Arrange circuits, control and protection for general ...
Transcript of Arrange circuits, control and protection for general ...
Arrange circuits, control
and
protection
for
general electrical installations
Week 3: Prospective Fault Current and Short Circuit Temperature Rise
All writing in BLUE is examinable
All writing in RED is
NOT examinable.
Slide 2 of 41
Prospective Fault Current
To cover:
1) What is it?
2) How to calculate at terminals of Tx:
3) How to calculate at MSB:
4) How to calculate at DB:
Slide 3 of 41
FLI worst case, not enough I.PFC worst case, too much I. Both Ω’s law
Prospective Fault Currents (PFC) (also
known as prospective short-circuit current) is a calculation or measurement ofhow high thecurrent could be inthe event of ashort circuit.
Reference: 2.5.4AS/NZS 3000
Slide 4 of 41
When an arc is initiated, the live conductors are in close enough proximity to create sparking. The arc itself is caused by uncontrolled conduction of electrical current from phase to phase, or from phase to earth/neutral, and this ionises the surrounding air.
When conductive metal is vaporized, a pressure wave develops. A phase to phase, or phase to earth/neutral arc fault can escalate into a three phase arc within a millisecond. The heat energy and intense light produced at this stage is known as the arc flash.
Reference NHP Technical newsletter
Slide 5 of 41
The energy released as a transformer dissipates it’s magnetic field energy can cause enough heat to instantly vaporise copper.
(Heated so hot it bypassesthe liquid phase and goesstraight to a gas causinga fatal explosion)
Slide 6 of 41
Slide 7 of 41
H= I2 R t
The heat generated (in Joules) is to the square of the current times the resistance times the time it is there.
Double the current, quadruple the heating effect
Slide 8 of 41
If we put in adequately rated Circuit Breakers and/or Fault Current Limiters (HRC fuses) we can interrupt fault currents before the switchboards explodes
Slide 9 of 41
Common size CBs1.5 kA3 kA4.5 kA6 kA9 kA
A 6 kA breaker can interrupt faults up to 6000A
Cheap
Slide 10 of 41
The fault current must be interruptedhere before it is reaches it’s maximum.
Slide 11 of 41
3 Feb 2015 fatality in Western Australia
EnergySafety (WA) has imposed new safety precautions for the type of high-voltage (HV) switches involved in the 3 February Morley Galleria Shopping Centre explosion.
The HV oil-insulated combined-fuse switches produced by Long & Crawford Manchester must be completely disconnected from the electricity supply before any person may open the switch’s lid.
Announcing this today the Director of EnergySafety, Ken Bowron said that the Morley Galleria accident wasstark evidence of the inherent danger associated with these switches.”
Slide 12 of 41
Transformers (Tx) have a high PFC
As do batteries,however Solarpanels don’thave high PFCs
A commonIndustrial1 MVA Tx willlikely have a PFC close to 30 kA
Slide 13 of 41
A fault like 3000 10A welders
Slide 14 of 41
0.01Ω
400V0.02Ω
=20kA230V0.01Ω
=23kA
PFC is highest phase to Earth (when at close to the terminals of the transformer)
230V, 0.01Ω0.01Ω
0.01Ω400V, 0.02Ω
Slide 15 of 41
0.01Ω
400V0.04Ω
=10kA230V0.03Ω
=7.67kA
PFC is highest phase to phase (when far from the transformer)
230V, 0.03Ω0.01Ω
0.01Ω
400V,0.04Ω
0.01Ω
0.01Ω
0.01Ω
Slide 16 of 41
The PFC at at the terminals of a TX (I
PFCTX)
Can be calculated
(or measured live using a Fault Loop Impedance tester)
Slide 17 of 41
To calculate IPFCTX
The kVA rating, voltage and % impedance of the TX must be know.
Line current in a three phase system can be calculated using the formulaP = √3 V I (Using line V and I: P = √3 V
L I
L)
Slide 18 of 41
PT – Transformer kVA rating
VL – Line voltage (400 volts)
IL – Line current
PT=√3VLILPT
√3×VL=√3×VL×IL√3×VL
IL=PT
√3×VL
IL=250,000
√3×400V(250KVATX)
=360.85A
Slide 19 of 41
Transformer name plates are stamped with the % Impedance which was measured using the following test...
Slide 20 of 41
At 1%of 6.35 kV=63.5V=90.2 AAt 2%of 6.35kV=127.04V=180.4 AAt 3%of 6.35kV=190.5V=270.6 AAt 4%V6.35kV=254V=360.8A
This is a 4% impedance TX
Full line current
V ADead short in secondary with Ammeter
VariableVoltageSupply
Tx360.8 A per phase at 6.35KV−11kV phase−phase
VL=VP×√3
VP=VL√3
Slide 21 of 41
If a fault causes 360A to flow with only 4% of the voltage, what will 100% of the supply voltage cause?
360A×100%4%
=9kA
( 3600.04
=9kA)
Will also give you the same answer
IPFCTX=IL×100%% impTx
Slide 22 of 41
TXCM
PEN
MENP/E
MSBSM DB
Conductive pipes
Building Materials
Ground
The return path could be any number of parallel paths to earth
Slide 23 of 41
TXCM
0Ω
MSBSM DB
Therefore we take a conservative approach and say that the return path = 0Ω (Estimating a low resistance means we allow for more current and put in better circuit protection devices)
Slide 24 of 41
In the ACT:30,000A in commercial 10,000A in domestic 3Φ 6,000A in domestic 1Φ
SM – Sub mainCM – Consumer mainTX – transformerMSB – Main switch board
(Yet another application of ohms law)
ZTX=Volts (230V)
Perspective fault Current
IPFCMSB=V
ZTX+ZCM
IPFCDB=V
ZTX+ZCM+ZSM
Slide 25 of 41
CM MSB SM1 DB1
ZTX=230V30,000A IPFCMSB=
VZTX+ZCM
SM2
DB2
IPFCDB1=V
ZTX+ZCM+ZSM1
IPFCDB2=V
ZTX+ZCM+ZSM2
TX
Slide 26 of 41
TXMSB DB1
DB2
0.002 0.02
0.04
Example
ZTX=23030,000
=0.00767
IPFCMSB=230
(0.00767+0.002)=23.78KA
IPFCDB2=230
(0.00767+0.002+0.04)=4.63kA
IPFCDB1=230
(0.00767+0.002+0.02)=7.75kA
Slide 27 of 41
To find the values of Zcm, Zsm etc.Look up the value in Tables 34 to 39 AS/NZS 3008.
Slide 28 of 41
Use worst case assuming cold copper
Slide 29 of 41
Slide 30 of 41
ZCM=Table 34 0.00703Ω/kM÷1000×60m=0.0042Ω
Example:
What is the resistance of 60m of 300mm2 single core cable?
1) Look up value on Table 352) Divide by 1000 to change Ωs per km to Ωs per m.3) Times value by length
Slide 31 of 41
Select appropriately rated CB
If the calculatedPFC is 4.8kA, Select the next
size up.
A CB or Fuse that is rated to interrupt the maximum (prospective) fault current that could be present at the SWB.
1.5 kA3 kA4.5 kA6 kA9 kA
Slide 32 of 41
Cascading of CB’s may be used if the same brand of CB is installed upstream (at the MSB)
Slide 33 of 41
Example: With a 25 kA CB upstream 6kA breakers can have a rupturing capacity of 14kA
Slide 34 of 41
This is because both circuit breakers start to open together increasing the overall breaking capacity of the pair.
MSB DB
Short Circuit Temperature Rise (SCTR)
To cover:
1) What is it?
2) How to Select cables
Slide 35 of 41
SCTR is “Prospective Fault Current for cables”
All currents caused by a short-circuit shall be interrupted before the temperature of the conductors reaches the permissible limit. (Cables must withstand fault current)
(111 PVC) (143 XLPE)
I2 t<K2S2
Factor dependant on the material
Time CB to trip
CSA
“Let throughenergy”
“Energy the cable can withstand”
<
PFC
I2t is found off manufactures specifications
Reference 5.3 AS/NZS 3008
(111 PVC) (143 XLPE)
I2 t<K2S2
Factor dependant on the material
Time CB to trip
CSA
“Let throughenergy”
“Energy the cable can withstand”
<
PFC
I2t is found off manufactures specifications
Reference 5.3 AS/NZS 3008
Slide 38 of 41
Look up I2t
Slide 39 of 41
CSA
40kA2S
10kA
20A CB
Slide 40 of 41
Example X-90
Start 90° (table 1)Finish 250° (table 53)
K rating = 143 (table 52)
Look up k value using Tables 1, 53 and 52 AS/NZS 3008
Example V-90
Start 75° (table 1)Finish 160° (table 53)
K rating = 111 (table 52)
I2 t<K2S2
Will a 2.5mm2 cable withstand temperature rise when subjected to a 10kA fault and protected by a 20A CB?
40kA2S(specs)
111(V-90)
2.5mm2
(CSA)
40k<111x 2.5
40k<77k
YES