and separately in each pole

    core area.

    Case 2. There are currents of zero sequence. Variant a: currents of zero

    sequence develop in both transformer windings. These are transformers with

    winding connection Yn/Yn, /Yn. Magnetizing current of zero sequence may be neclected because it contains small total current of sequence and may be written

    as:

    000000 cbaCBA IIIIII &&&&&& ===== . Thus, magnetizing strength of zero sequence currents of both windings is

    mutually balanced in each transformer phase. In such a situation zero sequence

    resistance is . Zero components of secondary voltage originate due to

    small voltage drop . Therefore, in transformers with winding connection

    Yn/Yn, /Yn at non-balanced load phase voltage system is insignificantly distorted.

    scS ZZ =0asc IZ &

    Variant b: zero sequence currents develop only in one winding. There are

    transformers with winding connection Yn/Yn. Zero sequence currents flow only

    in secondary winding, they are considered to be magnetizing as they are not

    balanced by the currents in primary winding. Zero sequence e.m.f. equals

    , where is resistance of magnetizing circuit for zero

    sequence currents. E.m.f. may reach high values. For example, in shell-type

    transformers, core-shell-type design and transformer banks magnetizing circuit

    resistance for zero sequence currents are equal to magnetizing circuit resistance

    for positive sequence currents

    000 amS IZE && = 0mZSE0

    scm ZZ =0 . Therefore, at 42

  • 43

    )( na III 05.002.000 = && zero sequence e.m.f. nS UE 0 and the system of phase m.m.f. and voltages is markedly distorted that is unacceptable and dangerous for

    single-phase loads. Vector direction depends on the phase of zero sequence

    currents and is determined by load conditions.

    S

    E

    &

    Zero sequence e.m.f. does not influence linear voltage value, as zero

    components disappear in phase voltage differences.

    Winding connection Y/Yn in transformers of shell-type, shell-core-type

    designs and transformer banks is not used as a rule but if necessary the third

    winding is arranged in each phase. It is delta-connected winding. This winding

    terminals are not derived outside if this winding is meant only for balancing zero

    sequence currents.

    In a core-type transformer and winding connection Y/Yn distortion of

    phase voltage system with zero sequence currents is less as . scMO ZZ

    F and electromagnetic torque directions will change to

    the opposite ones as well.

  • 68

    The torque will be braking and the machine will run at generator effect

    duty and will release active power to the mains. Slip for generator effect duty is

    0S

    2.6. Voltage Equations of an Induction Motor

    There is no electric linking between rotor and stator winding of an

    induction motor. There is only magnetic linking and stator winding energy is

    conveyed to rotor winding by magnetic field. In this respect an induction motor

    is analogous to the two-winding transformer, namely, stator winding is primary

    and rotor winding is secondary.

    Like in a transformer, in an induction motor there is resultant magnetic

    flux linked both with stator and rotor windings and there are two leakage

    fluxes as well. is leakage flux of stator winding and

    1 2 is leakage flux of

    rotor winding.

    The amplitude of the resultant magnetic flux m rotating at frequency induces e.m.f. in stationary stator winding, its effective value being

    1n

    mwfE = 1111 44.4 . Magnetic leakage flux induces leakage e.m.f. in stator winding, the

    value is determined by voltage drop in inductive of stator winding

    1

    111 xIjE = && ,

  • 69

    where is inductive leakage reactance of stator winding phase. 1x

    Voltage equation of stator winding phase energized at voltage will be

    written as follows

    1U

    11111 rIEEU =++ &&&& , where is voltage drop in pure resistance of stator winding phase . 11 rI 1rFinal equation does not differ from the voltage equation for primary

    transformer winding

    111111 rIxIjEU ++= &&&& . Resultant magnetic flux outrunning rotating rotor induces e.m.f. in

    rotor winding

    SEwSfwfE mwmwS === 22212222 44.444.4 where is e.m.f. frequency in the rotating rotor, is

    e.m.f. induced in winding phase of a stationary rotor.

    Sff = 12 SE2 2E

    Magnetic leakage flux induces leakage e.m.f. in rotor winding, the

    value of which is determined by the voltage drop in inductive reactance of this

    winding

    2

    SxIjE = 222 && , where is inductive reactance of rotor winding leakage phase of a

    stationary rotor.

    2x

    The voltage equation for rotor winding is

    2222 rIEE S =+ &&& , where is pure resistance of rotor winding phase. 2r

    Final equation is written

  • 70

    0/22222 = SrIxIjE &&& .

    2.7. Equations of M.M.F. and Induction Motor Currents

    The resultant magnetic flux in an induction motor is produced by joint

    action of m.m.f. of stator and rotor windings 1F 2F

    ( ) mm RFRFF // 021 &&&& =+= , where is magnetic resistance of motor magnetic circuit, is resultant

    m.m.f. which is equal to winding m.m.f. of stator at open-circuit duty

    mR 0F

    pwImF w11010 45.0 = ,

    where is open-circuit current in stator winding phase. 0I

    M.m.f. of stator and rotor windings per a pole provided motor running

    under load conditions are

    pwImF w11111 45.0 = ;

    wImF w22222 45.0 = ,

    where is number of rotor winding phases, is winding coefficient of rotor

    winding .

    2m 2w

    When changing the load on motor shaft the currents in stator and rotor

    change as well. The resultant magnetic flux remains unchanged as the

    voltage applied to stator winding is invariable (

    1I

    2I

    constU =1 ) and is balanced by stator winding e.m.f. 1E

    11 EU && .

  • 71

    As e.m.f. is proportional to the resultant magnetic flux it remains invariable at load change

    1E

    constFFF =+= 210 &&& ,wImwImwIm www 222211111101 45.045.045.0 += &&& .

    Dividing this equality into wm w11145.0 we obtain the current equation of an induction motor

    21111222210 IIwmwmIII ww +=+= &&&& ,

    where 111

    22222

    w

    w

    wmwmII =& is rotor current referred to stator winding.

    The final current equation of an induction motor is

    ( )201 III += &&& . From this equation it follows that there are two components in stator

    current of an induction motor, i.e. magnetizing ( almost-constant )

    component ( ) and alternating component compensating rotor

    winding m.m.f. Thus, the rotor winding current exerts the same demagnetizing

    action on engine magnetic system as the secondary winding current of a

    transformer does.

    0I&

    opII 0 2I &

    2.8. Referred Parameters of Rotor Winding, Vector Diagram

    and Equivalent Circuit of an Induction Motor

    Rotor winding parameters are brought to the form of stator winding so

    that e.m.f. vectors, voltages and current of stator and rotor windings could be

    shown in one vector diagram. In so doing rotor winding with phase number ,

    with phase turn number and winding coefficient is substituted for the

    2m

    2w 2w

  • 72

    winding with values , , and the powers, and phase shifts of e.m.f.

    vectors and rotor currents should be unchanged.

    1m 1w 1w

    Given stationary rotor referred rotor e.m.f. is e22 kEE = , where ( )221121e / wwEEk ww == is the transformation ratio of an induction motor

    voltage under the stationary rotor.

    Referred rotor current is ikII /22 = , where is the transformation ratio of induction

    motor current.

    ( ) 2e1222111 // mkmwmwmk wwi ==

    Unlike transformers transformation coefficients of voltage and current of

    induction motors are not equal ( ikk e ). This is because the phase numbers in windings of stator and short-circuit rotor are not equal ( 21 mm ). Only in phase rotor engines with these coefficients are equal. 21 mm =

    Referred resistances of rotor winding phase are

    ikkrr = e22 ;

    ikkxx = e22 .

  • There is the specificity of

    determination of phase number

    and phase turns number .

    Each limb of this winding is

    considered to be one phase,

    therefore phase turns number is

    2m 2w

    5.02 =w , winding coefficient being 12 =w and phase number equals limbs number in short-

    circuit rotor winding, i.e.

    22 zm = . Voltage equation of rotor

    winding in the referred form is

    0/22222 = srIxIjE &&

    Fig. 2.8

    Value may be written as follows sr /2( ) ssrrrssrsrsr /1/// 222222 +=+= ,

    As a result, the voltage equation for rotor winding in the referred form

    becomes

    ( ) ssrIrIxIjE /10 2222222 = &&&& . Hence it follows that induction motor is electrically much like the

    transformer running at resistive load.

    For induction motors just as for transformers the vector diagram is plotted

    by equations of currents and voltages of stator and rotor windings (Fig. 2.8).

    73

  • 74

    )Phase shift angle between e.m.f. and current is

    . Electrical equivalent circuits of an induction motor

    correspond to voltage and current equations and to vector diagram as well.

    2E& 2I &( 222 / rsxarctg =

    In Fig. 2.9(a) T-shape equivalent circuit is shown. Magnetic linking of stator and

    rotor windings is substituted for electric linking as it takes place in transformer

    equivalent circuit. Pure resistance ( ) ssr /12 may be considered as external alternating resistance cut in to stationary rotor winding. This resistance value is

    defined by the slip, i.e. mechanical load on motor shaft.

    L-shaped equivalent circuit in which magnetizing circuit is taken out to

    input terminals of equivalent circuit is more convenient for practical application.

    To keep invariable the value of open-circuit current resistances of stator

    winding phases and are turned on in series to this circuit. The obtained

    circuit is convenient as it consists of two parallel circuits, namely, magnetizing

    one with current and operating circuit with current

    0I&

    1r 1x

    0I& ( )12 cI & . Parameter calculation of L-shaped operating equivalent circuit requires

    improvement by introducing coefficient into design formulae such as the ratio

    of phase voltage supply circuit and phase e.m.f. of stator winding at ideal

    open-circuit duty (

    1c

    1U

    0=s ). As open-circuit current is small at this duty turns out to be not much larger than e.m.f. and coefficient slightly differs from

    unity. For motors of 3 kW and above we obtain

    1U

    1E 1c

    02.105.11 =c .

  • 75

    Fig. 2.9

  • 76

    2.9. Energetic Diagrams of Active and Reactive Power of an

    Induction Motor

    Energetic diagram of induction motor active power (Fig. 2.10) may be

    shown in the following way.

    A motor consumes the active power from the mains

    11111 cos= IUmP . Some part of this power is lost as electrical losses in pure resistance of

    stator winding , another portion is lost in the form of magnetic

    stator core losses .

    12

    111 rImpel =mm rImp = 201

    The remaining active power is electromagnetic power released by

    magnetic field from stator to rotor

    emP

    ( ) srImsrImppPP melem // 2222222111 === .

    Fig. 2.10

    Some electromagnetic voltage is lost as electrical losses in pure resistance

    of rotor winding . ( ) 222222212 rImrImpel ==

  • 77

    The remainder of this power is converted into mechanical power induced

    in the rotor

    ( ) ( ) ( ssrImssrImpPP elemmec /1/1 222222212 === )mec

    mecp

    adp

    .

    Some part of mechanical energy P is

    lost inside the machine itself in the form of

    mechanical losses (for ventilation,

    friction in bearings and on the brushes of

    slip-ring induction motor if the brushes do

    not raise under operating conditions) and

    additional losses (due t high

    harmonics of winding m.m.f. and stator

    and rotor toothing). Fig. 2.11

    Net mechanical power on the shaft is ad2 ppPP mecmec = . The sum of motor losses is

    ad21 pppppP mecelmel ++++= , = PPP 12 .

    Motor efficiency is ( )112 /1/ PPPP == . It is necessary to mention the following important relations emel Psp =2 ,

    . They show that for reducing and increasing efficiency it

    is required to obtain small slip

    ( ) emmec PsP = 1 2elps of the motor.

    Nominal values of efficiency, slip and power factor of modern general-

    purpose induction motors are

    95.072.0 =n ; 05.002.0 =ns ; 95.070.0cos =n .

  • 78

    Energetic diagram of induction motor reactive power (Fig. 2.11) may be

    shown in the following way.

    The motor consumes the reactive power from the mains

    11111 sinQ = IUm . For leakage flux of stator and rotor winding initiation reactive powers

    , are used. 12111 xImq = ( ) 222222212 xImxImq ==

    Reactive power spent for motor resultant magnetic flux

    is the main portion of reactive power of the motor, which is significantly higher

    than in transformers due to the air gap. Large values and significantly

    influence power factor of the motor and reduce its value.

    mm xIm = 201Q

    mQ 0I

    2.10. Induction Motor Torques

    Electromagnetic torque of an induction motor is produced by current

    interaction in rotor winding with rotating magnetic flux and is proportional to

    electromagnetic power

    ( ) ( ) ( )srImspPM elem === 12221121 //// , where pfn /260/2 111 == is angular rotation frequency of magnetic flux.

    The above expression shows that electromagnetic torque is proportional to

    electrical losses power in rotor winding. From L-shape equivalent circuit the

    current in the closed working circuit is

  • 79

    )( ) (( ) ( )22112211

    1

    22

    2111

    21

    2111

    112

    /

    /

    xcxsrcr

    Uxcxcsrcrc

    UcI

    +++

    =+++

    =

    Electromagnetic torque formula becomes

    ( ) ( )[ ]221122111 2211

    /2 xcxsrcrsfrUmpM +++= .

    Parameter values of an induction motor equivalent circuit at load change

    remain practically invariable as well as the voltage in winding phase and

    frequency .

    1U

    1f

    Therefore one may conclude that electromagnetic torque at any slip value

    is proportional to phase voltage squared (phase rotor current squared). The less

    is electromagnetic torque, the larger are such parameters of equivalent circuit as

    , , . 1r 1x 2xConsider the dependence (relation) of electromagnetic torque on slip

    at , and fixed parameters of equivalent circuit

    (Fig. 2.12). This dependence is called mechanical characteristic of an induction

    motor.

    ( )sfM = constU =1 constf =1

    Under the slip value 0=s and =s the electromagnetic torque 0=M . Mechanical characteristic exhibits two extrema and maximum induction motor

    torque at generator effect duty is slightly larger than at driving duty

    ( mmmg MM > ).

    Critical slip value corresponding to maximum torque is obtained from

    the first derivative of the expression for electromagnetic torque, which is

    equated to zero

    scs

  • 80

    ( )22112111 / xcxrrscr ++= .

    Fig. 2.12

    Substituting the expression of critical slip to the formula of

    electromagnetic torque we obtain the expression for the maximum

    electromagnetic torque

    ( )[ ]2211211112

    11

    4 xcxrrcfUmpM m +++= ,

    where the sign (+) corresponds to driving and the sign (-) corresponds to

    generator effect duty of an induction motor.

    Electromagnetic torque reaches maximum value at crss = and further in spite of the increase of the torque reduces as current becomes more

    inductive ( ). As noted above the active component of

    current determines the value . This active component first increases as

    2I 2I ([ // 222 srxarctg = )]

    2I 2I increases and then it reduces in spite of the increase of 2I . It should be taken

  • 81

    into account that with increase the voltage drop in stator winding increases

    and, as a result, e.m.f. and flux

    1I

    1E somewhat reduce. For general-purpose induction motors it is defined as ( )2111 xcxr +

  • 82

    When analysing induction motor operation we shall use mechanical

    characteristic shown in Fig. 2.13. When cutting the motor in the

    magnetic stator flux possessing no inertia begins rotating at synchronous

    frequency and engine rotor under the effect of inertia forces remains

    stationary ( ) and slip

    ( )sfM =

    1n

    0=n 1=s . Expression of initial starting electromagnetic torque of the motor is

    [ ]2' 2112'2111'

    22

    11

    )()(2 xcxrcrfrUmpM S +++++= .

    Engine rotor begins rotating under the effect of this torque. In this case the

    slip decreases and the torque increases according to characteristic ( )sfM = . Under the critical slip the torque reaches maximum value . At further

    rotation frequency increase torque reduces until it reaches the value which is

    equal to the sum of opposing torques applied to engine rotor, namely, open-

    circuit torque and net torque (

    crs m

    0M 2M st20 MMMM =+= - static torque ). It should be taken into account that at slips close to unity (starting motor

    duty) equivalent circuit parameters significantly change their values. The

    reasons are considered to be amplification of magnetic saturation of stator and

    rotor teeth layers ( inductive reactance of leakage and decreases ),

    current displacement effect in rotor bars (increase of pure resistance and

    1x 2x2r 2x

    decrease). Calculation of starting characteristics is made by the corresponding

    parameters of equivalent circuit.

    Static torque is equal to the sum of opposing torques at uniform rotor

    rotation ( ). At rated load of the motor steady duty of motor operation

    is determined according to mechanical characteristic by point with coordinates

    and .

    stM

    constn =

    nMM = nss =

  • 83

    Mechanical characteristic analysis shows that a stable induction motor

    performance is possible at slips being less than critical ( crss < ), i.e. in the area of mechanical characteristic. It is in this area that the load change on motor

    shaft is accompanied by the corresponding change of electromagnetic torque.

    When a motor runs at the nominal load there is equality of torques

    . If the net load torque increase up to value then the torque

    equality is impaired and rotor rotation frequency begins to reduce (slip

    increases). It brings to electromagnetic torque increase up to value

    (point ) and motor duty becomes stable again. If the motor was

    running at nominal load and net load torque decrease up to value occurred

    the torque equality is impaired again but rotor rotation frequency begins

    increasing (the slip decreases). It brings to electromagnetic torque decrease

    up to value (point ). Stable running conditions are restored

    again but at another values of and s.

    nn MMM 20 += 2

    20 MMM +=2M

    20 MMM +=

    Induction motor operation is unstable at slips . If one obtains

    electromagnetic motor torque

    crss mMM = and slip crss = then even a slight

    increase of load torque brings to electromagnetic torque M decrease. Futher slip

    increase follows until it reaches the value 1=s , i.e. until the rotor stops running.

  • 84

    2.11. Starting Three-Phase Induction Motors ( IM )

    Induction motor starting requirements are the following:

    Induction motor should develop a starting torque large enough to

    make the rotor rotate and reach nominal frequency.

    Starting current should be limited by the value at which motor

    damage and normal running duty impairment do not occur.

    Starting diagram should be simple, the number and cost of starting

    devices should be small.

    2.11.1. Starting of Squirrel-Cage Induction Motor

    Direct starting. It is the simplest mode of starting. Stator winding is cut in

    directly to the mains at nominal voltage (Fig. 2.14). Starting current is

    nscscns IrUI 122

    11 )74( =+= . Direct starting is possible in case of

    powerful mains and starting current of

    induction motor does not cause large

    voltage drops in the mains (not more than

    1015%). Three modes of low-voltage starting.

    These modes of starting are used if direct

    starting is not available under the condition

    of permissible voltage drop in the mains.

    Starting torque decrease ( ) is 21s UM considered to be the drawback in this case. Fig. 2.14

  • 85

    There for these modes may be realized when starting of an induction

    motor at light-running or partial load is possible. This often occurs in powerful

    high-voltage motors.

    Reactor starting (Fig. 2.15). The first switch SW1 is cut in. Voltage is

    applied to stator winding via three-phase reactor R; therefore stator winding is

    powered by reduced voltage.

    Reactor reactance is

    chosen so that voltage in stator

    winding phase is not less than

    65% of the nominal one.

    rx

    Having reached stable

    rotating frequency the switch

    SW2 is cut in. It shunts reactor R

    and as a result full line voltage,

    which is equal to nominal stator

    winding, is applied across the

    terminals of stator winding.

    Fig. 2.15 Starting current at reactor starting is ( )2211 rscscnsr rUI ++= and it decreases as compared with the current under the direct starting

    ( )22

    22

    1

    1

    scsc

    rscsc

    sr

    s

    rr

    II

    +++= .

    The voltage across stator winding terminals decreases at initial stage of

    starting the same number of times.

    Initial stage of reactor starting decreases as compared with the initial

    stage of direct starting

    srM

    s

  • 86

    ( )22

    22

    sr

    s

    scsc

    rscsc

    rr

    M

    +++= times.

    In the above relations the changes of the value at starting are not taken

    into account. It is not difficult to do if necessary.

    sc

    Autotransformer starting (Fig. 2.16). At first switches SW1 and SW2 are

    cut in and reduced up to ( nU173.055.0 ) voltage is applied to stator winding of induction motor via autotransformer AT.

    After a stable rotation frequency is reached the switch SW2 is cut off and

    the voltage is applied to stator winding via some winding portion of

    autotransformer, the latter working like a reactor in this case. Then switch SW3

    is cut in and full line voltage equal to

    nominal voltage of stator winding is

    applied across the terminals of stator

    winding.

    If the starting autotransformer decreases

    starting voltage of IM k times ( is

    transformation ratio of autotransformer),

    then the starting current of IM and current

    across low-voltage side of

    autotransformer also decrease times.

    AT ATk

    ATk

    Starting torque , proportional to

    squared voltage across the terminals of

    IM stator winding will reduce times.

    s

    2ATk

    Fig. 2.16

  • Starting current across high-voltage side and supply current decrease

    times as well.

    2ATk

    Thus, at autotransformer starting IM starting torque and starting supply

    current reduce a similar number of times. At reactor starting IM starting current

    is also starting supply current and starting torque decreases more rapidly

    than the starting current. Therefore, at similar values of starting current the

    starting torque will be higher at autotransformer starting. In spite of this

    advantage of the autotransformer starting over the reactor starting, which is

    achieved at the expense of more complicated construction and rise in price of

    starting devices, this mode of starting is used seldom compared with reactor one

    when reactor starting does not provide necessary starting torque.

    s

    Starting by star-delta switching (Fig. 2.17). This mode was widely used

    at low-voltage IM starting but had

    lost its significance at mains

    power increase and is used seldom

    now.

    For its application all the six

    terminals of stator winding are

    brought out. In so doing line

    voltage equals nominal phase

    voltage of stator winding. At the

    very starting stator winding is

    star-connected. When stable

    rotation frequency is achieved

    winding connection diagram

    changes for delta connection by

    switching SW. Fig. 2.17 Fig. 2.17

    Under this mode of starting

    87

  • 88

    voltage across stator winding phases is applied 3 times decreased compared

    with nominal one, starting torque decreases threefold, starting phase current

    decreases 3 times and starting line current decreases threefold. Thus, the

    considered mode of starting is equal to autotransformer starting at 3AT =k but commutational overvoltage occurs in stator winding of induction motor at

    starting switch.

    2.11.2. Slip-Ring Induction Motor Starting

    Starting rheostat possessing

    several stages as a rule is cut in to rotor

    winding circuit. It is calculated for

    instantaneous current flows (Fig. 2.18).

    Initial starting torque may be

    increased up to maximum motor torque

    maxs MM = at fixed resistsnce of starting rheostat RRs ( )ms= (Fig. 2.19). Resistance value of starting rheostat

    may be determined by equating

    critical slip to unity, i.e.

    ( )mRs

    ( )( ) ( ) 1221121s21 =+++= xcxrRrs mcr . Fig. 2.18 Referred active phase resistance of starting rheostat is

    ( ) ( ) 121221121s / crcxcxrR m ++= . Actual resistance of starting rheostat is defined as follows

    ( ) ( ) ( )21122s / wwmm kwkwRR = .

  • 89

    Usually one chooses .

    With rotor rotation frequency increase

    starting rheostat resistance is reduced

    changing one stage for another. Starting

    rheostat stages are calculated so that

    during switch the torque should be

    changed within the chosen range from

    up to .

    ( )mRR ss

    maxs,M mins,M

    Fig. 2.19

    2.12. Regulation of Induction Motor Rotation Frequency

    Rotor rotation frequency of IM is ( ) ( )( )spfsnn == 1/601 11 . It follows from this expression that rotor rotation frequency may be regulated by

    changing any of three values, namely, slip s, current frequency in stator winding

    and pole number of stator winding 2p. 1f

    Rotation frequency regulation by slip change occurs only in a loaded

    induction motor. Under light running conditions the slip and rotor rotation

    frequency remain practically invariable.

    Evaluation assessment of any mode of rotation frequency regulation is

    made according to the following indices:

    possible regulation range,

    smooth regulation,

    drive efficiency change at regulation.

  • 90

    Rotation frequency regulation by changing supplied voltage. Induction

    motor torque is proportional to ; therefore mechanical motor characteristics

    at voltages less than nominal one (Fig. 2.20) are located under the natural

    characteristic.

    21U

    If static torque is

    constant, then the slip of

    induction motor increases at

    voltage drop in stator winding,

    rotor rotation frequency

    decreases. Slip regulation using

    this mode is possible within the

    range

    stM

    scss

  • 91

    . Therefore, resultant electromagnetic torque

    of induction motor decreases:

    contains reverse component ( reversing field ) which develops torque rM

    directed opposition to torque op

    r= o

    ase supply (2), the latter being asymmetrical limit of three-phase

    voltag

    single-

    phase

    s a rule this

    rotatio

    ostat

    construction this rotation frequency regulation may be smooth or stepwise.

    p .

    Fig. 2.21

    Mechanical motor characteristics in this case [Fig. 2.21(a)] are positioned

    in th range between symmetrical voltage characteristic (1) and characteristic at

    single-ph

    e.

    Asymmetry regulation of applied voltage is provided by cutting in

    regulation autotransformer AT [Fig. 2.21(b)] to one of the phases.

    The drawback of this mode of regulation is a narrow regulation range and

    efficiency decrease of the motor at asymmetrical voltage increase. A

    n frequency regulation is used only in smaller rating motors.

    Rotating frequency regulation by changing the pure resistance in rotor

    circuit. This regulation of rotation frequency is available only in wound rotor

    induction motors. Regulation rheostat similar to starting one but meant for

    continuous duty is cut in to rotor circuit. Depending on regulation rhe

  • 92

    Mech