NFPA 13-1999 FAQs
NFPA131999FAQs
ResponsestoFAQsarepreparedbyNFPAtechnicalstafftoassistusersinreadingandunderstandingNFPAcodesandstandards.Theresponses,however,arenotFormalInterpretationsissuedpursuanttoNFPARegulations.Anyopinionsexpressedarethepersonalopinionsoftheauthor(s),anddonotnecessarilyrepresenttheofficialpositionoftheNFPAoritsTechnicalCommittees.Inaddition,theresponsesareneitherintended,norshouldbereliedupon,toprovideprofessionalconsultationorservices.
1. DoIneedsprinklersinmybuilding?NFPA13istheNFPAdocumentthatspecifiestheminimumrequirementsfordesigningandinstallingsprinklersystems.Itdoesnotspecifywhichbuildingsrequireasprinklersystem.TherequirementtoinstallasprinklersystemcomplyingwithNFPA13canusuallybefoundinoneofthefollowingsources:buildingcode;federal,stateorlocalregulations;insurer'srequirements;accreditationrequirements;orowner'srequest.
2. IfIhaveadrypipesprinklersystemunderapitchedroofexceedingaslopeof16.7%,doIapplybothareaincreasesfromSection72.3.2.5andSection72.3.2.6?Yes,bothsectionswouldbeappliedcumulativelytothedesignareachosenfromFigure72.3.1.2inaccordancewithSection72.3.2.8.Thisisshowninthefollowingexample:TheapplicationareadeterminedfromFigure72.3.1.2is1500squarefeet.AsrequiredbySection72.3.2.5,1500squarefeetisincreasedby30%to1950squarefeetforthesteeplypitchedroof.AsrequiredbySection72.3.2.6,the1950squarefeetisincreasedby30%forthedrypipesystem.Therefore,theoriginaldensitychosenfromFigure72.3.1.2mustbeappliedover2535squarefeet.Ensurethattherearenootherdesignareamodificationsrequiredforthesystembeinginstalled.
3. CanplasticpipebeusedonasprinklersystemcomplyingwithNFPA13?Section33.5allowstheuseofplasticpipethathasbeenspecificallylistedforfireprotectionuse.Thispipemustbeinstalledinaccordancewithitslistinglimitations,includinginstallationinstructions.
4. WhatisthelimitforthecalculatedwatervelocityinasprinklersystemcomplyingwithNFPA13?NFPA13doesnotspecifyamaximumlimitforthecalculatedwatervelocity.
5. Dowalkintypefreezers,coolers,vaultsandsafesrequiresprinklers?Yes.AsexplainedbyFormalInterpretation786,theseareasrequiresprinklersbecausetheyarepartofthepremises.NFPA13requiresthatsprinklersbeinstalledthroughoutthepremisesinaccordancewithSection51.1.Therearenoexceptionsprovidedwhichallowfor
-
NFPA 13-1999 FAQs
sprinkleromissionintheseareas.
6. InapplyingtheThreeTimesRule'forsprinklerobstructions(i.e.Section56.5.2.2),whatdimensionisthe24inchmaximumreferringto?Thismaximumdimensionisthedimensionmeasuredfromthesprinklertothenearestedgeoftheobstruction.Isolatedobstructionsthataremorethan24inchesawayfromstandarduprightandpendentsprinklersdonotgenerallycreateasignificantobstruction.
7. Aresprinklersrequiredinclosets?Yes.TherearelimitedexceptionsspecifiedinSection513.9.2forcertainsmallclosetsinthedwellingunitsofhotelsandmotels.
8. Canasupplycontrolvalvebeinstalleddownstreamofthefiredepartmentconnection?TheconfusionthatbringsaboutthisquestionisusuallycausedbySection515.2.4.2,theExceptiontoSection514.1.1.2,andExceptionNo.1toSection514.1.1.8.Thesesectionsarenecessarytodifferentiatethefiredepartmentconnectionfromothertypesofwatersupplies.Normally,acontrolvalveisrequiredbeforeandaftereachcheckvalveinasourceofsupply.Thevalvesarerequiredsothatthecheckvalvecanbeisolatedandserviced.Aswell,acontrolvalveisnormallyrequiredineachautomaticsourceofsupplyinaccordancewithSection514.1.1.2.However,thesecontrolvalvesarenotnecessary,norallowed,inthefiredepartmentconnectionpiping.Whilethecontrolvalvesarenotallowedinthefiredepartmentconnectionpipingitself,controlvalvescanbeinstalleddownstreamfromthefiredepartmentconnectionpipinginaccordancewith514.1.1.Itwouldbeimpracticaltorequireafiredepartmentconnectionafterallcontrolvalvesinamultizoneormultisystemarrangement.Furthermore,Section514.1.1.3ofNFPA13requiresthatallvalvescontrollingwatersuppliesbesupervisedintheopenposition.Inallcases,thearrangementforthefiredepartmentconnectionmustcomplywithSection515.2.3.
9. Ifawatercurtainisinstalled,whatistheequivalentfireseparationrating?NFPA13doesnotspecifyanequivalentfireseparationratingforwatercurtainsinstalledinaccordancewithSection513.4anddesignedinaccordancewithSection79.7.
10. Whatistheallowablereductioninfireseparationratingsinabuildingwhereasprinklersystemisinstalled?NFPA13doesnotaddresssuchreductions.Somebuilding/firecodeswillspecifyanallowablereductioninfireseparationratingsforcertainbuildingswheresprinklersareprovidedinaccordancewithNFPA13.Youwouldneedtoconsultwiththeapplicablebuilding/firecodeforyourparticularprojecttodetermineifthereareanyallowablereductions.
-
NFPA 13-1999 FAQs
11. Aresprinklersrequiredintheupperportionofanarchitecturalceilingfeature,evenwhentherearenoopeningstoaboveandthesprinklersatthelowerportiondonotexceedareaofcoveragelimitations?Thisquestionusuallyariseswitharchitecturalfeaturessuchasskylightsandroomswithmultilevelceilings.Thegeneralconcernwiththesetypesoffeaturesisthepotentialforheattopocket'andthenegativeimpacttotheoperationofthesprinklers.Thiscouldbetrueevenifsprinklersarespacedwithintheirlimitationsforallowableareaofprotection.NFPA13doesnotspecificallyaddressthesprinklerrequirementsforthesearchitecturalfeatures.However,theapplicablesectionsofChapter5doaddressthedistancebelowtheceilingthatsprinklersmustbepositioned.Theneedforsprinklersintheupperportioncanbedeterminedbasedonthedistancefromtheupperleveltothepositionatwhichthesprinklerswouldbeinstalledonthelowerlevel.IfthisdistanceexceedstheallowabledistancesspecifiedinChapter5,thensprinklerswouldberequiredattheupperlevel.ObstructionsspecifiedbyChapter5toanyofthesprinklerswouldalsoneedtobeexaminedandaccountedfor.
12. Aresprinklersrequiredwithinfurniture?No.Sprinklersarerequiredwithinallpermanentspacesofthestructure,suchasclosets,inaccordancewithSection51.1.Moveablefurnitureitems,suchasdesks,dressersandwardrobes,donotrequiresprinklerswithinthemevenwhentheyareaffixedtothepermanentstructureofthebuilding.
13. MustIdesignthesprinklersystemtoprotectthesamehazardthroughoutthestructure?No.NFPA13doesnotrequirethattheentirestructurebeprotectedasasinglehazardclassification.Therearethreeimportantthingstokeepinmind,however,whendesigningasystemwithmultiplehazardclassifications.Thefirstisthatyouwilllockthebuildinguseintothehazardconfigurationthatthesprinklersystemisdesignedfor.Iftheentirespacewasprotectedforthehighesthazard,however,thebuildinguserwouldnothavetoworryaboutthegenerallocationsofthedifferenthazards.Additionally,thehydrauliccalculationprocedureandsystemlayoutbecomemorecomplexwithmultiplehazardclassificationsthanwherethehighesthazardisusedthroughout.Lastly,Section71.2specifiesrequirementsforbuildingswithtwoormoreadjacenthazardoccupancies.
14. IftherearenohoseconnectionsinsideabuildingsprinkleredtocomplywithNFPA13,willthewaterdemandneedtoincludeahosestreamallowance?Yes.AnoutsidehosestreamdemandwouldberequiredinaccordancewithSection72.3.1.1.
15. DoesNFPA13addressfiresprinklersystemsprotectingstorageabove12feet?Yes.The1999editionofNFPA13incorporatedthefiresprinklersystemdesignandinstallationrequirementsfromNFPA231(StandardforGeneralStorage),NFPA231C(StandardforRackStorageofMaterials),NFPA231D(StandardforStorageofRubberTires),
-
NFPA 13-1999 FAQs
NFPA231E(RecommendedPracticefortheStorageofBaledCotton)andNFPA231F(StandardfortheStorageofRollPaper).TheotherrequirementsofNFPA231,NFPA231C,NFPA231D,NFPA231EandNFPA231FwereincorporatedintoanewstandardNFPA230(StandardfortheFireProtectionofStorage).
16. HowaretheNFPA13designandinstallationrequirementsarrangedforsystemsprotectingstorageandspecialdesignapproaches?Atableofcontentsisasfollows:73Palletized,SolidPiled,BinBox&ShelfStorage73.1General
73.2ClassIIV73.3Plastics74RackStorage74.1General74.2ClassIIV(upto25storage)74.3ClassIIV(over25storage)74.4Plastics75IdlePalletStorage76RubberTireStorage77BaledCottonStorage78RollPaperStorage79SpecialDesignApproaches79.1General79.2ResidentialSprinklers79.3QuickResponseEarlySuppressionSprinklersQRES(reserved)79.4LargeDropSprinklers(ClassIIV&Plastics)
-
NFPA 13-1999 FAQs
79.5EarlySuppressionFastResponseSprinklersESFR(ClassIIV&Plastics)79.6ExposureProtection79.7WaterCurtains79.8ProtectionofSteelColumns
17. IsthereaceilingheightatwhichNFPA13permitstheomissionofsprinklers?No.