Cálculos Eléctricos 3.14.1
Lista de Cargas del Sistema POTENCIA TOTALDatos generales Alimentación Consumo unitario T. Uso Factor
N° TAG Descripción Ubicación Cant. Tipo Voltios Sist. Valor Unidad FP Eff % Horas Oper. VA W VAR1 Bomba del SCI SCI 1 AC 480 3 Fases 100 HP 0.95 98 8 1.00 76091.84 72287.24 23759.672 Bomba Jockey SCI 1 AC 480 3 Fases 10 HP 0.95 98 8 1.00 7609.18 7228.72 2375.973 AC 240 1 Fase 0.2 A 0.00 0.00 0.00 0.004 AC 240 1 Fase 333 VA 0.00 0.00 0.00 0.005 110 0.00 0.00 0.00 0.006 110 0.00 0.00 0.00 0.007 110 0.00 0.00 0.00 0.008 110 0.00 0.00 0.00 0.009 110 0.00 0.00 0.00 0.00
10 110 0.00 0.00 0.00 0.0011 110 0.00 0.00 0.00 0.0012 110 0.00 0.00 0.00 0.0013 110 0.00 0.00 0.00 0.0014 110 0.00 0.00 0.00 0.0015 110 0.00 0.00 0.00 0.0016 110 0.00 0.00 0.00 0.0017 110 0.00 0.00 0.00 0.0018 110 0.00 0.00 0.00 0.0019 110 0.00 0.00 0.00 0.0020 110 0.00 0.00 0.00 0.0021 110 0.00 0.00 0.00 0.0022 110 0.00 0.00 0.00 0.0023 110 0.00 0.00 0.00 0.0024 110 0.00 0.00 0.00 0.0025 110 0.00 0.00 0.00 0.0026 110 0.00 0.00 0.00 0.0027 110 0.00 0.00 0.00 0.0028 110 0.00 0.00 0.00 0.0029 110 0.00 0.00 0.00 0.0030 110 0.00 0.00 0.00 0.00
Sub Total 79515.97 26135.64
Proyecto: TOMOPORO TOTAL [VA] 83701.02Instalación: SCI kVA 83.70
Fecha: 3/20/2009 Reserva 10.00%
Carga Total de Diseño 92.07 kVA
Observaciones / Comentarios
4/110
Cálculos Eléctricos Para Motor
Nombre del Proyecto: FechaCódigo: 4/12/2023
Nombre del motor:
Datos del Motor
Tipo de Motor: MOTOR DE INDUCCIONTipo de alimentación: Trifasico
Clase NEMA: B De propósito generalTipo de aislamiento NEMA: F 155°C MAX (operación)
Codigo letra rotor bloqueado NEMA: G 5.6 - 6.29 kVA/HPPotencia: 100 HP
Potencia Activa salida: 74.57 kW (Rotor)Potencia Activa entrada: 80.18 kW (Alimentación)
Potencia Aparente entrada: 94.33 kVAVoltaje nominal: 460 V
Frecuencia de alimentación: 60 HzCorriente nominal: 118.40 A
Corriente de arranque: 746.16 A (6.3 In)FP: 0.85Eff.: 93 %
Factor de Servicio: 1.15N° de Polos: 4 Cerramiento: TEFC
Velocidad de sincronismo: 1800 RPMDeslizamiento aprox: 1.27 %
Velocidad de operación aprox: 1777 RPMFrame NEMA: 404T
Datos de Alimentador
Factor mult. de corriente: 125 % (CEN 2004 430.22) Corriente de diseño: 124A X 125% = 155A
Tabla aplicada: 310-16 CEN 2004Material: COBRE
Voltaje de Operación: 0 - 2000 V 0
Temp. Op.: 90°CFact. Temp: 36-40 °C 91% de la capacidad nominal del cable
Calibre: 2/0 AWG/MCMCapacidad del cable: 177.45 A
Conductores por fase: 1Cap. Total por fase: 177.45 A
% carga en el cable: 87.35% @155A% Reserva: 12.65%
Material del ducto: PVCResistencia: 0.330 Ohm/kM CEN 2004 Tabla 9 0.00033 Ohm/M
Reactancia: 0.141 Ohm/kM CEN 2004 Tabla 9 0.000141 Ohm/M
Longitud del cable: 180.0 MCaída de tensión: 2.85 % a corriente nominal
Máxima caída permitida: 5 %Caída durante el arranque: 9.76 % 6 X In (FP=0,2 IEEE Std 399-1997)
Max caída al arranque: 15 %
Totalmente Cerrado con ventilación externa
Corriente a plena carga en base a un motor de: 100 HP con un voltaje de operación de: 460 V la corriente a plena carga es: 124 A, según CEN 2004
M
5/110
Datos de Canalización
Aislante: 4Diametro: 15.68 mm X Conductor 9
Area Total: 579.30 mm2
Diametro de Ducto: Pulgadas 11
Tipo: 10
Diametro: 101.5 mm
Area Total: 8091.37 mm2
Ocupacion: 7.16%
Protección y Arranque
Protección contra cortocircuitos
Tipo: Interruptor automatico de disparo instantaneoCaracterística de motor: Polifasico todo proteccion
Ajuste máximo del dispositivo: 800 % la corriente de diseño (CEN 2004 430-152)Cap. de corriente del dispositivo: 15 A Amperios Frame
Máxima corriente de ajuste: 992.00 A Amperios de disparoMarca: CualquieraPolos: 3
Voltaje Max: 600 V
Contactor Arrancador / Protección contra sobrecargaTipo de Arranque: Arranque directo.Tipo de contactor: No Reversible
Característica: Motores con un factor de servicio no menor a 1,15Ajuste de corriente según CEN: Articulo 430-32
Factor para ajuste de protección: 125 % InMáxima corriente de ajuste: 155.00 A Tipo de Contactor
Tamaño del contactor: 3 NEMA AC-3Voltaje de operación: 460/575 V Cant.
Cap. Del contactor hasta: 50 HP 2
Amper-Frame: 90 A 2
Sistema de puesta a tierraTipo de conductor: Desnudo
Cantidad de conexiones: 2 Puntos Calibre mínimo: 2 AWG CEN 2004 tabla 250-122
Contactos auxiliares NAContactos auxiliares NC
6/110
Gabinete de control / potencia
Área de instalaciónClase: No Clasificada
División: N/A
Gabinete o TableroUbicación: Exterior
Cerramiento: 1 NEMATipo de protección: Para propósitos generales
Capacidad de las barras: 400 A Instalación: Auto soportado
Otras caracteristicas
Verde
Roja
Ambar
Notas
V3.14.1 fm
Botón de START
Botón de STOP
Voltímetro
Amperímetro Luz indicadora 1
Luz indicadora 2
Luz indicadora 3
Comunicación con PLC
Comunicación con RTU
Calentador internoSelector de operación
Pantalla digital
Ventilación interna
Botón paro de emergencia
TX auxiliar para control
Fusibles para sist. control
460 V
Barra
3(1 X 2/0 AWG/MCM)
Interruptor 15A (AF) / 992A (AT)
460 V
NEMA 3
AC-3
Arrancador 120 V
155A (AT)
Circuito de Control
100 HP
M
8/110
Cálculos Eléctricos Para Transformador
Nombre del Proyecto: Código: Fecha
Nombre del transformador: 4/12/2023
Datos Eléctricos
Potencia: 75 kVA Clase del transformador :Tipo de alimentación: Trifasico Transformadores Monofásicos de Distribución Tipo Intemperie/Po
Impedancia base: 3.07 mΩ Enfriamiento: (IEEE C57.93)Frecuencia: 60 Hz
Relación de Trans.: 1:1
Primario SecundarioTipo de conexión: Delta Tipo de conexión: Estrella
Hilos: 2 Hilos: 3Voltaje de línea: 0.48 kV L-L Voltaje de línea: 0.48 kV L-L (480 V)Voltaje de fase: 0.48 kV Voltaje(s) de fase: 0.277128129 kV
Corriente de línea: 90.21 A kV L-N (0 V)Corriente de Fase: 52.08 A Corriente de línea: 90.21 A
Conexión del neutro: No tiene Corriente de Fase: 90.21 AConexión del neutro: solidamente a tierra
Alimentadores
Primario SecundarioFactor mult. de corriente 125 % Factor mult. de corriente 125 %
Corriente de diseño: 112.76 A Corriente de diseño: 112.76 AMaterial: COBRE Material: COBRE
Voltaje de Operación Cable: 5001-35000 V Voltaje de Operación Cable: 0 - 2000 VTabla aplicada: Tabla 310.73 CEN 2004 Tabla aplicada: Tabla 310.16 CEN 2004
Calibre 2 AWG / MCM Calibre 1/0 AWG / MCMTemp. Op. 90°C 0 Temp. Op. 90°C
Fact. Temp 36-40 °C Fact. Temp 36-40 °CCorriente nominal cable 150 A Corriente nominal cable 154.7 A
Conductores por fase 1 Conductores por fase 1Cap. Total por fase 150 A Cap. Total por fase 154.7 A
% carga en el cable 75.18% % carga en el cable 72.89%% Reserva 24.82% % Reserva 27.11%
Calibre del neutro: 4 AWG / MCM Calibre del neutro: 4/0 AWG / MCM 0Conductores por neutro: 1 Conductores del neutro: 2 0
Datos de canalización
Primario Secundario
Calibre de conductores 2 AWG / MCM Calibre de conductores 1/0 AWG / MCMAislante THW Aislante THW
Tabla 5 CEN 2004 Tabla 5 CEN 2004Área del cable 86.14 mm2 Área del cable 143.70 mm2
Cantidad de cables 3 (Fases + Neutro igual calibre) Cantidad de cables 8 (Fases + Neutro igual calibre)
Área Total 258.42 mm2 Área Total 1149.58 mm2Tamaño tubería 4 " Tamaño tubería 4 "
Tipo : Tubo de PVC, Tipo A Tipo : Tubo de PVC Rigido, Sch. 40 y tubo de PETabla 4 CEN 2004 Tabla 4 CEN 2004
Área Total 8946.53 mm2 Área Total 8110.96 mm2% de Ocupación 2.89% % de Ocupación 14.17%
TIPO OA Sumergido en aceite, con enfriamiento natural.
9/110
Protecciones
Primario SecundarioLimitaciones sobre el lugar: Cualquiera
% Impedancia del TX: Mas de 6% pero menos de 10%
Tipo de protección: Fusible Tipo de protección: Interruptor automáticoTabla 450.3(B) CEN 2004 Tabla 450.3(B) CEN 2004
Ajuste max. del dispositivo: 250 % I de diseño Ajuste max. del dispositivo: 125 % I de diseñoCap. de corriente del dispositivo: 15 A AF Cap. de corriente del dispositivo: 200 A AF
Max corriente de ajuste: 281.91 A AD Max corriente de ajuste: 140.95 A AD
Sistema de puesta a tierraTipo de conductor: Desnudo
Cantidad de conexiones: 2 CEN 2004 tabla 250-122 Calibre mínimo: 2/0 0 AF: AMPERIOS FRAME
AD: AMPERIOS DE DISPARO
Otras características
Color de pintura: Gris
V3.14.1 fm
Indicador de temperatura
Indicador de presión
Indicador de nivel de liquido
Indicador de sobrecarga
Descargador de sobre voltajes
Instalado en
Interior
Exterior
Proyecto: TX:0
Cargas del TransformadorN° Descripción Carga Unidad FP Ef. VA W VAR1 carga 1 5 HP 0.99 100 3766.111111 3728.45 531.27535112 0 0 03 0 0 04 0 0 05 VA 0.707 0 0 06 VA 0 0 07 HP 90 0 0 08 HP 0 0 09 HP 0 0 0
10 HP 0 0 0
Voltaje del sistema 480 V Sub Total 3728.45 531.28
Total 3766.11 VA
Capacidad del Transformador 5.02% Uso
75 kVA 94.98% Reserva
71.23 kVA Reserva
Nota: todas las cargas se consideran trifásicas para fines del calculo, a menos que se exprese directamente en VA
S=√P2+Q2
5%
95%
Uso Reserva
11/110
Cálculos Eléctricos Banco de BateriasSegún norma IEEE 1115-2000
Nombre del Proyecto:Código: Fecha
Identificador : 4/12/2023
Tension terminal de celda: 1.1 V
Cap. Inicial del Banco: A-H
Temp. electrolito: °CMargen de diseño: 1.10 FD
Factor de envejecimiento 1.25 FE
Tabla de carga
Carga Descripcion
1 L1 0 30 30.00 37.18 18.592 L2 0 0 0.00 0 0.003 L3 0 0 0.00 0 0.004 L4 0 0 0.00 0 0.005 L5 0 0 0.00 0 0.006 L6 0 0 0.00 0 0.00
Aleatoria LA 0 0 0.00 0 0.00
TOTAL 18.59 A-HCapacidad Preliminar
Curva de carga
Tabla de comportamiento general de carga
SEC Desde (min) Hasta (min) Duracion(min) Total A
1 0 30 30.00 37.18 18.592 N/A N/A N/A N/A N/A3 N/A N/A N/A N/A N/A4 N/A N/A N/A N/A N/A5 N/A N/A N/A N/A N/A6 N/A N/A N/A N/A N/A7 N/A N/A N/A N/A N/A8 N/A N/A N/A N/A N/A9 N/A N/A N/A N/A N/A
10 N/A N/A N/A N/A N/A
Tiempo Inicio (min)
Tiempo Fin (min)
Duracion (min)
Corriente (A)
Capacidad (A-H)
Capacidad (A-H)
0 5 10 15 20 25 30 350
5
10
15
20
25
30
35
40
Tiempo (min)
Corriente (A)
12/110
Demanda Maxima: 37.18 ADemanda Minima: 37.18 A
Demanda Promedio: 37.18 A
Calculo del factor de capacidad n° T (MIN) T1 T2 A para T1 A para T2 Factor K1 Factor K2 Factor Kt1 30.000 30 - 266 0 1.387 - 1.3872 - - - - 0 - - -3 - - - - 0 - - -4 - - - - 0 - - -5 - - - - 0 - - -6 - - - - 0 - - -7 - - - - 0 - - -8 - - - - 0 - - -9 - - - - 0 - - -
10 - - - - 0 - - -11 - - - - 0 - - -12 - - - - 0 - - -13 - - - - 0 - - -14 - - - - 0 - - -15 - - - - 0 - - -16 - - - - 0 - - -17 - - - - 0 - - -18 - - - - 0 - - -19 - - - - 0 - - -20 - - - - 0 - - -
Curva del factor de corrección por temperatura de electrolito
-29 -20 -10 0 10 20 250
0.5
1
1.5
2
2.5
3
1s - 10 min
30 min
60 min
3 H
5 - 8 H
°C
Fac
tor
Tt
13/110
Hoja de selección de capacidad
Periodo Valor negativo (AH)
1 37 37 30.000 30.000 1.387 1.000 52 0Sub total 51.58 0.00
Total 51.58
1 37.18 37 30.000 30.000 1.387 1.000 51.58 0.002 0.00 -37 0.000 0.000 #N/A #N/A 0.00 #N/A
Sub total 0.00 0.00Total 0.00
1 37 37 30.000 30.000 1.387 1.000 52 02 0 -37 0.000 0.000 #N/A #N/A 0 #N/A3 0 0 0.000 0.000 #N/A #N/A 0 0
Sub total 0.00 0.00Total 0.00
1 37 37 30.000 30.000 1.387 1.000 52 02 0 -37 0.000 0.000 #N/A #N/A 0 #N/A3 0 0 0.000 0.000 #N/A #N/A 0 04 0 0 0.000 0.000 #N/A #N/A 0 0
Sub total 0.00 0.00Total 0.00
1 37 37 30.000 30.000 1.387 1.000 52 02 0 -37 0.000 0.000 #N/A #N/A 0 #N/A3 0 0 0.000 0.000 #N/A #N/A 0 04 0 0 0.000 0.000 #N/A #N/A 0 05 0 0 0.000 0.000 #N/A #N/A 0 0
Sub total 0.00 0.00Total 0.00
1 37 37 30.000 30.000 1.387 1.000 52 02 0 -37 0.000 0.000 #N/A #N/A 0 #N/A3 0 0 0.000 0.000 #N/A #N/A 0 04 0 0 0.000 0.000 #N/A #N/A 0 05 0 0 0.000 0.000 #N/A #N/A 0 06 0 0 0.000 0.000 #N/A #N/A 0 0
Sub total 0.00 0.00Total 0.00
1 37 37 30.000 30.000 1.387 1.000 52 02 0 -37 0.000 0.000 #N/A #N/A 0 #N/A3 0 0 0.000 0.000 #N/A #N/A 0 04 0 0 0.000 0.000 #N/A #N/A 0 05 0 0 0.000 0.000 #N/A #N/A 0 06 0 0 0.000 0.000 #N/A #N/A 0 07 0 0 0.000 0.000 #N/A #N/A 0 0
Sub total 0.00 0.00Total 0.00
Aleatoria 0 0 0.000 0.000 #N/A #N/A 0.000 0.000Total 0.00
Tamaño de la sección mayor 51.57 AH + Sección aleatoria 0AH = Tamaño sin corrección: 51.57 AH
Capacidad final :TSC X FD X FE = 70.91 AHV3.14.1 fm
Carga (A)
Cambio de carga (A)
Duracion (min)
Tiempo final de seccion (min)
Factor de capacidad (Kt)
Factor de temperatura (Tt)
Valor positivo (AH)
TABLA DE REFERENCIA CRUZADA
AWG AWG (en notación "X/0" ) MCM o kcmil
41 41 840 40 1039 39 1238 38 1637 37 2036 36 2535 35 3234 34 4033 33 5032 32 6331 31 8030 30 10029 29 12728 28 16027 27 20126 26 25425 25 32024 24 40423 23 50922 22 64221 21 81020 20 102119 19 128818 18 162417 17 204816 16 258215 15 325614 14 410613 13 517812 12 652911 11 823310 10 10 10382
9 9 13 130918 8 17 165077 7 21 208156 6 26 262485 5 33 330984 4 42 417353 3 53 526272 2 66 663611 1 84 836800 1 / 0 106 105518
Circular MILS
-1 2 / 0 133 133056-2 3 / 0 168 167780-3 4 / 0 212 211566
-3.7 4.7 / 0 250 250000-4.5 5.5 / 0 300 300000-5.2 6.2 / 0 350 350000-5.7 6.7 / 0 400 400000-6.3 7.3 / 0 450 450000-6.7 7.7 / 0 500 500000-7.5 8.5 / 0 600 600000-8.2 9.2 / 0 700 700000-8.5 9.5 / 0 750 750000-8.7 9.7 / 0 800 800000-9.2 10.2 / 0 900 900000-9.7 10.7 / 0 1000 1000000
-10.7 11.7 / 0 1250 1250000-11.4 12.4 / 0 1500 1500000-12.1 13.1 / 0 1750 1750000-12.7 13.7 / 0 2000 2000000
MCM significa 1000's (M) of (C)ircular (M)ilskcmil significa 1000's (K) of (C)ircular (M)ilsMil significa 1/1000 inchCircular Mil means the area of a circle 1/1000 inch in diameterAWG = -4.3125 LN (mm2) + 17.16 (approx interpolated)AWG = -4.3125 LN (inch2) - 10.74 (approx interpolated)
relationship to the cross sectional area of the wire.Fuente:http://lugsdirect.com/AWG%20wire%20sizes.htm
Logical AWG numbers are based on continuing the series in a logarithmic
TABLA DE REFERENCIA CRUZADA
0.003970.005010.006320.007970.010050.012670.015970.02014
0.02540.032030.040390.050930.064220.080970.102110.128750.162350.204730.258150.325520.41048
0.51760.652680.82301
1.03781.308641.65016
2.08082.623843.308594.172045.260846.633778.3650110.548113.3008
16.77221.149
26.668433.628142.404253.4705
Sección Transversal
en mm2
67.424985.021
107.209126.677152.012177.348202.683228.018253.354304.025354.695380.031405.366456.037506.708633.384760.061886.738
1013.415
MCM significa 1000's (M) of (C)ircular (M)ilskcmil significa 1000's (K) of (C)ircular (M)ilsMil significa 1/1000 inchCircular Mil means the area of a circle 1/1000 inch in diameterAWG = -4.3125 LN (mm2) + 17.16 (approx interpolated)AWG = -4.3125 LN (inch2) - 10.74 (approx interpolated)
relationship to the cross sectional area of the wire.Logical AWG numbers are based on continuing the series in a logarithmic
TABLA DE SELECCIÓN DE AISLANTES PARA CONDUCTORES ELÉCTRICOS
Mecánica PVC Polietileno
Resistencia a la Abrasión Buena Excelente
Resistencia a la Tracción Excelente Excelente
Elongación Buena Excelente
Resistencia a la Compresión Buena Excelente
Flexibilidad Buena Normal
Ambiental
Llama Buena Pobre
Humedad
Agua Dulce o Salada Buena Excepcional
Aceites de Petróleo
Aceite de Motor
Buena
Excelente
Fuel-oil
Petróleo Crudo
La Creosota Pobre Buena
Hidrocarburos parafínicos
GasolinaBuena
Excelente
Queroseno
Alcoholes
Isopropílico
Normal BuenaWood
Grain
Ácidos minerales
Sulfúrico
Excelente ExcelenteNítrico
Clorhídrico
Preparados Álcalis de hidróxido de sodio (lejía)
Hidróxido de potasio (potasa)Buena Excelente
Hidróxido de calcio (cal)
Cetonas
AcetonaPobre Buena
Metil Etil Cetona (MEK)
Esteres
Acetato de EtiloPobre Buena
Diluyentes para lacas
Hidrocarburos halogenados
Cloroformo
Pobre Pobre
Cloruro de Metilo
General
Deja residuos después de la combustión SI No
Índice de Oxigeno (ASTM D-2863) 23-30% 17-18%
Contenido Halógeno - % Peso 26 0
Temperatura Minima de instalación 14°F (-10°C) -40°F (-40°C)
Dimensional stability under hear Normal Normal
(Se deforma levemente por encima de los 60ºC)
(Se deforma levemente a altas temperaturas)
Tetracloruro de carbono
Temperatura Máxima de Operación 75°C (167°F) 75°C (167°F)
Nota: Si los cables se van a instalar en frío, deben ser calentados en el almacenamiento durante al menos 24 hrs. Antes de la instalación.
TABLA DE SELECCIÓN DE AISLANTES PARA CONDUCTORES ELÉCTRICOS
Neopreno CPE Termoplástico
Buena Buena Excelente
Excelente Excelente Buena
Excelente Excelente Buena
Excelente Excelente Buena
Excelente Excelente Normal
Excelente Excelente Buena
Buena Excelente Excelente
Buena Buena
Buena
(Pobre por encima de 110°C)
Normal Normal Buena
Pobre PobreExcelente
Normal Buena Buena
Excelente Excelente Excelente
Buena Excelente Excelente
Pobre Normal Buena
Pobre Normal Buena
Pobre Pobre Pobre
SI SI SI
31-39% 30-36% 30-34%
18 14 18-20
-4°F (-20°C) -4°F (-20°C) -40°F (-40°C)
Excelente Excelente Normal
Polietileno Cloro sulfonado
(Se deforma levemente a altas temperaturas)
90°C (194°F) 90°C (194°F) 75°C (167°F)
Nota: Si los cables se van a instalar en frío, deben ser calentados en el almacenamiento durante al menos 24 hrs. Antes de la instalación.
¿Cómo Ayudar?Si te gusta mi trabajo y quieres ayudar tienes 3 formas para poder hacerlo:
Envia tus comentarios o reportes de error a mi correo.
Entra a mi blog y pulsa sobre alguno de los anuncios de adsgoogle
Entra en mi blog y pulsa sobre "DONAR" en paypal
http://fidelsmc.blogspot.com/
http://fidelsmc.blogspot.com/
1
2
3
Caída de tensión sistemas Trifasico (Conductor de Cobre)Carga: 11150 VA 11.15 kVA
Longitud del circuito: 180 mTensión del sistema 480 V
FP: 0.85
Calibre del Cable: 8 1 Cond. por fase
Material de la tubería:R: 2.56 OHM/kMX: 0.171 OHM/kM
Caída de tensión: ∆V(%) = 1.97Voltaje Final: 470.52 V
2
( cos )
10
r x senk
kV
ΔV (% )=(kVA×m )×k
Caída de tensión sistemas Trifasico (Conductor de Cobre)
k=0.0009
2
( cos )
10
r x senk
kV
ΔV (% )=(kVA×m )×k
Caída de tensión sistemas Monofasicos (Conductor de cobre)Carga: 1500 VA 1.5 kVA
Longitud del circuito: 140 mTensión del sistema 480 V
FP: 0.8
Calibre del Cable: 12 1
Material de la tubería:R: 6.6 OHM/kMX: 0.177 OHM/kM
Caída de tensión: ∆V(%) = 0.98Voltaje Final: 475.28 V
V3.14.1
Regulación Max.
3%
5%
Caída de tensión sistemas Monofasicos (Conductor de cobre) Distancia0
0.643501110.6
0.00467552
Cond. por fase
k=0.0046
0.98185938
1
∆V(%) = 0.98 3
1000 22 10 220
k=(r×cosθ+x×senθ )
5×kV 2
ΔV (% )=(kVA×m )×k
Caida de tension en sistemas DC
0.018
Distancia del tramo [L]: 180 m
15 A
Voltaje del sistema [Vf]: 24 VDC
Calibre del cable:
Diámetro del cable: 1.63 mm
Area de cable [A]: 2.09 mm2
Resistencia del cable 3.11 Ω
Corriente del sistema [In]: 15 A
Resistencia de carga 1.6 Ω
Voltaje en terminales [Vl] 8.16 VDC
Regulación [ΔV%]: 66.00 %
Resistividad del cobre [ρ]: Ω×mm2
m
Tipo de carga
Vatios
Amperio
Dimensiones de Bancada Bancada Referencial Distancia Centro a Centro
(No representa la cantidad de Tubos reales)
Profundidad [H1]: 120 cm Nivel del Suelo
Cantidad de Filas: 1H1 120 cm
Cantidad de Columnas: 219cm
Espacio entre Ductos [V]: 8.84 cm H2158
Espacio entre Ductos [H]: 8.84 cm cm
Distancia Centro a ParedesDiámetro de Ductos [D]: 10.16 cm H H 38 cm
Distancia H2: 13.92 cm
Distancia H3: 13.92 cm H3 VV
Distancia V1: 13.92 cm V1 V219 cm
Distancia V2: 13.92 cm 57 cm
Total de Ductos: 2 19 cm
Profundidad Total: 158.0 cmAncho Total: 57.0 cm Dibujo sin escala
Convertir Descripción Final4 in 10.16 cm
19 cm 7.41 inBancada de 2 ductos de 10.16 cm de ancho c/u, en arreglo de 1 filas por 2 columnas a 120 cm bajo tierra, con una profundidad total de 158 cm y 57 cm de ancho
D
Calculo de corriente de corto circuito
Tension del sistema: 0.48 kVLugar: Barra 480
Impedancias del sistemaEquipo R X
Red 0.194 0.788Cable 0.374 0.270
TotalRt = 0.5680 ΩXt = 1.0582 ΩZt = 1.2010 Ω
Icc = 0.23 kA simR/X = 0.54
Factor K = 1.18 IEC60909
Icc asimetrica = 0.39 kA asim
Calculo de corriente de corto circuito
Motor Trifásico
Potencia: 30 HPVoltaje nominal: 0.46 kV en el lado de la falla
Eficiencia: 93 %FP: 0.9
Tipo: Motor de alta velocidad
Xd" Xd´ XdMotor de alta velocidad 15 25 80
Motor de Baja velocidad 35 50 100Compensador 25 40 160
T1. Reactancias en % de motores y compensadores
Se tiene que:
Sn = 26.73 kW
Luego:
X = 25
Xm = 1979.25 mOhm 1.979254114
Rm = 395.85 mOhm
0.20
2.01845107Zt= 2018.45 mOhm
Por lo tanto: Icc, sim = 60.53 kA simétricos
Luego tenemos que: K = 1.54 , para 0.20 ( IEC 60909 )
nm S
VXX
2
100
R t
X t
=
I cc=√2×K×I cc , sim
Sn=P
FP×η
Análisis
Sub Transitorio
Transitorio
Ralignl¿m ¿ ¿=0,2 Xm¿
Rm
Xm
=
I cc , sim=V n2
√3×Z t
Z t=√R t2+ X t
2
Finalmente: Icc = 131.90 kA asimétricosBasado en la norma UTE C 15-105 y IEC 60 909. 1.540952
Calculo de corriente de corto circuito
Transformador trifásico
Potencia: 75 kVAVoltaje en lado de falla (V2): 0.48 kV V1: 13.8 kV
Voltaje de corto circuito %: 4 Tabla T1Ra: 0.568032196 Ohm Rr 0.000687222 Ohm reflejada
Xa: 1.058234384 Ohm Xr 0.001280284 Ohm reflejada
T1. Tensión de cortocircuito Vcc normalizada para los transformadores MT/BT de distribución pública.
kVA 630 800 1000 1250 1600 2000Vcc (%) 4 4.5 5 5.5 6 7
Se tiene que: Z del transformador
Por lo tanto: Zt = 122.88 mΩ 0.12288
Se tiene que: X del transformador
Por lo tanto: Xt = 122.88 mΩ Xr =1.28mΩ
Se tiene que: R del transformador
Por lo tanto: Rt = 24.576 mΩ Rr =0.687mΩ
Luego: 0.20 0.126704406
Zt = 126.70 mΩ
Se tiene que:
Por lo tanto: Icc, sim = 1049.86 kA simetricos
Luego tenemos que: K = 1.54 , para 0.20 ( IEC 60909 )
Z t=V cc×V n2
Sn
I cc , sim=V n2
√3×Z t
X t≈Z t
Rt≈0 ,20×X t
R total
X total
=
R t
X t
=
I cc=√2×K×I cc , sim
Z total=√( R t+Rr )2+( X t+Xr )
2
Finalmente: Icc = 2279.13 kA asimetricosBasado en la norma UTE C 15-105 y IEC 60 909. 1.535052081
Calculo de corriente de corto circuitoAporte de corriente de la red electrica
Tension Nominal: 13.8 kVIcc: 17 kA sim
Scc: 234.6 MVAIcc Asimetrica: 35.27 kA asim
Ra/Za: 0.239Za: 0.812 ΩXa: 0.788 ΩRa: 0.194 Ω
Ra/Xa: 0.246Factor K: 1.467 (IEC 60909)
13.8kV 17kA sim
Red electrica
PDVSA 90619.1.089Caída de tensión método amperios piePotencia de lámparas: 1600 WVoltaje de operación: 277 V
Distancia entre lámparas: 30 MTramo inicial: 20.00 M
Cantidad de Luminarias: 30Distancia entre lámpara: 98.424 FT
N Amperios Distancia (FT) A-pie
0 65.6 20.00 --1 5.78 65.6 20.00 378.92 5.78 131.2 40.00 757.83 5.78 196.8 60.00 1136.84 5.78 262.4 80.00 1515.7
5 5.78 328.0 100.00 1894.66 5.78 393.6 120.00 2273.57 5.78 459.2 140.00 2652.48 5.78 524.8 160.00 3031.39 5.78 590.4 180.00 3410.3
10 5.78 656.0 200.00 3789.211 5.78 721.6 220.00 4168.112 5.78 787.2 240.00 4547.013 5.78 852.8 260.00 4925.914 5.78 918.4 280.00 5304.815 5.78 984.0 300.00 5683.816 5.78 1049.6 320.00 6062.717 5.78 1115.2 340.00 6441.618 5.78 1180.8 360.00 6820.519 5.78 1246.4 380.00 7199.420 5.78 1312.0 400.00 7578.321 5.78 1377.6 420.00 7957.3
Total 87529.8 A-P
Calibre del conductor:Factor K: 10.7
Area: 211600 Mil Circular
Caida de tension: 4.43 V
% de Caida de tension: 1.60%
Distancia (M)
Calculo de caída de tensión para circuitos monofásicos de iluminación
Tensión del sistema 0.12 kV Calibre del cable:
Factor de potencia 0.95 Canalizacion:Cantidad de Postes 29 Resistencia:
P. Poste 100 VA Reactancia:D0 114 m
DEP 5 m
NºkVA x m
1 100 114 114 11.42 100 5 119 11.93 100 5 124 12.44 100 5 129 12.95 100 5 134 13.4 k = 0.0056 100 5 139 13.97 100 5 144 14.48 100 5 149 14.99 100 5 154 15.4
10 100 5 159 15.911 100 5 164 16.4 ∆V(%) = 3.0712 100 5 169 16.913 100 5 174 17.414 100 5 179 17.9 Voltaje Final:15 100 5 184 18.416 100 5 189 18.917 100 5 194 19.418 100 5 199 19.919 100 5 204 20.420 100 5 209 20.921 100 5 214 21.422 100 5 219 21.923 100 5 224 22.424 100 5 229 22.925 100 5 234 23.426 100 5 239 23.927 100 5 244 24.428 100 5 249 24.929 100 5 254 25.430 0 5 0 0
Total 533.6 kVA x m
Potencia [VA]
Paso de Distancia [m]
Distancia [m]
k=(r×cosθ+x×senθ )
5×kV 2
ΔV (% )=(kVA×m )×k
2
Calculo de caída de tensión para circuitos monofásicos de iluminación
0.39 Ω/km0.144 Ω/km
3.079049760.0057703330.317560429
0.3122499
116.31 V
k=(r×cosθ+x×senθ )
5×kV 2
ΔV (% )=(kVA×m )×k
CalibreCalculo de Alimentador
Datos de la CargaCarga nominal: 150000 VA
Tension del sistema: 220 VFp: 0.9 Temperatura ambienteEff: 95 % °C
Factor de diseño: 125 %Corriente: 393.65 A Conductores por fase
Datos del ConductorCalibre: 1000 AWG/MCM
Capacidad nominal: 545 AFactor correcion Temp: 0.94Conductores por fase: 1
Capacidad Total: 512.30 ATabla 310,16
Alimentación
Monofasica
Trifásica
Temperatura del cable
60 °C 75 °C 90 °CTipo de Carga
W
HP
A
VA
Lista de Cables Monopolares
TAG COVENIN 398 Desdes Hasta
Cal
ibre
Fa
se
s
P-001 (#)
P-002 (#)
P-003 (#)
P-004 (#)
P-005 (#)
P-006 (#)
P-007 (#)
P-008 (#)
P-009 (#)
P-010 (#)
P-011 (#)
P-012 (#)
P-013 (#)
P-014 (#)
P-015 (#)
P-016 (#)
P-017 (#)
P-018 (#)
P-019 (#)
P-020 (#)
P-021 (#)
P-022 (#)
P-023 (#)
P-024 (#)
P-025 (#)
P-026 (#)
P-027 (#)
P-028 (#)
P-029 (#)
Tension Oper (V)
Tension Max (V) Tipo Aislante
Dis
tan
cia
(M
)
Ca
nt.
A
ct.
X
Fa
se
Cal
ibre
N
eutr
o
P-030 (#)
Proyecto: Nomenclatura COVENIN
LinksIndicación de X fases de n conductores monopolares por fase, calibre Y, mas m conductores de neutro (N) calibre
Aralven (Cables)
X (n×Y )+mN ¿Y '+ pT ¿Y '' ¿
Co
nd
Ac
t.
Observaciones
0 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 00 0 0 0
Ca
nt.
Ne
utr
o
X G
F
Ca
lib
re
Tie
rra
Ca
nt.
Tie
rra
X
GF
Ca
nti
da
d
Co
nd
. A
cti
vo
(M
)
Ca
nti
da
d
Co
nd
. N
eu
tro
(M
)
Ca
nti
da
d
Co
nd
. T
ierr
a
(M)
0 0 0 0
conductores monopolares por fase, calibre Y, mas m conductores de neutro (N) calibre Y’, mas p conductores de tierra (T) calibre Y’’.
AISLANTES DE CONDUCTORESTipo Descripcion
DESNUDO Sin recubrimiento
FXT TFF TWF
RHHN AISLANTE DE MATERIAL TERMOPLASTICO, XLPE 600 V. - 90 ºC, ANTILLAMA.
THHN
THW
TTU
TW
XHHW
Los conductores flexibles de cobre tipo FXT, TFF y TW-F son utilizados para alambrado de aparatos, cableado de tableros eléctricos de control, baterías de vehículos, instalaciones generales industriales y comerciales donde se requiera de gran flexibilidad debido a las dificultades de trabajo y en general como cables sometidos a continuo movimiento, tal como se especifica en el National Electrical Code. Este tipo de conductor puede ser usado en lugares secos y húmedos, su temperatura máxima de operación es 60 ºC y su tensión de servicio para todas las aplicaciones es 600 V.
Los conductores de cobre tipo THHN o THWN-2 son utilizados para circuitos de fuerza y alumbrado en edificaciones industriales, comerciales y residenciales, son especialmente aptos para instalaciones especiales por ductos difíciles y usarse en zonas abrasivas o contaminadas con aceites, grasas, gasolinas, etc. y otras sustancias químicas corrosivas como pinturas, solventes, etc., tal como se especifica en el National Electrical Code. Este tipo de conductor cuando es utilizado como THHN puede ser usado en lugares secos con temperatura máxima de operación de 90 ºC, pero si es utilizado como THWN-2 puede ser usado en lugares secos y húmedos con temperatura máxima de operación de 90 ºC, así mismo cuando están expuestos a aceites, grasas, pinturas, solventes químicos, etc., su temperatura máxima de operación es 75 ºC. En cuanto a su tensión de servicio, para todas las aplicaciones, es de 600 V.
Los conductores de cobre tipo THW son utilizados para circuitos de fuerza y alumbrado en edificaciones industriales, comerciales y residenciales donde se requiera de mayor seguridad, tal como se especifica en el National Electrical Code. Este tipo de conductor puede ser usado en lugares secos y húmedos, su temperatura máxima de operación es de 75 ºC y su tensión de servicio para todas las aplicaciones es 600 V.
Los conductores de cobre tipo TTU-0.6 KV. son utilizados para circuitos de fuerza y alumbrado en edificaciones industriales y comerciales, son especialmente aptos para instalaciones a la intemperie o directamente enterrados, tal como se especifica en el National Electrical Code. Este tipo de conductor puede ser usado en lugares secos y húmedos, su temperatura máxima de operación es 75 ºC y su tensión de servicio para todas las aplicaciones es 600 V.
Los conductores de cobre tipo TW son utilizados para circuitos de fuerza y alumbrado en edificaciones industriales, comerciales y residenciales, tal como se especifica en el National Electrical Code. Este tipo de conductor puede ser usado en lugares secos y húmedos, su temperatura máxima de operación es 60 ºC y su tensión de servicio para todas las aplicaciones es 600 V
Los conductores de cobre tipo XHHW son utilizados para circuitos de fuerza y alumbrado en edificaciones industriales y comerciales, son especialmente aptos para instalaciones a la intemperie, tal como se especifica en el National Electrical Code. Este tipo de conductor puede ser utilizados en lugares secos y húmedos, su temperatura máxima de operación es 90 ºC y su tensión de servicio para todas las aplicaciones es 600 V.
AISLANTES DE CONDUCTORESDescripcion
Sin recubrimiento
AISLANTE DE MATERIAL TERMOPLASTICO, XLPE 600 V. - 90 ºC, ANTILLAMA.
Los conductores flexibles de cobre tipo FXT, TFF y TW-F son utilizados para alambrado de aparatos, cableado de tableros eléctricos de control, baterías de vehículos, instalaciones generales industriales y comerciales donde se requiera de gran flexibilidad debido a las dificultades de trabajo y en general como cables sometidos a continuo movimiento, tal como se especifica en el National Electrical Code. Este tipo de conductor puede ser usado en lugares secos y húmedos, su temperatura máxima de operación es 60 ºC y su tensión de servicio para todas las aplicaciones es 600 V.
Los conductores de cobre tipo THHN o THWN-2 son utilizados para circuitos de fuerza y alumbrado en edificaciones industriales, comerciales y residenciales, son especialmente aptos para instalaciones especiales por ductos difíciles y usarse en zonas abrasivas o contaminadas con aceites, grasas, gasolinas, etc. y otras sustancias químicas corrosivas como pinturas, solventes, etc., tal como se especifica en el National Electrical Code. Este tipo de conductor cuando es utilizado como THHN puede ser usado en lugares secos con temperatura máxima de operación de 90 ºC, pero si es utilizado como THWN-2 puede ser usado en lugares secos y húmedos con temperatura máxima de operación de 90 ºC, así mismo cuando están expuestos a aceites, grasas, pinturas, solventes químicos, etc., su temperatura máxima de operación es 75 ºC. En cuanto a su tensión de servicio, para todas las aplicaciones, es de 600 V.
Los conductores de cobre tipo THW son utilizados para circuitos de fuerza y alumbrado en edificaciones industriales, comerciales y residenciales donde se requiera de mayor seguridad, tal como se especifica en el National Electrical Code. Este tipo de conductor puede ser usado en lugares secos y húmedos, su temperatura máxima de operación es de 75 ºC y
Los conductores de cobre tipo TTU-0.6 KV. son utilizados para circuitos de fuerza y alumbrado en edificaciones industriales y comerciales, son especialmente aptos para instalaciones a la intemperie o directamente enterrados, tal como se especifica en el National Electrical Code. Este tipo de conductor puede ser usado en lugares secos y húmedos, su temperatura máxima de operación es 75 ºC y su tensión de servicio para todas las aplicaciones es 600 V.
Los conductores de cobre tipo TW son utilizados para circuitos de fuerza y alumbrado en edificaciones industriales, comerciales y residenciales, tal como se especifica en el National Electrical Code. Este tipo de conductor puede ser usado en lugares secos y húmedos, su temperatura máxima de operación es 60 ºC y su tensión de servicio para todas las
Los conductores de cobre tipo XHHW son utilizados para circuitos de fuerza y alumbrado en edificaciones industriales y comerciales, son especialmente aptos para instalaciones a la intemperie, tal como se especifica en el National Electrical Code. Este tipo de conductor puede ser utilizados en lugares secos y húmedos, su temperatura máxima de operación es
Metros de cable por nivel de tension (TOTAL)
600 5000 15000 3500
18 AWG 0 0 0 016 AWG 0 0 0 014 AWG 0 0 0 012 AWG 0 0 0 010 AWG 0 0 0 08 AWG 0 0 0 06 AWG 0 0 0 04 AWG 0 0 0 03 AWG 0 0 0 02 AWG 0 0 0 01 AWG 0 0 0 0
1/0 AWG 0 0 0 02/0 AWG 0 0 0 03/0 AWG 0 0 0 04/0 AWG 0 0 0 0250 MCM 0 0 0 0300 MCM 0 0 0 0350 MCM 0 0 0 0400 MCM 0 0 0 0500 MCM 0 0 0 0600 MCM 0 0 0 0700 MCM 0 0 0 0750 MCM 0 0 0 0800 MCM 0 0 0 0900 MCM 0 0 0 0
1000 MCM 0 0 0 01250 MCM 0 0 0 01500 MCM 0 0 0 01750 MCM 0 0 0 02000 MCM 0 0 0 0
V
/
C
ali
br
e
Ocupacion de ductosCable Monopolar
N° Calibre Aislante Cantidad
1 3 11.52 104.23 312.69
2 0 4.60 16.62 0.00
3 0 4.60 16.62 0.00
4 0 4.60 16.62 0.00
5 0 4.60 16.62 0.00
Area Total 312.69 mm2
Tipo de Ducto:
Diametro:
PulgadasDiametro** 52 mm
Diámetro mínimo recomendado Area Total 2123.72 mm21 1/4 "
Max. Ocupacion 40.00% Ocupación 14.72%
** Según tabla del CEN 2004
Diametro* mm
Area por cable mm2
Total Grupo mm2
*Fabricante del cable: Aralven
Factor de Potencia
Potencia: 18600FP (%): 41Cos(θ): 0.41Sen(θ): 0.91
S 45365.85 VAP 18600.00 WQ 41377.54 VAR
Potencia
Aparente [VA]
Activa [W]
Reactiva [VAR]0 5000 10000 15000 20000 25000 30000 35000 40000 45000
0
5000
10000
15000
20000
25000
30000
35000
40000
45000
Triangulo de potencia
(W)
(VA
R)
2
S P QVA 18600 7626 16964.79071W 45365.85366 18600 41377.53833VAR 20392.82452 8361.058052 18600
x yp 0 0
18600.00 0Q 18600.00 0
18600.00 41377.54S 0 0
18600.00 41377.54
eje 0 18600.0041377.54 0
0 5000 10000 15000 20000 25000 30000 35000 40000 45000
0
5000
10000
15000
20000
25000
30000
35000
40000
45000
Triangulo de potencia
(W)
(VA
R)
TABLERO ELECTRICO
Tipo de Tablero: Instalacion: C. Interrupción [kA]: Fases: Proyecto: NLAB Auto soportado 22 3 ejemplo
Polos: Cerramiento NEMA: Color: Alimentador Principal: Instalacion:18 3R GRIS INDUSTRIAL Calibre Aislante Cnd X fase Conduit Entrada ejemplo
Voltaje del Tablero [V]: Corriente de Barras [A]: Interruptor principal 3P [A]:250 MCM THHN 1 4 Superior
Nombre del Tablero:240 100 400 ejemplo
A B C
Tuberia Conductor Interruptor Interruptor Conductor Tuberia
Carga Conectada VA Material Aislante Calibre Tipo Nº Nº Tipo Calibre Aislante Material VA Carga Conectada
Carga Nº 1
1500
PVC 2 1 THHN 6 AWG QC 20
1 2
30 THQC 250 MCM TTU 1 4 PVC
1000
Carga Nº 21500 3 4 1000
1500 5 6 1000
CARGA 4
500
PVC 2 1 THHN 14 AWG QC 20
7 8
90 THQC 14 AWG TTU 1 2 PVC
1250
CARGA 3500 9 10 1250
500 11 12 1250
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
VA A % POT. RESERVA
A 4250 10.22 0.33 0.00 VA
B 4250 10.22 0.33 0.00%
C 4250 10.22 0.33
V3.14.1 TOTAL 12750
Diametro [pul]
Cond. por fase
In [A] 3P
In [A] 3P
Cond. por fase
Diametro [pul]
BARRA DE TIERRABARRA DE NEUTRO
TABLERO ELECTRICO
Tipo de Tablero: Instalacion: C. Interrupción [kA]: Fases: Proyecto: NLAB Auto soportado 22 2 ejemplo
Polos: Cerramiento NEMA: Color: Alimentador Principal: Instalacion:36 3R GRIS INDUSTRIAL Calibre Aislante Cnd X fase Conduit Entrada ejemplo
Voltaje del Tablero [V]: Corriente de Barras [A]: Interruptor principal 3P [A]:1/0 AWG THHN 2 4 Superior
Nombre del Tablero:240 100 400 ejemplo
A B
Tuberia Conductor Interruptor Interruptor Conductor Tuberia
Carga Conectada VA Material Aislante Calibre Tipo Nº Nº Tipo Calibre Aislante Material VA Carga Conectada
carga 1 1500 PVC 2 1 THW 12 AWG QC 20 1 2 PVC 2 1 THW 12 AWG QC 20 1500 carga 2
carga 4 1500 PVC 2 1 THW 12 AWG QC 20 3 4 PVC 2 1 THW 12 AWG QC 20 1500 reserva
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
VA A % POT. RESERVA
A 3000 7.22 50.00 1500.00 VA
B 3000 7.22 50.00 25.00%
V3.14.1 TOTAL 6000
Diametro [pul]
Cond. por fase
In [A] 3P
In [A] 3P
Cond. por fase
Diametro [pul]
BARRA DE TIERRABARRA DE NEUTRO
SEPARACIÓN MINIMA RECOMENDADA ENTRE DUCTOS Y BANDEJAS
NIVELES
1.- APLICACIONES ALTAMENTE SUSCEPTIBLES A RUIDOS.
SEÑALES DE INSTRUMENTOS DE 4-20 mA 24Vdc, OTRAS SEÑALES ANÁLOGAS < 50Vdc Y TRASMISORES DIGITALES
SEÑALES DISCRETAS DE 24 Vdc
BUSES DE COMUNICACIONES DE INSTRUMENTOS ANALÓGICOS +- 50Vdc
BUSES DE COMUNICACIONES DE INSTRUMENTOS DIGITALES +- 24Vdc
CIRCUITOS DE TERMOCUPLA Y RTD
CIRCUITOS TELEFÓNICOS
2.- APLICACIONES MEDIANAMENTE SUSCEPTIBLES A RUIDOS
ILUMINACION E INTERRUPTORES DE 24Vdc O MENOS
SEÑALES ANALOGICAS > 50 Vdc < 28 Vac DE RIZO
3.- APLICACIONES BAJAMENTE SUSCEPTIBLES A RUIDOS
ALIMENTADORES EN 120/240 Vac DE MENOS DE 20 A
ILUMINACION E INTERRUPTORES DE 24Vdc O MAS
SEÑALES ANALOGICAS > 50 Vdc < 28 Vac DE RIZO
4.- APLICACIONES DE POTENCIA INTERMEDIA
PRIMARIOS Y SECUNDARIOS DE TRANSFORMADORES < 5kVA
BARRAS AC O DC 0-800 V CON CORRIENTES MAYORES A 20 A
5.- APLICACIONES DE ALTA POTENCIA
BARRAS AC O DC> 1kW Y/O CORRIENTES MAYORES A 800 A
CASO DE ESTUDIO
CASO: NIVEL A: NIVEL B:
2 5
SEPARACIÓN MINIMA RECOMENDADA:
12 IN 30.48 CM
NOTAS
1 Esta hoja no aplica para ductos no metálicos
2 La distancia definida aquí, indica el espacio mínimo entre el tope y el fondo de las bandejas o el espacio lateral entre ellas.
3 Estas distancias también aplican como el espacio entre bandejas y equipos de potencia menores a 100kVA
4 Las distancia mínimas de los ductos se indican en referencia al exterior de los mismos
5
6 Los niveles 3 y 4 pueden ser canalizados en la misma bandeja siempre que se coloque una barrea entre ellos
7
8 Las bandejas de todos los niveles deben ser metálicas solidamente aterradas.
9
10
Fuentes:
Cuando señales de distintos niveles deban cruzarse, deben hacer en un ángulo de 90º. Cuando no sea posible mantener las distancias de separación se debe interponer una barrera metálica aterrada.
Cuando sea impractico separarlos, los niveles 1 y 2 pueden ser usados en la misma bandeja, siempre que tenga una barrera metálica aterrada entre ellos.
Bandejas y ductos de los niveles 1 y 2 no podrán ser llevadas en paralelo con equipos de alta potencia cerrados mayores a 100kVA a 150 cm de las bandejas y 80 cm de los ductos.
Cunado no se posible mantener el espacio indicado arriba, se debe minimizar el recorrido en paralelo de las rutas, en tal caso, el recorrido no podrá superar los 150 cm de longitud.
PIP PCCEL001
IEEE 518
BANDEJAS PORTACABLES
Lista de Cables
Tipo de Bandeja: CABLES MONOPOLARES
Material:
Carga de Trabajo: Lbs/ft.
Espacio entre soportes: ft.
Clase NEMA: 8C
Calculado: 33.75 cm CABLES MULTICONDUCTORES
Ancho Seleccionado: 22.5 cm
Bandeja de ancho menor a la requerida
Caso de Estudio
Cables 1000kCMIL o mayores
Cables 250kCMIL a 1000kCMIL
Cables Mayores a 1000kCMIL con menores a 1000 kCMIL
Con algun cable instalado entre 1/0 y 4/0
Calibres 4/0 o Mayores
Calibres menores a 4/0
Cables 4/0 o mayores con cables menores a 4/0
Cables control / alumbrado / señalizacion
2 3 1 2 SelecciónTipo de bandeja Carga de Trabaj Distancia entre soportes Material Altura 3Escalera 50 8 Aluminio 3Perforado ranurado 75 12 Acero Inoxida 4
100 16 Acero Galvan 520 Fibra de Vidri 6
ancho de bandejas15
22.5304560 Bandejas75 ###90 22.30
33.7511.0968.6024.1549.81
7.26
Lista de Cables
Selección
Bandejas
CABLE MONOPOLARBandejas de fondo escalera o ventilado
Cables 1000 kCMIL o mayoresCantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2)
5 25.40 506.71 2533.54 12.7
10 28.40 633.47 6334.71 28.4
10 31.11 760.13 7601.34 31.11
36 33.60 886.68 31920.59 120.96
36 35.92 1013.36 36480.86 129.312
392-10(a) (1) NEC 2008 Ancho de conductores 322.48
20% Reserva: 64.50
Ancho total de Bandeja (cm) 386.98
Cables 250kCMIL a 1000kCMILCantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2)
5 13.51 143.35 716.75 2.58
8 13.51 143.35 1146.81 4.13
5 19.42 296.20 1481.01 5.33
2 14.66 168.79 337.59 1.22
5 19.42 296.20 1481.01 5.33
392-10(a) (2) NEC 2008 Ancho Minimo (cm) 18.59
20% Reserva: 3.72
Ancho total de Bandeja (cm) 22.30
Area Total (mm2)
Ancho Requerido (cm)
Fuente: lugsdirect.com
Area Total (mm2)
Ancho Requerido (cm)
Fuente: Aralven
Cables mayores a 1000kCMIL con menores a 1000kCMIL
Cables Mayores o iguales a 1000kCMIL
Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2)
6 25.40 506.71 3040.24 15.24
1 31.11 760.13 760.13 3.11
Cables menores a 1000kCMIL
Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2)
5 25.52 511.51 2557.53 9.21
2 4.47 15.69 31.39 0.11
2 8.93 62.63 125.26 0.45
392-10(a) (3) NEC 2008 Ancho Minimo (cm) 28.12
20% Reserva: 5.62
Ancho total de Bandeja (cm) 33.75
Con algun cable instalado entre 1/0 y 4/0 Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2)
5 18.48 268.22 1341.11 9.24
0 13.51 143.35 0.00 0
0 17.46 239.43 0.00 0
0 17.46 239.43 0.00 0
0 17.46 239.43 0.00 0
392-10(a) (4) NEC 2008 Ancho de conductores 9.24
20% Reserva: 1.85
Ancho total de Bandeja (cm) 11.09
Area Total (mm2)
Ancho Requerido (cm)
Area Total (mm2)
Ancho Requerido (cm)
Fuente: Aralven
Area Total (mm2)
Ancho Requerido (cm)
Fuente: Aralven
CABLE MULTICONDUCTORBandejas de fondo escalera o ventilado
CALIBRES 4/0 O MAYORESCantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2) Area Total (mm2)
2 34.88 955.53 1911.05 6.98
5 25.52 511.51 2557.53 12.76
3 54.86 2364.09 7092.28 16.46
1 55.90 2454.22 2454.22 5.59
2 76.90 4644.54 9289.08 15.38
NEC 2008 392.9 (a) (1) Ancho de conductores 57.17
Los cables deben ser instalados en una sola capa 20% Reserva: 11.43
Ancho total de Bandeja (cm) 68.60
CABLES MENORES A 4/0Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2) Area Total (mm2)
10 13.51 143.35 1433.51 4.73
5 15.96 200.06 1000.29 3.30
2 18.90 280.55 561.10 1.85
3 36.30 1034.91 3104.73 10.25
0 36.30 1034.91 0.00 0.00
NEC 2008 392.9 (a) (2) Ancho Minimo (cm) 20.13
20% Reserva: 4.03
Ancho total de Bandeja (cm) 24.15
Ancho Requerido (cm)
Fuente: Manual de gedisa
Ancho Requerido (cm)
Fuente: Manual de gedisa
CABLES 4/0 O MAYORES CON CABLES MENORES
Cables Mayores a 4/0
Cantidad Tipo de Conductor Calibre Diam. (mm) Area (mm2) Area Total (mm2)
6 34.88 955.53 5733.16 20.93
1 76.90 4644.54 4644.54 7.69
Cables menores a 4/0
2 13.51 143.35 286.70 0.95
5 13.51 143.35 716.75 2.37
2 30.40 725.83 1451.67 4.79
2 30.40 725.83 1451.67 4.79
NEC 2008 392.9 (a) (3) Ancho Minimo (cm) 41.51
Todos los cables mayores a 4/0 se deben instalar en una sola capa 20% Reserva: 8.30
Ancho total de Bandeja (cm) 49.81
CABLES CONTROL / ALUMBRADO / SEÑALIZACION
Nº Conductores Tipo de Aislante Calibre
11.10 96.77 2419.22 6.05
23.20 422.73 0.00 0.00
16.30 208.67 0.00 0.00
16.30 208.67 0.00 0.00
14.40 162.86 0.00 0.00
NEC 2008 392.9 (b) Ancho de conductores 6.05
Se considera la altura de la bandeja como 10cm 20% Reserva: 1.21
Ancho total de Bandeja (cm) 7.26
Ancho Requerido (cm)
Fuente: Manual de gedisa
Diam. (mm)
Area (mm2)
Area Total (mm2)
Ancho Requerido (cm)
Fuente: Manual de gedisa
Calculo del Factor K para transformadores
I Base = 1 A
Armónicos
1 3 5 7 9 11 13
% de Ib ### 50 0 72 0 33 69 324
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
Forma de Onda
1
nI
I
1 3 5 7 9 11 130
10
20
30
40
50
60
70
80
90
100
Espectro
Armónico
Armónico
1 1 13 0.5 0.55 0 07 0.72 0.729 0 0
11 0.33 0.3313 0.69 0.69
%TDH-F
Algunos Valores Tipicos de K
Corriente RMS
In 1
nI
I
0 50 ### 28 ### 67 310 0 0 0 0 0 0 0 0
0.01 0 0.1 0.1 0.1 0.2 0.2 0.3 0.4180.01 0 0.1 0.2 0.3 0.4 0.4 1 0.8170.02 0.1 0.2 0.3 0.4 1 1 1 1.1760.03 0.1 0.2 0.4 1 1 1 1 1.4810.03 0.1 0.3 0.5 1 1 1 1 1.7170.04 0.1 0.4 1 1 1 1 1 1.8770.05 0.1 0.4 1 1 1 1 1 1.9560.05 0.2 0.5 1 1 1 1 1 1.9560.06 0.2 1 1 1 1 1 1 1.8820.07 0.2 1 1 1 1 1 0.4 1.7440.07 0.2 1 1 1 1 1 0.1 1.5560.08 0.2 1 1 1 1 0.4 0 1.3330.09 0.3 1 1 1 1 0.1 0 1.0940.09 0.3 1 1 1 0.5 0 -1 0.856
0.1 0.3 1 1 1 0.3 0 -1 0.6360.11 0.3 1 1 1 0.1 -1 -1 0.4480.11 0.3 1 1 1 0 -1 -1 0.3040.12 0.4 1 1 0.5 0 -1 -1 0.2110.13 0.4 1 1 0.3 0 -1 -1 0.1740.13 0.4 1 1 0.2 -1 -1 -1 0.1910.14 0.4 1 1 0.1 -1 -1 -1 0.2580.15 0.4 1 1 0 -1 -1 0 0.3670.15 0.5 1 1 0 -1 -1 0 0.5060.16 0.5 1 1 0 -1 -1 0.2 0.6610.17 0.5 1 1 0 -1 -1 0.5 0.820.17 1 1 0.4 -1 -1 0 1 0.9670.18 1 1 0.3 -1 -1 0 1 1.0910.19 1 1 0.2 -1 -1 0.2 1 1.180.19 1 1 0.1 -1 -1 0.4 1 1.227
0.2 1 1 ### -1 -1 1 1 1.2290.21 1 1 0 -1 0 1 1 1.1840.21 1 1 0 -1 0 1 1 1.0970.22 1 1 0 -1 0 1 0.4 0.9750.23 1 1 0 -1 0.1 1 0.2 0.8270.23 1 1 0 -1 0.3 1 0 0.6670.24 1 1 -1 -1 0.5 1 0 0.5060.25 1 1 -1 -1 1 1 -1 0.3610.25 1 1 -1 -1 1 1 -1 0.2420.26 1 1 -1 -1 1 0.4 -1 0.1610.27 1 1 -1 0 1 0.2 -1 0.1270.27 1 1 -1 0 1 0 -1 0.1440.28 1 0.5 -1 0 1 0 -1 0.2150.29 1 0.4 -1 0 1 0 -1 0.3360.29 1 0.4 -1 0.2 1 -1 -1 0.503
0.3 1 0.3 -1 0.3 1 -1 0 0.7060.31 1 0.2 -1 0.4 1 -1 0 0.9330.31 1 0.2 -1 1 1 -1 0.2 1.17
0.32 1 0.1 -1 1 0.4 -1 0.5 1.4030.33 1 0.1 -1 1 0.2 -1 1 1.6180.33 1 ### -1 1 ### -1 1 1.8010.34 1 0 -1 1 0 -1 1 1.9420.35 1 0 -1 1 0 -1 1 2.0320.35 1 0 -1 1 -1 0 1 2.0650.36 1 0 -1 1 -1 0 1 2.040.37 1 0 -1 1 -1 0.1 1 1.9590.37 1 0 0 1 -1 0.3 0.4 1.8280.38 1 0 0 1 -1 1 0.2 1.6540.39 1 0 0 1 -1 1 0 1.4480.39 1 -1 0 1 -1 1 0 1.222
0.4 1 -1 ### 1 -1 1 -1 0.9890.41 1 -1 0.1 0.5 -1 1 -1 0.760.41 1 -1 0.2 0.3 -1 1 -1 0.5480.42 1 -1 0.3 0.2 -1 1 -1 0.3610.43 1 -1 0.4 0 0 1 -1 0.2070.43 1 -1 0.5 0 0 1 -1 0.0890.44 1 -1 1 0 0 0.5 -1 0.0080.45 1 -1 1 0 0.1 0.3 -1 -0.040.45 1 -1 1 -1 0.2 0 0 -0.050.46 1 -1 1 -1 0.4 0 0 -0.040.47 1 -1 1 -1 1 0 0.2 -0.010.47 1 -1 1 -1 1 -1 0.5 0.0330.48 1 -1 1 -1 1 -1 1 0.0730.49 1 -1 1 -1 1 -1 1 0.1080.49 1 -1 1 -1 1 -1 1 0.132
0.5 1 -1 1 -1 1 -1 1 0.140.51 1 -1 1 -1 1 -1 1 0.1320.51 1 -1 1 -1 1 -1 1 0.1080.52 1 -1 1 -1 1 -1 1 0.0730.53 1 -1 1 -1 1 -1 0.5 0.0330.53 1 -1 1 -1 1 0 0.2 -0.010.54 1 -1 1 -1 0.4 0 0 -0.040.55 1 -1 1 -1 0.2 0 0 -0.050.55 1 -1 1 0 0.1 0.3 -1 -0.040.56 1 -1 1 0 0 0.5 -1 0.0080.57 1 -1 1 0 0 1 -1 0.0890.57 1 -1 0.4 0 0 1 -1 0.2070.58 1 -1 0.3 0.2 -1 1 -1 0.3610.59 1 -1 0.2 0.3 -1 1 -1 0.5480.59 1 -1 0.1 0.5 -1 1 -1 0.76
0.6 1 -1 ### 1 -1 1 -1 0.9890.61 1 -1 0 1 -1 1 0 1.2220.61 1 0 0 1 -1 1 0 1.4480.62 1 0 0 1 -1 1 0.2 1.6540.63 1 0 0 1 -1 0.3 0.4 1.8280.63 1 0 -1 1 -1 0.1 1 1.9590.64 1 0 -1 1 -1 0 1 2.040.65 1 0 -1 1 -1 0 1 2.0650.65 1 0 -1 1 0 -1 1 2.032
0.66 1 0 -1 1 0 -1 1 1.9420.67 1 ### -1 1 ### -1 1 1.8010.67 1 0.1 -1 1 0.2 -1 1 1.6180.68 1 0.1 -1 1 0.4 -1 0.5 1.4030.69 1 0.2 -1 1 1 -1 0.2 1.170.69 1 0.2 -1 0.4 1 -1 0 0.933
0.7 1 0.3 -1 0.3 1 -1 0 0.7060.71 1 0.4 -1 0.2 1 -1 -1 0.5030.71 1 0.4 -1 0 1 0 -1 0.3360.72 1 0.5 -1 0 1 0 -1 0.2150.73 1 1 -1 0 1 0 -1 0.1440.73 1 1 -1 0 1 0.2 -1 0.1270.74 1 1 -1 -1 1 0.4 -1 0.1610.75 1 1 -1 -1 1 1 -1 0.2420.75 1 1 -1 -1 1 1 -1 0.3610.76 1 1 -1 -1 0.5 1 0 0.5060.77 1 1 0 -1 0.3 1 0 0.6670.77 1 1 0 -1 0.1 1 0.2 0.8270.78 1 1 0 -1 0 1 0.4 0.9750.79 1 1 0 -1 0 1 1 1.0970.79 1 1 0 -1 0 1 1 1.184
0.8 1 1 ### -1 -1 1 1 1.2290.81 1 1 0.1 -1 -1 0.4 1 1.2270.81 1 1 0.2 -1 -1 0.2 1 1.180.82 1 1 0.3 -1 -1 0 1 1.0910.83 1 1 0.4 -1 -1 0 1 0.9670.83 0.5 1 1 0 -1 -1 0.5 0.820.84 0.5 1 1 0 -1 -1 0.2 0.6610.85 0.5 1 1 0 -1 -1 0 0.5060.85 0.4 1 1 0 -1 -1 0 0.3670.86 0.4 1 1 0.1 -1 -1 -1 0.2580.87 0.4 1 1 0.2 -1 -1 -1 0.1910.87 0.4 1 1 0.3 0 -1 -1 0.1740.88 0.4 1 1 0.5 0 -1 -1 0.2110.89 0.3 1 1 1 0 -1 -1 0.3040.89 0.3 1 1 1 0.1 -1 -1 0.448
0.9 0.3 1 1 1 0.3 0 -1 0.6360.91 0.3 1 1 1 0.5 0 -1 0.8560.91 0.3 1 1 1 1 0.1 0 1.0940.92 0.2 1 1 1 1 0.4 0 1.3330.93 0.2 1 1 1 1 1 0.1 1.5560.93 0.2 1 1 1 1 1 0.4 1.7440.94 0.2 1 1 1 1 1 1 1.8820.95 0.2 0.5 1 1 1 1 1 1.956
1 0.1 0.4 1 1 1 1 1 1.9561 0.1 0.4 1 1 1 1 1 1.8771 0.1 0.3 0.5 1 1 1 1 1.7171 0.1 0.2 0.4 1 1 1 1 1.4811 0.1 0.2 0.3 0.4 1 1 1 1.1761 0 0.1 0.2 0.3 0.4 0.4 1 0.8171 0 0.1 0.1 0.1 0.2 0.2 0.3 0.418
1 ### ### ### ### ### ### ### ###1 0 0 0 0 0 0 0 -0.421 0 0 0 0 0 0 -1 -0.82
1.02 0 0 0 0 -1 -1 -1 -1.181 0 0 0 -1 -1 -1 -1 -1.481 0 0 -1 -1 -1 -1 -1 -1.72
1.04 0 0 -1 -1 -1 -1 -1 -1.881 0 0 -1 -1 -1 -1 -1 -2
1.05 0 0 -1 -1 -1 -1 -1 -21.06 0 -1 -1 -1 -1 -1 -1 -1.881.07 0 -1 -1 -1 -1 -1 0 -1.741.07 0 -1 -1 -1 -1 -1 0 -1.561.08 0 -1 -1 -1 -1 0 0.1 -1.331.09 0 -1 -1 -1 -1 0 0.4 -1.091.09 0 -1 -1 -1 0 0.1 1 -0.86
1.1 0 -1 -1 -1 0 0.3 1 -0.641.11 0 -1 -1 -1 0 1 1 -0.451.11 0 -1 -1 -1 0.1 1 1 -0.31.12 0 -1 -1 0 0.2 1 1 -0.211.13 0 -1 -1 0 0.4 1 1 -0.171.13 0 -1 -1 0 1 1 1 -0.191.14 0 -1 -1 0 1 1 1 -0.261.15 0 -1 -1 0.1 1 1 0.3 -0.371.15 0 -1 -1 0.2 1 1 0 -0.511.16 0 -1 -1 0.4 1 1 0 -0.661.17 -1 -1 0 1 1 0.5 -1 -0.821.17 -1 -1 0 1 1 0.3 -1 -11.18 -1 -1 0 1 1 0.1 -1 -1.091.19 -1 -1 0 1 1 0 -1 -1.181.19 -1 -1 0 1 1 0 -1 -1.23
1.2 -1 -1 ### 1 1 -1 -1 -1.231.21 -1 -1 0.1 1 0.4 -1 -1 -1.181.21 -1 -1 0.2 1 0.2 -1 -1 -1.11.22 -1 -1 0.3 1 0.1 -1 0 -11.23 -1 -1 0.4 1 0 -1 0 -0.831.23 -1 -1 0.5 1 0 -1 0.1 -0.671.24 -1 -1 1 1 0 -1 0.4 -0.511.25 -1 -1 1 1 -1 -1 1 -0.361.25 -1 -1 1 1 -1 -1 1 -0.241.26 -1 -1 1 1 -1 0 1 -0.161.27 -1 -1 1 0.4 -1 0 1 -0.131.27 -1 -1 1 0.3 -1 0 1 -0.141.28 -1 0 1 0.1 -1 0.2 1 -0.211.29 -1 0 1 0 -1 0.5 1 -0.341.29 -1 0 1 0 -1 1 1 -0.5
1.3 -1 0 1 0 -1 1 0.3 -0.711.31 -1 0 1 0 -1 1 0 -0.931.31 -1 0 1 -1 -1 1 0 -1.171.32 -1 0 1 -1 0 1 0 -1.41.33 -1 0 1 -1 0 1 -1 -1.621.33 -1 ### 1 -1 ### 1 -1 -1.8
1.34 -1 0.1 1 -1 0.2 1 -1 -1.941.35 -1 0.1 1 -1 0.4 1 -1 -21.35 -1 0.2 1 -1 1 0.3 -1 -2.071.36 -1 0.2 1 -1 1 0.1 -1 -21.37 -1 0.3 1 -1 1 0 -1 -21.37 -1 0.4 0.4 -1 1 0 0 -1.831.38 -1 0.4 0.3 -1 1 -1 0 -1.651.39 -1 0.5 0.2 -1 1 -1 0.1 -1.451.39 -1 1 0.1 -1 1 -1 0.3 -1.22
1.4 -1 1 ### -1 1 -1 1 -11.41 -1 1 0 0 1 -1 1 -0.761.41 -1 1 0 0 1 -1 1 -0.551.42 -1 1 0 0 1 -1 1 -0.361.43 -1 1 0 0 0.5 -1 1 -0.211.43 -1 1 0 0.1 0.3 -1 1 -0.091.44 -1 1 -1 0.2 0.1 0 1 -0.011.45 -1 1 -1 0.4 0 0 1 0.0361.45 -1 1 -1 1 0 0 0.3 0.0491.46 -1 1 -1 1 0 0.2 0.1 0.0371.47 -1 1 -1 1 -1 0.4 0 0.0071.47 -1 1 -1 1 -1 1 0 -0.031.48 -1 1 -1 1 -1 1 -1 -0.071.49 -1 1 -1 1 -1 1 -1 -0.111.49 -1 1 -1 1 -1 1 -1 -0.13
1.5 -1 1 -1 1 -1 1 -1 -0.141.51 -1 1 -1 1 -1 1 -1 -0.131.51 -1 1 -1 1 -1 1 -1 -0.111.52 -1 1 -1 1 -1 1 -1 -0.071.53 -1 1 -1 1 -1 1 0 -0.031.53 -1 1 -1 1 -1 0.4 0 0.0071.54 -1 1 -1 1 0 0.2 0.1 0.0371.55 -1 1 -1 1 0 0 0.3 0.0491.55 -1 1 -1 0.4 0 0 1 0.0361.56 -1 1 -1 0.2 0.1 0 1 -0.011.57 -1 1 -1 0.1 0.3 -1 1 -0.091.57 -1 1 0 0 0.5 -1 1 -0.211.58 -1 1 0 0 1 -1 1 -0.361.59 -1 1 0 0 1 -1 1 -0.551.59 -1 1 0 0 1 -1 1 -0.76
1.6 -1 1 ### -1 1 -1 1 -11.61 -1 1 0.1 -1 1 -1 0.3 -1.221.61 -1 0.5 0.2 -1 1 -1 0.1 -1.451.62 -1 0.4 0.3 -1 1 -1 0 -1.651.63 -1 0.4 0.4 -1 1 0 0 -1.831.63 -1 0.3 0.5 -1 1 0 -1 -21.64 -1 0.2 1 -1 1 0.1 -1 -21.65 -1 0.2 1 -1 1 0.3 -1 -2.071.65 -1 0.1 1 -1 0.4 1 -1 -21.66 -1 0.1 1 -1 0.2 1 -1 -1.941.67 -1 ### 1 -1 ### 1 -1 -1.81.67 -1 0 1 -1 0 1 -1 -1.62
1.68 -1 0 1 -1 0 1 0 -1.41.69 -1 0 1 -1 -1 1 0 -1.171.69 -1 0 1 0 -1 1 0 -0.93
1.7 -1 0 1 0 -1 1 0.3 -0.711.71 -1 0 1 0 -1 1 1 -0.51.71 -1 0 1 0 -1 0.5 1 -0.341.72 -1 0 1 0.1 -1 0.2 1 -0.211.73 -1 -1 1 0.3 -1 0 1 -0.141.73 -1 -1 1 0.4 -1 0 1 -0.131.74 -1 -1 1 1 -1 0 1 -0.161.75 -1 -1 1 1 -1 -1 1 -0.241.75 -1 -1 1 1 -1 -1 1 -0.361.76 -1 -1 1 1 0 -1 0.4 -0.511.77 -1 -1 1 1 0 -1 0.1 -0.671.77 -1 -1 0.4 1 0 -1 0 -0.831.78 -1 -1 0.3 1 0.1 -1 0 -11.79 -1 -1 0.2 1 0.2 -1 -1 -1.11.79 -1 -1 0.1 1 0.4 -1 -1 -1.18
1.8 -1 -1 ### 1 1 -1 -1 -1.231.81 -1 -1 0 1 1 0 -1 -1.231.81 -1 -1 0 1 1 0 -1 -1.181.82 -1 -1 0 1 1 0.1 -1 -1.091.83 -1 -1 0 1 1 0.3 -1 -11.83 -1 -1 0 1 1 0.5 -1 -0.821.84 0 -1 -1 0.4 1 1 0 -0.661.85 0 -1 -1 0.2 1 1 0 -0.511.85 0 -1 -1 0.1 1 1 0.3 -0.371.86 0 -1 -1 0 1 1 1 -0.261.87 0 -1 -1 0 1 1 1 -0.191.87 0 -1 -1 0 0.4 1 1 -0.171.88 0 -1 -1 0 0.2 1 1 -0.211.89 0 -1 -1 -1 0.1 1 1 -0.31.89 0 -1 -1 -1 0 1 1 -0.45
1.9 0 -1 -1 -1 0 0.3 1 -0.641.91 0 -1 -1 -1 0 0.1 1 -0.861.91 0 -1 -1 -1 -1 0 0.4 -1.091.92 0 -1 -1 -1 -1 0 0.1 -1.331.93 0 -1 -1 -1 -1 -1 0 -1.561.93 0 -1 -1 -1 -1 -1 0 -1.741.94 0 -1 -1 -1 -1 -1 -1 -1.881.95 0 0 -1 -1 -1 -1 -1 -2
2 0 0 -1 -1 -1 -1 -1 -22 0 0 -1 -1 -1 -1 -1 -1.882 0 0 -1 -1 -1 -1 -1 -1.722 0 0 0 -1 -1 -1 -1 -1.482 0 0 0 0 -1 -1 -1 -1.182 0 0 0 0 0 0 -1 -0.822 0 0 0 0 0 0 0 -0.422 ### ### ### ### ### ### ### ###
Calculo del Factor K para transformadores
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
Forma de Onda
2
1
nI
I
nI
I
2
nI
I
22nI
nI
1 3 5 7 9 11 130
10
20
30
40
50
60
70
80
90
100
Espectro
Armónico
1 1 1 10.25 0.5 0.25 2.25
0 0 0 00.5184 0.72 0.5184 25.4016
0 0 0 00.1089 0.33 0.1089 13.17690.4761 0.69 0.4761 80.4609
116.34 Factor K 122.2894
Basado en la norma IEEE 519
Algunos Valores Tipicos de K
Fuente:Nota tecnica 2
Ing. Mauricio Ardón.FASOR, S.A. de C.V.
2
1
nI
I
nI
I
2
nI
I
22nI
nI
Transformadores en Delta Abierta
Voltaje de línea Primario:13.8 kV
Voltaje de línea Secundario:480 V
Potencia de cada TX monofasico:25 kVA
Potencia Trifasica nominal:43.28 kVA
Corriente Nominal Primario:1.81 A
Corriente Nominal Secundario:52.08 A
Ampacidad de CablesBasado en IEEE 339-1997
1.- Factor de corrección por temperatura del ambiente y del conductor
Parametros Base:
Temperatura del Cable (TC): Temperatura Ambiente (TA):
ºC ºC
Ft = 0.93
2.- Factor de corrección por resistividad térmica
Tipo de Instalación:
Tamaño del Conductor
AWG / MCM
Cantidad de Circuitos
Resistividad térmica del Suelo
Fth = 0.96
3.- Factor de Agrupamiento
Configuracion:
ºC cm
W
A
B
Calibre del Cable:
AWG / MCM
Numero de Filas (Capas):
Numero de Columnas:
Fth = 0.84
Se
gú
n T
ab
la 3
10
.16
CE
N 2
00
4
Cable a emplear
Temperatura de Operación Normal
Capacidad Nominal: Capacidad Final de Conductor
30 A
A: Verifique que las temperaturas sean similaresB: Verifique que los calibres sean iguales
A
B
B
###
3
###
###
###
###
3.- Factor de Agrupamiento
###
###
###
###
Factor de corrección
###
F = 0.93 X 0.96 X 0.84
F = 0.749952 ###75°C
90°C
Capacidad Final de Conductor
22.499 A
t th gF F F F
Calculo de Corriente máxima de Corto Circuito
Calibre del Cable:
Área: 250000 CMIL
Frecuencia: 60 Hz
Duración del Corto C: 100 Ciclos1.67 Seg
Temp. De Operación: 90 ºC
Temp. Max Corto C: 250 ºC
Corriente de CC: 13.93 kA
Formula Aplicada
Donde:
Icc: Corriente de Corto CircuitoA: Área del Conductor en MCMt: Tiempo de Corto Circuito en seg.
T1: Temperatura de operación del cableT2: Temperatura Max. De Corto Circuito
Fuente: Okonite
2
1cc
T 2340,0297 log
T 234I A
t
CanalizacionTamaño 4 "
Tuberia No Metalica Electrica
Diametro 0 mmArea total 0.00 mm2
Area 31% 0.00 mm2Area 40% 0.00 mm2Area 53% 0.00 mm2
Tamaño
3/8 0 0 9.7 01/2 15.8 14.2 16.1 16.83/4 20.9 19.3 20.9 21.91 26.6 25.4 25.9 28.1
1 1/4 35 34 32.4 36.81 1/2 40.9 39.8 39 42.7
2 52.5 51.3 51.8 54.62 1/2 69.4 0 63.5 64.9
3 85.2 0 76.2 80.73 1/2 97.4 0 88.9 93.2
4 110 0 101.6 105.85 0 0 0 06 0 0 0 0
Tuberia Metalica Electrica
Tuberia No Metalica Electrica
Tubo Metalico Flexible
Tubo Metalico Intermedio IMC
12.5 12.6 12.5 0 016 16 16 16 13.4
21.1 21 21.1 21.2 18.326.8 26.5 26.8 27 23.835.4 35.1 35.4 35.4 31.940.3 40.7 40.3 41.2 37.551.6 52.4 51.6 52.9 48.6
0 0 63.3 63.2 58.20 0 78.3 78.5 72.70 0 89.4 90.7 84.50 0 102.1 102.9 96.20 0 0 128.8 121.10 0 0 154.8 145
Tubo No Flexible hermetico a los liquidos (Tipo
FNMC-B)
Tubo No Flexible hermetico a los liquidos (Tipo FNMCA-A*)
Tubo No Flexible hermetico a los
liquidos
Tubo Metalico Rigido
Tubo de PVC Rigido, Sch. 80
0 0 015.2 17.8 020.4 23.1 026.1 29.8 034.5 38.1 040.4 43.7 052 54.7 56.4
62.1 66.9 077.3 82 84.889.4 93.7 96.6
101.5 106.6 108.9127.4 0 135153.2 0 160.9
Tubo de PVC Rigido, Sch. 40 y tubo de PE-AD
Tubo de PVC, Tipo A
Tubo de PVC, Tipo EB
CALIBRE AISLANTE Cant Cables14 THW 1
Diametro 4.14 mmArea 13.49 mm2
Area Total 13.49 mm2
CEN 1999 Tabla 5THW TW THHN
Calibre Diametro Seccion mm2 Diametro Seccion mm2 Diametro18 0 0.0016 0 0.0014 4.14 13.49 3.38 8.99 2.8212 4.62 16.80 3.86 11.73 3.310 5.23 21.53 4.47 15.73 4.168 6.76 35.98 5.99 28.25 5.486 7.72 46.92 6.454 8.94 62.92 8.233 9.65 73.32 8.942 10.46 86.14 9.751 12.5 123.02 11.33
1/0 13.51 143.70 12.342/0 14.68 169.67 13.513/0 16 201.55 14.834/0 17.47 240.28 16.3250 19.43 297.23 18.06300 20.83 341.60 19.45350 22.12 385.22 20.75400 23.31 427.78 21.94500 25.47 510.74 24.1600 28.27 629.20 26.69700 30.07 711.88 28.5750 30.93 753.18 29.36800 31.75 793.65 30.17900 33.37 876.70 31.8
1000 34.85 956.19 33.271250 39.09 1203.021500 42.21 1402.721750 45.11 1602.092000 47.8 1798.85
Resistencia y reactancia de conductoresCalibre: 250 Conductore por fase 1
Mat. de la tuberia: Aluminio
Distancia: 2000 M
Resistencia 0.187 Ohm/kM R: 0.374Reactancia 0.135 Ohm/kM X: 0.270
CALIBRE TEMP. MATERIAL COR. Temp.8 75°C COBRE 36-40
Cap. Nominal 50 AFactor Correc. 0.88
Capacidad 44 A
Tabla 310.16 CEN 1999
Calibre COBRE ALUMINIO60°C 75°C 90°C 60°C 75°C 90°C
AWG/kcmil TW*, UF* TW*, UF*
18 0 0 14 0 0 016 0 0 18 0 0 014 20 20 25 0 0 012 25 25 30 0 20 2510 30 35 40 25 30 358 40 50 55 30 40 456 55 65 75 40 50 604 70 85 95 55 65 753 85 100 110 65 75 852 95 115 130 75 90 1001 110 130 150 85 100 115
1/0 125 150 170 100 120 1352/0 145 175 195 115 135 1503/0 165 200 225 130 155 1754/0 195 230 260 150 180 205250 215 255 290 170 205 230300 240 285 320 190 230 255350 260 310 350 210 250 280400 280 335 380 225 270 305500 320 380 430 260 310 350600 355 420 475 285 340 385700 385 460 520 310 375 420750 400 475 535 320 385 435800 410 490 555 330 395 450900 435 520 585 355 425 4801000 455 545 615 375 445 5001250 495 590 665 405 485 5451500 520 625 705 435 520 5851750 545 650 735 455 545 6152000 560 665 750 470 560 630
TEMP AMB.21-25 1.08 1.05 1.04 1.08 1.05 1.0426-30 1 1 1 1 1 131-35 0.91 0.94 0.96 0.91 0.94 0.9636-40 0.82 0.88 0.91 0.82 0.88 0.9141-45 0.71 0.82 0.87 0.71 0.82 0.8746-50 0.58 0.75 0.82 0.58 0.75 0.8251-55 0.41 0.67 0.76 0.41 0.67 0.7656-60 0.58 0.71 0.58 0.7161-70 0.33 0.58 0.33 0.5871-80 0.41 0.41
Ampacidades admisibles de los conductores aislados para tensiones nominales de 0 a 2000 V y 60°c a 90°c con no mas de tres conductores portadores de corriente en una canalización, cable
o directamente enterrados, basadas en una temperatura ambiente de 30°c
FEPW*, RH*, RHW*,
THHW*, THW*,
THWN*, XHHW*,
USE*, ZW*
TBS, SA, SIS, FEP*, FEPB*, MI,
RHH*, RHW-2, THHN*, THHW*, THW-2*,
THWN-2*, USE-2, XHH,
XHHW*, XHHW-2,
ZW-2
RH*, RHW*, THHW*, THW*,
THWN*, XHHW*,
USE*
TBS, SA, SIS, THHN*,
THHW*, THW-2,
THWN-2, RHH*,
RHW-2, USE-2, XHH,
XHHW, XHHW-2,
ZW-2
CALIBRE TEMP. Tension2 90°C 2001-5000 V
Cap. Nominal 130 A
Capacidad 130 A
Tabla 310.73 CEN 1999
Calibre 2001-5000 V 5001-35000 VAWG/kcmil 90°C 105°C 90°C 105°C
8 55 616 75 84 83 934 97 110 110 1202 130 145 150 1651 155 175 170 190
1/0 180 200 195 2152/0 205 225 225 2553/0 240 270 260 2904/0 280 305 295 330250 315 355 330 365350 385 430 395 440500 475 530 480 535750 600 665 585 655
1000 690 770 675 755
Ampacidades de cables triples aislados o de tres conductores de cobre sencillos, en un conducto físicamente aislado, al aire libre,
basadas en temperaturas de conductor de 90°C en una temperatura ambiente de 40°C
CALIBRE TEMP. Tension4/0 90°C 5001-35000 V
Cap. Nominal 230 A
Capacidad 230 A
Tabla 310.74 CEN 1999
Calibre 2001-5000 V 5001-35000 VAWG/kcmil 90°C 105°C 90°C 105°C
8 43 486 58 65 65 724 76 85 84 942 100 115 115 1301 120 135 130 150
1/0 140 155 150 1702/0 160 175 175 2003/0 190 210 200 2254/0 215 240 230 260250 250 280 255 290350 305 340 310 350500 380 425 385 430750 490 545 485 540
1000 580 645 565 640
Ampacidades de cables triples aislados o de tres conductores de aluminio sencillos, en un conducto físicamente aislado, al aire libre, basadas en temperaturas de conductor de 90°C en una temperatura
ambiente de 40°C
A AAC AACS AC ACSR ACSR-AG AL ACSR-AW AF
Al Alta frecuencia AM Amplitud
Armadura
Atenuación
ATM
AW
AWG
AWM
Bel BIL Bit Blindaje
C c.a.
c.c. c.d. Capacitador
Ancho de banda Apertura numérica
Baja Frecuencia
Capacitancia
Capacitor
CATV
CCS CCTV
CL2 CL3 CM Conductividad
CP CPE CSA
Cu CuSn CV CW CXC DCS DGN Diafonía Dieléctrico Dispersión
DIT DRS
Capacitancia mutua
Circuito en serie
Circuito paralelo
Constante dieléctrica
Dispersión cromática
Dispersión modal
DS
Efecto piel
EIA/TIA
EP(R)
EPDM f
FA Fan-out
Fase FCC FDDI FEP
FM FOA FOW FTP
G G-GC
Glosario de términos relacionados con conductores eléctricos y cables para telecomunicaciones H
HDPE Higroscópico
Hilo dren HMWP HP HPN
HPOF
Hz I I2R IACS
Electromagnético
ICEA
IEC
IEEE
Iexc Impedancia
Inductancia
ISO ITU Jumper kCM
kV l LAN LDPE
lpi Longitudinal
lpof m.s.n.m Malla Mc Mi
MIC
mp
mp-gc MTW Multimodo
Multiplexar MV
Indice de refracción
Línea balanceada Línea de transmisión Longitud de onda de Malla
mw NEC Neopreno NFPA
NM
NM-B o NMC-B
NMC NMX NOM
Non break out
NZ
OA Ohm
OTDR
OW Pantalla PCC PCG
PCM PE
PFA
PFAH PG
Pig-tail PILC Plástico Plastificante Plenum PMD
Pérdidas por doblez
Polietileno celular
Polilam
Polímero
POT psi PVC PVDF
RDI REA (RUS)
Reactancia
RG/U RH/RW
RHH RHW
RHW-2 SA SBR
SDH SE SF
SFF SH
SHD
SHD-GC SHD.
SIC
SIS
SJ SJO
Resistencia a la abrasión
SJT SJ
SMT SNM
SO
SONET SPT
ST
STP
SU SV
SVT SVTO TA
TAGA
TAGT TC
TEFLON* TF
TFE TFF TFFN TFN THHN
THHW
THW1
THW-21 THWN
TP
TPT TP TTU
TW
UD UF
UHF UL
Unimodo
URD
USE
USG UTP V VA
VHF Volt
VW-1 W
WDM
XHHW
XHHW-2 XLP
XT
Velocidad de la luz Velocidad de propagación
Ampere: Unidad utilizada para denominar la intensidad de corriente eléctrica. All Aluminum Conductor: conductor o cable de hilos de aluminio. Aluminum Alloy Standed Conductor: cable de aleación de aluminio. Armored Cable: cables provistos de una armadura metálica flexible. Aluminum Conductor Steel Reinforced: conductor de aluminio con centro de acero galvanizado. ACSR con aleación de aluminio para alta temperatura (150°C) y acero de alta resistencia. Símbolo del aluminio. ACSR con centro de acero recubierto con aluminio (Alumo-Weld). También conocido como ACSR-AS.
Símbolo del aluminio. La banda de 3 MHz a 1 GHz. Amplitud Modulada. El valor máximo de variación de una onda. Es la diferencia entre los valores superior e inferior de una banda de frecuencias dada. Se expresa en Hertz.
Appliance Wiring Material: Conductores destinados al alambrado interno de aparatos electrodomésticos. La banda de 30-300 KHz.
Es una unidad que representa el logaritmo de la razón de dos niveles. Basic Impulse Insulation Level: nivel básico de aislamiento al impulso. Es un dígito binario.
Símbolo de capacitancia y grados centígrados.
Corriente continua (ver c.d.) Corriente directa: Es la corriente eléctrica donde los electrones fluyen en una sola dirección.
Audio Frecuencia: Rango de frecuencias que caen dentro del rango perceptible del oído humano: aproximadamente 20 a 20, 000 Hz
Es la medida de aceptación angular de una fibra óptica, que es aproximadamente el seno de la mitad del ángulo del cono de aceptación de la fibra. Cinta corrugada de acero que tiene la función de proteger el cable contra maltrato mecánico y ataque de roedores. En aplicaciones especiales se llegan a usar armaduras de cinta engargolada o de alambres de acero.
Es el decremento en magnitud de una onda mientras esta viaja en medio transmisor, sea un cable o un circuito. La atenuación se mide como una razón o como logartimo de la razón (decibel). Siglas en inglés para la técnica de codificación y conmutación en bloques llamada Asynchronous Transfer Mode y que permite multiplexar señales de velocidades distintas en un mismo canal digital. American Wire Gauge: escala de calibres americanos para alambres y cables, también conocida como b&s (Brown and Sharpe) Wire Gauge. American Wire Gauge: Escala de calibres americanos para alambres y cables, también conocida como B&S (Brown and Sharpe) Wire Gauge.
Capa conductiva en un cable que tiene la función de reducir la interferencia electomagnética. Puede ser una malla de alambres, una cinta metálica o una cinta plástica metalizada.
Corriente alterna: Es una corriente que períodicamente revierte la dirección del flujo de electrones. La razón en la que un ciclo completo ocurre por unidad de tiempo (normalmente un segundo) se le denomina frecuencia de la corriente.
Dos superficies conductoras separadas por un material dieléctrico. La capacitación es determinada por el área de las superficies, tipo de dieléctrico y el espaciamiento entre los conductores.
Es la capacitancia que existe entre dos concluctores cuando los demás conductores están conectados entre sí.
Siglas en lnglés para conductores de acero cubierto cle cobre (Copper Cladded Steel). Circuito Cerrado cle TeleVisión. Es un circuito cuyos componentes distribuidos a lo largo de camino común.
Cables para circuitos Clase 2, según NEC-725, bajo voltaje y potencia. Idem a CL2, para 300 volts máximo, bajo potencia. Circular Mil: área de un circuito con un diámetro de 1/1000 de pulgada.
Caballos de Potencia: también conocido como HP. Chlorinated PolyEthylene: polietileno clorado.
Símbolo del cobre. Símbolo que denota cobre estañado. Continuous Vulcanization: proceso de vulcanización en línea con la extrusión. CopperWeld: varilla de acero, con recubrimiento de cobre. Designación de cable coaxial por CSA (Canadian Standars Association). Cables para Distribución Comercial Subterránea. Dirección General de Normas de la Secretaría de Comercio y Fomento Industrial. Transferencia no deseada de señal entre distintos canales de un equipo a cable. Es un medio aislante (no-conductivo).
Dispositivo de Interconexión Terminal: es el límite entre la red pública y la que es responsabilidad del usuario. Cables para Distribución Residencial Subterránea (tipo URD).
Es la propiedad que tiene un material dieléctrico situado en medio de dos conductores de almacenar electricidad cuando existe una diferencia de potencial entre los conductores. La unidad de medida es el Farad, que es el valor de capacitancia que almacenará una carga de un Cuolomb cuando exista una diferencia de potencial de un volt entre los conductores.
Dos superficies conductoras separadas por un material dieléctrico. La capacitancia es determinada por el área de las superficies, tipo de dieléctrico y el espaciamiento entre los conductores. Community Antena TeleVision: término empleado para los cables coaxiales destinados a los sistemas de televisión comunitaria.
Es un circuito en el cual un mismo voltaje se presenta en todos los componentes, con corriente dividida entre estos de acuerdo a su resistencia o impedancias.
La capacidad de un material para permitir el flujo de electrones, medido por la corriente por unidad de voltaje aplicado. Es el recíproco de la resistividad. También se llama permitividad. Es aquella propiedad del dieléctrico que determina la cantidad de energía electróstatica que puede almacenarse cuando es aplicado un voltaje.
Canadian Standard Association: Institución canadiense para la certificación de equipo eléctrico y electrónico acorde a las normas que ellos mismos publican.
Fenómeno por el cual componentes de la luz transmitida por la fibra sufren retrasos distintos. Es la suma de varios efectos, principalmente dispersión modal y dispersión cromática. Puede limitar la velocidad de transmisión.
Es el retraso diferente que sufren las distintas longitudes de onda que componen a luz portadora, por tener velocidades distintas en la fibra. En fibras con diseño estándar la dispersión cromática tiene un valor mínimo o nulo en la ventana de 1310 nm.
Es el retraso diferente que presentan los modos de propagación en una fibra multimodo por viajar en ángulos distintos, no existe en las fibras unimodo en las que se transmite un modo de propagación.
Siglas en inglés para dispersión corrida, son las fibras unimodo con dispersión mínima enla ventana de 1550 nm.
Asociación de las industrias electrónica y de comunicaciones en EUA.
Ethylene Propylene Dionomer: etileno-propileno dieno monómero.
Forced Air: enfriamiento con aire forzado.
Es la relación angular entre ondas. Flexible Control Cable: cable control, flexible. Fiber Distribution Digital Interface: especificación para la red de datos 100% óptica a 100 Mb/s.
Frecuencia modulada. Forced Oil and Air: enfriamiento con aceite forzado y aire. Forced Oil and Water: enfriamiento con aceite forzado y agua.
Ground: cable flexible para minas con conductores para conexión a tierra, 600 ó 2000 volts.
Glosario de términos relacionados con conductores eléctricos y cables para telecomunicaciones
High Density PolyEthylene (PE): polietileno de alto densidad.
Es un alambre desnudo que está en contacto con el blindaje del cable a lo largo de toda su longitud. High Molecular Weight Polyethylene: polietileno de alto peso molecualr. Horse Power: caballo de potencia.
Hertz: Es la unidad de medida de frecuencia: 1 ciclo por segundo. Símbolo utilizado para designar corriente. Fórmula de potencia en Watts, donde I=corriente en amperes, R=resistencia en Ohms.
Es la tendencia que tiene la corriente alterna de viajar en el perímetro del conductor con el incremento de la frecuencia.
Se reflere a la combinación de campos eléctricos y magnéticos originado por el movimiento de los electrones por el conductor. Fluorinated Ethylene Propylene: aislamiento de etileno-propileno fluorado.Ethylene Propylene (Rubber): aislamiento a base de etileno-propileno.
Frecuencia: El número de veces que una acción periódica ocurre en un lapso de tiempo: Es el número de Hertz en los que una corriente eléctrica completa 1 seg.
Cable óptlco para conectorizar, que permite separar las fibras individuales sin necesidad de darles protección adicional.
Nombre abreviado para tetrafluoruroetileno-exafluoruropropileno, material aislante con excelentes propiedades eléctricas y químicas que se usan en cables categoría plenum.
Foiled Twisted Pair: cables multipares para datos blindados por medio de una cinta plástica aluminizada con hilo dren.
Ground-Ground Check: cable flexible para minas, con conductores para conexión a tierra y un conductor aislado para verificar la continuidad de los conductores de tierra, 600 ó 2000 volts.
Henry: Es la unidad práctica de inductancia que producirá un incremento de voltaje de 1 Volt cuando la corriente cambie a razón de un ampere/seg.
Propiedad de algunos materiales de absorber agua del ambiente. Las cintas e hilos usados en cables no deben hacerlo.
Heater Cord Parallel Neoprene: cordón paralelo de dos conductores flexibles con aislamiento elastomérico para aparatos electrodomésticos resistentes al calor, 90 °C, 600 volts. High Pressure Oil Filled: cables tipo Pipe (tubo) de alta tensión con aislamiento de papel impregnado instalados dentro de un tubo de acero con aceite a alta presión.
International Annealed Copper Standard: patrón internacional para la conductividad del cobre (igual al 100% para el cobre electrolítico recocido).
Corriente de excitación.
International Standards Organization: organización internacional de normalización. International Telecomunication Union: organización para normalización internacional en Cable para conexiones en un distribuidor, puede ser un par de cobre o una fibra Monotel con conectores.
kiloVolt: unidad de medida de tensión eléctrica igual a 1000 volts. Símbolo utilizado para designar corriente. Local Area Network: red de datos de corta longitud en un edificio o conjunto de edificios. Low Density PolyEthylene (PE): polietileno de bajo densidad,
Es el arreglo de dos o más conductores o una guía de onda que se utiliza para transferir señales de un lugar a otro.
Es la distancia entre picos o nodos sucesivos de una onda.
Low Pressure Oil Filled: cables con aislamiento de papel impregnado tipo Autocontenidos para alta tensión. . Metros sobre el nivel del mar. Es un grupo de filamentos metálicos entretejidos para formar una esfructura tubular la Metal Clad: cable armado con una cubierta metálica del tipo interlock o tubo corrugado.
MP-Ground Check: MP con un conductor aislado para verificar la continuidad de los conductores de tierra. Machine Tool Wire: conductor con aislamiento termoplástico para alambrado de máquinas herramientas.
Combinación de varias señales para enviarlas por un solo canal de transmisión. Medium Voltage Cable: cables cona aislamiento sólido para tensiones de 2001 a 35,000 volts.
Insulated Cable Engineers Association: nombre actual de IPCEA (Power), asociación norteamericana para la normalización de conductores eléctricos. International Electrotechnical Commission: organización internacional encargada de la normalización de productos eléctricos. Institute of Electrical and Electronic Engineers: principal asociación a nivel mundial de ingenieros en electricidad, electrónica y materias afines.
Es la oposición total de un circuito, cable, o algún componente al paso de la corriente alterna. Esta incluye a la resistencia y a la reactancia. La unidad de medida es el Ohm y su símbolo es la Z. Es un promedio del índice de refracción para las longitudes de onda en la ventana de transmisión; es un dato necesario que se debe conocer para medir la distancia de un enlace en un OTDR. Es la propiedad de un conductor o un circuito que se resiste al cambio de corriente. Su unidad de medida es el Henry y su símbolo es L.
kiloCircularMil:unidad de área del sistema norteamericano de calibres de conductores eléctricos, igual a 1000 circular mils (CM). Anteriormente conocida como MCM.
Es un cable que tiene 2 conductores idénticos con las mismas características electromagnéticas en relación a los demás conductores y tierra.
Paper Insulated: proceso para la fabricación de cables telefónicos con aislamiento de papel aplicado longitudinalmente.
Mineral Insulated: cable con aislamiento mineral de óxido de magnesio y cubierta de tubo de cobre o acero, para alta temperatura y resistencia al fuego, 90 a 250 °C. Técnica de modulación en que la amplitud de una señal analógica en cierto momento se expresa con un número binario de 8 cifras. Mine Power Feeder Cable: cable alimentador para minas con tres conductores de fase y tres conductores para conexión a tierra.
Fibras que tienen un núcleo relativamente grande (50 micras o más), que permiten transmitir varios haces luminosos llamados modos de propagación.
Micro m Wave: microonda. Natinal Electrical Code: Norma general sobre productos e instalaciones Policloropreno, hule sintético empleado como aislamiento y cubierta de cables flexibles.
NM o NMC con aislamiento de THHN.
NM con cubierta elastomérica resistente a la corrosión; para ambientes secos o húmedos. Norma Mexicana; documentos publicados por organismos privados autorizados. Son de uso voluntario. Norma Oficial Mexicana: documentos publicados por la DGN para la normalización y especificación de productos.
Oil and Air: enfriamiento natural aire-aceite.
Oil and Water: enfriamiento con aceite-agua. Vea blindaje. Designación de CSA para los cables de uso interior (Premises Comunication Cable).
Siglas en inglés para la técnica de modulación llamada en español MIC (Modulación por Impulsos Codificados) Polietileno, puede ser de los tipos HMWP,HDPE y LDPE.
PerFluoro-Alkoxy: cables para alta temperatura; ambiente seco, con aislamiento de Perfluoro-Alkoxy, hasta 200 °C.
PerFluoro-Alkoxy Heat: PFA con temperaturas mayores de hasta 250 °C.
Fibra óptica Monotel con conector en una punta. Papel Insulated Lead Cover: cable para media tensión aislado con papel impregnado y con cubierta de plomo. Sustancia poliméricas que incluyen tanto materiales naturales como sintéticos. Es un químico que se agrega al plástico pare hacerlo más suave y flexible. Cables que cumplen con las normas de seguridad parta poder instalarse sin tubo conduit sobre el falso plafón.
Técnica de introducir burbujas en el plástico del aislamiento pare bajar la capacitancia del cable.
National Fire Protection Association: asociación americana para la protección contra incendios responsable de la publicación del NEC. Non-Metallic Sheathed Cable: conductores aislados y con cubierta no metálica resistente a la humedad, retardante de la flama; sugerido para ambientes secos.
Cable óptico para distribución en edificios en el que las fibras no tienen protección individual para separarlas del resto.
Fibras ópticas de baja dispersión cromática, pero nunca igual a una de 1530 a 1560 mm, permite transmisión de varios portadores (ver WDM).
Es la unidad eléctrica de resistencia. Es el valor de resistencia a través del cual una diferencia de potencial de 1 Volt mantendrá una corriente de un ampere. Reflectómetro óptico en dominio de tiempo, es un equipo que inyecta un pulso de luz a la fibra y detecta las reflexiones, permite medir atenuación y longitud de un enlace.
Portable Cable Control and Ground conductors: cable flexible para minas con conductores de control y para conexión a tierra, 600 ó 2000 volts.
Es la forma que toma la curva de atenuación que es causada por: a)Una fibra óptica curveada alrededor de un radio de curvatura cerrado, o b) Microdobleces causados por esfuerzo mecánico de la fibra.
Portable Cable Ground Conductor: cable flexible para minas con conductores de fase y para conexión a tierra, 600 ó 2000 volts.
Siglas en inglés para el fenómeno de dispersión por polarización de modos, en el que existe una diferencia de velocidad entre los componentes de campo eléctrico y magnético de un mismo modo de propagación.
Cordón paralelo con aislamiento termoplástico para 300 volts, 60 °C. pounds per square inch: libras por pulgada cuadrada. PolyVinyl Chloride: cloruro cle poli-vinilo, compuesto ampliamente usado como aislamiento y cubierta.
Red Digital Integrada; servicio de alta velocidad para grandes usuarios a través de la red pública.
Capacidad de resistir desgaste superficial.
Radio Frecuency Guide, Universal: designación para cables coaxiales para radiofrecuencias.
Rubber High Heat: cables con aislamiento y cubierta de hule sintético, para 90 °C, 600 V.
Igual a RHW pero con aislamiento de 90 °C en ambiente seco y húmedo. Silicone Asbestos: cables aislados con hule silicón y malla de asbesto o fibra de vidrio.
Siglas en inglés pare el sistema de transmisión óptica sincrono (Synchronous Digital Hierarchy). Service Entrance: uno o más conductores con o sin cubierta exterior usados para alimentación de servicios. Silicone Rubber Fiber Glass: alambre o cable de 7 hilos aislados con hule silicón y malla de fibra de vidrio, 200 °C.
Silicone Rubber Fiber Glass Flexible: SF con conductor más flexible, 150 °C.
Synthetic Insulated Switchboard Cable: cable para tableros con aislamiento elastomérico sintético, 90 °C, 600 volts.
Hard Service Cord Junior: cordón uso rudo para servicio ligero con aislamiento elastomérico, 300 volts. SJ Oil Resistant: SJ con aislamiento resistente al aceite.
Cinta de aluminio ó de acero con espesor entre 0. 15 y 0.2 mm que tiene un recubrimiento plástico en una o ambas caras, lo que permite que se adhiera a la cubierta de polietileno de un cable formando una barrera contra la humedad.
Es una substancia hecha de muchas unidades químicas moleculares. El término polímero es regularmente usado en vez de plástico, hule o elastómero.
PolyVinyliDene Fluoride: compuesto termoplástico a base de fluor usado generalmente como cubierta en cables para construcción.
Rural Electrification Administracion: oficina norteamericana del Departamento de Agricultura encargada de normalización de equipos ofrecidos por las compañías telefónicas independientes. Es una medida de los efectos combinados de capacitancia e inductancia en corriente alterna. Es la variación que dicha oposición tiene con la frecuencia de la corriente. Su símbolo es X.
Rubber Heat, Rubber Moisture (Water): cables con aislamiento y cubierta de hules sintéticos para 75 °C en ambiente seco y 60 °C en húmedo, 600 volts.
Rubber Heat Moisture (Water): cables con aislamiento y cubierta de hules sintéticos para75 °C en ambiente seco y húmedo.
Styrene Butadiene Rubber: elastómero sintético a base de Estireno y Butadieno, empleado para aislamiento y cubierta de cordones flexibles, se conocía como GRS (Government Rubber Standard).
Shielded Mining Cable Single Conductor: cable monopolar flexible para minas con pantalla y cubierta para uso pesado. Shielded mining Cable with Ground Conductors: cable trifásico flexible para minas con pantalla. "D" significa que cada conductor de fase lleva pantalla y que el cable tres conductores para conexión a tierra. Ground Check: SHD con un conductor aislado para el circuito de comprobación de continuidad de conexión a tierra y dos conductores de tierra. Specific Inductive Capacity: inductancia capacitiva específica, constante dieléctrica de un material que es la relación que existe entre un condensador con el material como dieléctrico y el mismo condensador con aire como dieléctico.
Thermoplastic: SJ con aislamiento y cubierta termoplástica, 60 °C, 300 volts (90 y105 °C con aislamiento de PVC).
Construcción igual al SPT pero con conductores clase M.
Siglas en inglés para el sistema de transmisión óptica sincrono de EUA (Synchronous Optical NETwork)
Término empleado para denominar la tubería de PVC Subterránea.
SV con aislamiento y cubierta Termoplástica, 60 a 90 °C, 300 volts. SVT Oil Resistant: SVT con cubierta resistente al aceite, 60 °C.
TAGA sustituyendo la cubierta final de asbesto por una cinta de Teflón*.
Marca registrada de DuPont para el poli-tetraflouretileno, también denominado PTFE.
Cable para alta temperatura aislado con Teflón*, 250 °C. TF Flexible: TF pero con conductor flexible. Thermoplastic Fixture Flexible Nylon: TFN con conductor flexible. TF Nylon: TF con aislamiento de PVC y cubierta de nylon, 90 °C, 600 volts.
THW para 90 °C en ambientes secos y húmedos
Shielded Non-Metallic-Sheathed Cable: dos o más conductores aislados con un núcleo de material resistente a la humedad y retardante de la llama; sobre el conjunto lleva una pantalla a base de hilos y cintas; cubierta exterior de material no metálico resis
Service Cord Oil Resistant: cordón uso rudo para servicio pesado; aislamiento y cubierta elastomérica; la cubierta es resistente al aceite, hasta 90 °C, 600 volts.
Service Parallel Thermoplastic: cordón paralelo con aislamiento de PVC para servicio ligero, 60 °C, 300 volts. (90 y 105 °C con aislamiento de PVC). Hard Service Cord Thermoplastic: cable o cordón uso rudo para servicio pesado con aislamiento y cubierta termoplástica, 60 a 105 °C, 600 volts. Shielded Twisted Pair: cables multipares para datos, blindados con una cinta plástica aluminizada y una malla de hilos de cobre estañado.
Service Cord Vacuum Cleaner: cordón tipo uso rudo flexible para conexión de aspiradoras con aislamiento y cubierta elastomérica, 60 °C, 300 volts.SV con cubierta de neopreno.
Thermoplastic Asbestos: cable para alambrado de tableros con aislamiento termoplástico; carda de asbesto y trenza de algodón retardante a la llama, 90 °C, 600 volts (En desuso). Teflón*-Asbestos-G lass-Asbestos: conductor con aislamiento de Teflón trenza de asbesto, trenza de fibra de vidrio y malla de eabesto para circuitos de fuerza y control, 250 °C, 600 volts.
Power and Control Tray Cable: dos o más conductores aislados con o sin conductor de tierra y con una cubierta exterior de material no metálico, y aprobado para usarse en instalaciones en charolas, canalizaciones o soportado por un hilo mensajero.
Thermoplastic Fixture: alambre o cable de 7 hilos para alambrado de aparatos eléctricos , aislamiento de PVC, 60 °C, 600 volts.
Thermoplastic High Heat Nylon: alambre o cable con aislamiento de PVC y cubierta de nylon, 90 °C en ambiente seco, 600 volts. Thermoplastic High Heat Moisture (Water) Resistant: cable aislado con PVC para 90 °C en ambientes secos y 75 °C en húmedos, 600 volts. Thermoplastic Heat and Moisture (Water) Resistant: alambre o cable con aislamiento de PVC par a75 °C en ambientes secos o húmedos, 600 volts.
THW con cubierta de nylon, resistente a la humedad, aceites e hidrocarburos, 75 °C en ambientes húmedos, 600 volts. Tinsel Cord Parallel: dos conductores paralelos extraflexibles con aislamiento y cubierta elastomérica para uso ligero en dispositivos de hasta 50 watts.
Thermoplastic: TP pero con aislamiento y cubierta termoplásticos, 125 volts. Thermoplastic (or Thermoset) Insulation, Thermoplastic Jacket. Underground
Underground Distribution: cables para distribución subterránea, también conocidos como cables DS.
Ultra High Frequency: ultra alto frecuencia. Es la banda de 300 a 3000 MHz.
Fibras que tienen un núcleo pequeño que permite transmitir un solo haz luminoso llamado modo de propagación.
Underground Residential Distribution: cables de distribución residencial subterránea, también conocidos como DRS.
United States Standard Gauge: escala para calibres de lámina de acero. Unshielded Twisted Pair: cables multipares para datos, sin blindaje. Volt: unidad utilizada para denominar tensión eléctrica. Volt Ampere: unidad de potencia aparente para transformadores. 2.998x108 m/seg.
Very High Frecuency: extra alta frecuencia, 30 a 300 MHz.
Vertical Wire Flame Test: prueba de resistencia a la flama colocando el especimen en posición vertical.
XHHW para 90 °C en ambientes secos y húmedos.
Xmas Tree Cord: cordón paralelo, dos conductores aislados con PVC para series de árboles de navidad.
Thermoplastic Building Wire Moisture (Water) Resistant: alambre o cable aislado con PVC resistente a la humedad, 60 °C, 600 volts.
Underground Feeder: cable de uno o varios conductores con aislamiento y cubierta termoplástica para acometidas subterráneas en baja tensión.
Underwrites Laboratories, Inc.: institución (privada) dedicada al reconocimiento y aprobación de productos eléctricos y electrónicos, acorde a sus propias normas.
Underground Service Entrance: cable para acometidas subterráneas en baja tensión, aislamiento y cubiertas elastoméricas.
La velocidad de transmisión de la energía eléctrica en una longitud de cable comparado con la velocidad que tendrá en el aire. Se estima generalmente en porcentaje.
Es la unidad de tensión eléctrica: 1 Volt será la tensión eléctrica que causará que 1 ampere de corriente fluya a través de una resistencia de 1 Ohm.
Cables flexibles para minas: redondos o planos de uno o varios conductores con aislamiento y cubiertas elastoméricas para servicio extrapesado. Siglas en inglés para la multiplexación por división de longitud de onda. En estos sistemas se transmiten en forma simultánea varias longitudes de onda independientes. Cross (X)-Linked Polyethylene High Heat and Moisture (Water) Resistant: cable con aislamiento de polietileno de cadena cruzada, 90 °C ambiente seco y 75 °C en ambiente húmedo, 600 volts.
Cross (X)-Linked Polyethylene: polietileno de cadena cruzada, también conocida como polietileno vulcanizado o XLPE.
CÁLCULOS ELÉCTRICOS
Ing. FIDEL MORENO
Maracaibo - Venezuela