Ejemplo Selectividad T7
description
Transcript of Ejemplo Selectividad T7
4
4/78
U V = 400 V
Ik = 95 kA
QF1
T6L800 PR223EF In800
(E3H800 PR122/P-LSI In800)
QS1
T6D800
(E3S/MS 1000)
WC16x(1x400)+2x(1x240)+1G400Ib = 740 AIz = 1050 AL = 17 mPVC
X
P
QF2
T5L630 PR223EF In630
(T6L630 PR222DS-LSI In630)
QS2
T5D630
(T6D630)
WC26x(1x300)+2x(1x150)+1G300Ib = 540 AIz = 681.6 AL = 25 m
X
P
QF3
T4L250 PR223EF In250
(T4L250 PR222DS-LSI In250)
L1
In = 200.0 A
Ik = 74 kA
Ik = 54.5 kA
Switchboard A
Switchboard B
WC33x(1x150)+1x(1x95)+1G95Ib = 200 AIz = 275.0 AL = 10 m
X
P
L
QF4
T4L250 PR223EF In250
(T4L250 PR222DS-LSI In250)
L2
In = 200.0 A
WC43x(1x95)+1x(1x50)+1G50Ib = 200 AIz = 207 AL = 40 m
X
P
L
QF6
T4L250 PR223EF In250
(T4H250 PR222DS-LSI In250)
L4
In = 170 A
WC43x(1x95)+1x(1x50)+1G50Ib = 170 AIz = 207 AL = 30 m
QF5
T4L250 PR223EF In250
(T4H250 PR222DS-LSI In250)
L3
In = 170 A
WC53x(1x95)+1x(1x50)+1G50Ib = 170 AIz = 207 AL = 60 m
X
P
L
X
P
L1
SD
C2
10
F2
4F0
00
1
1SDC210015D0705
Ejemplo de aplicaciónEn el siguiente ejemplo se muestra una comparación entre una instalación en la cual la selectividad
ha sido realizada con técnicas tradicionales y la misma instalación en la cual la selectividad se obtiene
con el sistema EFDP con PR223.
La selectividad con métodos tradicionales acondiciona fuertemente la elección de los dispositivos,
dirigiéndola hacia tamaños diferenciados en función a la posición de los interruptores en la instalación.
En la siguiente tabla se reseñan las ventajas que proceden del uso del nuevo relé electrónico.
Solución tradicional Solución con EFDP
QF1 E3H800 PR122/P T6L800 PR223EF
QS1 E3S/MS1000 T6D800
QF2 T6L630 PR221DS T5L630 PR223EF
QS2 T6D630 T5D630
Cuadro A
Cuadro B
Aplicaciones particulares
Selectividad de zona