    ALD24VAV-LONVAV room controller with display

    Two 0...10 V outputs, LON-communication

    ALD24VAV-LON is a controller for zone control of VAV and heating with LON Works communication

    Setpoint 0…30°C• Internal or external sensor• Setpoint offset +/- 3K• 0...10 V outputs for VAV-control and heating

    • Input for occupancy control• Input for CO2 sensor• Input for external 0…10 V transferred to LON net

    • LON Mark profile 8502 network variables

    Function

    ALD24VAV-LON is a room controller for wall mounting. It hasbuilt-in temperature sensor and two 0…10 V outputs for controlsignal to VAV-controller and heating valve actuator. Thecontroller has adjustable P- and I-time and input for occupancycontrol and CO2-sensor. There is also an extra 0…10 V inputthat is transfered as a network variable to the LON Worksnetwork. Settings are made using the menu system in thedisplay or by the LON Works network. Actual temperature andoutput levels are shown continuously in the display. All settingsare also possible to shift via the LON network.

    SensorsThe controller has built-in sensor. Alternatively external sensor(Regin NTC 0…30°C) can be used. In this mode the jumperexternal/internal inside is reset. It is also possible to sendtemperature sensor value to the controller via the LON network.

    SetpointIs set in the setting-level menu. The controller uses heatingsetpoint and cooling (VAV) setpoint. The settings are factoryset to 21°C or 23°C. If occupancy control is used there aredifferent setpoints in different states.

    Setpoint offsetBy pressing [+] or [-] button on the front individual setpointadjustments can easily be made, without entering the settinglevel of the menu system (settable +/- 3K in 0.5 steps).

    Heating outputIs possible to activate/deactivate via the menu system.

    VAV outputFor connection to a damper actuator or VAV-damper controllerfor 0…10 V input. Minimum and maximum air volume can be set

    in the VAV-damper controller. Minimum limit can also be set viaLON Works network.

    Occupancy controlThe controller has an input for closing contact from the

    occupancy detector or similar device. When presence isdetermined the controller runs with comfort setpoint for heatingrespectively VAV(cooling). If presence is not detected, thecontroller works in unoccupied mode, with reduced setpoint forheating and raised setpoint for cooling.

    Via the LON network it is possible to control the occupancystatus in three states: Occupied• Unoccupied• Energy hold-off

    Energy hold-offVia LON network it is possible to set the controller in energy-hold-off mode. Both outputs are set to zero and the roomtemperature is allowed to decrease to frost level (10 degrees)or increase to 30 degrees. Below 10°C the heating output is

    activated and above 30°C the cooling output is activated.

    CO2  sensor inputALD24VAV-LON also has an input for 0…10 V signal from CO2-sensor. When the CO2 level exceeds a preset level (factorysetting 800 ppm) the VAV output signal is forced to increase, inorder to increase the air volume to the room. The CO2-levelsetpoint can be changed via the display.

    Display and menu systemTo access the menu settings, do as follows:

    Press buttons [< ] and [>] continously for five seconds.The display shows the current software version. Then pressbutton [–] three times, the controller enters setting level andgives access to setpoints, control parameters etc.To send a service-pin message over the LON-network, the

    buttons [>] and [-] are held down followed by a press on the [-]button. The display shows ”lon”. If a wink message is received,the display blinks between showing ”lon” and showing ”—” for10 seconds to indicate the physical location of the device. Seeoverleaf.

  • 8/20/2019 Ald24vav Lon Gb

    2/2AB Regin Telefon: +46 31 720 02 20

    Technical data

    Wiring and dimensions

    Supply voltage 24 V AC +/- 15% 50-60 HzPower consumption 4 VAAmbient temp 0…50°C (working range built-in sensor 0…30°C)Storage temp –40...+50°CAmbient humidity Max 90% RHProtection class IP20

    This product confirms with the requirements of European EMC standardsCENELEC EN50081-1 and EN50082-1 and carries the CE-mark

    InputsExternal sensor 0…30°C (NTC sensor)Occupancy Closing contact from i.e. presence detector IR24-PExternal 0…10 V Can be used to transfer the VAV position to the LON works networkCO2 sensor 0…10 V corresponding to 0…2000 ppm CO2-level

    OutputsControl (output) signal Two, 0…10 V DC, 1 mACommunication LON Works, electrical interface FT 3120

    Network variable interface according to LON Mark profile 8502See separate specification: LON Interface description.

    Settings  (menu) Factory settings (rangeability 0...30°C)Temperature 21°C, Heating setpoint

    24°C, VAV (cooling) setpointAt occupancy control Heating setpoint comfort 21°C

    VAV(cooling) setpoint comfort 23°CHeating setpoint unoccupied 16°CVAV(cooling) setpoint unoccupied 28°C

    P-band 0.5…99.9 K (5 K)I-time 0…999 s (0 means integration function not active)Calibration (temp. sensor) +/- 3 K (internal or external sensor)Occupancy function Active or inactive (Factory setting: Unactivated)Heating output Active or inactive (Factory setting: Unactivated)Jumper BY1 Right= Internal sensor (factory setting)

    Left= External sensor

    Network variables File: network_variables_ALD24VAV-LON... (file can be reqired from regin by mail or from our web site)

    • Bargraph for heating and cooling (VAV) output

    • Occupancy control,Person in room (the frame) means occupiedPerson out of room means unoccupied

    • Actual temperature is displayed in 0.1°C steps

    Display

    86 mm

    115 mm

    Depth: 27 mm

    1 Supply voltage 24 V AC2 System voltage neutral 24 V AC3 Output 0…10 V, (heating)4 Signal neutral5 Output 0…10 V, VAV (cooling)6 Signal neutral7 External sensor8 Occupancy control input

    9 Input 0…10 V external signal10 Signal neutral11 Input 0…10 V CO2-sensor12 Signal neutral13 LON net B14 LON net A15 Protective earth