Specification Sheet Flow Computer Division Website: www.EmersonProcess.com 6.3:IOM2 September 2002 DI and PI Modules (ROC800-Series) Discrete Input (DI) and Pulse Input (PI) modules for the ROC800-Series Remote Operations Controller provide the ROC with the ability to monitor various discrete and pulse input field values. The maximum number of modules that a ROC809 can support is nine. The need for fuses has been eliminated on the Input/Output (I/O) modules through the extensive use of current-limiting short-circuit protection and surge protection techniques. This results in less maintenance for remote locations. The I/O modules are self-resetting after the fault clears. These modules can be installed in any module slot. Modules can easily be installed or removed from the module slots at any time by removing the two captive screws accessible from the front of the unit. Modules are hot-swappable, meaning the module can be removed and another module of the same type can be installed under power. The modules are hot-pluggable, meaning they may be installed directly into unused module slots under power. The modules are also self-identifying via ROCLINK™ 800 Configuration Software. All modules have removable terminal bocks for convenient wiring and servicing. The terminal blocks can accommodate a wide range of wire gauges up to 12 American Wire Gauge (AWG). Each module provides 2500 Volts DC of isolation from other modules and the backplane including power and signal isolation. The DI and PI modules each have their own integrated short-circuit protected isolated power supply. This power supply allows the field circuitry to be completely isolated from backplane and the Central Processor Unit (CPU). This protection limits current during a short-circuit and is auto-recoverable after the fault clears. Light-emitting diodes (LEDs) indicate the current status for each channel of the module. Discrete Inputs The Discrete Input (DI) modules module provides eight channels for measuring discrete inputs. The DI modules monitor the status of relays, open collector/ open drain type solid-state switches, and other two- state devices. Each DI channel can also be software configured to function as a latched DI. A latched DI remains in the active state until reset. Other parameters can invert the field signal and gather statistical information on the number of transitions and the time accumulated in the on or off state. The fastest time that each channel within the module can be read is 250 times per second. Externally Powered DeviceOpen Collector or Open Drain Type ROC809 Powered Dry Contact + + DI DIW11056.dsf +V Field Wiring Representative Internal Circuit 6.6 K Discrete Input Wiring Pulse Inputs The Pulse Input (PI) modules module provides two channels for measuring either a low speed or high speed pulse signal. The PI module processes signals from pulse-generating devices and provides a calculated rate or an accumulated total. The PI is most commonly used to interface to relays or open collector / open drain type solid-state devices. The Pulse Input can be used to interface to either self- powered or ROC800-Series powered devices. The high speed input supports signals up to 12 KHz while the low speed input is used on signals less than 125 Hz. D301175X012

Transcript of 63_IOM2

Specification Sheet

Flow Computer DivisionWebsite: www.EmersonProcess.com

6.3:IOM2September 2002

DI and PI Modules (ROC800-Series)Discrete Input (DI) and Pulse Input (PI) modules forthe ROC800-Series Remote Operations Controllerprovide the ROC with the ability to monitor variousdiscrete and pulse input field values. The maximumnumber of modules that a ROC809 can support isnine.

The need for fuses has been eliminated on theInput/Output (I/O) modules through the extensiveuse of current-limiting short-circuit protection andsurge protection techniques. This results in lessmaintenance for remote locations. The I/O modulesare self-resetting after the fault clears.

These modules can be installed in any module slot.Modules can easily be installed or removed from themodule slots at any time by removing the twocaptive screws accessible from the front of the unit.Modules are hot-swappable, meaning the modulecan be removed and another module of the sametype can be installed under power. The modules arehot-pluggable, meaning they may be installeddirectly into unused module slots under power. Themodules are also self-identifying via ROCLINK™800 Configuration Software.

All modules have removable terminal bocks forconvenient wiring and servicing. The terminalblocks can accommodate a wide range of wiregauges up to 12 American Wire Gauge (AWG).

Each module provides 2500 Volts DC of isolationfrom other modules and the backplane includingpower and signal isolation.

The DI and PI modules each have their ownintegrated short-circuit protected isolated powersupply. This power supply allows the field circuitryto be completely isolated from backplane and theCentral Processor Unit (CPU). This protection limitscurrent during a short-circuit and is auto-recoverableafter the fault clears.

Light-emitting diodes (LEDs) indicate the currentstatus for each channel of the module.

Discrete Inputs

The Discrete Input (DI) modules module provideseight channels for measuring discrete inputs. The DImodules monitor the status of relays, open collector/open drain type solid-state switches, and other two-state devices. Each DI channel can also besoftware configured to function as a latched DI. Alatched DI remains in the active state until reset.Other parameters can invert the field signal andgather statistical information on the number oftransitions and the time accumulated in the on or offstate. The fastest time that each channel within themodule can be read is 250 times per second.

ExternallyPoweredDeviceOpen Collector

orOpen Drain Type

ROC809 PoweredDry Contact

+–

+–

DI

DIW11056.dsf

+V

Field WiringRepresentativeInternal Circuit

6.6 K Ω

Discrete Input Wiring

Pulse Inputs

The Pulse Input (PI) modules module provides twochannels for measuring either a low speed or highspeed pulse signal. The PI module processessignals from pulse-generating devices and providesa calculated rate or an accumulated total. The PI ismost commonly used to interface to relays or opencollector / open drain type solid-state devices. ThePulse Input can be used to interface to either self-powered or ROC800-Series powered devices. Thehigh speed input supports signals up to 12 KHzwhile the low speed input is used on signals lessthan 125 Hz.

D30

1175

X01

2

Specification Sheet6.3:IOM2

Page 2

External PoweredOpen Collector or

Open Drain Device

Channel High

PIW11059.dsf

PI

12 KHz PI& Level Detection

125 Hz PI& Level Detection External Powered

Contact-ClosureDevice

Channel Low

Field WiringRepresentativeInternal Circuit

+

+

L

H

L

H

Pulse Input Wiring (externally powered)

ROC800 PoweredOpen Collector or

Open Drain Device

Channel High

PIW1105a.dsf

PI

Meter Coil

– +

Field Wiring

12 KHz PI& Level Detection

RepresentativeInternal Circuit

+

+T

L

H

L

H

Pulse Input Wiring (ROC800-Series powered)

Discrete Input Module Specifications

FIELD WIRING TERMINALS

Terminal Label Definition1 CH 1 CH1 Positive2 CH 2 CH 2 Positive3 CH 3 CH 3 Positive4 CH 4 CH 4 Positive5 CH 5 CH 5 Positive6 CH 6 CH 6 Positive7 CH 7 CH 7 Positive8 CH 8 CH 8 Positive9 COM Common10 COM Common

INPUTQuantity: 8 channels.

Type: Optically isolated inputs, common voltagesource.

Minimum Scan Period: 4 msec.

Input Impedance: 6.6 KΩ.

Maximum Input Overload Voltage: ±24 Volts DC,continuous.

Minimum On-state Input Current: 1.1 mA.

Maximum Off-state Input Current: 0.35 mA.

POWER CONSUMPTIONMain power supply loading at the Battery Terminals(at 12.0 Volts DC):

No Channels Active: 19mA

Additional loading that may apply:

Per Active Channel: 3.2 mA

Per Active LED: 1.5mA

WIRING12 AWG at the removable terminal block.

LEDS8 green LEDs indicate the status of the channels.

ISOLATIONField to Logic: 2500 Volts DC, 1 minute minimum.

Field to Power: 2500 Volts DC, 1 minute minimum.

Module to Module: 2500 Volts DC, 1 minuteminimum.

WEIGHT49.9 g (1.76 oz).

Specification Sheet6.3:IOM2

Page 3

Pulse Input Module Specifications

FIELD WIRING TERMINALS

Terminal Label Definition1 CH1 L CH1 Low Speed2 CH1 H CH 1 High Speed3 COMM CH 1 Common4 COMM CH 1 Common5 CH2 L CH 2 Low Speed6 CH2 H CH 2 High Speed7 COMM CH 2 Common8 COMM CH 2 Common9 +T Loop Power10 +T Loop Power

INPUTQuantity: 2-channels.

Type: Optically isolated inputs, common voltagesource, and terminal selectable high/low speedhardware filter on each channel.

Filter Cutoff Frequency:High Speed Input: 12 KHz.Low Speed Input: 125 Hz.

Input Impedance: 2 KΩ.typical

Minimum On-State Input Current: 2.00 mA.

Maximum Off-State Input Current: 1.7 mA.

POWER CONSUMPTIONMain power supply loading at the Battery Terminals(at 12.0 Volts DC):

No Channels Active: 21mA

Additional loading that may apply:

Per Active Channel: 7.4 mA

Per Active LED: 1.5mA

+T @ 12V: 1.25 * Measured Current Draw at+T Terminal

+T @ 24V: 2.5 * Measured Current Draw at+T Terminal

WIRING12 AWG at the removable terminal block.

LEDS2 green LEDs indicate the status of the channels.

ISOLATIONField to Logic: 2500 Volts DC, 1 minute minimum.

Field to Power: 2500 Volts DC, 1 minute minimum.

Module to Module: 2500 Volts DC, 1 minuteminimum.

WEIGHT56.7 g (2.0 oz).

Specification Sheet

Emerson Process Management

Flow Computer DivisionMarshalltown, IA 50158 U.S.A.Houston, TX 77065 U.S.A.Pickering, North Yorkshire UK Y018 7JA

© Fisher Controls International, Inc. 2002. All Rights Reserved.

6.3:IOM2Page 4

Discrete Input and Pulse Input Common Specifications

DIMENSIONSAll I/O modules for the ROC800-Series unit have thesame dimensions and are designed to fit in anymodule slot.

26 mm W by 133 mm H by 75 mm D(1.04 in. W by 5.25 in. H by 2.96 in. D).

ENVIRONMENTAL

Operating Temp: -40 to 85°C (-40 to 185°F).

Storage Temp: -55 to 100°C (-67 to 212°F).

Relative Humidity: IEC68-2-3; 5-95% non-condensing.

Vibration: IEC68-2-6; 0.15 mm/sec2 @ 10-150 Hz.

Mechanical Shock: IEC68-2-27; 11 ms, sinusoidal50 Gs non-operating, 15 Gs operating.

Thermal Shock: IEC68-2-14; Air to air from -20 to85°C (-4 to 185°F).

APPROVALSComplies with the CE certifications:EN55011 (Emissions).EN61000-4-2 (Electrostatic Discharge Immunity).EN61000-4-4 (Electrical Fast Transients Immunity).EN61000-4-6 (Conducted Immunity).EN61000-4-8 (Power Frequency Magnetic FieldImmunity).EN61000-6-2 (Radiated RF Immunity).

Meets CSA Standards:CSA 22.2 No. 14-91M.CSA 22.2 No. 213-M1987.Class I, Division 2, Groups A, B, C, and D.

ROCLINK is a mark of one of the Emerson Process Management companies. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks arethe property of their respective owners.

The contents of this publication are presented for informational purposes only. While every effort has been made to ensure informational accuracy, they are not tobe construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Fisher Controlsreserves the right to modify or improve the designs or specifications of such products at any time without notice. The contents of this publication are presented forinformational purposes only. While every effort has been made to ensure informational accuracy, they are not to be construed as warranties or guarantees, expressor implied, regarding the products or services described herein or their use or applicability. Fisher Controls reserves the right to modify or improve the designs orspecifications of such products at any time without notice.