6RMI0-02A
Inverter SingleWall Mounted
(60Hz/R410A)
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
2/48
1Inverter Single
1. Models line up.........................................................................................5
2. Specifications .........................................................................................8
3. Dimensional drawings .........................................................................10
4. Wiring diagrams ...................................................................................18
5. Refrigerant cycle diagram ...................................................................23
6. Capacity tables .....................................................................................27
7. Capacity coefficient factor...................................................................32
8. Operation range....................................................................................35
9. Air flow and temperature distributions(reference data)....................36
10. Sound level .........................................................................................38
11. Remote controller ...............................................................................41
12. Installation...........................................................................................44
Inverter Single-60Hz(R410A)
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
3/48
6RMI0-02A
2 Inverter Single
Publication historyPlb.No Outdoor Units Notes Publication in
6RMI0-02A All models Added New models July.2010
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
4/48
6RMI0-02A
3 Inverter Single
Test condition of international standard CLASSIFICATION KSC ISO ARI AHAM AS SSA 9306 5151 210/240 1861.1 385
Indoor
DBC(F) 27.0 27.0 26.7(80) 26.7(80) 27.0 29.0
Cooling WBC(F) 19.5 19.0 19.4(67) 19.4(67) 19.0 19.0
Capacity Outdoor DBC(F) 35.0 35.0 35.0(95) 35.0(95) 35.0 46.0 WBC(F) 24.0 24.0 23.9(75) 23.9(75) 24.0 24.0
Indoor
DBC(F) 20.0 20.0 21.1(70) 21.1(70) 21.0 21.0
Heating WBC(F) 15.0 15.0 15.6(60) 15.6(60) 15.0 15.5
CapacityOutdoor
DBC(F) 7.0 7.0 8.3(47) 8.3(47) 7.0 7.0
WBC(F) 6.0 6.0 6.1(43) 6.1(43) 6.0 6.0
Indoor
DBC(F) 32.0 32.0 26.7(80) 32.2(90) 32.0 29.0Maximum
WBC(F) 23.0 23.0 19.4(67) 22.8(73) 23.0 19.0Cooling
Outdoor DBC(F) 43.0 43.0 46.1(115) 43.3(110) 43.0 54.0
Operating WBC(F) 26.0 26.0 23.9(75) 25.6(78) 26.0 24.0
Indoor
DBC(F) 27.0 27.0 26.7(80) 26.7(80) - -Maximum
WBC(F) 19.0 19.0 19.4(67) 22.8(73) - -Heating
Outdoor
DBC(F) 21.0 24.0 23.9(75) 23.9(75) - -Operating
WBC(F) 15.0 18.0 18.3(65) 18.3(65) - -
EnclosureIndoor
DBC(F) 27.0 27.0 26.7(80) 26.7(80) 27.0 27.0
Sweat / WBC(F) 24.0 24.0 23.9(75) 23.9(75) 24.0 24.0
CondensateOutdoor
DBC(F) 27.0 27.0 26.7(80) 26.7(80) 27.0 27.0
Disposal WBC(F) 24.0 24.0 23.9(75) 23.9(75) 24.0 24.0
Freeze-up/ Indoor DBC(F) 21.0 21.0 19.4(67) 21.1(70) 21.0 21.0
Low WBC(F) 15.0 15.0 13.9(57) 15.6(60) 16.0 16.0
Temperature
Outdoor DBC(F) 21.0 21.0 19.4(67) 21.1(70) 21.0 21.0
WBC(F) 15.0 15.0 13.9(57) 15.6(60) 16.0 16.0
KS : Korea Standard AS : Australia StandardISO : International Standard Organization SSA : Saudi Arabian StandardARI : Airconditioning and Refrigeration Institute
AHAM : Association of Home Appliance Manufacturers
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
5/48
6RMI0-02A
4 Inverter Single
General Description
Split type of Air conditioners are known by the category name of Wall Mounted Type of units.These units canbe easily installed in a small space and have exceptional Cooling capacity.Designed for Low-noise operation,itensures a pleasant air conditioned environment.
LG Offers various types of units to its customers to suit for the best application and requirement.The following
are the important categories offered by LG :1) General Wall Mounted Type Units : Units with Simplicity in design.
2) Art Cool Units : A new concept of cooling introduced by LG in the field of Air Conditioning.
3) Inverter Units : These units are capable of minimising the Power consumption with the unique invertertechnology.
Some of the Important Features of these units are listed below :
1) Providing Health to the Customers : By having Filters such as Plasma Filter which is capable of removing theMicro Organisms up to 0.1 microns.
2) Long Term Money Saving : By providing the Features such as Gold Fin, Auto Clean etc. to maintain the
same performance for years.3) Best Comfort : With Features such as Sleep Mode,Timer,Auto Restart etc.
The Units are available with many standard and optional features which give our Customers the choice toselect the unit of their own desire.For details refer to the detailed specification followed after this description.
LG Electronics Inc.Air Conditioning Company
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
6/48
6RMI0-02A
5 Inverter Single
Models line up
1. Models Line up
1.1 Indoor Unit
Indoor Unit Type Capacity[kW(kBtu/h)] Model name
C/O
2.63(9) ASNQ093B1U0 (VA093CL.NB0)
3.51(12) ASNQ123B1U0 (VA123CL.NB0)
5.27(18) ASNQ183C2U0 (VA183CL.NB0)
7.03(24) ASNQ243C2U0 (VA243CL.NB0)
H/P
2.63(9) ASNW093ERH0
3.51(12) ASNW123ERH0
5.27(18) ASNW1838RH0
7.03(24) ASNW2438RH0
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
7/48
6RMI0-02A
6 Inverter Single
1.2 Outdoor UnitHeat pump ASUQ093B1U0 (VA093CL.UB0) ASUQ123B1U0 (VA123CL.UB0)
Total capacity index of connectable kW 2.63 3.51 indoor units kBtu/h 9 12 Power supply 220V, 60Hz
Chassis
Heat pump ASUW093ERH0 ASUW123ERH0
Total capacity index of connectable kW 2.63 3.51 indoor units kBtu/h 9 12 Power supply 220V, 60Hz
Chassis
Heat pump ASUQ183C2U0 (VA183CL.UB0) ASUQ243C2U0 (VA243CL.UB0)
Total capacity index of connectable kW 5.27 7.03 indoor units kBtu/h 18 24 Power supply 220V, 60Hz
Chassis
Models line up
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
8/48
6RMI0-02A
7 Inverter Single
Heat pump ASUW1838RH0 ASUW2438RH0
Total capacity index of connectable kW 5.27 7.03 indoor units kBtu/h 18 24 Power supply 220V, 60Hz
Chassis
Models line up
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
9/48
6RMI0-02A
8 Inverter Single
Specifications
2. SpecificationsLibero Inverter (C/O)
Note : O : Applie, X : Not applied, : No relation Filters are optional in some specific areas. For Circuit Breaker Rating, please conform to local standards whenever necessary.
Sales Model VA093CL VA123CL VA183CL VA243CLModels Unit AS-Q093B1U0 AS-Q123B1U0 AS-Q183C2U0 AS-Q243C2U0
Cooling CapacitykW 0.89~2.64~3.70 0.89~3.23~4.30 0.90~5.28~5.715 0.88 ~ 7.03 ~ 8.56
Btu/h. 3,070~9,000~12,620 3,070~11,000~14,660 3,070~18,000~19,500 3,000~24,000~29,200
Heating CapacitykW NA - -
Btu/h. - -Power Input Cooling/Heating W 681 840 1510 2300
Running Current Cooling/Heating A 3.1 4.0 6.6 10.3Starting Current Cooling/Heating A 3.1 4.0 6.6 10.3
EERW/W 4.1 3.85 3.49 3.04
Btu/h.W 13.2 13.1 11.9 10.4SEER 16.4 19.6 17 16.3HSPF - -Power Supply / V / Hz 1/220/60 1/220/60 1/220/60 1/220/60Power Factor % 94.7 97.1 99.4 99.4
Air Flow Rate Indoor,Maxm3/min(CFM) 11.0(388) 11.0(388) 19.5(689) 21(741)
Outdoor,Max m3/min(CFM) 27.0(953) 33(1,165) 60(2,119) 58(2,048)Moisture Removal l/h. 1.1 1.3 1.9 2.7
Sound Level Indoor,H/M/LdB(A)3 39 / 33 / 24 / 19 39 / 33 / 24 / 19 42 / 38 / 34 / 30 45 / 40 / 35 / 29
Outdoor,Max dB(A)3 47 47 53 53Refrigerant & Charge (at 7.5 m) g(oz) R410A, 900(25.5) R410A, 950 (33.5) R410A, 1,350(47.62) R410A, 1,800(63.5)Additional Refrigerant charge g/m(oz/ft) 20(0.22) 20(0.22) 20(0.21) 35(0.38)
Compressor
Type Rotary Rotary Twin Rotary Twin RotaryModel GA102DBA GA102DBA GKT141DAA GJT240DAAMotor Type Brushless DC Motor Brushless DC Motor Brushless DC Motor Brushless DC MotorOil Type PVE(FVC68D) FVC68D FVC68D PVE(FVD68C)
Oil Charge cc 310 310 570 900O.L.P. name - - - -
Fan(Indoor) TypeCross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan
Motor Output W 20 20 30 76.1
Fan(Outdoor)Type Propeller Propeller Propeller PropellerMotor Type BLDC BLDC AC ACMotor Output W 43 43 61/75 (50/60Hz) 150
Circuit Breaker* A 15 15 20 30Power Supply Cable No.*mm2 3*1.0 3*1.0 3*1.5 3*2.5Power and Transmission Cable No.*mm2 No.*mm2 4*1.0 (Including Earth) 4*1.0 (Including Earth) 4*1.5 (Including Earth) 4*2.5 (Including Earth)
Piping Connections Liquid Sidemm(in) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8)
Gas Side mm(in) 9.52(3/8) 9.52(3/8) 12.70(1/2) 15.88(5/8)Drain Hose(O.D / I.D.) mm(in) 21.5 / 16.0(0.85 / 0.63) 21.5 / 16.0(0.85 / 0.63) 21.5 / 16.0(0.85 / 0.63) 21.5 / 16.0(0.85 / 0.63)
DimensionsIndoor (W*H*D)
mm 895*285*195 895*285*195 1,030*325*250 1,030*325*250inch 35.2*11.2*7.7 35.2*11.2*7.7 40.6*12.8*9.84 40.6*12.8*9.84
Outdoor (W*H*D)mm 717*483*230 770*545*245 870*655*320 870*800*320inch 28.2*19.0*9.1 30.3*21.5*9.6 34.3*25.79*12.6 34.3*31.5*12.6
Net Weight Indoorkg(lbs) 11(24.5) 11(24.5) 17(37.5) 17(37.5)
Outdoor kg(lbs) 28(61.7) 30(66.1) 46(101.4) 60(132.3)
Gross Weight Indoorkg(lbs) 13.5(29.7) 13.5(29.7) 19(41.9) 19(41.9)
Outdoor kg(lbs) 30(66.1) 33(72.8) 53(116.8) 64(141.1)
Operation Range Cooling(Outdoor)C 10~48(50~118.4) 10~48(14~118.4) 10~48(50~118.4) 10~48(50~118.4)
Heating(Outdoor) C - - - -Piping Length (Min/Max) m(ft) 7.5(24.6) / 15(49.2) 7.5(24.6) / 15(49.2) 5 / 20(65.6) 7.5(24.6) / 30(98.4)Chargeless m(ft) - - 5~7.5 -Max. Elevation Difference m(ft) 7(23) 7(23) 15(49.2) 15(49.2)Tool Code(Chassis) Indoor + Outdoor SB + UA3 SB + UL SC + UE SC + UE1+
Functions
Temperature Control Thermistor Thermistor Thermistor ThermistorAllergy free filter O O O OPlasma Filter O O O OPrefilter(washable/anti-fungus) O O O OAuto Clean O O O OCHAOS Wind(Auto Wind) O O O OSteps, Fan/Cool/Heat 5/6/- 5/6/- 5/6/- 5/6/-Airflow Direction Control(up& Down) Auto Auto Auto AutoAirflow Direction Control(left & right) Auto Auto Auto AutoRemote Controller Type Wireless LCD(EZ-Remocon) Wireless LCD(EZ-Remocon) Wireless LCD(EZ-Remocon) Wireless LCD(EZ-Remocon)Setting TemperatureRange
Cooling 18C ~ 30C 18C ~ 30C 18C ~ 30C 18C ~ 30CHeating - - - -
Auto Operation (Micom Control) O O O OAuto Changeover (Micom Control) - - - -Self Diagnosis O O O OTimer 24h On/Off 24h, On/Off 24h, On/Off 24h On/OffSleep Operation O O O OSoft Dry Operation O O O ORestart Delay(minute) 3 3 3 3Deice Control(Defrost) - - - -Hot Start - - - -Jet Cool O O O OLow Ambient Operation - - - -Special Function - - - -
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
10/48
6RMI0-02A
9 Inverter Single
Specifications
Note : O : Applie, X : Not applied, : No relation Filters are optional in some specific areas. For Circuit Breaker Rating, please conform to local standards whenever necessary.
Artcool InverterSales Model
AS-W093ERH0 AS-W123ERH0 AS-W1838RH0 AS-W2438RH0Models Unit
Cooling Capacity kW 0.89~2.70~3.70 0.89~3.52~4.04 1.76~5.28~5.80 3.87~7.03~7.74Btu/h. 3,070~9,200~12,620 3,070~12,000~13,800 6,000~18,000~19,800 13,200~24,000~25,500
Heating CapacitykW 0.89~3.52~5.00 0.89~4.54~5.49 1.40~6.07~6.65 3.37~8.09~8.88
Btu/h. 3,070~12,000~17,060 3,070~15,500~18,720 4,800~20, 700~22,700 12,300~27,600~29,700Power Input Cooling W 690 1120 1675 2450Running Current Cooling/Heating A 3.2 / 4.2 5.0 / 5.9 7.3 / 7.3 11.0 / 13.0
Starting Current Cooling/Heating A 3.2 / 4.2 5.0 / 5.9 7.3 / 7.3 11.0 / 13.0EER
W/W 3.91 3.14 3.15 2.87Btu/h.W 13.33 10.71 10.75 9.8
SEER 19.7 18.7 16.2 16.2HSPF 9.5 9.5 8.2 8.2Power Supply / V / Hz 1/220/60 1/220/60 1/220/60 1/220/60Power Factor % 94.2 98.7 98.3 96.8
Air Flow Rate Indoor,Max m3/min(CFM) 10.5(371) 10.5(371) 16(565) 20.3(717)Outdoor,Max m3/min(CFM) 27(954) 27(954) 42(1483) 58(2048)
Moisture Removal l/h. 1.2 1.5 2.1 2.7
Sound Level Indoor,H/M/LdB(A)3 31 / 27 / 22 35 / 29 / 25 42 / 39 / 36 43 / 40 /36
Outdoor,Max dB(A)3 45 45 54 55Refrigerant & Charge (at 7.5 m) g(oz) R410A, 1,000(35.3) R410A, 1,000(35.3) R410A, 1,200(42.3) R410A, 1,800(63.0)Additional Refrigerant charge g/m(oz/ft) 20(0.22) 20(0.22) 20(0.21) 30(0.32)
Compressor
Type Rotary Rotary E-Scroll RotaryModel 5RS102XAA21 5RS102XAA21 5CS130XCC03 5KD240XCA21Motor Type Brushless DC Motor Brushless DC Motor Brushless DC Motor Brushless DC MotorOil Type PVE(FV50S) PVE(FV50S) RB68A PVE(FV50S)Oil Charge cc 320 320 480 900O.L.P. name - - - -
Fan(Indoor) TypeCross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan
Motor Output W 20 20 30 30
Fan(Outdoor)Type Propeller Propeller Propeller PropellerMotor Type BLDC BLDC AC Induction AC InductionMotor Output W 43 43 65 76.5
Circuit Breaker* A 15 15 20 30Power Supply Cable No.*mm2 3*1.0 3*1.0 3*1.5 3*2.5Power and Transmission Cable No.*mm2 No.*mm2 4*1.0 (Including Earth) 4*1.0 (Including Earth) 4*1.5 (Including Earth) 4*2.5 (Including Earth)
Piping Connections Liquid Side mm(in) 6.35(1/4) 6.35(1/4) 6.35(1/4) 9.52(3/8)Gas Side mm(in) 9.52(3/8) 9.52(3/8) 12.70(1/2) 15.88(5/8)
Drain Hose(O.D / I.D.) mm(in) 21.5 / 16.0(0.85 / 0.63) 21.5 / 16.0(0.85 / 0.63) 21.5 / 16.0(0.85 / 0.63) 21.5 / 16.0(0.85 / 0.63)
DimensionsIndoor (W*H*D)
mm 912*282*165 912*282*165 1,107*299*200 1,107*299*200inch 35.9*11.1*6.5 35.9*11.1*6.5 43.6*11.8*7.9 43.6*11.8*7.9
Outdoor (W*H*D)mm 770*545*245 770*545*245 870*655*320 870*800*320inch 30.3*21.5*9.6 30.3*21.5*9.6 34.3*25.79*12.6 34.3*31.5*12.6
Net Weight Indoorkg(lbs) 10(22) 10(22) 15(33.1) 15(33.1)
Outdoor kg(lbs) 32(71) 32(71) 46(101) 60(132)
Gross Weight Indoorkg(lbs) 12.0(26.5) 12.0(26.5) 17(37.5) 17(37.5)
Outdoor kg(lbs) 37(81.6) 37(81.6) 50(110.2) 64(141.1)
Operation Range Cooling(Outdoor) C -5~43(23~109.4) -5~43(23~109.4) -5~43(23~109.4) -5~43(23~109.4)Heating(Outdoor) C -10(-15)~24(14.0~75.2) -10( -15)~24(14.0~75.2) -10( -15)~24(14.0~75.2) -10( -15)~24(14 .0~75.2)
Piping Length (Max) m(ft) 15(49.2) 15(49.2) 15(49.2) 30(98.4)Max. Elevation Difference m(ft) 7.5(24.6) 7.5(24.6) 7.5(24.6) 15(49.2)Tool Code(Chassis) Indoor + Outdoor SE MIRROR + UL SE MIRROR + UL S8 + UE S8 + UE1
Functions
Temperature Control Thermistor Thermistor Thermistor ThermistorAllergy free filter - - - -Plasma Filter O O O OPrefilter(washable/anti-fungus) O O O OAuto Clean O O O OCHAOS Wind(Auto Wind) O O O OSteps, Fan/Cool/Heat 3/4/3 3/4/3 3/4/3 3/4/3Airflow Direction Control(up& Down) Auto Auto Auto AutoAirflow Direction Control(left & right) Auto Auto Auto AutoRemote Controller Type Wireless LCD(EZ-Remocon) Wireless LCD(EZ-Remocon) Wireless LCD(EZ-Remocon) Wireless LCD(EZ-Remocon)Setting TemperatureRange
Cooling 18C ~ 30C 18C ~ 30C 18C ~ 30C 18C ~ 30CHeating 16C ~ 30C 16C ~ 30C 16C ~ 30C 16C ~ 30C
Auto Operation (Micom Control) - - - -Auto Changeover (Micom Control) O O O OSelf Diagnosis O O O OTimer 24h, On/Off 24h, On/Off 24h, On/Off 24h, On/OffSleep Operation O O O OSoft Dry Operation O O O ORestart Delay(minute) 2 2 3 3Deice Control(Defrost) O O O OHot Start O O O OJet Cool O O O OLow Ambient Operation O O O OSpecial Function - - - -
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
11/48
6RMI0-02A
10 Inverter Single
3. Dimensional drawings3.1 Indoor Units
7 0
7 0
1 3 3
9 5
R i g h t r e a r p i p i n g
L e f t r e a r p i p i n g
I n s t a l l a t i o n P l a t e
P l a c e a l e v
e l o n r a i s e d t a b
U n i t O u
t l i n e
2 1 7
1 7 5
4 4 2
4 4 2
L i b e r o
C H A S S I S C O
D E :
S B
2 1 0
3
8 8 5
2 1 0
2 8 5
2
1
4
5 0
. 5
5 9
. 5 1 5 9
. 5
2 3
5
[ U n
i t : m m
]
Dimensional drawings
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
12/48
6RMI0-02A
11Inverter Single
Dimensional drawings
2 5 0
1 0 3 0
3 2 5 2 1 0
7 0
7 0
6 9
5 6
R i g h
t r e a r
p i p i n
g
L e f t r e a r
p i p i n g
I n s t a l l a t i o n P l a t e
M e a s u
r i n g T a p e
M e a s u
r i n g T a p e
H a n g e r
P l a c e a l e v
e l o n r a i s e d t a b
U n i t O u
t l i n e
2 0 7
1 0 5
( U n i t : m m
)
4 6 0
5 7 0
L i b e r o
C H A S S I S C O D E :
S C
4
[ U n
i t : m m
]
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
13/48
A R T C O O L
M i r r o r
D i s p
l a y
& s
i g n a
l r e c e
i v e r
P a r t
N a m e
F r o n
t p a n e
l
A i r s u c
t i o n g r i
l l e
I n s t a
l l a t i o n p
l a t e
K n o c
k o u
t h o
l e
F o r
p i p e a n
d c a
b l e
5
N o . 2 4 3 1
R e m a r k
N o
t e
9 1 2
5 0
5 0 * 6 =
3 0 0
3 5 4
5 6 7
2 8
7 1
7 7
1 4 8
1 0 7
2 8 2
2 8 2
5 1
5 3
5 0
3 7
5 1
2 - R
1 6
5
1 6 5
2
4
1 7 1
3
1 .
U n
i t s h o u
l d b e
i n s
t a l l e d i n c o m p
l i a n c e w
i t h t h e
i n s
t a l l a t i o n m a n u a
l
i n t h e
p r o
d u c
t b o x .
2 .
U n
i t s h a
l l b e g r o u n
d e
d i n a c c o r d a n c e w
i t h t h e
l o c a l r e g u
l a t i o n s o r
a p p l i c a
b l e n a
t i o n a
l c o
d e s .
3 .
T h e U
n i t i s p o w e r e
d f r o m
t h e o u
t d o o r u n
i t .
T h e r e
f o r e
p o w e r c a
b l e
s
h o u l
d b e c o n n e c
t e d w
i t h t h e o u
t d o o r u n
i t .
1
C H A S S I S C O D E :
S E
[ U n
i t : m m
]
6RMI0-02A
12 Inverter Single
Dimensional drawings
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
14/48
6RMI0-02A
13 Inverter Single
Dimensional drawings
4 5
1 4 0
7 0 1
8 8
9 2 6
6 5
2 2 1
4 5 2 9 6
1 7 5
7 0
A R T C O O L
M i r r o r
D i s p
l a y
& s
i g n a
l r e c e
i v e r
P a r t
N a m e
F r o n
t p a n e
l
A i r s u c
t i o n g r i
l l e
K n o c
k o u
t h o
l e
F o r p
i p e a n
d c a
b l e
N o . 2 4
I n s t a
l l a t i o n p
l a t e
5 3 1
R e m a r k
N o
t e
1 .
T h e u n
i t s
h o u
l d n o
t b e
i n s
t a l l e d i n a c
l o s e
d a r e a .
2 .
I n a n a r e a o r s p a c e
h a v
i n g n o p r o p e r c
i r c u
l a t i o n ,
a n a
i r g u
i d e s
h o u
l d
b e
i n s t a l l e d o n
t h e o u
t d o o r s
i d e .
3 1
2
4
2 9 9
4 8
9 3
1 2 2
2 0 0
1 1 0 7
1 0
6 3
5 3
5 8
7 2
5
C H A S S I S C O D E :
S 8
[ U n
i t : m m
]
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
15/48
3.2 Outdoor Units
C H A S S I S C
O D E :
U A 3
[ U n
i t : m m
]
Dimensional drawings
Inverter Single14
6RMI0-02A
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
16/48
Dimensional drawings 6RMI0-02A
15 Inverter Single
C H A S S I S C O
D E :
U L
5 4 0
1 0
6 5 4 . 3
7 7 0
4 5
0
2 7 5
4 5 0
2 6 1
5
2 3
5 5
. 3
4
2 4 5
1
5 6
2 4 5
2 8 5
7 7 0
5 1 8
. 4
2 6 7
[ U n
i t : m m
]
Inverter Single
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
17/48
Dimensional drawings 6RMI0-02A
16 Inverter SingleInverter Single
1
C H A S S I S C O
D E :
U E
8 7 0
5 4 6
1 6 0
3 4 0
3 6 0
5 4
. 6
3 0 1
5 3 1
6 5 5
6 3 0
5 1 3
3 1 9
2 5
7 6 . 4
7 9
3 2 0
[ U n
i t : m m
]
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
18/48
Dimensional drawings 6RMI0-02A
17 Inverter Single
7 6 . 4
7 9
8 7 0
1 6 0
5 4 6
3 4 0
3 6 0
5 4 . 6
3 0 1
3 1 9
5 3
1
8 0 0
2 5
3 2 0
4 2 3
5
1
C H A S S I S C O
D E :
U E 1
[ U n
i t : m m
]
Inverter Single
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
19/48
Wiring diagrams 6RMI0-02A
18 Inverter SingleInverter Single
4. Wiring diagrams
Models: ASNQ093B1U0 (VA093CL.NB0), ASNQ123B1U0 (VA123CL.NB0)
Models: ASNQ183C2U0 (VA183CL.NB0), ASNQ243C2U0 (VA243CL.NB0)
4.1 Indoor units
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
20/48
Wiring diagrams 6RMI0-02A
19 Inverter Single
Models: ASNW093ERH0 , ASNW123ERH0
Models: ASNW1838RH0 , ASNW2438RH0
Inverter Single
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
21/48
Wiring diagrams 6RMI0-02A
20 Inverter SingleInverter Single
4.2 Outdoor units
Models: ASUQ093B1U0 (VA093CL.UB0)
Models: ASUQ123B1U0 (VA123CL.UB0)
Inverter Single
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
22/48
Wiring diagrams 6RMI0-02A
21Inverter SingleInverter SingleInverter Single
Models: ASUQ183C2U0 (VA183CL.UB0)
C N
_ C E N T R A L
Models: ASUQ243C2U0 (VA243CL.UB0)
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
23/48
Wiring diagrams 6RMI0-02A
22 Inverter SingleInverter Single
Models: ASUW1838RH0 , ASUW2438RH0
Models: ASUW093ERH0 , ASUW123ERH0
Inverter Single
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
24/48
Refrigerant cycle diagram 6RMI0-02A
23 Inverter SingleInverter SingleInverter Single
5. Refrigerant cycle diagram
Models : AS-Q093B1U0 (VA093CL.SB0), AS-Q123B1U0 (VA123CL.SB0)
CompressorAccumulatorTh6
Indoor Unit Outdoor Unit
HeatExchanger
(Evaporator)
HeatExchanger
(Condenser)
Gas Side
3-Way Valve
2-Way Valve
Liquid Side
Cooling
EEV
Th1
Th2
Th6Th3
Th7
Th4
LOC. Description PCB Connector
Th1 Thermistor for sunction air temperatureCN-TH1(Indoor)
Th2 Thermistor for evaporator inlet temperature
Th3 Thermistor for evaporator outlet temperature CN-TH2(Indoor)
Th4 Thermistor for evaporator middle temperature CN-TH3(Indoor)
Th5 Thermistor for discharge pipe temperature CN-TH2(OUTDOOR)
Th6 Thermistor for condensing temperature CN-TH1(OUTDOOR)
Th7 Thermistor for outdoor air temperature CN-TH1(OUTDOOR)
EEV : Electronic Expansion Valve
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
25/48
Refrigerant cycle diagram 6RMI0-02A
24 Inverter SingleInverter Single
Models : AS-Q183C2U0 (VA183CL.SB0), AS-Q243C2U0 (VA243CL.SB0)
Inverter Single
Indoor Unit Outdoor Unit
HeatExchanger(Evaporator)
HeatExchanger(Condenser)
Compressor
Accumulator
Gas Side
3-Way Valve
2-Way Valve
Liquid Side
CoolingHeating
Reversing Valve
EEV
Th1
Th2
Th6Th3
Th7
Th4
Th5
LOC. Description PCB Connector
Th1 Thermistor for suction air temperatureCN-TH1(Indoor)
Th2 Thermistor for evaporator inlet temperature
Th3 Thermistor for evaporator outlet temperature CN-TH2(Indoor)
Th4 Thermistor for evaporator middle temperature CN-TH3(Indoor)
Th5 Thermistor for discharge pipe temperatureCN-TH3(OUTDOOR)
Th6 Thermistor for suction pipe temperature
Th7 Thermistor for condensing temperatureCN-TH2(OUTDOOR)
Th8 Thermistor for outdoor air temperatureTh9 Thermistor for condensing middle temperature CN-TH4(OUTDOOR)
EEV : Electronic Expansion Valve
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
26/48
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
27/48
Refrigerant cycle diagram 6RMI0-02A
26 Inverter SingleInverter Single
Modes : AS-W1838RH0 , AS-W2438RH0
Indoor Unit Outdoor Unit
HeatExchanger(Evaporator)
HeatExchanger(Condenser)
EEV
Compressor
Accumulator
Gas Side
3-Way Valve
2-Way Valve
Liquid Side
CoolingHeating
Reversing Valve
Th1
Th2
Th3
Th5
Th4
Th6Th7
Inverter Single
LOC. Description PCB Connector Th1 Thermistor for indoor air temperature CN_TH1(INDOOR)
Th2Thermistor for evaporating temperature
CN_TH2(INDOOR)
Th3 CN_TH3(INDOOR)
Th4 Thermistor for outdoor air temperatureCN_TH2(OUTDOOR)
Th5 Thermistor for condensing temperature
Th6 Thermistor for discharge pipe temperatureCN_TH3(OUTDOOR)
Th7 Thermistor for suction pipe temperature
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
28/48
Capacity tables 6RMI0-02A
27 Inverter SingleInverter Single
6. Capacity tables6.1 Cooling Capacity
AS-Q093B1U0 (VA093CL.SB0)
CWB CDB TC SHC PI TC SHC PI TC SHC PI 14.0 20.0
16.0 22.0 18.0 25.0 19.0 27.0 22.0 30.0 24.0 32.0
2.16 2.45 0.65 2.10 2.47 0.63 2.04 2.49 0.57
2.31 2.40 0.70 2.25 2.44 0.66 2.19 2.45 0.58 2.47 2.35 0.71 2.41 2.39 0.66 2.35 2.40 0.56 2.55 2.35 0.71 2.49 2.39 0.66 2.43 2.39 0.56 2.78 2.22 0.72 2.72 2.25 0.67 2.66 2.26 0.56 2.94 2.15 0.73 2.88 2.19 0.68 2.82 2.19 0.57
Outdoor Air Temperature : CDB
40 43 46
Indoor AirTemperature
CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 16.0 22.0 18.0 25.0 19.0 27.0 22.0 30.0 24.0 32.0
2.59 2.34 0.38 2.48 2.37 0.39 2.32 2.42 0.53 2.25 2.46 0.59 2.75 2.30 0.51 2.63 2.33 0.51 2.48 2.38 0.62 2.41 2.42 0.67 2.91 2.25 0.55 2.79 2.28 0.55 2.64 2.33 0.65 2.57 2.37 0.69 2.99 2.25 0.56 2.87 2.27 0.56 2.72 2.32 0.66 2.64 2.36 0.68 3.23 2.12 0.56 3.11 2.15 0.57 2.96 2.19 0.68 2.88 2.23 0.71 3.39 2.06 0.55 3.27 2.08 0.58 3.11 2.13 0.69 3.04 2.16 0.73
Outdoor Air Temperature : CDB
20 25 32 35
Indoor AirTemperature
Symbol NotesAFR : Air flow rate [m 3/min] 1. All capacities are net, evaporator fan motor heat is deducted.DB : Dry bulb temperature [C] 2. Indicates nominal maximum capacity.WB : Wet bulb temperature [C] 3. Direct interpolation is permissible. Do not extrapolateTC : Total capacity [kW] 4. Capacities are based on the following conditions:SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5mPI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)
AS-Q123B1U0 (VA123CL.SB0)
CWB CDB TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 16.0 22.0 18.0 25.0 19.0 27.0 22.0 30.0 24.0 32.0
2.64 2.73 0.80 2.56 2.76 0.78 2.49 2.78 0.70 2.83 2.68 0.86 2.76 2.72 0.82 2.68 2.73 0.71 3.02 2.62 0.87 2.95 2.67 0.82 2.88 2.67 0.69 3.12 2.62 0.87 3.04 2.66 0.81 2.97 2.66 0.69 3.41 2.47 0.89 3.33 2.51 0.82 3.26 2.52 0.69
3.60 2.40 0.91 3.52 2.44 0.84 3.45 2.44 0.70
Outdoor Air Temperature : CDB
40 43 46
Indoor AirTemperature
CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20.0
16.0 22.0 18.0 25.0 19.0 27.0 22.0 30.0 24.0 32.0
3.17 2.61 0.46 3.03 2.64 0.48 2.84 2.70 0.65 2.76 2.74 0.73
3.36 2.57 0.63 3.22 2.59 0.63 3.04 2.65 0.77 2.95 2.69 0.82 3.56 2.51 0.68 3.42 2.54 0.68 3.23 2.59 0.81 3.14 2.64 0.85 3.65 2.50 0.69 3.51 2.53 0.69 3.33 2.59 0.81 3.23 2.63 0.84 3.95 2.36 0.69 3.81 2.39 0.71 3.62 2.44 0.83 3.53 2.48 0.88 4.14 2.30 0.68 4.00 2.32 0.71 3.81 2.37 0.85 3.72 2.41 0.90
Outdoor Air Temperature : CDB
20 25 32 35
Indoor AirTemperature
Inverter Single
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
29/48
6RMI0-02A
28 Inverter Single
Capacity tables
Inverter SingleInverter Single
Symbol NotesAFR : Air flow rate [m 3/min] 1. All capacities are net, evaporator fan motor heat is deducted.DB : Dry bulb temperature [C] 2. Indicates nominal maximum capacity.WB : Wet bulb temperature [C] 3. Direct interpolation is permissible. Do not extrapolateTC : Total capacity [kW] 4. Capacities are based on the following conditions:SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5mPI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)
AS-Q183C2U0 (VA183CL.SB0)
CWB CDB TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 16.0 22.0 18.0 25.0 19.0 27.0
22.0 30.0 24.0 32.0
4.31 4.42 1.43 4.19 4.47 1.40 4.07 4.50 1.26 4.62 4.34 1.54 4.51 4.41 1.47 4.39 4.42 1.28 4.94 4.25 1.57 4.82 4.32 1.47 4.70 4.32 1.25 5.10 4.24 1.57 4.98 4.31 1.46 4.86 4.31 1.23
5.57 4.00 1.60 5.45 4.07 1.48 5.33 4.07 1.23 5.88 3.88 1.63 5.76 3.95 1.51 5.64 3.95 1.26
Outdoor Air Temperature : CDB
40 43 46
Indoor AirTemperature
CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 16.0 22.0 18.0 25.0 19.0 27.0 22.0 30.0 24.0 32.0
5.18 4.23 0.83 4.95 4.28 0.87 4.65 4.37 1.17 4.51 4.44 1.31 5.50 4.16 1.13 5.27 4.20 1.14 4.97 4.29 1.38 4.82 4.37 1.48 5.81 4.07 1.22 5.59 4.11 1.23 5.28 4.20 1.45 5.14 4.27 1.54 5.97 4.06 1.24 5.75 4.10 1.25 5.44 4.19 1.46 5.28 4.26 1.51 6.45 3.83 1.24 6.22 3.87 1.27 5.91 3.96 1.50 5.76 4.02 1.58 6.77 3.72 1.23 6.54 3.76 1.28 6.23 3.84 1.53 6.08 3.90 1.61
Outdoor Air Temperature : CDB
20 25 32 35
Indoor AirTemperature
AS-Q243C2U0 (VA243CL.SB0)
CWB CDB TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 16.0 22.0 18.0 25.0 19.0 27.0 22.0 30.0 24.0 32.0
5.74 5.31 2.18 5.58 5.37 2.14 5.42 5.41 1.92 6.16 5.22 2.35 6.00 5.30 2.24 5.84 5.31 1.94 6.58 5.10 2.39 6.42 5.19 2.24 6.26 5.20 1.90 6.78 5.09 2.39 6.63 5.18 2.23 6.47 5.18 1.88 7.41 4.81 2.43 7.25 4.89 2.25 7.10 4.90 1.88 7.83 4.67 2.48 7.67 4.74 2.30 7.51 4.75 1.93
Outdoor Air Temperature : CDB
40 43 46
Indoor AirTemperature
CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 16.0 22.0 18.0 25.0 19.0 27.0 22.0 30.0 24.0 32.0
6.89 5.09 1.27 6.59 5.14 1.33 6.19 5.25 1.78 6.00 5.34 1.99 7.32 5.00 1.72 7.02 5.05 1.74 6.61 5.16 2.10 6.42 5.25 2.26 7.74 4.89 1.86 7.44 4.94 1.87 7.03 5.05 2.21 6.84 5.13 2.34 7.95 4.87 1.88 7.65 4.93 1.90 7.24 5.04 2.23 7.03 5.12 2.30 8.59 4.60 1.88 8.28 4.66 1.93 7.87 4.76 2.28 7.67 4.83 2.41 9.02 4.47 1.87 8.70 4.52 1.95 8.29 4.62 2.33 8.09 4.69 2.46
Outdoor Air Temperature : CDB
20 25 32 35
Indoor AirTemperature
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
30/48
6RMI0-02A
29 Inverter Single
Capacity tables
Inverter Single
Symbol NotesAFR : Air flow rate [m 3/min] 1. All capacities are net, evaporator fan motor heat is deducted.DB : Dry bulb temperature [C] 2. Indicates nominal maximum capacity.WB : Wet bulb temperature [C] 3. Direct interpolation is permissible. Do not extrapolateTC : Total capacity [kW] 4. Capacities are based on the following conditions:SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5mPI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)
AS-W093ERH0
CWB CDB TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 16.0 22.0 18.0 25.0 19.0 27.0
22.0 30.0 24.0 32.0
2.20 2.30 0.66 2.14 2.33 0.64 2.08 2.35 0.58 2.36 2.26 0.71 2.30 2.30 0.67 2.24 2.30 0.58 2.53 2.21 0.72 2.46 2.25 0.67 2.40 2.25 0.57 2.61 2.21 0.72 2.54 2.24 0.67 2.48 2.25 0.56
2.85 2.08 0.73 2.79 2.12 0.68 2.73 2.12 0.56 3.01 2.02 0.74 2.95 2.06 0.69 2.89 2.06 0.58
Outdoor Air Temperature : CDB
40 43 46
Indoor AirTemperature
CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 16.0 22.0 18.0 25.0 19.0 27.0 22.0 30.0 24.0 32.0
2.65 2.21 0.38 2.53 2.23 0.40 2.38 2.28 0.53 2.31 2.32 0.60 2.81 2.17 0.52 2.69 2.19 0.52 2.54 2.24 0.63 2.47 2.27 0.68 2.97 2.12 0.56 2.86 2.14 0.56 2.70 2.19 0.66 2.63 2.23 0.70 3.05 2.11 0.57 2.94 2.14 0.57 2.78 2.18 0.67 2.70 2.22 0.69 3.30 2.00 0.57 3.18 2.02 0.58 3.02 2.06 0.69 2.95 2.10 0.72 3.46 1.94 0.56 3.34 1.96 0.58 3.18 2.00 0.70 3.11 2.03 0.74
Outdoor Air Temperature : CDB
20 25 32 35
Indoor AirTemperature
AS-W123ERH0
CWB CDB TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 16.0 22.0 18.0 25.0 19.0 27.0 22.0 30.0 24.0 32.0
2.87 3.52 1.06 2.79 3.55 1.04 2.72 3.58 0.93 3.08 3.45 1.15 3.00 3.51 1.09 2.92 3.52 0.95 3.29 3.38 1.16 3.21 3.44 1.09 3.13 3.44 0.92 3.40 3.37 1.16 3.32 3.43 1.09 3.24 3.43 0.92 3.71 3.18 1.18 3.63 3.24 1.10 3.55 3.24 0.92 3.92 3.09 1.21 3.84 3.14 1.12 3.76 3.15 0.94
Outdoor Air Temperature : CDB
40 43 46
Indoor AirTemperature
CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 16.0 22.0 18.0 25.0
19.0 27.0 22.0 30.0 24.0 32.0
3.45 3.37 0.62 3.30 3.40 0.65 3.10 3.48 0.87 3.01 3.54 0.97 3.66 3.31 0.84 3.51 3.34 0.85 3.31 3.42 1.02 3.21 3.47 1.10 3.88 3.24 0.91 3.72 3.27 0.91 3.52 3.34 1.07 3.42 3.40 1.14
3.98 3.23 0.92 3.83 3.26 0.93 3.63 3.33 1.09 3.52 3.39 1.12 4.30 3.05 0.92 4.15 3.08 0.94 3.94 3.15 1.11 3.84 3.20 1.17 4.51 2.96 0.91 4.36 2.99 0.95 4.15 3.06 1.13 4.05 3.11 1.20
Outdoor Air Temperature : CDB
20 25 32 35
Indoor AirTemperature
Inverter Single
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
31/48
6RMI0-02A
30 Inverter Single
AS-W2438RH0
CWB CDB TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 16.0 22.0 18.0 25.0 19.0 27.0 22.0 30.0 24.0 32.0
5.74 5.40 2.33 5.58 5.46 2.28 5.42 5.50 2.04 6.16 5.31 2.51 6.00 5.40 2.38 5.84 5.41 2.07 6.58 5.19 2.54 6.42 5.28 2.38 6.26 5.29 2.02 6.78 5.18 2.55 6.63 5.27 2.38 6.47 5.28 2.00 7.41 4.89 2.59 7.25 4.97 2.40 7.10 4.98 2.00 7.83 4.75 2.64 7.67 4.83 2.45 7.51 4.84 2.05
Outdoor Air Temperature : CDB
40(104) 43(109.4) 46(114.8)
Indoor AirTemperature
CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 16.0 22.0 18.0 25.0 19.0 27.0
22.0 30.0 24.0 32.0
6.89 5.17 1.35 6.59 5.23 1.41 6.19 5.35 1.90 6.00 5.44 2.12 7.32 5.08 1.83 7.02 5.14 1.85 6.61 5.25 2.24 6.42 5.34 2.40 7.74 4.97 1.98 7.44 5.03 2.00 7.03 5.14 2.35 6.84 5.22 2.49 7.95 4.96 2.01 7.65 5.02 2.02 7.24 5.13 2.38 7.03 5.21 2.45
8.59 4.68 2.01 8.28 4.74 2.06 7.87 4.84 2.43 7.67 4.92 2.57 9.02 4.55 1.99 8.70 4.60 2.08 8.29 4.70 2.48 8.09 4.78 2.62
Outdoor Air Temperature : CDB
20 25 32 35
Indoor AirTemperature
Capacity tables
Inverter Single
Symbol NotesAFR : Air flow rate [m 3/min] 1. All capacities are net, evaporator fan motor heat is deducted.DB : Dry bulb temperature [C] 2. Indicates nominal maximum capacity.WB : Wet bulb temperature [C] 3. Direct interpolation is permissible. Do not extrapolateTC : Total capacity [kW] 4. Capacities are based on the following conditions:SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5mPI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor)
AS-W1838RH0
CWB CDB TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 16.0 22.0 18.0 25.0 19.0 27.0 22.0 30.0 24.0 32.0
4.31 4.01 1.59 4.19 4.06 1.56 4.07 4.09 1.40 4.62 3.94 1.71 4.51 4.01 1.63 4.39 4.02 1.42 4.94 3.86 1.74 4.82 3.92 1.63 4.70 3.93 1.38 5.10 3.85 1.74 4.98 3.91 1.62 4.86 3.92 1.37 5.57 3.63 1.77 5.45 3.69 1.64 5.33 3.70 1.37 5.88 3.53 1.81 5.76 3.59 1.68 5.64 3.59 1.40
Outdoor Air Temperature : CDB
40 43 46
Indoor AirTemperature
CWB CDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20.0 16.0 22.0 18.0 25.0 19.0 27.0 22.0 30.0 24.0 32.0
5.18 3.84 0.93 4.95 3.89 0.97 4.65 3.97 1.30 4.51 4.04 1.45 5.50 3.78 1.25 5.27 3.82 1.27 4.97 3.90 1.53 4.82 3.97 1.64 5.81 3.69 1.36 5.59 3.74 1.36 5.28 3.82 1.61 5.14 3.88 1.70 5.97 3.68 1.37 5.75 3.73 1.38 5.44 3.81 1.62 5.28 3.87 1.68 6.45 3.48 1.37 6.22 3.52 1.41 5.91 3.60 1.66 5.76 3.65 1.76 6.77 3.38 1.36 6.54 3.42 1.42 6.23 3.49 1.69 6.08 3.55 1.79
Outdoor Air Temperature : CDB
20 25 32 35
Indoor AirTemperature
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
32/48
6RMI0-02A
31Inverter SingleInverter SingleInverter Single
Capacity tables
CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI 16.0 2.65 0.73 2.78 0.72 3.02 0.75 3.22 0.80 3.58 0.86 3.78 0.90 4.10 0.95
18.0 2.62 0.74 2.78 0.73 3.02 0.77 3.22 0.83 3.55 0.88 3.73 0.91 4.09 0.9720.0 2.60 0.76 2.78 0.75 3.02 0.79 3.21 0.85 3.52 0.90 3.71 0.93 4.10 0.9721.0 2.60 0.77 2.78 0.76 3.02 0.80 3.21 0.86 3.50 0.91 3.71 0.93 4.07 0.9722.0 2.59 0.77 2.78 0.77 3.02 0.82 3.20 0.87 3.47 0.92 3.70 0.94 4.04 0.9724.0 2.56 0.79 2.75 0.80 2.99 0.84 3.17 0.89 3.44 0.93 3.64 0.95 3.99 0.98
Outdoor Air Temperature : CWB
-15 -10 -5 0 6 10 15
Indoor AirTemperature
AS-W093ERH0
CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI 16.0 3.41 1.11 3.59 1.08 3.89 1.13 4.16 1.22 4.61 1.30 4.88 1.35 5.29 1.44
18.0 3.38 1.13 3.59 1.11 3.90 1.16 4.16 1.25 4.58 1.33 4.82 1.38 5.28 1.4620.0 3.36 1.15 3.58 1.14 3.90 1.20 4.15 1.28 4.54 1.36 4.78 1.40 5.29 1.4721.0 3.35 1.16 3.58 1.15 3.90 1.22 4.14 1.30 4.51 1.37 4.78 1.41 5.25 1.4722.0 3.34 1.17 3.59 1.17 3.90 1.23 4.12 1.32 4.48 1.38 4.78 1.42 5.21 1.4724.0 3.30 1.20 3.55 1.20 3.85 1.27 4.09 1.35 4.44 1.41 4.70 1.43 5.15 1.48
Outdoor Air Temperature : CWB
-15 -10 -5 0 6 10 15
Indoor AirTemperature
AS-W123ERH0
CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI 16.0 4.56 1.44 4.80 1.41 5.20 1.47 5.56 1.58 6.17 1.69 6.52 1.76 7.08 1.88
18.0 4.52 1.46 4.79 1.44 5.21 1.52 5.56 1.63 6.13 1.73 6.44 1.80 7.05 1.9020.0 4.49 1.49 4.79 1.48 5.21 1.56 5.54 1.67 6.07 1.77 6.40 1.82 7.07 1.9121.0 4.48 1.51 4.79 1.50 5.21 1.58 5.53 1.69 6.03 1.79 6.40 1.84 7.02 1.9122.0 4.47 1.52 4.79 1.52 5.21 1.60 5.51 1.71 5.99 1.80 6.39 1.85 6.96 1.9124.0 4.42 1.56 4.75 1.57 5.15 1.65 5.47 1.75 5.94 1.83 6.28 1.86 6.88 1.93
Outdoor Air Temperature : CWB
-15 -10 -5 0 6 10 15
Indoor AirTemperature
AS-W1838RH0
CDB TC PI TC PI TC PI TC PI TC PI TC PI TC PI 16.0 6.08 2.36 6.40 2.31 6.94 2.41 7.41 2.59 8.22 2.78 8.69 2.89 9.43 3.08
18.0 6.02 2.40 6.39 2.36 6.95 2.48 7.40 2.67 8.17 2.84 8.58 2.94 9.40 3.1120.0 5.98 2.44 6.39 2.43 6.95 2.55 7.39 2.74 8.09 2.90 8.52 2.99 9.42 3.1321.0 5.97 2.47 6.39 2.46 6.95 2.59 7.37 2.77 8.04 2.93 8.52 3.01 9.36 3.1322.0 5.96 2.49 6.39 2.49 6.95 2.63 7.35 2.81 7.98 2.95 8.51 3.02 9.28 3.1324.0 5.88 2.55 6.33 2.56 6.86 2.70 7.29 2.87 7.92 3.00 8.37 3.05 9.17 3.16
Outdoor Air Temperature : CWB
-15 -10 -5 0 6 10 15
Indoor AirTemperature
AS-W2438RH0
6.2 Heating Capacity
Symbol NotesAFR : Air flow rate [m 3/min] 1. All capacities are net, evaporator fan motor heat is deducted.DB : Dry bulb temperature [C] 2. Indicates nominal maximum capacity.WB : Wet bulb temperature [C] 3. Direct interpolation is permissible. Do not extrapolateTC : Total capacity [kW] 4. Capacities are based on the following conditions:SHC : Sensible capacity [kW] - Interconnecting Piping Length 7.5mPI : Power Input [kW] - Level Difference of Zero.
(Comp.+ indoor fan motor+outdoor fan motor) - Outdoor air : 85%RH. However, the condition on nominal capacityis 7CDB/6CWB
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
33/48
6RMI0-02A
32 Inverter Single
7. Capacity coefficient factor
Inverter Single
Libero Inverter (C/O)
Capacity coefficient factor
100
90
80
707.5 15 5030
24K,30K 18K 9K,12K
C a p a c i t y ( % )
Total Pipe Length(m)
Cooling
Inverter Single
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
34/48
6RMI0-02A
33 Inverter SingleInverter SingleInverter Single
Capacity coefficient factor
Artcool Inverter
100
90
80
707.5 15 5030
18K, 24K
18K, 24K
9K,12K
C a p a c i t y ( % )
Total Pipe Length(m)
100
90
80
707.5 15 5030
9K,12K
C a p a c i t y ( % )
Total Pipe Length(m)
Cooling
Heating
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
35/48
6RMI0-02A
34 Inverter SingleInverter Single
Capacity coefficient factor
Notes Equivalent pipe length = actual pipe length + number of band x 0.3 Additional Refrigerant Charge
Example: For Model 12k Btu/h having 20m pipe length, additional refrigerant to be charged is (20-7) x 20 = 260g* Refer to the specification for the maximum pipe length of each model.
CAUTION: Capacity is based on standard length
and maximum allowance length is onthe basis of reliability.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
Model No. Max. Pipe Length[m(ft)] A Max. Elevation[m(ft)] B AdditionalRefrigerant[g/m(oz/ft)]
AS-Q093B1U0 15(49.2) 7(23) 20(0.22)
AS-Q123B1U0 15(49.2) 7(23) 20(0.22)
AS-Q183C2U0 20(65.6) 15(49.2) 20(0.22)AS-Q243C2U0 30(98.4) 15(49.2) 35(0.38)
AS-Q243C2U0 15(49.2) 7.5(24.6) 20(0.22
AS-W123ERH0 15(49.2) 7.5(24.6) 20(0.22)
AS-W1838RH0 15(49.2) 7.5(24.6) 20(0.22)
AS-W2438RH0 30(98.4) 15(49.2) 30(0.32)
Inverter Single
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
36/48
6RMI0-02A
35 Inverter Single
Cooling
Indoor Unit [C DB]
OutdoorUnit
[C DB]
10
10
48
18 32
Continuousoperation
Operative
Operative: Intermittent operation due to the operationalconditions (indoor/outdoor temperature, humidity,load etc.) can cause the heating capacity todecrease.
Cooling
-15
-10
16 30
Operative
Continuousoperation
24
W a r m
i n g u p
O p e r a
t i o n
OutdoorUnit
[C DB]
Indoor Unit [C DB]
Heating
Indoor Unit [C DB]
OutdoorUnit
[C DB]
-5
43
18 32
Continuousoperation
Operative: Intermittent operation due to the operationalconditions (indoor/outdoor temperature, humidity,load etc.) can cause the heating capacity todecrease.
Inverter SingleInverter Single
Operation range
8. Operation range
Artcool Inverter
Libero Inverter (C/O)
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
37/48
6RMI0-02A
36 Inverter SingleInverter Single
Air flow and temperature distributions(reference data)
9. Air flow and temperature distributions(reference data)
2.63 kW (9kBtu/h) Cooling
Discharge angle:45
3.51 kW (12kBtu/h) Cooling
Discharge angle:45
28
29
0.55
1.0 0
0.7575
0 5
0 75
1 0
2
5m 4m 3m 2m 1m 0m0m
1m
2m
2.7mAir Velocity [m/s]
5m 4m 3m 2m 1m 0m0m
1m
2m
2.7mTemperature [ C]
233
244255
0.5
1.0
0.75
23
2425
1.25
1.55
5m 4m 3m 2m 1m 0m0m
1m
2m
2.7mAir Velocity [m/s]
255 244
233
5m 4m 3m 2m 1m 0m0m
1m
2m
2.7mTemperature [ C]
25 24
23
0.550.7575
1.00
0.50.75
1.0
1.5
Inverter Single
Libero Inverter (C/O)
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
38/48
6RMI0-02A
37 Inverter SingleInverter SingleInverter Single
Air flow and temperature distributions(reference data)
2.63 kW (9kBtu/h) Cooling
Discharge angle:45Heating
Discharge angle:50
3.51 kW (12kBtu/h) Cooling
Discharge angle:45Heating
Discharge angle:50
Air velocity [m/s]2.7m
2m
1m
0m0m1m2m3m4m5m
Temperature [C]2.7m
2m
1m
0m0m1m2m3m4m5m
0.75
1.0
0.5
25 24
23
Air velocity [m/s]2.7m
2m
1m
0m0m1m2m3m4m5m
Temperature [C]2.7m
2m
1m
0m0m1m2m3m4m5m
0.75
1.01.2
0.5
28
29 30
2.7mAir ve locity [m/s]
2m
1m
0m0m1m2m3m4m5m
2.7mTemperature [C]
2m
1m
0m0m1m2m3m4m5m
0.5
25 24
23
1.0
1.2
0.75
2.7mAir velocity [m/s]
2m
1m
0m0m1m2m3m4m5m
2.7mTemperature [ C]
2m
1m
0m0m1m2m3m4m5m
0.5
1.0
0.75
2829
30
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
39/48
6RMI0-02A
38 Inverter SingleInverter Single
Sound level
10. Sound levels
0.8m
1m
Microphone
Notes:- Sound measured at 1m away from the center of the unit.
- Data is valid at free field condition.- Data is valid at nominal operation condition.- Reference accoustic pressure 0dB=20Pa.- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.- The operating conditions are assumed to be standard.
Overall
ASNQ093B1U0ASNQ123B1U0
Sound Pressure Level
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
O c
t a v e
B a n
d S o u n
d P r e s s u r e L
e v e
l ( d B r e
2 0 P a
)
Octave Band Center Frequency (Hz)
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
ApproximateHearingThreshold
ASNQ243C2U0
ASNW1838RH0
ASNQ183C2U0
O c t a v e
B a n
d S o u n
d P r e s s u r e
L e v e
l ( d B r e
2 0 P a
)
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000Octave Band Center Frequency (Hz)
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
ApproximateHearingThreshold
O c t a v e
B a n
d S o u n
d P r e s s u r e
L e v e
l ( d B r e
2 0
P a
)
Octave Band Center Frequency (Hz)
ASNW093ERH0 ASNW123ERH0
O c t a v e
B a n
d S o u n
d P r e s s u r e
L e v e
l ( d B r e
2 0
P a )
10
20
30
40
50
60
70
80
O c t a v e
B a n
d S o u n
d P r e s s u r e
L e v e
l ( d B r e
2 0
P a )
10
20
30
40
50
60
70
80
ApproximateHearingThreshold
ApproximateHearingThreshold
O c t a v e
B a n
d S o u n
d P r e s s u r e
L e v e
l ( d B r e
2 0
P a )
20
30
40
50
60
70
80
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
ApproximateHearingThreshold
10.1 Indoor Units
Inverter Single
Model Sound Levels [dB(A)]H M L
ASNQ093B1U0 39 33 24ASNQ123B1U0 39 33 24ASNQ183C2U0 42 38 34ASNQ243C2U0 45 40 35ASNW093ERH0 31 27 22
ASNW123ERH0 35 29 25ASNW1838RH0 42 39 36ASNW2438RH0 43 40 36
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
40/48
6RMI0-02A
39 Inverter SingleInverter SingleInverter Single
Sound level
ASNW2438RH0
O c t a v e
B a n
d S o u n
d P r e s s u r e
L e v e
l ( d B r e
2 0 P a
)
Octave Band Center Frequency (Hz)
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
41/48
6RMI0-02A
40 Inverter SingleInverter Single
Sound level
ASUQ093B1U0ASUQ123B1U0
Sound Pressure Level
Octave Band Center Frequency (Hz)
S o u n
d P r e s s u r e
L e v e
l ( d B r e
2 0 P a
)
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
ApproximateHearingThreshold
ASUQ183C2U0ASUQ243C2U0
ASUW2438RH0ASUW1838RH0
O c t a v e
B a n
d S o u n
d P r e s s u r e
L e v e
l ( d B r e
2 0
P a
)
Octave Band Center Frequency (Hz)
ASUW093ERH0ASUW123ERH0
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
NC-1
NC-2
NC-2
NC-3
NC-3
NC-4
NC-4
NC-5
NC-5
NC-6
NC-6
ApproximateHearingThreshold
O c t a v e
B a n
d S o u n
d P r e s s u r e
L e v e
l ( d B r e
2 0
P a
)
Octave Band Center Frequency (Hz)
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
ApproximateHearingThreshold
O c t a v e
B a n
d S o u n
d P r e s s u r e
L e v e
l ( d B r e
2 0
P a
)
Octave Band Center Frequenc Hz
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
ApproximateHearingThreshold
O c t a v e
B a n
d S o u n
d P r e s s u r e
L e v e
l ( d B r e
2 0
P a
)
Octave Band Center Frequency (Hz)
P a
)
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000 8000NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
ApproximateHearingThreshold
1m
1m
Center ofOutdoor Unit
Notes:- Sound measured at 1m away from the center of the unit.
- Data is valid at free field condition.- Data is valid at nominal operation condition.- Reference accoustic pressure 0dB=20Pa.- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular room in which the equipment is installed.- The operating conditions are assumed to be standard.
Overall
10.2 Outdoor Units
Inverter Single
Model Sound Levels [dB(A)]HASUQ093B1U0 47ASUQ123B1U0 47ASUQ183C2U0 53ASUQ243C2U0 53ASUW093ERH0 45ASUW123ERH0 45
ASUW1838RH0 54ASUW2438RH0 55
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
42/48
Remote controller 6RMI0-02A
41Inverter SingleInverter Single
11. Remote controllerWireless Remote Controller
Inverter Single
The controls will look like the following.
ON/OFF BUTTONUsed to turn off/on the unit.
OPERATION MODE SELECTION BUTTONUsed to select the operation mode.
ROOM TEMPERATURE SETTING BUTTONSUsed to select the room temperature.
INDOOR FAN SPEED SELECTION BUTTONUsed to select fan speed in six steps low, medium-low,medium, medium-high, high and natural wind.
Cooling Operation
Auto Operation
Healthy Dehumidification Operation
Air Circulation
Operation Mode
SLEEP MODE AUTO BUTTONUsed to set sleep mode auto operation.
PLASMA BUTTONUsed to start or stop the plasma-purification.
Signal transmitter
SLEEP
Reset (display): When you press the reset button, all the functions shown on the screenof remote controller (above image), will be visible on the display. But some of thesefunctions are optional for your product and may not actually function.
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
43/48
Inverter SingleInverter Single
The controls will look like the following.
JET COOL BUTTONUsed to start or stop the speed cooling.The Jet Cool operates fan in super high speedin cooling mode.
TIME ADJUSTING BUTTONSUsed to adjust the time.
TIMER SET/CLEAR BUTTON(after adjusting)Used to set and to cancel the timer operation.
RESET BUTTONUsed prior to resetting time.
LED LUMINOSITY BUTTON
Used to adjust LED luminosity.
HORIZONTAL VANE CONTROL BUTTONUsed to set the desired vertical airflow direction.
VERTICAL LOUVER CONTROL BUTTON
Used to set the desired horizontal airflow direction.
AUTO CLEAN BUTTONUsed to set auto clean.
ENERGY SAVING COOLING BUTTONUsed to save Energy.
ROOM TEMPERATURE CHECKING BUTTONUsed to check the room temperature.
TIMER BUTTON(before adjusting)Used to set the current time and the time of starting / stopping.
Signal transmitter
SLEEP
Reset (display): When you press the reset button, all the functions shown on the screen of remotecontroller (above image), will be visible on the display. But some of these functions are optionalfor your product and may not actually function.
Inverter Single42
6RMI0-02ARemote controller
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
44/48
Inverter SingleInverter Single
ON OFF
CANCEL
AUTO CLEANSET
1
3
5
4
9
10
12
14
16
72
813
15
11
6
Cooling Operation
Auto Operation or Auto Changeover
Healthy Dehumidification Operation
Flip-up door(opened)
Heating Operation
Signal transmitter
Cooling Model( ), Heat Pump Model( )
1718
Operation Mode
The controls will look like the following. 1. START/STOP BUTTONUsed to turn off/on the unit.
2. OPERATION MODE SELECTION BUTTONUsed to select the operation mode.
3. ROOM TEMPERATURE SETTING BUTTONSUsed to select the room temperature.
4. INDOOR FAN SPEED SELECTOR BUTTONUsed to select fan speed in four stepslow, medium, high and CHAOS.
5. JET COOL/HEAT BUTTONUsed to start or stop the speed cooling/heating.(It operates fan in super high speed)
6. CHAOS SWING BUTTONUsed to stop or start louver movement and set thedesired up/down airflow direction.
7. ON/OFF TIMER BUTTONSUsed to set the time of starting and stoppingoperation.
8. TIME SETTING BUTTONSUsed to adjust the time.
9. TIMER SET/CANCEL BUTTONUsed to set and to cancel the timer operation.
10. SLEEP MODE AUTO BUTTONUsed to set sleep mode auto operation.11. AIR CIRCULATION BUTTON(OPTIONAL)
Used to circulate the room air without cooling orheating.
ENERGY-SAVING COOLING MODEBUTTON (OPTIONAL) For inverter type models
12. ROOM TEMPERATURE CHECKING BUTTONUsed to check the room temperature.
13. PLASMA BUTTON(OPTIONAL)Used to start or stop the plasma-purificationfunction.
14. HORIZONTAL AIRFLOW DIRECTIONCONTROL BUTTON (OPTIONAL)
Used to set the desired horizontal airflowdirection.15. RESET BUTTON
Used prior to resetting time.16. 2nd F BUTTON
Used prior to using modes printed in blue at thebottom of buttons.
17. AUTO CLEAN BUTTON(OPTIONAL)Used to set auto clean mode.In some models this button has a 2nd function ofLED luminosity control.
18. LCD LUMINOSITY BUTTON(OPTIONAL)Used to adjust LCD luminosity.
To use the functions printed in blue at the bottom of the buttons press 2 nd F button first and then the requiredfunction button. Pressing the 2 nd F button activates the blue printed function of the respective button. Tocancel the function press the 2nd F button again else it will automatically cancel if remains idle after 10seconds.
NOTICE
Inverter Single 43
6RMI0-02A Remote controller
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
45/48
Inverter SingleInverter Single
12. Installation
Installation Map
Connecting cable(Optional Parts)
Gas side piping (Optional Parts)Liquid side piping (Optional Parts)Additional drain pipe
Vinyl tape (Narrow)Drain Hose
Vinyl tape (Wide) Apply after carrying out a drainage test. To carry out the drainage
test, remove the air filters and pour water into the heatexchanger.
Saddle
Installation plateSleeveBushing-SleevePutty(Gum Type Sealant)Bend the pipe as closelyon the wall as possible,but be careful that itdoesn't break.
- The feature can be changed according a type of model.
You should purchase the installation parts.
NOTICE
Inverter Single44
6RMI0-02AInstallation
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
46/48
Installation 6RMI0-02A
45 Inverter SingleInverter SingleInverter Single
Connecting the Cables IndoorConnect the cable to the indoor unit by connecting the wires to the terminals on the control board individuallyaccording to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminalNo. are the same as those of the indoor unit.)
The circuit diagram is a subject to change without notice.
The earth wire should be longer than the common wires.
When installing, refer to the circuit diagram on the chassis cover.
Connect the wires firmly so that they may not be pulled out easily. Connect the wires according to color codes, referring to the wiring diagram.
Provide a circuit breaker betweenpower source and the outdoor unit asshown below.
The power cord connected to the outdoor unit should be complied with the followingspecifications (UL recognized or CAS certified).
The power connecting cable connected to the indoor and outdoor unit should be compliedwith the following specifications (UL recognized or CAS certified).
AirConditioner
Main power source
Circuit BreakerUse a circuit breakeror time delay fuse.
G N / Y L
2 0 m m
AWG_"B"
Connecting cable (208/230V)
1 0 3 m
m
G N / Y L
2 0 m m
Power supply cable (208/230V)
AWG_"A" 1 0 3 m
m
9k~12k 18k 24k~36k
15 20 25
CircuitBreaker
(A)
Capacity(Btu/h)
9k/12k/18k 24k/30k/36k 14 12
Power
"A"
Capacity(Btu/h)
9k/12k/16k/18k/24k/30k/36k18
Power
"B"
Capacity(Btu/h)
When using the separate wire as the power cord, please fix the separate wire into the control boxpanel by using tie wrap as the fixture.
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
47/48
Inverter SingleInverter Single
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion
on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunc-tion or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise itneeds additional anticorrosion treatment on the heat exchanger.
1. If you cant meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment.2. Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
Selecting the location(Outdoor Unit)1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
3) Select a well-drained place.
It should be strong enough like concrete to preventthe sea wind from the sea.
The height and width should be more than 150% ofthe outdoor unit.
It should be keep more than 70 cm of spacebetween outdoor unit and the windbreak for easyair flow.
Sea wind Sea wind
Sea wind
Windbreak
CAUTION
Installation Guide at the Seaside
Inverter Single46
6RMI0-02AInstallation
-
8/14/2019 6rmi0-02a 60hzr410a Mfl66305302 Epdb Srac Inv Csa
48/48
P/No.: MFL66305302
Air Conditioner20 Yeouido-dong, Yeongdeungpo-gu,Yeouido P.O.Box 335 Seoul,150-721, Korea.http://www.lgeaircon.com