Alnahdah Earthing
-
Upload
jmmankavil6230 -
Category
Documents
-
view
11 -
download
0
description
Transcript of Alnahdah Earthing
LARSEN & TOUBRO LIMITEDECC Division - EDRC (Electrical)
PROJECT: Relocation of Riyam Substation and Transformer REF NO: PAGE 02 OF 06Repair Shop. PREPARED CHECKED APPROVED DATE
TITLE: EARTHING DESIGN CALCULATION FOR SSJ AKS DM 3-03-2016
THIS DESIGN IS GENERALLY BASED ON IEEE 80 - 2000AREA OF CROSS SECTION
S = I x SQRT(t) / k
S = AREA OF CONDUCTOR IN Sq.mm
I = EARTH FAULT CURRENT IN AMPS
t = EARTH FAULT CLEARING TIME IN secs.
k = SQRT(( Qc x (B+20)/delta20) x ln ( 1+ (Qf-Qi)/(B+Qi)))
I = 25000 amps
t = 3 sec
Qc = 0.00345 J / °C mm3 { Data for copper conductor }
B = 234.5 °C
delta20 = 0.000020 Ohm.mm
Qi = 40 °C
Qf = 700 °C
k = SQRT( (0.00345x (234.5 + 20) /0.00002) x ln ( 1+ ((700-40 ) / (235 +40) ) )= 231.909
S = 25000 x SQRT (3.0) / 231.909= 186.72 Sq.mm
Corrosion allowance considered for the conductor in percentage = 10 %
Minimum area of cross-section required = ### Sq.mmHence conductor size selected is, 300 Sq.mm (Which is the minimum size specified in the specification)
CONDUCTOR SIZE CHOSEN IS 50 x 6 Copper Flat
S/S - Riyam
Qc = Volumetric Heat capacity of conductor ( J / oC mm3 )
B = Reciprocal of Temp.Coefft. of Resistivity ( oC )
delta20 = Electrical Resistivity of conductor at 20 oC ( Ohm.mm )
Qi = Initial Temperature of Conductor ( oC )
Qf = Final Temperature of Conductor ( oC )
1 10.01.07 FOR APPROVAL AKS AKS
0 FOR APPROVAL AKS AKS
No. DATE REMARKS CHKD APPD
REVISION
PROJECT : MADINAT AL NAHDAH PRIMARY S/S 33/11.5kV SIGN DATE
DSND SSJ 10.01.07
PACKAGE : DRWN - -
CHKD AKS 10.01.07
TITLE : SCALE APPD AKS 10.01.07
EARTHING DESIGN CALCULATION - MAIN GRID DRG.No. REV.
CODE1
LARSEN & TOUBRO LIMITEDECC - Division EDRC
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
PROJECT: MADINAT AL NAHDAH PRIMARY S/S 33/11.5kV REF NO: PAGE 01 OF 04PREPARED CHECKED APPROVED DATE
TITLE: EARTHING DESIGN CALCULATION - MAIN GRID SSJ AKS AKS 3-03-2016
CALCULATIONS ARE BASED ON IEEE 80 - 2000.DESIGN DATASystem Voltage = 33 kV
System Grounding = SOLID
Soil Resistivity p = 52.1 Ohm.m
Top Layer resistivity ps = 5000 Ohm.m
Max. Earth Fault Current (I) = 2000 AMPS
Conductor Size = 50 x 6 Copper Flat
Equivalent diameter d = 0.0195 m
Length of Substation L = 34.93 m
Breadth of Substation B = 34.93 m
No: of grids in X direction = 2
No: of grids in Y direction = 2
Equivalent Number of grids N=na*nb*nc*nd = 2
factor na = 2*Lc/Lp na = 2.000 factor nb= Sqrt(Lp/4/sqrt(A)) nb = 1.000 factor nc = (Lx*Ly/A)*e(0.7*A/Lx/Ly) nc = 1.000 factor nd = Dm / sqrt(Lx^2+Ly^2) nd = 1.000
Spacing of conductors D = 29 m
Total length of conductors Lc = 140 m
Peripheral length of the grid in mtr Lp = 139.72 m
Area of Grid Ag = ### sq.m
Depth of burial h = 0.6 m (As per specification)
Depth of Top Layer hs = 0.1 m
Total No of electrodes m = 14 Nos
Length of electrode Lr = 3 m
= 42 m
Maximum length of Lx = 34.93 mgrid conductor in X-Direction
Maximum length of Ly = 34.93 mgrid conductor in Y-Direction
Dm is the max distance bet any two points in = 49.40 i.e. Sqrt (34.93^2+34.93^2)the grid in mtr
Diameter of electrodes d1 = 15 mm
Duration of Fault Current ts = 1 sec
Total length of electrodes LR
LARSEN & TOUBRO LIMITED
ECC Division - EDRC (Electrical)
PROJECT: MADINAT AL NAHDAH PRIMARY S/S 33/11.5kV REF NO: LTO/193/SSSRM/0005 PAGE 01 OF 04PREPARED CHECKED APPROVED DATE
TITLE: EARTHING DESIGN CALCULATION - MAIN GRID SSJ AKS AKS 3-03-2016
Tolerable Touch Potential (BASED ON IEEE 80 - 2000 CHAPTER 8)
Etouch = ( 1000 + 1.5 * Cs * ps ) * 0.116 / SQRT(ts) For body weight of 50 kg
Cs = 1 - a * { ( 1- p/ps) / ( 2 * hs + a) } Refer Equation-27 of page 23 of IEEE 80 - 2000a = 0.09 m
1 - 0.090*{( 1 - 52 / 5000 ) / ( 2 * 0.10 + 0.090 ) }Cs = 0.6929
Etouch = (1000 + 1.5 * 0.6929 * 5000 ) * 0.116 / SQRT( 1.0 )= 718.81 Volts
Tolerable Step Potential (BASED ON IEEE 80 - 2000 CHAPTER 8)
Estep = ( 1000 + 6.0 *Cs * ps ) * 0.116 / SQRT(ts) For body weight of 50 kgEstep = (1000 + 6.0 * 0.6929 * 5000 ) * 0.116 / SQRT( 1.0 ) = 2527.25 Volts
Mesh Potential Attainable (BASED ON IEEE 80 - 2000 CHAPTER 16)Refer Equation-91 of page 94 of IEEE 80 - 2000
Emesh = ( p * Km * Ki * I ) / (Lc + Lr)
Km =
Kii = 1.00 for grids with ground rods in perimeter
Kh = SQRT ( 1+ h/ho)ho = 1.00 m ( reference depth of grid)Kh = SQRT( 1 + 0.600 / 1.0 ) = 1.2649
Km = 1/ (2 * 22/7) * { ln [ 29.0^2/ (16 * 0.600 * 0.02 ) + (29.0 + 2 * 0.600 ) ^2 /( 8 * 29.0 * 0.02) - 0.600/ ( 4 * 0.02) ] + 1.00 / 1.2649 * ln [ 8 / (22/7 * (2 * 2.00 - 1 ) ) ] }
= 1.3237Ki = 0.644 + 0.148 * n = 0.644 + 0.148 *2
= 0.9400Emesh = 26*0.4421*2.5680*22500 / (800+56)
= 713.49 Volts
Step Potential Attainable (BASED ON IEEE 80 - 2000 CHAPTER 16)
Estep = ( p * Ks * Ki * I ) / ( 0.75*Lc + 0.85*m*Lr )
Ks =
n = 2 (Higher of the no.of grids in X & Y direction)Ks = ( 1 / 22/7 ) * { 1 / (2 * 0.600 ) + 1 / ( 29.0 + 0.600 ) + 1 / 29.0 * ( 1 - 0.5^(2 - 2 ) }
= 0.2759 Estep = ( 52 * 0.2759 * 0.9400 * 2000 ) / ( 0.75 * 139.7 + 0.85 * 14 *3 )
= 192.35 Volts
1/ (2 * ) * { ln[ D^2 /(16 * h * d)+ (D + 2h ) ^2 / (8* D * d) - h / (4 * d) ]
+ Kii / Kh ln[8 / ( * (2 * n-1) ) ] }
1 / * { 1 / (2 * h) + 1 / (D + h) + 1 / D * (1- 0.5^(n-2) ) }
LARSEN & TOUBRO LIMITEDECC Division - EDRC (Electrical)
PROJECT: MADINAT ALMADINAT AL NAHDAH PRIMARY S/S 33/11.5kV REF NO: LTO/193/SSSRM/0005 PAGE 01 OF 04PREPARED CHECKED APPROVED DATE
TITLE: EARTHING DESIGN CALCULATION - MAIN GRID SSJ AKS AKS 3-03-2016
Comparison of Tolerable Etouch & Estep and Attainable Emesh & Estep
Tolerable Etouch = 718.81 Volts
Tolerable Estep = 2527.25 Volts
Attainable Emesh = 713.49 Volts
Attainable Estep = 192.35 Volts
Since Attainable Emesh is less than Tolerable Etouch andAttainable Estep is less than Tolerable Estep, the design is safe.
The minimum conductor to be buried in ground for meeting the Touch and Step potential can be calculated as follows:
Emesh(tolerable) = ( p * Km * Ki * Ig ) / ( Lc + Lr )
( Lc + Lr ) = ( p * Km * Ki * Ig ) / Emesh(tolerable)
= (52.1 * 1.3237 * 0.9400 * 2000.000 ) / 718.813= 180.37 Mtr
Estep(tolerable) = ( p * Ks * Ki * Ig ) / ( 0.75*Lc + 0.85*Lr )
(0.75 * Lc+0.85* Lr ) ( p * Ks * Ki * Ig ) / Estep(tolerable)
= (52.1 * 0.2759 * 0.9400 * 2000.000 ) / 2527.254
= 10.69 Mtr**
Actual conductor buried is 281m which greater than the minimum required length Hence the design is safe
LARSEN & TOUBRO LIMITEDECC Division - EDRC (Electrical)
PROJECT: MADINAT AL NAHDAH PRIMARY S/S 33/11.5kV REF NO: LTO/193/SSSRM/0005 PAGE 01 OF 04PREPARED CHECKED APPROVED DATE
TITLE: EARTHING DESIGN CALCULATION - MAIN GRID SSJ AKS AKS 3-03-2016
CACULATION OF GROUNDING RESISTANCE
BASED ON IEEE 80-2000 CHAPTER 14
RESISTANCE OF GROUND RODS
Re =
K1 = 1.37 Refer Fig 25A page 67 IEEE 80 - 2000Re = 52 / (2 * 14 * 22/7 * 3 ) * [ ln (8 * 3 / 15 / 1000 )) - 1 + 2 * 1.37 *
(3 / sqrt(1220)) * (sqrt (14)-1)^2 ] = 2.6983 Ohms
RESISTANCE OF GROUND GRIDRs =
K1 = 1.37
K2 = 5.7 Refer Fig 25B page 67 IEEE 80 - 2000h' = SQRT(d * h)
= SQRT(0.02 * 0.60) = 0.1083 Rs = ( 52 / (22/7 * 139.72)) * [ ln ( 2 * 139.72 / 0.1083 ) + 1.37 *
( 139.72 / sqrt (1220.10 )) - 5.7 ] = 0.9119 Ohms
MUTUAL RESISTANCE BETWEEN GROUND GRID AND GROUND RODSRse =
K1 = 1.37
K2 = 5.7Rse = 52 / (22/7 * 139.72) * [ln (2 * 139.72 / 3 ) + 1.37 *
( 139.72 / sqrt (1220.10 )) - 5.7 + 1] = 0.63644 Ohms
COMBINED RESISTANCE OF GROUND GRID AND GROUND RODS
Rg = (Re * Rs - Rse^2 ) / ( Re + Rs - 2 * Rse)Rg = ( 2.6983 * 0.9119 - 0.6364^2 ) / ( ( 2.6983 * 0.9119 - 2 * 0.6364 )
= 0.8794 Ohms
CONCLUSIONHence the design adopted meets the specification requirement with respect to i) STEP & TOUCH POTENTIALii) COMBINED RESISTANCE OF GRID & GROUND RODS < 1.0 OHM
NOTEThe conductors shall be uniformly distributed in substation area leaving the space for Building.
Earth mat conductor as per above calculation shall be laid in s/s around the building adopting the calculated
spacing.
p / (2 * m * * l ) * [ln (8 * l / d) - 1 + 2 * K1 * l / SQRT(A) * (SQRT(m)-1)^2 ]
p / ( * Lc) * [ ln (2 * Lc / h') + K1 *( Lc / SQRT(A)) - K2 ]
p /( * Lc) * [ln (2 * Lc / l) + K1 * (Lc / SQRT(A)) - K2 + 1]
LARSEN & TOUBRO LIMITEDECC Division - EDRC (Electrical)
PROJECT: MADINAT AL NAHDAH PRIMARY S/S 33/11.5kV REF NO:PREPARED CHECKED APPROVED DATE
TITLE: SSJ AKS AKS 3-03-2016S/S -CONDUCTOR SIZING
THIS DESIGN IS GENERALLY BASED ON IEEE 80 - 2000AREA OF CROSS SECTION
S = I x SQRT(t) / k
S = AREA OF CONDUCTOR IN Sq.mm
I = EARTH FAULT CURRENT IN AMPS
t = EARTH FAULT CLEARING TIME IN secs.
k = SQRT(( Qc x (B+20)/delta20) x ln ( 1+ (Qf-Qi)/(B+Qi)))
I = 25000 amps
t = 3 sec
Qc = 0.00345 J / °C mm3 { Data for copper conductor }
B = 234.5 °C
delta20 = 0.000020 Ohm.mm
Qi = 40 °C
Qf = 700 °C
k = SQRT( (0.00345x (234.5 + 20) /0.00002) x ln ( 1+ ((700-40 ) / (235 +40) ) )= 231.909
S = 25000 x SQRT (3.0) / 231.909= 186.72 Sq.mm
Corrosion allowance considered for the conductor in percentage = 20 %
Minimum area of cross-section required = ### Sq.mmHence conductor size selected is, 300 Sq.mm (Which is the minimum size specified in the specification)
CONDUCTOR SIZE CHOSEN IS 50 x 6 Copper Flat
Qc = Volumetric Heat capacity of conductor ( J / oC mm3 )
B = Reciprocal of Temp.Coefft. of Resistivity ( oC )
delta20 = Electrical Resistivity of conductor at 20 oC ( Ohm.mm )
Qi = Initial Temperature of Conductor ( oC )
Qf = Final Temperature of Conductor ( oC )
307124533.xls Page No. 8 of 10
LARSEN & TOUBRO LIMITEDECC DIVISION-EDRC(ELECTRICAL)
CONSTRUCTION GROUP
PROJECT: Construction of 2x20 MVA, 33/11kV ALNAHDAH Primary S/S & 33kV LineCLIENT: Muscat Electricity Distribution CompanyCONSULTANT: Energoprojekt - Entel LLC
TITLE: PREPARED CHECKED APPROVED DATE
DOCUMENT NO: SSJ AKS AKS 22.12.06
Direction
East 68.90 N 46.83
. E 68.90
North 46.83 S ###
. W 42.31
West 42.31
.
South 105.98
.
Area of the polygon = 8497Radius of eqv. Circle 52.01
52.01 ohm-m
Remarks:
2. Calculations are based on IS:3043
3. Formula used is
where s - distance b/w spikesd - depth of the spiker - earth resistance
Avg. Resistivity (Ohm-
m)
Avg. Soil Resistivity =
The lowest resistivity outcome in all the samples is 35.18 ohm-meter in the West direction. Hence corrosion allowance of 15 % to be considered as Per CBAP guidelines.
1. Polygon drawn for the average Resistivity values available in N,E,W,S directions. Resultant Resistivity is calculated as the equivalent radius of the polygon area.
Re sistivity={2∗Π∗s∗r if ( d<s /20)
4∗Π∗s∗r
1+{(2∗s
√( s∗s )+(4∗d∗d ))−(s √(s∗s )+(d∗d ))} if (d≥s /20 )
0.00
100.00
200.00
46.83
68.90
105.98
42.31
307124533.xls Page No. 9 of 10
LARSEN & TOUBRO LIMITEDECC DIVISION-EDRC(ELECTRICAL)
CONSTRUCTION GROUP
PROJECT: Construction of 2x20 MVA, 33/11kV ALNAHDAH Primary S/S & 33kV LineCLIENT: Muscat Electricity Distribution CompanyCONSULTANT: Energoprojekt - Entel LLC
TITLE: PREPARED CHECKED APPROVED DATE
DOCUMENT NO: SSJ AKS AKS 22.12.06
0.00
100.00
200.00
46.83
68.90
105.98
42.31
307124533.xls Page No. 10 of 10
LARSEN & TOUBRO LIMITEDECC DIVISION-EDRC(ELECTRICAL)
CONSTRUCTION GROUP
PROJECT: Construction of 2x20 MVA, 33/11kV ALNAHDAH Primary S/S & 33kV LineCLIENT: Muscat Electricity Distribution CompanyCONSULTANT: Energoprojekt - Entel LLC
TITLE: PREPARED CHECKED APPROVED DATE
DOCUMENT NO. SSJ AKS AKS 22.12.06
Sl No. Direction Remarks
2 250 2.2 55.29 68.9 East5 250 0.97 60.95
10 250 0.72 90.48
2 250 2.14 53.78 46.83 North5 250 0.64 40.21
10 250 0.37 46.49
2 250 2 50.27 42.31 West5 250 0.66 41.47
10 250 0.28 35.18
2 250 3.7 92.99 105.98 South5 250 1.64 103.04
10 250 0.97 121.89
Distance between spikes
Depth of Spike (m)
Earth resistance
()
Earth resistivity
(-m)
Average Value (-m)