6505-8
-
Upload
akhilkuwar -
Category
Documents
-
view
215 -
download
0
Transcript of 6505-8
-
8/2/2019 6505-8
1/18
CONCRETE MIX DESIGN
Objective of concrete mix design:
To determine the most economical and
practical combination of available materials
(i.e. aggregates, cements, water, admixtures,
etc.) to produce a concrete that will satisfy
the performance requirements.
Design Considerations:
Acceptable workability of fresh concrete.
Adequate durability and strength of
hardened concrete.
Uniform appearance of hardened concrete.
Economy.
-
8/2/2019 6505-8
2/18
Most Important Factor Affecting Workability: Water
Content
Most Important Factor Affecting Strength: Water-
Cement Ratio
Most Important Factors Affecting Durability: Water-
Cement Ratio and Cement Content
Most Important Factor Affecting Appearance:
Proportioning of fine and coarse aggregates
-
8/2/2019 6505-8
3/18
ABSOLUTE VOLUME METHOD
EXAMPLE 1
Design Criteria:Structure: Foundation
Exposure: Below ground, mild climate, no sulfates
Specified compressive strength, fc:
3,000 psi @ 28 days
Data not available to establish the standard deviation of
compressive strength.
Slump of fresh concrete: 3 - 4 inches
Properties of aggregates to be used:Coarse Agg. Fine Agg.
Spec. gravity 2.68 2.64
Absorption 0.5% 0.7%
Natural moisture 2% 6%
Dry-rodded unit wt. 100 pcf -
Nom. max. size of agg. 1.5 inches -
Fineness modulus - 2.8
Cement used: Type I, non-air-entraining
-
8/2/2019 6505-8
4/18
Design Procedures
(1) Determine Required Average Compressive Strength
When the standard deviation of the compressive strength is
known, the required average compressive strength, fcr is
equal to the larger of the following two values:
fcr = fc + 1.34 S
fcr = fc + 2.33 S - 500
where
fc = specified compressive strength, psi
S = standard deviation, psi
If data are not available to establish the standard deviationof the compressive strength, use Table 9-11.
-
8/2/2019 6505-8
5/18
-
8/2/2019 6505-8
6/18
-
8/2/2019 6505-8
7/18
(3) Determine Mixing Water Requirement & Air
Content
Mixing water (Table 9-5) : 300 lb / yd3 (3-4 in.slump, non-air-entra., nom. max. agg. size: 1.5 in.)
Air content (Table 9-5) : 1%
(4) Calculate Required Cement Content
Minimum cement content (Table 9-7): 470 lb/yd3
(This table is applicable since the concrete is to be
placed below ground)
Cement based on w/c : 300/0.55 = 545 lb/yd3
Use 545 lb/yd3
-
8/2/2019 6505-8
8/18
Water Requirement for Various Slumps and Aggregate Sizes
Water Requirement for Various Slumps and Aggregate Sizes
-
8/2/2019 6505-8
9/18
-
8/2/2019 6505-8
10/18
(7) Adjustments for Agg. Moisture
Wt. of agg. in natural moisture condition:
Coarse Agg.: 1917 X 1.02 = 1955 lb
Fine Agg.: 1266 X 1.06 = 1342 lb
Mixing water contributed by agg.:
Coarse Agg.: 1917 X (0.02 - 0.005) = 29 lb
Fine Agg.: 1266 X (0.06 - 0.007) = 67 lb
96 lb
Adjusted mixing water: 300 - 96 = 204 lb
-
8/2/2019 6505-8
11/18
-
8/2/2019 6505-8
12/18
Trial Mix
Under-sanded mix
Concrete mix with proper amount of sand
-
8/2/2019 6505-8
13/18
-
8/2/2019 6505-8
14/18
Check unit weight of trial mix
Check air content
of trial mix
-
8/2/2019 6505-8
15/18
EXAMPLE 2
Design Criteria:Structure: Loading-dock slab
Exposure: Severe freeze-thaw, no deicers or
sulfates
Specified compressive strength (fc) : 4,000
psi @ 28 days. Standard deviation of
compressive strength is 450 psi .
Slump of fresh concrete: 1 - 2 inches
Properties of aggregates to be used:
Coarse Agg. Fine Agg.
Spec. gravity 2.68 2.64
Absorption 0.5% 0.7%
Natural moisture 0.3% 0.5%
Dry-rodded unit wt. 102 pcf -
Nom. max. size of agg. 3/4 inch -
Fineness modulus - 2.8
Cement Used: Type I with air-entraining admixture
-
8/2/2019 6505-8
16/18
DESIGN PROCEDURES:
(1) Determine Required Average Compressive Strengthfcr = fc + 1.34 S
= 4000 + 1.34 (450)
= 4603 psi
fcr = fc + 2.33 S - 500
= 4000 + 2.33 (450) - 500
= 4549 psi
Use a required average compressive strength of 4603 psi.
(2) Determine Water Cement Ratio
w/c for strength (Table 9-3) : 0.43w/c for exposure (Table 9-1): 0.45
Design strength (4600 psi) > 4500 psi O.K.(Table 9-2 is not applicable)
Use w/c = 0.43(3) Determine Mixing Water Requirement & Air Content
Mixing water (Table 9-5) : 280 lb / yd3 (1-2 in. slump,air- entrained, nom. max. agg. size: 3/4 in.)
Air content (Table 9-5) : 6%(4) Calculate Required Cement Content
Minimum cement content (Table 9-7): 540 lb/yd3(For concrete to be placed on ground)
Cement based on w/c : 280/0.43 = 651 lb/yd3
Use 651 lb/yd3
-
8/2/2019 6505-8
17/18
(5) Determine Coarse Aggregate Content
Dry-rodded volume (Table 9-4) 0.62 yd3/yd3
(F.M. of sand = 2.8, nom. max. size = 3/4 inch)Dry wt. of C.A.per yd3 of concrete:
0.62 X 27 X 102 = 1707 lb.
(6) Determine Fine Aggregate Content
Absolute Volume of ingredients (per yd3)
Water 280/62.4 = 4.487 ft3
Cement 651/(3.15X62.4) = 3.312 ft3
C.A. 1707/(2.68X62.4) = 10.207 ft3
Air 0.06 X 27 = 1.62 ft3
Total = 19.626 ft
3
Absolute Volume of Sand = 27 - 19.626 = 7.374 ft3
Dry Wt. of sand = 7.374 X 2.64 X 62.4 = 1215 lb.
(7) Adjustments for Agg. MoistureWt. of agg. in natural moisture condition:
Coarse Agg.: 1707 X 1.003 = 1712 lb
Fine Agg.: 1215 X 1.005 = 1221 lb
Additional water needed:
Coarse Agg.: 1707 X (0.005 - 0.003) = 3.4 lb
Fine Agg.: 1215 X (0.007 - 0.005) = 2.4 lb
6 lb
Adjusted mixing water: 280 + 6 = 286 lb
-
8/2/2019 6505-8
18/18
Summary of Mix Ingredients for 1 yd3 of concrete
Water 286 lb
Cement 651 lb
Coarse Agg. 1712 lb
Fine Agg. 1221 lb
3870 lb
Calculated Unit Wt.: 3870/27 = 143.3 pcf