1 Chap. 11 Balanced Three- Phase Circuits Contents 11.1 Balanced Three-Phase Voltages 11.2 Three-Phase Voltage Sources 11.3 Analysis of the Wye-Wye Circuit 11.4 Analysis of the Wye-Delta Circuit 11.5 Power Calculations in Balanced Three-Phase Ckts 11.6 Measuring Average Power in Three-Phase Circuits Objectives 1.了了了了了了了了了了 Y-Y 了了了了2. 了了了了了了了了了了 Y-Δ 了了了了3. 了了了了了了了了了了了了 ( 了了了了 了了了了了了了了了 ) 了了了

Transcript of 電路學CH 11講義

Page 1: 電路學CH 11講義

1

Chap. 11 Balanced Three-Phase Circuits

Contents11.1 Balanced Three-Phase Voltages11.2 Three-Phase Voltage Sources11.3 Analysis of the Wye-Wye Circuit11.4 Analysis of the Wye-Delta Circuit11.5 Power Calculations in Balanced Three-Phase Ckts11.6 Measuring Average Power in Three-Phase Circuits

Objectives1.了解如何分析平衡三相 Y-Y 連接電路。2. 了解如何分析平衡三相 Y-Δ 連接電路。3. 具有計算任何三相電路功率 ( 平均功率、無效功率及複數功

率 ) 之能力。

Page 2: 電路學CH 11講義

Practical Perspective

2

為了經濟效益,對於大功率電力的產生、輸送、分配皆以 三相電路來完成。三相系統的基本架構,是由電壓源經由變壓器及傳輸線連 接至負載。三相電路電源與負載之連接方式有 Y-Y, Y-Δ, Δ-Y 及 Δ-Δ 等連接方式。

Page 3: 電路學CH 11講義

11.1 Balanced Three-Phase Voltages

3

三相電壓:a 相電壓 (a-phase voltage)b 相電壓 (b-phase voltage)c 相電壓 (c-phase voltage)

abc 相序 (abc phase sequence) 或正相序 (positive phase sequence) :

b 相電壓落後 a 相電壓 120°c 相電壓領先 a 相電壓 120°

acb 相序 (acb phase sequence) 或負相序 (negative phase sequence) :

b 相電壓領先 a 相電壓 120°c 相電壓落後 a 相電壓 120°

平衡三相電源 : 大小相同、頻率相同、相位角各差120o

Page 4: 電路學CH 11講義

11.2 Three-Phase Voltage Sources

4

三相電源由三個分開的繞組所產生: Y 形接法及 Δ 形接法。 中性端子 (neutral terminal) : Y 形電源的共同端,接點 n 。

Page 5: 電路學CH 11講義

Three-Phase Source with Winding Impedances

5

三相電壓源及負載間有四種不同的接法由於其他三種接法皆可化簡成 Y-Y 等效電路,故而先行分析 Y-Y 電路。

Page 6: 電路學CH 11講義

11.3 Analysis of the Wye-Wye Circuit

6

圖示三相 Y-Y 系統,包含第四條導線連接電源與負載之中性端。Zga, Zgb, Zgc 分別代表各相電壓源之內阻。

Zla, Zlb, Zlc 分別代表各相電源至負載之導線阻抗。ZA, ZB, ZC 則代表各相負載阻抗。

平衡三相 ?

Page 7: 電路學CH 11講義

Conditions for a Balanced Three-phase Circuit

7

平衡三相電路的條件:1. 電壓源 Va'n, Vb'n, Vc'n 構成一組平衡三相電源。2. 每相電壓源之阻抗相同,亦即 Zga = Zgb =Zgc 。3. 每相導線阻抗相同,亦即 Z1a = Z1b = Z1c 。4. 每相負載阻抗相同,亦即 ZA = ZB = ZC 。

若為平衡三相電路

兩個中性端沒有電位差中性導線電流 =0

= 0

平衡三相電路各線路之電流在平衡三相系統中,具有平衡的三相電流,所以一旦計算出 IaA 電流,就可直接寫出 IbB, IcC 之電流。

Page 8: 電路學CH 11講義

Single-phase Equivalent Circuit

8

單相等效電路中之 IaA 並非平衡三相電路的中性導線電流,真正中性導線的電流為當線電流 IaA 求出後,便可計算出其他的電壓。

負載端的線電壓 VAB, VBC,VCA 可用相電壓 VAN, VBN,VCN 來表示。

Page 9: 電路學CH 11講義

Line-to-line Voltages & Line-to-Neutral Voltages

9

abc( 正 ) 相序

acb( 負 ) 相序

線電壓之大小等於相電壓大小的 倍線電壓構成一組平衡三相電壓線電壓組領先相電壓組 30°

3

Line-to-Neutral Voltages

Line-to-line Voltages

abc( 正 ) 相序

注意:若為 acb( 負 ) 相序,則線電壓組落後相電壓組 30°

Page 10: 電路學CH 11講義

Line Voltage, Phase Voltage, Line Current & Phase Current

10

線電壓 (line voltage) :線與線之間的電壓相電壓 (phase voltage) :指單相兩端的電壓線電流 (line current) :指單一線上的電流相電流 (phase current) :指單相內之電流

以表示單相的量,如: V, I, Z, P 及 Q 分別代表每相之電壓、 電流、阻抗、實功率及無效功率。

在 Y 型接法 線電流與相電流相同 線電壓 = line-to-line voltage 相電壓 = line-to-neutral voltage在型接法 線電壓與相電壓相同 相電壓 line-to-neutral voltage

Page 11: 電路學CH 11講義

EX 11.1 Analyzing a Y-Y Circuit

11

A balanced three-phase Y-connected generator with positive sequence has an impedance of 0.2 + j 0.5 / and an internal voltage of 120 V/ .The generator feeds a balanced three-phase Y-connected load having an impedance of 39 + j 28 / . The impedance of the line connecting the generator to the load is 0.8 + j 1.5 / . The a-phase internal voltage of the generator is specified as the reference phasor.

a) Construct the a- phase equivalent

circuit of the system.

a-phase equivalent

b) Find IaA , IbB , and IcC.

正相序負相序

Page 12: 電路學CH 11講義

EX 11.1 Analyzing a Y-Y Circuit (Contd.)

12

c) Find VAN , VBN , and VCN. 正相序

d) Find VAB , VBC , and VCA.

e) Find Van , Vbn , and Vcn.

f) Find Vab , Vbc , and Vca.

正相序

負相序

正相序

負相序正相序負相序

負相序

Page 13: 電路學CH 11講義

11.4 Analysis of the Wye-Delta Circuit

13

-to-Y transformation

a-phase equivalent

平衡三相

Page 14: 電路學CH 11講義

Line Currents & Phase Currents in

14

acb( 負 ) 相序線電流之大小等於相電流大小的 倍線電流構成一組平衡三相電流線電流組落後相電流組 30°

3

Line Currents

abc( 正 ) 相序

注意:若為 acb( 負 ) 相序,則線電流組落後相電流組 30°

abc( 正 ) 相序Phase Currents

Page 15: 電路學CH 11講義

EX 11.2 Analyzing a Y- Circuit

15

The Y-connected source feeds a -connected load through a distribution having an impedance of 0.3 + j 0.9 / . The load impedance is 118.5 + j 85.8 / . Use the a-phase internal voltage as the reference.

a) The a-phase equivalent

b) The line currents IaA , IbB & IcC

c) The phase voltages at the load terminals

Y

Page 16: 電路學CH 11講義

EX 11.2 Analyzing a Y- Circuit (Contd.)

16

d) The phase currents of the load

e) The line voltages at the source terminals

Check!

Page 17: 電路學CH 11講義

11.5 Power Calculations in Balanced Three-Phase Circuits

17

Average Power in a Balanced Wye Load

Page 18: 電路學CH 11講義

Complex Power in a Balanced Wye Load

18

Page 19: 電路學CH 11講義

Power Calculations in a Balanced Delta Load

19

Page 20: 電路學CH 11講義

Instantaneous Power in a Three-Phase Circuit

20

若以線至中性點瞬時電壓 vAN 為參考,且為正相序, 為相位角差,各單相的瞬時功率可表示為 pA, pB, pC ,總瞬時功率 pT 為三者之和。

Page 21: 電路學CH 11講義

EX 11.3 Calculating Power in a Three-Phase Y-Y Circuit

21

Consider the circuit described in EX 11.1 .

a) The average power per phase delivered to the load

b) The total average power delivered to the load

c) The total power lost in the line

d) The total internal power lost in the generator

e) The total number of magnetizing vars absorbed by the load

f) The total complex power delivered by the source

Check!

Page 22: 電路學CH 11講義

EX 11.4 Calculating Power in a Three-Phase Y- Circuit

22

Consider the circuit described in EX 11.2 .

a) The total complex power delivered to the -connected load

b) The percentage of the average power reaching the load

From EX 11.2

99.25%687.74682.56

Page 23: 電路學CH 11講義

EX 11.5 Three-Phase Power with an Unspecified Load

23

a) The a-phase equivalent

A balanced three-phase load requires 480 kW at a lagging power factor of 0.8. The load is fed from a line having an impedance of 0.005 + j 0.025 /. The line voltage at the terminals of the load is 600 V.

b) The magnitude of the line currents

Page 24: 電路學CH 11講義

EX 11.5 Three-Phase Power with an Unspecified Load (Contd.)

24

c) The magnitude of the line voltage at the sending end of the line

d) The power factor at the sending end of the line

Page 25: 電路學CH 11講義

11.6 Measuring Average Power in Three-Phase Circuits

25

右圖由 n 條導線供應功率的一般網 路,以 n 為參考電壓點,其總功率 p = v1i1 +v2i2 + … + vn-1in-1 。對三相平衡電路而言,因為中性線沒有電流通過,故只需兩個瓦特計,即可量測總功率。

用來測量三相電路功率的基本儀表,稱為電動力瓦特表 (electrodynamometer wattmeter) ,內含兩個線圈,一為電流線圈 (current coil) ,通過此線圈之電流與負載電流成正比;另一個稱為電壓線圈 (potential coil) ,通過此線圈之電流與負載電壓成正比。瓦特計指針的偏轉量與通過電流線圈電流有效值、電壓線圈兩端電壓有效值、電流和電壓間相角的餘弦值三者之乘積成正比。

Page 26: 電路學CH 11講義

The Two-Wattmeter Method

26

VCB

兩個瓦特計量測功率之特性:1.若功率因數大於 0.5 時,兩個瓦特計皆是正值。2.若功率因數等於 0.5 時,其中一個瓦特計的值為零。3.若功率因數小於 0.5 時,其中一個瓦特計為負值。4.當相序相反時,則兩個瓦特計之量測值剛好對換。

正向序

Page 27: 電路學CH 11講義

EX 11.6 Computing Wattmeter Readings in Three-Phase Circuits

27

a)

Calculate the reading of each wattmeter in the previous circuit if the phase voltage at the load is 120 V and (a) Z = 8 + j 6 ; (b) Z = 8 j 6 ;(c) Z = 5+j5√3 ; and (d) Z = 10∠−75◦ .

c)

b) d)

Check!

Page 28: 電路學CH 11講義

Transmission and Distribution of Electric Power

28

變電所三相的實功率為 3.6 MW ,無效功率為 3.6 MVAR ,線電壓為 13.8 KV ,配電線阻抗為0.6 + j 4.8 。

若電力系統必須將電壓準位維持在公稱值 (nominal value) 之 5.8 % 範圍內,則代表發電廠之線電壓範圍應介於 13 kV 至 14.6 kV 之間。利用連接於變電所之電容器提供無效功率