    Fan Coil Unit (DDW)

    Catalogue/Engineering Data PCUA14-10

    Horizontal UnitModel: DDW020H-DDW450H

    Air Flow: 2,000m3

    /h-45,000m3

    /h

    Vertical UnitModel: DDW040V-DDW450V

    Air Flow: 4,000m3/h-45,000m

    3/h

  • 8/19/2019 ED-DDW-201401B

    2/27

    1

     

    DDWDouble Skin Fan Coil unit

    Contents

    Note: Installation and maintenance are to be performed only by qualied personnel who are

    familiar with local codes and regulations, and experienced with this type of equipment.

    Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.

    Warning: Moving machinery and electrical power hazard may cause severe personal injury or

    death. Disconnect and lock off power before servicing equipment.

      Literature No.:  PCUA14-10

      Supersedes: ED-DDW-201311B

    Nomenclature....................................................................................................................... 2

    Features................................................................................................................................ 3

    Specications ...................................................................................................................... 4

    Dimensions ........................................................................................................................ 10

    Fan Discharge Type ........................................................................................................... 16

    Selection Software ............................................................................................................ 17

    Special Notes ..................................................................................................................... 18

    Wiring Diagrams ................................................................................................................ 19

    Installation.......................................................................................................................... 20

    Servicing And Maintenance ............................................................................................. 22

    Common Failures .............................................................................................................. 24

  • 8/19/2019 ED-DDW-201401B

    3/27

    2

     

    DDW Double Skin Fan Coil unit

    Nomenclature

    D D W 080 H   R   08   -4   L-  F F   B   EExport

    Design ID

    Discharge Type

      F - Horizontal Discharge Type

      T - Top Discharge Type

    Power Supply:

      F - 380-415V/3N~/50Hz

      R - 380V/3N~/60Hz  P - 208-230V/3N~/60Hz

      Q - 460V/3N~/60Hz

    Pipe Connection:

      R - Left Hand

      L - Right Hand

      (Facing Air Discharge)

    Coil Rows:

      4 - 4 Rows

      6 - 6 Rows

    External Total Pressure  08 - 80 Pa; 15 - 150Pa

      22 - 220Pa; 30 - 300Pa

     Air Conditioning

      R - Return Air 

      F - Fresh Air 

    Structure Type

      H - Horizontal

      V - Vertical

     Air Flow

      080 - 8000m3/h

    DDW - Double-Skin FCU

  • 8/19/2019 ED-DDW-201401B

    4/27

    3

     

    DDWDouble Skin Fan Coil unit

    Features

    General Information

    DAIKIN DDW air handling units are designed to meet the needs of the terminal air conditioning market. DDW

    units are full featured handlers that are applicable for the central air-conditioning systems installed in hotels,

    supermarkets, hospitals and ofce buildings.

    Without Frame Type

    DDW units are equipped with no frame structure patent of DAIKIN and prevent air leakage angle design,to ensure

    no cold bridge and low leakage rate.

    Casing

    DDW Casing units is of double-skin panels and assembled with self supporting modular panel elements with an

    integrated base frame made of galvanized steel. assembled 25mm polyurethane foam offer ideal heat/sound

    insulation.

    Filter 

    Washable nylon primary air lter, removable and easy installation. Bag lter is optional.

    Coil Selection

     All the computing results and the products built on these results have passed strict test. This ensures their safe,

    reliable and effcient operation.

    Sirocco Fan

    High efcient and quiet titled multi-blade double-intake fans.

    Motor 

    V-belt driving,Class F,IP55 provide different amounts of air ow and ETP to meet different needs.

  • 8/19/2019 ED-DDW-201401B

    5/27

    4

     

    DDW Double Skin Fan Coil unit

    Specifcations

    DDW-H (Horizontal)

    NOTES:

    1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY.

    2) STANDARD RETURN AIR COOLING CONDITIONS: 27ºC DB/19.5ºC WB;

      STANDARD FRESH AIR COOLING CONDITIONS: 34ºC DB/28ºC WB;

      STANDARD RETURN AIR HEATING CONDITION: 21ºC DB; STANDARD FRESH AIR HEATING CONDITION: 0ºC WB STANDARD CHILLED

    WATER ENTERING/LEAVING CONDITIONS: 7ºC FOR ENTERING WATER; 12ºC FOR LEAVING WATER;

      STANDARD HOT WATER ENTERING/LEAVING CONDITIONS: 60ºC FOR ENTERING WATER; 50ºC FOR LEAVING WATER;

    3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDW

    SELECTION SOFTWARE.

    4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL.

    5)  THE I, II, III, IV INDI CADES THE PARAMETERS CNDER DEFINED TOTAL PRESSURE CONDITION.

    6)  THE MOTOR OUTPUT POWER IS TESTED UNDER THE CORRESPONDING EXTERNAL TOTAL PRESSURE I, II, III, IV INDI CATES AND THE

    UALNE IN THE BARCFET IS THE MOTOR OUTPUT POWER OF CODWS UNITS THE OTHER VAIUE IS THE 4 ROWS UNITS.

    Model DDW020H DDW030H DDW040H DDW050H DDW060H DDW080H

    Nominal Air Flow (m3 /h) 2000 3000 4000 5000 6000 8000

    Internal+External

    Static pressure

    (Pa)

    I(5) 80 80 80 - - -

    II(5) 150 150 150 150 150 150

    III(5) 220 220 220 220 220 220

    IV(5) -- - - 300 300 300

    Nominal cooling

    capacity (kW)

      4 Rows (Return air) 12 17 24 30 37 49

    4 Rows (Fresh air) 28 41 56 66 80 111

    6 Rows (Return air) 15 23 32 38 46 61

    6 Rows (Fresh air) 34 52 67 86 103 136

    Nominal heatingcapacity (kW)

      4 Rows (Return air) 19 29 40 49 60 81

    4 Rows (Fresh air) 32 48 65 80 97 1306 Rows (Return air) 23 35 47 59 71 94

    6 Rows (Fresh air) 37 56 75 93 112 149

    Coil

    Type Corrugated aluminum n mechanically bonded with copper tube

    FPI 12

    Working pressure

    (MPa)1.6

    Entering/Leaving

    water pipeR1-1/2 R1-1/2 R2 R2 R2 R2

    Condensing water pipe R1-1/4

    Copper pipie diameter

    (mm)12.7

    Fan

    Type/Material High Efcient Centrifugal Multi-blades Fan/Galavnize Steel

    Drive type V-belt

    Fan disdchargeorientation

    Lower horizontal discharge/Top discharge

    Motor 

    Power supply 380V/3N~/50Hz

    Motor type 3-Phase Asynchronous Motor,Class F, no less than IP54

    Motor output

    power (kW)

    I(5) 0.37(0.37)(6) 0.55(0.55) 0.55(0.75) - - -

    II(5) 0.37(0.55) 0.55(0.75) 0.75(1.1) 1.1(1.1) 1.1(1.5) 1.5(2.2)

    III(5) 0.55(0.55) 0.75(0.75) 1.1(1.1) 1.1(1.5) 1.5(1.5) 2.2(2.2)

    IV(5) - - - 1.5(1.5) 1.5(2.2) 2.2(2.2)

    Filter Type/Material Nylon

    Thickness (mm) 21

    Casing Type 25mm Double skin,outer plate material is color coated steel,inner plate material is EG steel

    Unit weight (kg)4 Rows 132 155 172 196 215 253

    6 Rows 142 161 184 203 227 278

    Unit dimension

    Height (mm) 600 650 730 730 800 800

    Width (mm) 900 1050 1080 1250 1320 1680

    Length (mm) 960 1000 1100 1060 1150 1150

    Packing

    dimension

    Height (mm) 800 850 930 930 1000 1000

    Width (mm) 1150 1300 1330 1500 1570 1930

    Length (mm) 1170 1210 1310 1270 1360 1360

  • 8/19/2019 ED-DDW-201401B

    6/27

    5

     

    DDWDouble Skin Fan Coil unit

    DDW-H (Horizontal) 

    NOTES:1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY.2) STANDARD RETURN AIR COOLING CONDITIONS: 27ºC DB/19.5ºC WB;  STANDARD FRESH AIR COOLING CONDITIONS: 34ºC DB/28ºC WB;  STANDARD RETURN AIR HEATING CONDITION: 21ºC DB; STANDARD FRESH AIR HEATING CONDITION: 0ºC WB STANDARD CHILLED

    WATER ENTERING/LEAVING CONDITIONS: 7ºC FOR ENTERING WATER; 12ºC FOR LEAVING WATER;  STANDARD HOT WATER ENTERING/LEAVING CONDITIONS: 60ºC FOR ENTERING WATER; 50ºC FOR LEAVING WATER;

    3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDWSELECTION SOFTWARE.

    4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL.5)  THE I, II, III, IV INDI CADES THE PARAMETERS CNDER DEFINED TOTAL PRESSURE CONDITION.

    6)  THE MOTOR OUTPUT POWER IS TESTED UNDER THE CORRESPONDING EXTERNAL TOTAL PRESSURE I, II, III, IV INDI CATES AND THE

    UALNE IN THE BARCFET IS THE MOTOR OUTPUT POWER OF CODWS UNITS THE OTHER VAIUE IS THE 4 ROWS UNITS.

    Model DDW100H DDW120H DDW150H DDW180H DDW200H DDW250H

    Nominal Air Flow (m3 /h) 10000 12000 15000 18000 20000 25000

    External

    total 

    pressure

    (Pa)

    I(5) - - - - - -

    II(5) 150 150 150 150 150 150

    III(5) 220 220 220 220 220 220

    IV(5) 300 300 300 300 300 300

    Nominal

    cooling

    capacity

    (kW)

      4 Rows (Return air) 62 73 95 108 121 152

    4 Rows (Fresh air) 139 166 194 233 266 333

    6 Rows (Return air) 76 91 118 144 151 190

    6 Rows (Fresh air) 170 204 263 316 346 430

    Nominal

    heating

    capacity

    (kW)

      4 Rows (Return air) 101 120 152 182 200 250

    4 Rows (Fresh air) 159 193 242 291 325 404

    6 Rows (Return air) 118 141 179 213 237 297

    6 Rows (Fresh air) 186 223 283 335 373 467

    Coil

    Type Corrugated aluminum n mechanically bonded with copper tube

    FPI 12

    Working pressure (MPa) 1.6

    Entering/Leaving

    water pipeR2 R2 R2-1/2 R2-1/2 R2-1/2 R3

    Condensing water pipe R1-1/4

    Copper pipie diameter (mm) 12.7

    Fan

    Type/Material High Efcient Centrifugal Multi-blades Fan/Galavnize Steel

    Drive type V-belt

    Fan disdcharge orientation Lower horizontal discharge/Top discharge

    Motor 

    Power source 380V/3N~/50Hz

    Motor type 3-Phase Asynchronous Motor,Class F, no less than IP54

    Motor output power

    (kW)

    I(5) - - - - - -

    II(5) 2.2(2.2)(6)  2.2(3.0) 3.0(4.0) 4.0(4.0) 4.0(4.0) 5.5(5.5)

    III(5) 2.2(2.2) 3.0(3.0) 4.0(4.0) 4.0(5.5) 4.0(5.5) 5.5(7.5)

    IV(5) 2.2(3.0) 3.0(3.0) 4.0(4.0) 5.5(5.5) 5.5(5.5) 7.5(7.5)

    Filter Type/Material Nylon

    Thickness (mm) 21

    Casing Type25mm Double skin,outer plate material is color coated steel,inner plate material is

    EG steel

    Unit weight

    (kg)

    4 Rows 313 325 347 444 479 557

    6 Rows 335 354 415 497 535 600

    Unit

    dimension

    Height (mm) 930 1050 1180 1240 1240 1430

    Width (mm) 1690 1690 1940 2120 2300 2400

    Length (mm) 1170 1170 1170 1310 1310 1310

    Packing

    dimension

    Height (mm) 1130 1250 1380 1440 1440 1630

    Width (mm) 1940 1940 2190 2370 2550 2650

    Length (mm) 1380 1380 1380 1520 1520 1520

  • 8/19/2019 ED-DDW-201401B

    7/27

    6

     

    DDW Double Skin Fan Coil unit

    Model DDW300H DDW350H DDW400H DDW450H

    Nominal Air Flow (m3 /h) 30000 35000 40000 45000

    External total

    pressure (Pa)

    I(5)

    300 300 300 300II(5) 400 400 400 400

    III(5) 500 500 500 500

    IV(5) 600 600 600 600

    Nominal cooling

    capacity (kW)

      4 Rows (Return air) 178 205 238 266

      4 Rows (Fresh air) 390 448 520 577

      6 Rows (Return air) 222 256 296 329

      6 Rows (Fresh air) 490 556 639 703

    Nominal heating

    capacity (kW)

      4 Rows (Return air) 295 337 391 437

      4 Rows (Fresh air) 472 534 604 670

      6 Rows (Return air) 371 398 450 500

      6 Rows (Fresh air) 544 629 719 802

    Coil

    Type Corrugated aluminum n mechanically bonded with copper tube

    FPI 12

    Working pressure (MPa) 1.6

    Entering/Leaving

    water pipeR3 R2-1/2 R2-1/2 R2-1/2

    Condensing water pipe R1-1/4

    Copper pipie diameter

    (mm)12.7

    Fan

    Type/Material High Efcient Centrifugal Multi-blades Fan/Galavnize Steel

    Drive type V-belt

    Fan disdcharge

    orientationHorizontal discharge /Top discharge

    Motor 

    Power source 380V/3N~/50Hz

    Motor type 3-Phase Asynchronous Motor,Class F, no less than IP54

    Motor output

    power (kW)

    I(5) 7.5(11)(6) 11(11) 11(15) 15(15)

    II(5) 11(11) 11(15) 15(15) 15(18.5)

    III(5) 11(11) 15(15) 15(15) 18.5(18.5)

    IV(5) 15(15) 15(15) 18.5(18.5) 18.5(18.5)

    Filter Type/Material Nylon

    Thickness (mm) 21

    Casing Type 25mm Double skin,outer plate material is color coated steel,inner plate material is EG steel

    Unit dimension

    Height (mm) 1549 1709 1869 2029

    Length (mm) 1646 1646 1806 1806

    Width (mm) 2766 2766 2926 2926

    Packing

    dimension

    Height (mm) 1566 1726 1886 2046

    Width (mm) 1846 1846 2006 2006Length (mm) 2966 2966 3126 3126

    DDW-H (Horizontal) 

    NOTES:

    1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY.

    2) STANDARD RETURN AIR COOLING CONDITIONS: 27ºC DB/19.5ºC WB;

      STANDARD FRESH AIR COOLING CONDITIONS: 34ºC DB/28ºC WB;

      STANDARD RETURN AIR HEATING CONDITION: 21ºC DB; STANDARD FRESH AIR HEATING CONDITION: 0ºC WB STANDARD CHILLED

    WATER ENTERING/LEAVING CONDITIONS: 7ºC FOR ENTERING WATER; 12ºC FOR LEAVING WATER;

      STANDARD HOT WATER ENTERING/LEAVING CONDITIONS: 60ºC FOR ENTERING WATER; 50ºC FOR LEAVING WATER;

    3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDW

    SELECTION SOFTWARE.

    4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL.

    5) THE I, II, III, IV INDI CADES THE PARAMETERS CNDER DEFINED TOTAL PRESSURE CONDITION.

    6) THE MOTOR OUTPUT POWER IS TESTED UNDER THE CORRESPONDING EXTERNAL TOTAL PRESSURE I, II, III, IV INDI CATES AND THE

    UALNE IN THE BARCFET IS THE MOTOR OUTPUT POWER OF CODWS UNITS THE OTHER VAIUE IS THE 4 ROWS UNITS.

  • 8/19/2019 ED-DDW-201401B

    8/27

    7

     

    DDWDouble Skin Fan Coil unit

    DDW-V (Vertical) 

    NOTES:

    1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY.

    2) STANDARD RETURN AIR COOLING CONDITIONS: 27ºC DB/19.5ºC WB;

      STANDARD FRESH AIR COOLING CONDITIONS: 34ºC DB/28ºC WB;

      STANDARD RETURN AIR HEATING CONDITION: 21ºC DB; STANDARD FRESH AIR HEATING CONDITION: 0ºC WB STANDARD

    CHILLED WATER ENTERING/LEAVING CONDITIONS: 7ºC FOR ENTERING WATER; 12ºC FOR LEAVING WATER;

      STANDARD HOT WATER ENTERING/LEAVING CONDITIONS: 60ºC FOR ENTERING WATER; 50ºC FOR LEAVING WATER;

    3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDW

    SELECTION SOFTWARE.

    4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL.

    5) MODEL DDW040~250V ARE WITHOUT FRAME; DDW300~450V ARE WITH FRAME TYPE.

    6) THE I, II, III, IV INDI CADES THE PARAMETERS CNDER DEFINED TOTAL PRESSURE CONDITION.

    7) THE MOTOR OUTPUT POWER IS TESTED UNDER THE CORRESPONDING EXTERNAL TOTAL PRESSURE I, II, III, IV INDI CATES

     AND THE UALNE IN THE BARCFET IS THE MOTOR OUTPUT POWER OF CODWS UNITS THE OTHER VAIUE IS THE 4 ROWS UNITS.

    Model DDW040V DDW050V DDW060V DDW080V DDW100V DDW120V DDW150V

    Nominal Air Flow (m3 /h) 4000 5000 6000 8000 10000 12000 15000

    External

    total

    pressure

    (Pa)

    I(6) - - - - - - -

    II(6) 150 150 150 150 150 150 150

    III(6) 220 220 220 220 220 220 220

    IV(6) 300 300 300 300 300 300 300

    Nominal

    cooling

    capacity

    (kW)

      4 Rows (Return air) 23 29 36 49 62 72 90

      4 Rows (Fresh air) 54 69 78 106 135 164 194

      6 Rows (Return air) 31 39 54 61 76 94 118

      6 Rows (Fresh air) 69 85 102 132 164 202 259

    Nominal

    heating

    capacity

    (kW)

      4 Rows (Return air) 39 49 59 80 100 120 152

      4 Rows (Fresh air) 64 80 96 128 161 193 241

      6 Rows (Return air) 47 59 71 95 119 141 176

      6 Rows (Fresh air) 75 93 112 149 187 223 279

    Coil

    Type Corrugated aluminum n mechanically bonded with copper tubeFPI 12

    Working pressure (MPa) 1.6

    Entering/Leaving

    water pipeR2 R2 R2 R2 R2 R2 R2-1/2

    Condensing water pipe R1-1/4

    Copper pipie diameter (mm) 12.7

    Fan

    Type/Material High Efcient Centrifugal Multi-blades Fan/Galavnize Steel

    Drive type V-belt

    Fan disdcharge orientation Top discharge

    Motor 

    Power source 380V/3N~/50Hz

    Motor type 3-Phase Asynchronous Motor,Class F, no less than IP54

    Motor output power

    (kW)

    I(6) - - - - - - -

    II(6) 0.75(1.1)(7) 1.1(1.1) 1.5(1.5) 1.5(2.2) 2.2(2.2) 2.2(3.0) 3.0(4.0)

    III(6) 1.1(1.1) 1.1(1.5) 1.5(2.2) 2.2(2.2) 2.2(2.2) 3.0(3.0) 4.0(4.0)

    IV(6) 1.1(1.5) 1.5(1.5) 2.2(2.2) 2.2(2.2) 2.2(3.0) 3.0(3.0) 4.0(5.0)

    Filter Type/Material Nylon

    Thickness (mm) 21

    Casing Type 25mm Double skin,outer plate material is color coated steel,inner plate material is EG steel

    Unit weight

    (kg)

    4 Rows 199 225 246 274 345 369 432

    6 Rows 208 237 259 305 367 399 474

    Unit

    dimension

    Height (mm) 1283 1343 1403 1613 1853 1923 1673

    Length (mm) 980 1140 1210 1320 1390 1530 2090

    Width (mm) 650 650 650 810 900 900 900

    Packing

    dimension

    Height (mm) 1470 1530 1590 1800 2040 2110 1860

    Width (mm) 860 860 860 1020 1110 1110 1110

    Length (mm) 1160 1320 1390 1500 1570 1710 2270

  • 8/19/2019 ED-DDW-201401B

    9/27

    8

     

    DDW Double Skin Fan Coil unit

    DDW-V (Vertical)

    NOTES:1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY.2) STANDARD RETURN AIR COOLING CONDITIONS: 27ºC DB/19.5ºC WB;  STANDARD FRESH AIR COOLING CONDITIONS: 34ºC DB/28ºC WB;  STANDARD RETURN AIR HEATING CONDITION: 21ºC DB; STANDARD FRESH AIR HEATING CONDITION: 0ºC WB STANDARD CHILLED

    WATER ENTERING/LEAVING CONDITIONS: 7ºC FOR ENTERING WATER; 12ºC FOR LEAVING WATER;  STANDARD HOT WATER ENTERING/LEAVING CONDITIONS: 60ºC FOR ENTERING WATER; 50ºC FOR LEAVING WATER;3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDW

    SELECTION SOFTWARE.4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL.5) MODEL DDW040~250V ARE WITHOUT FRAME; DDW300~450V ARE WITH FRAME TYPE.6) THE I, II, III, IV INDI CADES THE PARAMETERS CNDER DEFINED TOTAL PRESSURE CONDITION.7) THE MOTOR OUTPUT POWER IS TESTED UNDER THE CORRESPONDING EXTERNAL TOTAL PRESSURE I, II, III, IV INDI CATES AND THE

    UALNE IN THE BARCFET IS THE MOTOR OUTPUT POWER OF CODWS UNITS THE OTHER VAIUE IS THE 4 ROWS UNITS.

    Model DDW180V DDW200V DDW250V DDW300V DDW350V DDW400V DDW450V

    Nominal Air Flow (m3 /h) 18000 20000 25000 30000 35000 40000 45000

    Externaltotal

    pressure

    (Pa)

    I

    (6)

    - - - 300 300 300 300II(6) 150 150 150 400 400 400 400

    III(6) 220 220 220 500 500 500 500

    IV(6) 300 300 300 600 600 600 600

    Nominal

    cooling

    capacity

    (kW)

      4 Rows (Return air) 109 121 154 178 205 238 266

      4 Rows (Fresh air) 239 266 342 390 448 520 577

      6 Rows (Return air) 135 152 193 222 256 296 329

      6 Rows (Fresh air) 313 347 427 490 556 639 703

    Nominal

    heating

    capacity

    (kW)

      4 Rows (Return air) 183 200 250 295 337 391 437

      4 Rows (Fresh air) 292 325 393 472 534 604 670

      6 Rows (Return air) 214 237 297 371 398 450 500

      6 Rows (Fresh air) 336 373 469 544 629 719 802

    Coil

    Type Corrugated aluminum n mechanically bonded with copper tube

    FPI 12

    Working pressure (MPa) 1.6

    Entering/Leaving

    water pipeR2-1/2 R2-1/2 R3 R3 R2-1/2 R2-1/2 R2-1/2

    Condensing water pipe R1-1/4

    Copper pipie diameter (mm) 12.7

    Fan

    Type/Material High Efcient Centrifugal Multi-blades Fan/Galavnize Steel

    Drive type V-belt

    Fan disdcharge orientation Top discharge

    Motor 

    Power source 380V/3N~/50Hz

    Motor type 3-Phase Asynchronous Motor,Class F, no less than IP54

    Motor output power

    (kW)

    I(6) - - - 7.5(11) 11(11) 11(15) 15(15)

    II(6) 4.0(4.0)(7)  4.0(4.0) 5.5(5.5) 11(11) 11(15) 15(15) 15(18.5)

    III(6) 4.0(5.5) 4.0(5.5) 5.5(7.5) 11(11) 15(15) 15(15) 18.5(18.5)

    IV(6) 5.5(5.5) 5.5(5.5) 7.5(7.5) 15(15) 15(15) 18.5(18.5) 18.5(18.5)

    Filter Type/Material Nylon

    Thickness (mm) 21

    Casing Type 25mm Double skin,outer plate material is color coated steel,inner plate material is EG steel

    Unit weight

    (kg)

    4 Rows 485 538 622 - - - -

    6 Rows 536 595 664 - - - -

    Unit

    dimension

    Height (mm) 1923 1983 2043 2555 2715 3035 3195

    Length (mm) 2240 2320 2670 2766 2766 2926 2926

    Width (mm) 900 900 900 1006 1006 1166 1166

    Packing

    dimension

    Height (mm) 2110 2170 2230 2572 2732 3052 3212

    Width (mm) 1110 1110 1110 1206 1206 1366 1366

    Length (mm) 2420 2500 2850 2966 2966 3126 3126

  • 8/19/2019 ED-DDW-201401B

    10/27

    9

     

    DDWDouble Skin Fan Coil unit

    DDW-H

    DDW-V

    NOTES:

    THE DATA IS FOR STANDARD UNIT.ESP VALUE IS BASED ON ETP VALUE.FOR EXAMPLE,THE ESP VALUE IS 50PA WHEN ETP IS 80PA

    FOR DDW020H UNIT.

    External static presure check list

    Unit model DDW020H DDW030H DDW040H DDW050H DDW060H DDW080H DDW100H DDW120H DDW150H DDW180H DDW200H

    Nominal air fow (m3/h) 2000 3000 4000 5000 6000 8000 10000 12000 15000 18000 20000

    ETP (Pa)

    I 80 80 80  - - - - - - - -

    II 150 150 150 150 150 150 150 150 150 150 150

    III 220 220 220 220 220 220 220 220 220 220 220

    IV - - - 300 300 300 300 300 300 300 300

    ESP (Pa)

    I 50 34 39  - - - - - - - -

    II 120 104 109 86 104 68 99 77 35 61 85

    III 190 174 179 156 174 138 169 147 105 131 155

    IV - - - 236 254 218 249 227 185 211 235

    Unit model DDW040V DDW050V DDW060V DDW080V DDW100V DDW120V DDW150V DDW180V DDW200V

    Norminal air fow (m3/h) 4000 5000 6000 8000 10000 12000 15000 18000 20000

    ETP (Pa)

    I - - - - - - - - -

    II 150 150 150 150 150 150 150 150 150

    III 220 220 220 220 220 220 220 220 220

    IV 300 300 300 300 300 300 300 300 300

    ESP (Pa)

    I - - - - - - - - -

    II 69 86 58 68 85 56 78 61 85

    III 139 156 128 138 155 126 148 131 155

    IV 219 236 208 218 235 206 228 211 235

    Unit model DDW250H DDW300H DDW350H DDW400H DDW450H DDW250V DDW300V DDW350V DDW400V DDW450V

    Norminal air fow (m3/h) 25000 30000 35000 40000 45000 25000 30000 35000 40000 45000

    ETP (Pa)

    I - 300 300 300 300 - 300 300 300 300

    II 150 400 400 400 400 150 400 400 400 400

    III 220 500 500 500 500 220 500 500 500 500

    IV 300 600 600 600 600 300 600 600 600 600

    ESP (Pa)

    I - 201 165 188 159  - 201 165 188 159

    II 48 301 265 288 259 48 301 265 288 259

    III 118 401 365 388 359 118 401 365 388 359

    IV 198 501 465 488 459 198 501 465 488 459

    DDW-H/V

  • 8/19/2019 ED-DDW-201401B

    11/27

    10

     

    DDW Double Skin Fan Coil unit

    DDW-H (Horizontal)

    DDW-H Horizontal Discharge

    DDW-H Top Discharge

    Hanging holes 4- 15

    Condensationwater drain pipe C

    Leavingwater pipe D

    Leaving water pipe DManual air vent

    Condensation waterdrain pipe C

    Entering water pipe D

    Hanging holes 4- 15

    Enteringwater pipe D

    Unit: mm

    Dimension Width Length Height Return air Supply air Hanging holesConnection pipe

    dimension

    Entering

    water pipe

    Condensation

    water drain pipe

    MODEL W L H F G A B K M N J S E P Q R D C

    DDW020H 900 960 600 810 460 298 262 1080 1020 910 150 201 191 85 158 276 R 1-1/2 R 1-1/4

    DDW030H 1050 1000 650 960 510 331 289 1230 1170 950 150 207 280 85 158 339 R 1-1/2 R 1-1/4

    DDW040H 1080 1100 730 990 590 395 341 1260 1200 1050 150 177 234 85 164 454 R 2 R 1-1/4

    DDW050H 1250 1060 730 1160 625 395 341 1430 1370 1010 150 216 317 85 164 454 R 2 R 1-1/4

    DDW060H 1320 1150 800 1230 660 471 404 1500 1440 1100 150 243 324 85 164 518 R 2 R 1-1/4

    DDW080H 1680 1150 800 1590 660 471 404 1860 1800 1100 150 243 529 85 164 518 R 2 R 1-1/4

    Dimensions

  • 8/19/2019 ED-DDW-201401B

    12/27

  • 8/19/2019 ED-DDW-201401B

    13/27

    12

     

    DDW Double Skin Fan Coil unit

    DDW-H (Horizontal)

    F

          L

     A      4      0

    W A

    90

          G

          1      2      5

          B

          J

          H

          6      3

          P

    DDW-H Horizontal Discharge

     

    Enteringwater pipe D

    Leavingwater pipe D

    Enteringwater pipe D

     

    Condensation water drain pipe C

     

    Leaving water pipe D

    Manual air vent

    T

    Unit: mm

    Dimension Width Length Height Return air Supply

    air Hanging holes

    Connection

    pipe

    dimension

    Entering

    water pipe

    Condensation

    water drain pipe

    MODEL W L H F G A B E T J S P D C

    DDW300H 2766 1646 1549 2670 1390 569 569 273 450 352 200 98 R 3 R 1-1/4

    DDW350H 2766 1646 1709 2670 1550 569 569 284 450 352 203 98 R 2-1/2 R 1-1/4

    DDW400H 2926 1806 1869 2830 1710 638 638 266 500 352 213 98 R 2-1/2 R 1-1/4

    DDW450H 2926 1806 2029 2830 1870 638 638 266 500 352 213 98 R 2-1/2 R 1-1/4

  • 8/19/2019 ED-DDW-201401B

    14/27

    13

     

    DDWDouble Skin Fan Coil unit

    F

     AB S

         4     0

         G

         6     3

    90 L

    N

    E

    M

    W

         P     Q

         R

         H

    Manual air vent

    DDW-V Top Discharge

    Leaving

    water pipe D

    Enteringwater pipe D

    Condensation

    water drain pipe C

    DDW-V (Vertical)

    Unit: mm

    Dimension Width Length Height Return air Supply air Hanging holesConnection pipe

    dimension

    Entering

    water

    pipe

    Condensation

    water drain

    pipe

    MODEL W L H F G A B M N S E P Q R D C

    DDW040V 980 650 1283 890 655 331 289 960 630 71 444 85 164 518 R 2 R 1-1/4

    DDW050V 1140 650 1343 1050 687 395 341 1120 630 84 480 85 164 518 R 2 R 1-1/4

    DDW060V 1210 650 1403 1120 740 395 341 1190 630 84 480 85 164 581 R 2 R 1-1/4

    DDW080V 1320 810 1613 1230 842 471 404 1300 790 98 517 85 164 708 R 2 R 1-1/4

    DDW100V 1390 900 1853 1300 1014 557 478 1370 880 98 574 85 164 835 R 2 R 1-1/4

    DDW120V 1530 900 1923 1440 1070 557 478 1510 880 102 639 85 164 899 R 2 R 1-1/4

  • 8/19/2019 ED-DDW-201401B

    15/27

    14

     

    DDW Double Skin Fan Coil unit

    DDW-V (Vertical)

    F

     A A ET

    W

          Q

         P

    M

         4     0

    B S

    H

         2     0

          G

    N

    90

         6     3

         R

    L

    DDW-V Top Discharge

    Leavingwater pipe D

    Entering water pipe D

    Condensation water drain pipe C

    Unit: mm

    Dimension Width Length Height Return air Supply air Hanging holesConnection pipe

    dimension

    Entering

    water

    pipe

    Condensation

    water drain

    pipe

    MODEL W L H F G A B M N S E P Q R D C

    DDW150V 2090 900 1673 2000 923 471 404 2070 880 144 167 85 172 756 R 2-1/2 R 1-1/4

    DDW180V 2240 900 1923 2150 1035 430 478 2220 880 100 440 85 172 883 R 2-1/2 R 1-1/4

    DDW200V 2320 900 1983 2230 1109 557 478 2300 880 98 156 85 172 946 R 2-1/2 R 1-1/4

    DDW250V 2670 900 2043 2580 1155 557 478 2650 880 100 156 85 178 997 R 3 R 1-1/4

  • 8/19/2019 ED-DDW-201401B

    16/27

    15

     

    DDWDouble Skin Fan Coil unit

            G

    TB A A

    L

    ES

    W

    M

    F

            P

     

            6        3

            H

            4        0

            6        3

            4        0

    Condensation

    water drain pipe C

    Entering

    water pipe D

    Lveaing

    water pipe D

    Entering

    water pipe D

    Leaving

    water pipe D

    DDW-V (Vertical)

    Unit: mm

    Dimension Width Length Height Return air Supply air Hanging holes

    Connection

    pipe

    dimension

    Entering water

    pipe

    Condensation

    water drain

    pipe

    MODEL W L H F G A B E T S P D C

    DDW300V 2766 1006 2555 2670 1390 569 569 284 450 305 98 R 3 R 1-1/4

    DDW350V 2766 1006 2715 2670 1550 569 569 273 450 305 98 R 2-1/2 R 1-1/4

    DDW400V 2926 1166 3035 2830 1710 638 638 276 500 357 98 R 2-1/2 R 1-1/4

    DDW450V 2926 1166 3195 2830 1870 638 638 267 500 357 98 R 2-1/2 R 1-1/4

    DDW-V Top Discharge

  • 8/19/2019 ED-DDW-201401B

    17/27

    16

     

    DDW Double Skin Fan Coil unit

     

    Top air discharge of DDW-V fans

    Fan Discharge Type

    Horizontal air discharge of DDW-H fans

    Horizontal Air Discharge For DDW-H

    Horizontal Type

    Top air discharge for DDW-H fans

    Top Air Discharge For DDW-H

    Horizontal Type

    Top Air Discharge For DDW-V Vertical

    Type

  • 8/19/2019 ED-DDW-201401B

    18/27

    17

     

    DDWDouble Skin Fan Coil unit

    Selection Software

    DAIKIN Smart Tools provide customers with more convenient and reliable services

    Professional model selection software for air handling units

    Convenient graphical user interface

      Providing most economic and reasonable combination solutions

      Provide different conguration options according to the requirements of the customer 

      Output the performance table of the unit according to the customer’s requirements

      Figuring out the component list and automatically calculate the price of the entire unit

      Output units arrangement drawing, development drawing and technical specications

  • 8/19/2019 ED-DDW-201401B

    19/27

    18

     

    DDW Double Skin Fan Coil unit

    Special Notes

       Facing air discharge, if the chilled hot water inlet/outlet is on your left, the unit is L connection. Otherwise,the unit is R connection.

      For vertical type unit,refer to the below chart to judge the connection.  Please provide unit model, quantity and operating condition when purchasing. Please contact us if any  

    other specications required.

    Figure 1 (Horizontal unit)

    Figure 2 (Vertical unit)

    Right connection

    Leaving air 

    Left connection

    Entering air 

    Right connection

    Left connection

    Entering air 

  • 8/19/2019 ED-DDW-201401B

    20/27

    19

     

    DDWDouble Skin Fan Coil unit

    Wiring Diagrams

    NOTE:

    TO CONNECT ELECTRIC CONTROL DEVICES, PLEASE USE OVER-CURRENT, SHORT CIRCUIT AND OVERHEAT

    PROTECTORS.

    Motor power input < 11kW  Motor power input ≥ 11kW

    M

    ~

    U V W

    M

    ~

    U2 V2 W2U1 V1 W1

  • 8/19/2019 ED-DDW-201401B

    21/27

    20

     

    DDW Double Skin Fan Coil unit

    Figure 1 Figure 2

    Unit: mm

    Installation

    Installing DDW

    Important Notice

    Installation and maintenance are to be performed only by technicians who are familiar with local rules and

    regulations, and experienced with this type of equipment.

    Make sure that the rated voltage of the power supply conforms to the voltage stated on the unit nameplate.

    Cut off all power supplies before mounting or maintaining the unit.

    Electric connections must conform to local laws and regulations.

    The voltage should uctuate within the range of ± 10% of the rated voltage.

    The unit must be well earthed to prevent insulation failures.

     All the wires must be securely connected.

    The design of water pipes and ducts must conform to the Specications of Heating, Ventilation and Air 

    Conditioning (GBJ19-87).

    DDW Mounting Location

    Make sure it is convenient to connect wires and pipes in the selected mounting location. The minimum space

    reserved around DDW horizontal units is shown in Figure 1; DDW vertical units are shown in Figure 2.

    5  0  0  

      5  0  0

    1    0    0    0    

      5  0  0

    5   0  0  

      1  0  0  0

  • 8/19/2019 ED-DDW-201401B

    22/27

  • 8/19/2019 ED-DDW-201401B

    23/27

    22

     

    DDW Double Skin Fan Coil unit

    Servicing And Maintenance 

    Notices

    Responsibilities And ObligationsThis product comes to you with the DAIKIN service warranty. Only DAIKIN technicians or experienced technicians

    authorized by DAIKIN are allowed to install, test or maintain these products.

    Using The Unit

     After installing the piping system, please rst wash the pipes. To do so, be sure to shut off the valve connected to

    the unit, to prevent unwanted things in the pipes from entering the coils or blocking the loop.

     After the installation, please check there is anything unwanted inside the fan. Turn the blades by hand. If no

    unusual noise is heard, turn on the fan, to see if it is running properly.

    Before turning on the water ow, please open the exhaust valve to let the air out of the pipe til l water ows out from

    the pipe.

    When the unit stops running, ll the coil with water or otherwise keep the pipe from erosion.When the environment temperature falls below 0°C in the winter, drain the pipe to prevent it from freezing.

    Clean the coils at regular intervals, to remove the dust from the coils. Clean the scale inside the coils every 2 or 3

    years. If possible, use soft water to supply hot/cold water to the coils.

    Check the unit lter for dust regularly; if possible, please use a pressure difference detector. Once the resistance

    reaches the limit, wash or replace the lter media in time.

     After the unit runs for a week, please readjust the V-belt. Afterwards, check the belt every three months.

    Servicing And Maintenance

     A sound maintenance schedule helps reduce operational failures.

     A dirty lter may worsen the performance and air ow of the unit. Thus, replace or wash the lter in time. Be sure

    to check the lter every month to see if it is clean enough.Wash the coils with compressed air or water. Brush the coil surface gently with a soft brush or use a vacuum

    cleaner to clean the dust.

    Do the following on a regular basis:

      Clean up the fans every 6 months, to keep them in good balance.

      Check and clean the water coils. Check the drain pipe in case dust or unwanted things block the pipes.

      Check if the bearing comes loose. If so, x the fastening screw tightly to the bearing.

      Clean the dirt in the coils at regular intervals.

    Check that the side front of the fan V-belt is ush with the side front of the motor V-belt, to make sure the pulleys

    are placed on a at plane. Usually, check using the four-point method (see Figure 5).

      Use V-belts of the same brand and model. Never mix old V-belts with new ones. Make sure that the V-belts

    match the pulley grooves.Use a tensiometer to check the V-belts, and tighten them properly (see Figure 6).

  • 8/19/2019 ED-DDW-201401B

    24/27

    23

     

    DDWDouble Skin Fan Coil unit

    Check and adjust the levelness of the V-belt using the four-point method, as shown in Figure 5.

    Check the tightness of the V-belt, as shown in Figure 6.

     A B C D

    Ruler 

     

    C  e n t  e r   t  o  c e n t  e r   

    s  p a c i  n g 

    Figure 6

    Figure 5

    The belt tension indicator acts on the

    midpoint of center-to-center spacing

    Torture 16mmevery meter 

  • 8/19/2019 ED-DDW-201401B

    25/27

    24

     

    DDW Double Skin Fan Coil unit

    Common Failures

    DDW

    Common

    Failures Locations Possible Causes Solutions

    Abnormal

    sound

    1. Blower

    Blower out off center Contact the seller

    Loose bearings due to large gap Contact the seller

    Blower is loose Contact the seller

    Loose connection between bearings Contact the seller

    Blower is damaged Contact the seller

    The fan fastening screw is loose Fasten the screw

    There are unwanted things inside fans. Remove unwanted things

    2. Drive

    Belt pulley is not fastened on the axis. Fasten the V-shaped belt

    V-shaped belt is loose. Adjust after it runs for 48 hours for the

    rst time. Adjust the V-shaped belt

    V-shaped belt is too tight Adjust the V-shaped beltThe V-shaped belt model is not right Replace the V-shaped belt

    V belts are of different lengthReplace V-shaped belts with those of the

    same lengthThe V-shaped belt pulley of the fan does not align with that of

    the motor Align the belt pulleys

    V-shaped belt is damaged Replace the V-shaped belt

    The screw xing the motor to the motor base is loose Fasten the screw

    3. Bearing

    Bearing failure Replace bearings

    Lack of lubricant oil Add lubricant oil

    The bearing housing is loose Fasten the bearing housing

    The bearing is not mounted ush Re-mount the bearing

    There are unwanted things inside bearings Remove unwanted thingsBearings are damaged Replace bearings

    Bearings are rusty De-rust or replace bearings

    4. Fan house

    There are unwanted things inside houses Remove the unwanted things

    House is loose Contact the seller

     Air intake house is damaged Contact the seller

    5. Electric appliances

    Incoming line is loose Fasten the incoming line

    Motor gives AC hum Contact the seller.

    Phase lack Supply 3-phase power

    6. Axis

    Bent or distorted Replace axis

    Balance weight is loose Fasten the balance weight

     Axis is loose Fasten axis

    7. Air speed is too highDuct is too small Re-design the duct

    Static pressure has not reached the set static pressure valueChange the V-shaped belt pulley to reduce

    the fan speed

    8. Periodical vibration

    The duct is too small Re-design the duct

    System is unstable  Adjust the system

    Duct vibrates as the fan pulsates Adjust the fan speed

    9. Noise caused by hi-

    speed wind passing

    the aperture & holes

    Duct leaks Seal it with glue

    10. When blocked,the high-speed air

    rattles or howls

    Duct turns too sharply Re-design the duct

    Duct expands sharply Re-design the duct

    Duct shrinks sharply Re-design the duct

     Air speed is too high inside the duct Re-design the duct

    Damping connector is too tight Re-adjust the damping connector

  • 8/19/2019 ED-DDW-201401B

    26/27

    25

     

    DDWDouble Skin Fan Coil unit

    Common

    failuresLocations Possible causes Solutions

    The fan is

    functioning

    but the air

    supply is

    insufcient

    1. FanBlower is mounted incorrectly Contact the seller 

    Fan rotates in the opposite direction Regulate the power phase sequence

    2. Duct system

     Actual resistance in the duct exceeds set resistance. Re-design the system

    Duct is poorly sealed Seal with glue

    Fireproof valve is shut off Shut on the reproof valve

    3. Filter Too dirty or even blocked Clean or replace lter  

    4. Coil Too dirty or even blocked Clean coil

    5. Blocked air supplyThe air inlet and the air outlet are not properly isolated. Thus,

    the air runs directly to the air inlet through the separator  Add air deector 

    6. Fan air inlet is

    blocked

    Elbow at the return air inlet and fan outlet are too close to the

    unit wallboardMove the fan

    The fan outlet is blocked Remove the obstructions

    7. No collimator tube at

    the fan outlet

     A length of straight tube is mounted at the fan outlet during

    fan testing. Without straight tube, the fan performance might

    be worsened. Thus, the fan may run faster to offset the

    resistance. (Check the fan speed)

    Mount collimator tube

    8. There’re unwanted

    things inside fan

    system

    The fan outlet is blocked Remove the obstructions

    There is an elbow at the fan outlet Re-design duct

    The fan is

    functioning

    but the air

    supply is

    too large

    1. System

    Improper duct size Remove the obstructions

    The access door is open Close the access door 

    The system is not well balanced and the actual resistance is

    lower than the set resistanceRe-design the system

    No air valve or air valve blade Mount wind valve or wind valve blower  

    Filter falls off  Re-mount the lter 

    2. Duct Return duct leaks Seal it with glue

  • 8/19/2019 ED-DDW-201401B

    27/27

    ● Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the

    world. Daikin Industries, Ltd. does not have control over which products are exported to and used in

    a particular country. Prior to purchase, please therefore conrm with your local authorized importer,

    distributor and/or retailer whether this product conforms to the applicable standards, and is suitable

    for use, in the region where the product will be used. This statement does not purport to exclude,

    restrict or modify the application of any local legislation.

    ● Ask a qualied installer or contractor to install this product. Do not try to install the product yourself.

    Improper installation can result in water or refrigerant leakage, electrical shock, re or explosion.

    ● Use only those parts and accessories supplied or specied by Daikin. Ask a qualied installer or

    contractor to install those parts and accessories. Use of unauthorized parts and accessories or

    improper installation of parts and accessories can result in water or refrigerant leakage, electrical

    shock, re or explosion.

    ● Read the User’s Manual carefully before using this product. The User’s Manual provides important

    safety instructions and warnings. Be sure to follow these instructions and warnings.

    If you have any enquiries, please contact your local importer, distributor and/or retailer.

    Warning

    The air conditioners manufactured

    by Daikin Industries have received

    ISO 9001 series certication for

    quality assurance.

    Certicate Number. 9601019

    The airconditioning factories of

    Daikin Industries have received

    environmental management system

    standard ISO 14001 certication.

    Certicate Number. EMS80362

    Cautions on product corrosion

    1. The units should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the

    unit close to the sea shore, contact your local distributor.