4446&4473
-
Upload
sunil-pillai -
Category
Documents
-
view
243 -
download
0
Transcript of 4446&4473
-
8/9/2019 4446&4473
1/43
Distributed Control System DEVLOPED AT RELIANCE INDUSTRIES
Prepared by : -
Chirag Chavda
Haresh Patel
-
8/9/2019 4446&4473
2/43
Evolution of discrete control
(relays) More recently relays has been used for control and
early electrical control was based on relays.
These relays allow power to be switched on and off
without a mechanical switch.
It is common to use relays to make simple logical
control decisions.
Modern control systems still include
relays, but these are rarely used forlogic. A relay is a simple device that
uses a magnetic field to control a
switch.
-
8/9/2019 4446&4473
3/43
When a voltage is applied
to the input coil, the
resulting current
creates a magnetic field.
The magnetic field pulls
a metal switch (or reed) towards
it and the contacts touch,
closing the switch. The contact
that closes when
the coil is energized is called
normally open. The normally closed
contacts touch when the input coilis not energized. When the input coil
is not energized the normally closed
contacts will be closed (conducting).
Contd..
-
8/9/2019 4446&4473
4/43
What is Relay ?
A relay is a simple device that uses magnetic fieldto control a switch.
In the fig.1 we see a 4 - pin relay. Relays have twocircuits: A control circuit (shown in GREEN) and aload circuit (shown in RED). The control circuit hasa small control coil while the load circuit has aswitch. The coil controls the operation of theswitch.
Current flowing through the control circuit coil (pins1 and 3) creates a small magnetic field whichcauses the switch to close, pins 2 and 4 as in fig.2.
The switch, which is part of the load circuit, is usedto control an electrical circuit that may connect to it.Current now flows through pins 2 and 4 shown inRED, when the relay is energized.
Fig, 1
Fig, 2
-
8/9/2019 4446&4473
5/43
Contd..
ACTUAL RELAY DESIGN
Current flows through thecontrol coil, which iswrapped around an iron
core. The iron coreintensifies the magneticfield. The magnetic fieldattracts the upper contactarm and pulls it down,closing the contacts andallowing power from thepower source to go to theload.
-
8/9/2019 4446&4473
6/43
Contd..
INSTRUMENT
TASK 1
(RELAY 1)
TASK 2
(RELAY 2)
TASK 3
(RELAY 3)
-
8/9/2019 4446&4473
7/43
PLC evolution
PLC was developed keeping the limitationsof the relay based control.
In the late 1970s with the introduction ofpthe basic capabilities of PLC were greatlyexpanded and improved. They were able toperform sophisticated math and datamanipulation functions, which greatlyincreased the use of programmablecontrollers in more complex controlapplications.
-
8/9/2019 4446&4473
8/43
PLC Defined
The National Electrical ManufacturersAssociation (NEMA), USA, definesprogrammable controller as a digitalelectronic apparatus with a programmablememory for storing instructions toimplement specific functions, such as logic,sequencing, timing, counting andarithmetic, to control machines andprocesses.
-
8/9/2019 4446&4473
9/43
Advantages ofPLC
Smaller physical size than hard-wiresolutions.
Cost effective for controlling complexsystems.
Easier and faster to make changes. PLCs have integrated diagnostics and
override functions. Diagnostics are centrally available. Applications can be immediately
documented.
-
8/9/2019 4446&4473
10/43
Contd..
Applications can be duplicated faster and lessexpensively.
Computational abilities allow more
sophisticated control. Trouble shooting aids make programming
easier and reduce downtime. Reliable components make these likely to
operate for years before failure. Ability to communicate with computer
-
8/9/2019 4446&4473
11/43
Application
Sequence control, timing, counting, datacalculation
Batch or continuous process control. Open loop or feedback process control,
process data acquisition and display. Precise motion / position control.
Safety and Interlocks Alarm handling Sequence Of Events (SOE)
-
8/9/2019 4446&4473
12/43
Components ofPLC Systems
POWER
SUPPLY
PROCESSOR
PROGRAMMING
DEVICEMEMORY
I/O SYSTEMINPUTS
OUTPUTS
-
8/9/2019 4446&4473
13/43
How PLCs Work ?
All PLCs contain a Central Processing Unit (CPU), Memory, Power supply,Input / Output modules and programming device.
-
8/9/2019 4446&4473
14/43
PLC Operation
A PLC works by continually scanninga program. We can think of this scan
cycle as consisting of 3 important steps. There are typically more than 3 but we
can focus on the important parts and not worry about the others. Typically the
others are checking the system and updating the current internal counter and
timer values.
Step 1-CHECK INPUT STATUS-First the PLC takes a look at each input to
determine if it is on or off. In other words, is the sensor connected to the first
input on? How about the second input? How about the third... It records thisdata into its memory to be used during the next step.
-
8/9/2019 4446&4473
15/43
Contd..
Step 2-EXECUTE PROGRAM-Next the PLC executes your program one
instruction at a time. Maybe your program said that if the first input was on
then it should turn on the first output. Since it already knows which inputs
are on/off from the previous step it will be able to decide whether the first
output should be turned on based on the state of the first input. It will storethe execution results for use later during the next step.
Step 3-UPDATE OUTPUT STATUS-Finally the PLC updates the status of theoutputs. It updates the outputs based on which inputs were on during thefirst step and the results of executing your program during the second step.Based on the example in step 2 it would now turn on the first outputbecause the first input was on and your program said to turn on the firstoutput when this condition is true.
After the third step the PLC goes back to step one and repeats the stepscontinuously. One scan time is defined as the time it takes to execute the 3steps listed above.
-
8/9/2019 4446&4473
16/43
A Level Application
Let's consider the following application:
We are controlling lubricating oil being dispensed from a tank. This is possibleby using two sensors. We put one near the bottom and one near the top, as
shown in the picture.
Here, we want the fill motor to pump lubricating oil into the tank until the high
level sensor turns on. At that point we want to turn off the motor until the level
falls below the low level sensor. Then we should turn on the fill motor andrepeat the process.
-
8/9/2019 4446&4473
17/43
Here we have a need for 3 I/O (i.e. Inputs/Outputs). 2 are inputs (the sensors)
and 1 is an output (the fill motor). Both of our inputs will be NC (normally
closed) level sensors. When they are NOT immersed in liquid they will be ON.
When they are immersed in liquid they will be OFF.
We will give each input and output device an address. This lets the plc knowwhere they are physically connected. The addresses are shown in the following
tables:
Inputs Address Output Address Internal Utility Relay
Low 0000 Motor 0500 1000
High 0001
A Level Application
-
8/9/2019 4446&4473
18/43
Below is what the ladder diagram will actually look like. Notice that we
are using an internal utility relay in this example. You can use the
contacts of these relays as many times as required. Here they are used
twice to simulate a relay with 2 sets of contacts. Remember, these relays
DO NOT physically exist in the plc but rather they are bits in a register
that you can use to SIMULATE a relay.
A Level Application
http://opt/scribd/conversion/tmp/scratch2745/D:/spm/Presentations/plc/PLC%20Animation.htm -
8/9/2019 4446&4473
19/43
Ladder Diagram (LAD)
-
8/9/2019 4446&4473
20/43
Scan time
Star output
scan
Start cycleOutput scan Input Scan
Start program
scan
Control program
scan
The input and output scans are normally very short relative to the time
required for the program scan
-
8/9/2019 4446&4473
21/43
Contd..
INSTRUMENT
(PLC)
TASK 1
(RELAY 1)
TASK 2
(RELAY 2)
TASK 3
(RELAY 3)
1000 RELAYS=1 PLC
-
8/9/2019 4446&4473
22/43
Triconex PLC
-
8/9/2019 4446&4473
23/43
PLCs in the Market
Triconex
Allen Bradley
Siemens Hitachi
GE Fanuc
Hima-Sella
Modicon
Mitsubishi
-
8/9/2019 4446&4473
24/43
DCS CENTUM XL DCS
-
8/9/2019 4446&4473
25/43
BENEFITS - DCS
Information is compressed into area that the eye can scan without head
movement.If economy permits, 2 to 3 CRTs are recommended.
One for overview display.
One for current interest group or graphics display.
One for alarm summary display.More concentration of centralized information.Ease of accessing display information through keyboard.Direct overview of entire process.Ability to anticipate incipient upsets.
Improved operator performanceHigher Degree of hardware standardization.Greater Controllability of Process Variables.
-
8/9/2019 4446&4473
26/43
WHY DISTRIBUTED
CONTROL?
MANAGEMENT Cost Reduction of Control Installation
By Reducing Number of Wires for signal transmission.
Inbuilt Algorithms in place of signal conditioning devices.
Less No. of Panels.
Panel Space Saving.
Control Room Design.
Cost of Heating, Ventilation, air conditioning.
Cost of Future Expansion Scalability of DCSMotorStarters
Servo motors
-
8/9/2019 4446&4473
27/43
Contd..
CENTUM XL DCS
-
8/9/2019 4446&4473
28/43
Access Control : Token Passing
Trans. Speed : 1 Mbps
Trans. Distance : 1 Km to 20km
Media : Coaxial/Optical Fibre
HF
EOPCEOPS
HF BUS
-
8/9/2019 4446&4473
29/43
STATION CAPACITY
Feedback Insts 255
Control Loops 80
Compu Expression 255
BSI 32
Switch Instruments 255
Valve o/p Monitoring 255
Sequence Tables 200
Internal Switches 2048
Contact Inputs 512
Contact Outputs 512
Timers 511
PresetCounters
Code Inputs
Code Outputs
Annunciator
message
255
Relational Exp 255
Sequence
Mess
255
-
8/9/2019 4446&4473
30/43
FCS Station display
-
8/9/2019 4446&4473
31/43
ENG
INEER
ING
STA
TION
SYSTEM GENERATION
ON STAND-ALONE
STATION
OPERATOR STATION
BUILDER
MOUSE DRIVEN
ISA SYMBOLS
CONTROL STATION
BUILDER
LOOP DIAG
SELF DOCUMENTATION
MULTI-WINDOW ENGS
-
8/9/2019 4446&4473
32/43
Powerful man /
machine
interface
Large application
capacity
Compact size
simplifies control
room layout
* 1 Second display update rate for operator
console display * Touch panel
* Powerful
graphic display
panel*Multi window
* Voice message output
*Super window
* 16- color display
* Basic language
* Upto 300 graphic display
* 16000 tags * 2,560 trend points * Compact * Support large screen CRT
EOPS
M
-
8/9/2019 4446&4473
33/43
MUL
TI-WIN
DOWE
OPS
-
8/9/2019 4446&4473
34/43
EOPS CAPACITY
FUNCTION MEMORYCAPACITY
NO. OF TAGS : max. 16000 MEMORY : 8 MB
NO. OF TREND POINTS: max2304
HARD DISK : 80MB
GRAPHIC PABNELS : 300 pages
BASIC USER AREA : 5 MB
NO. OF CRTs : upto 4
NO. OF PRINTERS : upto 4
NO. OF HARD COPIER : max 1
-
8/9/2019 4446&4473
35/43
Block diagram of DCS
-
8/9/2019 4446&4473
36/43
Contd
The arrow shows how the process has been done? Its a bi-directional process. It Controls the whole plant through control room. Its a heart of a DCS system. It shows that the how DCS is actually working? In Diagram All diagrams have their own number. And according to their numbers Process has been
done. So, this type DCS can actually work. the detail
description of it is shown into the Closed loop.
-
8/9/2019 4446&4473
37/43
EOPSPAN
EL
ORGANISATION
-
8/9/2019 4446&4473
38/43
Trend Panel
-
8/9/2019 4446&4473
39/43
SECURITY KEY
64 ONE-TOUCH FUNCTION
KEYS
DISPLAY PANELS
START BASIC
LOGGING REPORT
-
8/9/2019 4446&4473
40/43
Closed loop
-
8/9/2019 4446&4473
41/43
Contd..
For any Closed loop that are different parts as shown inupper figure.
In figure up to the junction box, that part is as the field side. While the other parts are at the control room.
In control room, the whole wires are comes in to the terminalbox, then it goes into the Barrier & redundancy.
Barrier provides 24V D.C. Supply, isolation, provide 4 to 20mA current and also adjust its current.
Then it goes into the Elco Board ,in this part 8 wires areconverted into 1 wire.
That wires are gone into Processor & Controller part. And this is a Bidirectional System. So, after applying logic it
goes into field side, into similar manner.
-
8/9/2019 4446&4473
42/43
Table of other DCS systems
Sr.no. Company name Models Year1 Yokogawa Centum series 19752 Honeywell TDC-2000,3000 1975
3 Taylor Mod III,Mod 300 1976
4 Hokushin 900/TX 19765 Foxboro SPECTRUM 1979
6 B.s.kent P4000(KELTRON) 1979 7 Fisher & porter DCF4000 1979
8 Beckman MV8000 1979
9 Fisher controls FISHER PROVOX 1979
10 Moore MYCRO 198011 Bailey NETWORK90 1980 12 Leed & Northup MAX-1 1980
-
8/9/2019 4446&4473
43/43
Any Queries????