SIRIUS 3RW44 manualGWA 4NEB 535 2195-02 DS 06 9-1
Circuit Examples 9Chapter Subject Page
9.1 Connection Examples for Main and Control Circuits 9-2
9.1.1 3RW44 in a Standard Circuit with Control via Keys 9-2
9.1.2 3RW44 in a Standard Circuit with Line Contactor and Control via PLC 9-3
9.1.3 3RW44 in a Standard Circuit and DC Braking Stopping Function for
Device Types 3RW44 22 to 3RW44 25
9-4
9.1.4 3RW44 in a Standard Circuit and DC Braking Stopping Function for
Device Types 3RW44 26 to 3RW44 47
9-5
9.1.5 3RW44 in an Inside Delta Circuit 9-6
9.1.6 3RW44 in a Standard Circuit and Control as per Contactor 9-7
9.1.7 3RW44 in a Standard Circuit with Soft Start/Stop and Additional Slow
Speed Function in both Directions of Rotation with one Parameter Set
9-8
9.1.8 Activation via PROFIBUS with Switching to Manual Operation Local (e.
g. at the Control Cabinet)
9-9
9.1.9 3RW44 in a Standard Circuit and Reversing Operation via MainContactors with one Parameter Set without Soft Stop 9-10
9.1.10 Reversing Operation with Soft Stop 9-11
9.1.11 Soft Starter for Pole-Changing Motor with Separate Windings and 2
Parameter Sets
9-12
9.1.12 Soft Starters for Dahlander Motors with 2 Parameter Sets 9-13
9.1.13 Parallel Starting of 3 Motors 9-14
9.1.14 Soft Starter for Serial Starting with 3 Parameter Sets 9-16
9.1.15 Soft Starter for Activation of a Motor with a Magnetic Fixing Brake 9-18
9.1.16 Emergency Stop Monitoring according to EN 954-1 Category 4 with
Safety Relay 3TK2823 and 3RW44
9-19
9.1.17 Soft Starter with Direct Switching (DOL) as Emergency Start 9-21
9.1.18 Soft Starter with Star-Delta Starter as Emergency Start (3RW44 in a
Standard Circuit)
9-22
9.1.19 Soft Starter and Frequency Converter on one Motor 9-23
http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
2/23
Circuit Examples
SIRIUS 3RW44 manual9-2 GWA 4NEB 535 2195-02 DS 06
9.1 Connection Examples for Main and Control Circuits
9.1.1 3RW44 in a Standard Circuit with Control via Keys
Alternative branch layout in a standard circuit
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
Main circuit Control circuit
Option 1a:
Standard circuit with circuit breaker and SITOR fuse(pure semiconductor protection)
Main circuit
Option 1b: Option 1c:
Standard circuit with all-range fuse(line and semiconductor protection) Standard circuit with line and SITOR fuse (puresemiconductor protection)
I >> I >> I >>
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
3/23
Circuit Examples
SIRIUS 3RW44 manualGWA 4NEB 535 2195-02 DS 06 9-3
9.1.2 3RW44 in a Standard Circuit with Line Contactor and Control via PLC
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
2) Caution: risk of restart!The start command (e.g. via PLC) must be reset when a group fault occurs, since an automatic restart is
executed when a start command is pending after the reset command is issued. This particularly applies to
motor protection tripping.
For safety reasons, we recommend integrating the group error output (terminals 95 and 96) into the control.
Main circuit Control circuit
Standard circuit with optional main contactor Activation of an optional main contactor and activation via PLC
I >> I >> I >>
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
4/23
Circuit Examples
SIRIUS 3RW44 manual9-4 GWA 4NEB 535 2195-02 DS 06
9.1.3 3RW44 in a Standard Circuit and DC Braking3) Stopping Function for Device Types
3RW44 22 to 3RW44 25
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
2)
2) Caution: risk of restart!
The start command (e.g. by the PLC) must be reset before a reset command is issued, as an automatic
restart is executed when a start command is pending after the reset command is issued. This particularly
applies to motor protection tripping. For safety reasons, we recommend integrating the group error output
(terminals 95 and 96) into the control.
3) If the "Combined braking" stopping function is selected, no braking contactor is required.
If the "DC braking" function is selected, a braking contactor must be additionally used.
For types, refer to the "Branch component layout (standard circuit)" table on page 10-21.The "DC braking" function is recommended for applications with larger centrifugal masses ( J load > J motor ).
Output 2 must be set to "DC braking contactor".
Main circuit Control circuit
I >> I >> I >>
http://-/?-http://-/?-http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
5/23
Circuit Examples
SIRIUS 3RW44 manualGWA 4NEB 535 2195-02 DS 06 9-5
9.1.4 3RW44 in a Standard Circuit and DC Braking3) Stopping Function for Device Types 3RW44 26
to 3RW44 66
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.2)
2) Caution: risk of restart!
The start command (e.g. by the PLC) must be reset before a reset command is issued, since an automaticrestart is executed when a start command is pending after the reset command is issued. This particularly
applies to motor protection tripping. For safety reasons, we recommend integrating the group error output
(terminals 95 and 96) into the control.
3) If the "Combined braking" stopping function is selected, no braking contactor is required.
If the "DC braking" function is selected, a braking contactor must be additionally used. For types, refer to
the "Branch component layout (standard circuit)" table on page 10-21.The "DC braking" function is recommended for applications with larger centrifugal masses ( J load > J motor ).
Output 2 must be set to "DC braking contactor".
4) K4 auxiliary relay, e.g.:
LZX:RT4A4T30 (230 V AC rated control supply voltage),
LZX:RT4A4S15 (115 V AC rated control supply voltage).
Main circuit Control circuit
I >> I >> I >>
http://-/?-http://-/?-http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
6/23
Circuit Examples
SIRIUS 3RW44 manual9-6 GWA 4NEB 535 2195-02 DS 06
9.1.5 3RW44 in an Inside Delta Circuit
Reversed direction of rotation in an inside delta circuit
Main circuit Option 1a: Control circuit Option 1: Activation via PLC
Main circuit Option 1b:
Notice Observe the wiring suggestions for the inside delta circuit on the main
circuit page. Faulty connection may cause breakdowns.
1) For permissible main and control voltage values, refer to Technical Data,pages 10-12 to 10-16.
2) Caution: risk of restart!The start command (e.g. by the PLC) must be reset before a reset
command is issued, as an automatic restart is executed when a start
command is pending after the reset command is issued. This
particularly applies to motor protection tripping.
For safety reasons, we recommend integrating the group error output
(terminals 95 and 96) into the control.
I >> I >> I >>
I >> I >> I >>
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
7/23
Circuit Examples
SIRIUS 3RW44 manualGWA 4NEB 535 2195-02 DS 06 9-7
9.1.6 3RW44 in a Standard Circuit and Control as per Contactor
Note
With this circuit type, the motor start may be delayed by up to 5 s after the start command, due to the
internal run times of the soft starter. Coasting down is the only possible stopping mode.
Notice
After the control supply voltage has been switched off and before restarting, the
device must be allowed to cool down for at least 30 s, as this influences the
effectiveness of the inherent protection of the soft starter.
This type of circuit is not recommended for higher switching frequencies as the
integrated fan cannot idle after the soft starter has been switched off, thus
reducing the switching frequency specified in the technical data.
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
Control circuit Main circuit
I >> I >> I >>
Us
t
>30 sON
OFF
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
8/23
Circuit Examples
SIRIUS 3RW44 manual9-8 GWA 4NEB 535 2195-02 DS 06
9.1.7 3RW44 in a Standard Circuit with Soft Start/Stop and Additional Slow Speed Function in both
Directions of Rotation with one Parameter Set
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
I > >
I > >
I > >
N o t e : p a r a m e t e r i z a t i
o n
S e t t h e c o n t r o l i n p u t f u n c t i o n s t o :
I N 1 : M o t o r r i g h t P S 1
I N 2 : M o t o r l e f t P S 1
I N 3 : S l o w - s p e e d m o d e
I N 4 : T r i p / r e s e t ( f a c t o r y d e f a u l t )
T h e s l o w - s p e e d p a r a m
e t e r s i n P a r a m e t e r S e t 1 m u s t b e s e t . M
o t o r r i g h t m e a n s r o t a t i o n i n l i n e p h a s e d
i r e c t i o n , m o t o r l e f t m e a n s r o t a t i o n a g a i n
s t t h e l i n e
p h a s e d i r e c t i o n .
N o t i c e
T h e s l o w - s p e e d f u n c t i o n i s n o t s u i t a b l e f o r c o n t i n u o u s o p e r a t i o n . T h e m o t o r h e a t i n g c a n b e c o m e u n r e l i a b l e i n c o n t i n u o u s o p e r a t i o n a t s l o w s p e
e d .
C a u t i o n - r i s k o f r e s t a r t :
T h e s t a r t c o m m a n d m
u s t b e r e s e t b e f o r e a r e s e t c o m m a n d i s i s s u e d , a s a n a u t o m a t i c r e s t a r t i s e x e c u t
e d w h e n a s t a r t c o m m a n d i s p e n d i n g a f t e r t h e r e s e t
c o m m a n d i s i s s u e d . T
h i s e s p e c i a l l y a p p l i e s t o m o t o r p r o t e c t i o n t r i p p i n g .
K 1 , K 2 , K 3 = r e l a y s f o
r c o n t a c t m u l t i p l i c a t i o n , e . g . f o r 2 3 0 V A C
o p e r a t i o n : 3 R S 1 8 0 0 - 1 B P 0 0
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
9/23
Circuit Examples
SIRIUS 3RW44 manualGWA 4NEB 535 2195-02 DS 06 9-9
9.1.8 Activation via PROFIBUS with Switching to Manual Operation Local
(e. g. at the Control Cabinet)
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
I > >
I > >
I > >
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
10/23
Circuit Examples
SIRIUS 3RW44 manual9-10 GWA 4NEB 535 2195-02 DS 06
9.1.9 3RW44 in a Standard Circuit and Reversing Operation via Main Contactors with one
Parameter Set without Soft Stop
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
I > >
I >
>
I > >
N o t i c e
T h e " C o a s t i n
g d o w n " s t o p p i n g m o d e m u s t b e
s e t o n t h e 3 R W 4 4 .
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
11/23
Circuit Examples
SIRIUS 3RW44 manualGWA 4NEB 535 2195-02 DS 06 9-11
9.1.10Reversing Operation with Soft Stop
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
I > >
I > >
I > >
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
12/23
Circuit Examples
SIRIUS 3RW44 manual9-12 GWA 4NEB 535 2195-02 DS 06
9.1.11 Soft Starter for Pole-Changing Motor with Separate Windings and
2 Parameter Sets
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
I > >
I > >
I > >
N o t i c e
T h e " C o a s t i n g d
o w n " s t o p p i n g m o d e m u s t b e s e t o n t h e 3 R W 4 4 .
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
13/23
Circuit Examples
SIRIUS 3RW44 manualGWA 4NEB 535 2195-02 DS 06 9-13
9.1.12Soft Starters for Dahlander Motors with 2 Parameter Sets
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
I > >
I > >
I > >
N o t i c e
T h e " C o a s t i n g d o w n " s t o p p i n g m o d e m u s t b e s e t
o n t h e 3 R W 4 4 .
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
14/23
Circuit Examples
SIRIUS 3RW44 manual9-14 GWA 4NEB 535 2195-02 DS 06
9.1.13Parallel Starting of 3 Motors
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
Notice
The rated output of the 3RW44 to be configured must be at least as high as the sum of the motor rated
outputs.
The loads should have similar mass moments of inertia and torque curves.
Control circuit
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
15/23
Circuit Examples
SIRIUS 3RW44 manualGWA 4NEB 535 2195-02 DS 06 9-15
Parallel Starting of 3 Motors
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
Notice
The rated output of the 3RW44 to be configured must be at least as high as the sum of the motor rated
outputs.
The loads should have similar mass moments of inertia and torque curves.
Main circuit
I >> I >> I >>
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
16/23
Circuit Examples
SIRIUS 3RW44 manual9-16 GWA 4NEB 535 2195-02 DS 06
9.1.14Soft Starter for Serial Starting with 3 Parameter Sets
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
N o t i c e
T h e " C o a s t i n g d o w n " s t o p p i n g m o d e m u s t b e s e t o n t h e 3 R W 4 4 .
N o t e
I n t h e c a s e o f i n c r e a s e d o p e r a t i n g s e q u e n c e s , t h e 3 R W 4 4 s h o u l d b e d i m e n s i o n e d a t l e a s t o n e c a p a c i t y
l e v e l h i g h e r t h a
n t h e h i g h e s t c o n n e c t e d m o t o r o
u t p u t .
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
17/23
Circuit Examples
SIRIUS 3RW44 manualGWA 4NEB 535 2195-02 DS 06 9-17
Soft starter for serial starting with 3 parameter sets (deactivate soft stop and 3RW44 motor
protection)
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
Note
In the case of increased operating sequences, the 3RW44 should be dimensioned at least one capacity level
higher than the highest connected motor output.
Notice
The "Coasting down" stopping mode must be set on the 3RW44.
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
18/23
Circuit Examples
SIRIUS 3RW44 manual9-18 GWA 4NEB 535 2195-02 DS 06
9.1.15Soft Starter for Activation of a Motor with a Magnetic Fixing Brake
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
I > >
I > >
I > >
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
19/23
Circuit Examples
SIRIUS 3RW44 manualGWA 4NEB 535 2195-02 DS 06 9-19
9.1.16Emergency Stop Monitoring according to EN 954-1 Category 4 with Safety Relay 3TK2823
and 3RW44
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
N o t i c e
I f a s t o p p i n g f u n c t i o n h a s b e e n s e t ( e x c e p t i o n : " C o a s t i n g d o w n " ) , a f a u l t m e s s a g e m a y o c c u r o n t h e s o f t s t a r t e r
w h e n t h e E m e r g e n c
y O f f c i r c u i t i s a c t i v a t e d ( e . g . " L o
s s o f p h a s e L 1 / L 2 / L 3 " o r " N o l i n
e v o l t a g e " ) .
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
20/23
Circuit Examples
SIRIUS 3RW44 manual9-20 GWA 4NEB 535 2195-02 DS 06
Emergency stop monitoring according to EN 954-1 category 4 with safety relay 3TK2823 and 3RW44
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
Notice
If a stopping function has been set (exception: "Coasting down"), a fault message may occur on the soft
starter when the Emergency Off circuit is activated (e.g."Loss of phase L1/L2/L3" or "No line voltage").
Main circuit
I >> I >> I >>
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
21/23
Circuit Examples
SIRIUS 3RW44 manualGWA 4NEB 535 2195-02 DS 06 9-21
9.1.17Soft Starter with Direct Switching (DOL) as Emergency Start
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
I > >
I > >
I > >
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
22/23
Circuit Examples
SIRIUS 3RW44 manual9-22 GWA 4NEB 535 2195-02 DS 06
9.1.18Soft Starter with Star-Delta Starter as Emergency Start (3RW44 in a Standard Circuit)
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
I > >
I > >
I > >
http://-/?-http://-/?-
-
8/21/2019 3rw Schematic
23/23
Circuit Examples
9.1.19Soft Starter and Frequency Converter on one Motor
1) For permissible main and control voltage values, refer to Technical Data, pages 10-12 to 10-16.
I > >
I > >
I > >