03 Power Factor

download 03 Power Factor

of 19

description

Power utilization calculation

Transcript of 03 Power Factor

  • Power Factor (PF)

  • Learning Outcomes

    At the end of the lecture, students are expected to be able

    to calculate the size of a capacitor for PF correction, and

    to calculate the total energy save per year, penalty per year and the payback period.

    EPO521 Nor Farahaida Abdul Rahman 2

  • Introduction

    PF is used to measure the efficiency level of electricity usage.

    =

    =

    cos

    = cos

    where = real power (W)

    = apparent power (VA) = 2 + 2

    = reactive power (Var)

    & = rms current & rms voltage

    cos = angle between & I P

    Q

    S

    q

    EPO521 Nor Farahaida Abdul Rahman 3

  • Causes of Low PF

    1. Transformer and induction motor

    Magnetic current magnetic field

    2. Arc lamps, electric discharge lamps and industrial heating system

    They require control gear in a form of chokes, ballasts and etc.

    3. Varying load condition

    During low load period, supply voltage is increase which increase magnetizing current.

    EPO521 Nor Farahaida Abdul Rahman 4

  • Effects of low PF

    1. Large kVA rating of equipment (more expensive).

    2. Greater conductor size (size of cable depends on current).

    3. Large copper losses (poor efficiency).

    4. Poor Voltage Regulation (VR).

    VR is a measure of change in the voltage magnitude between the sending and receiving end or from no load to full load conditions.

    5. Reduced handling capacity of system.

    6. Penalty from power utilities.

    EPO521 Nor Farahaida Abdul Rahman 5

  • PF Correction

    1. Static capacitor (bank).

    2. Synchronous condenser.

    3. Phase advancer.

    EPO521 Nor Farahaida Abdul Rahman 6

  • Static Capacitor (1)

    Install in shunt

    Utility side pole mounted racks, enclosed bank (LV) & substation banks (HV EHV).

    Load side individual or group loads.

    http://www.tamintablo.com/english/product/Capacitorbanks.aspx

    EPO521 Nor Farahaida Abdul Rahman 7

  • Static Capacitor (2)

    Advantages: cheapest, less maintenance and simplest method.

    Disadvantages:

    Resonance amplification of harmonic voltage overvoltage.

    Oversize capacitor and switching operation transient voltage tripping.

    repair is uneconomical.

    EPO521 Nor Farahaida Abdul Rahman 8

  • Synchronous Condenser (1)

    Connected in parallel with power supply; running on no load condition.

    It takes a leading current when over-exited, and therefore behaves as a capacitor.

    EPO521 Nor Farahaida Abdul Rahman 9

    https://jawnsy.wordpress.com/page/3/

  • Synchronous Condenser (2)

    Advantages

    Stepless control varying the field excitation

    Long useful life the windings have high thermal stability

    No resonance, voltage spike and static components

    Disadvantages losses in the motor, high maintenance cost, auxiliary circuit and noise

    EPO521 Nor Farahaida Abdul Rahman 10

  • Phase Advancer

    Used to improve the PF of induction motors.

    It is mounted on the same shaft as the main motor and is connected in the rotor circuit.

    It provides required magnetomotive force (MTF) or ampere turns to the rotor at slip frequency.

    Uneconomical to be applied on motors below 200hp.

    EPO521 Nor Farahaida Abdul Rahman 11

  • Example

    A 5 MVA transformer is loaded to 4.5 MVA at a power factor of 0.82 lag. The transformer has a rated conductor loss equal to 1% of the transformer rating. The tariff given by power utility is RM0.17/kWhr and the penalty charge is 0.20sen/kVARhr (if PF falls below 0.95). Assume that the transformer operates for 24 hours per day.

    EPO521 Nor Farahaida Abdul Rahman 12

  • a) Calculate the leading kVar necessary to correct the PF to 0.95 lag.

    Reactive power needed for PF correction, = 1 2

    where

    1 = reactive power before PF correction (Var)

    2 = reactive power after PF correction (Var)

    (Answer: 1,363kVar)

    EPO521 Nor Farahaida Abdul Rahman 13

  • b) Calculate the size of a PF-corrector capacitor. The capacitor will be installed in 3-phase system (400V, 50Hz, Y-configuration).

    PF capacitor, =

    2

    where

    = angular frequency = 2

    = operating frequency

    = rms voltage accross the capacitor terminal

    (Answer: 81,348F)

    EPO521 Nor Farahaida Abdul Rahman 14

  • c) Calculate energy saved per year.

    Energy saved per day(kWhr) = loss base operating hour

    loss (p.u.) = lossold PF lossnew PF

    loss p.u. = %loss real

    2

    (Answer: 90,490.8kWhr)

    EPO521 Nor Farahaida Abdul Rahman 15

  • d) Calculate cost saved per annum.

    Cost saved per year (RM) = energy saved per year (kWhr) tariff

    (Answer: RM15,383.44)

    EPO521 Nor Farahaida Abdul Rahman 16

  • e) Calculate the penalty charge per year

    Penalty RM = 1 in kVar operating hour penalty 0.01

    (Answer: RM23,879.76)

    Other alternative calculation, please refer TNB regulation.

    EPO521 Nor Farahaida Abdul Rahman 17

  • f) If the maximum demand charge per kVA is RM14 (assume per month), calculate the reduction in maximum demand and its saving in a month.

    Maximum demand, =

    (Answer: 616kVar, RM8,624)

    EPO521 Nor Farahaida Abdul Rahman 18

  • g) Calculate the cost of the PF capacitor and its payback period. Assume that the capacitor cost per kVar is RM150, the rate of depreciation per year is 7% and the bank interest charge per year is 8%,

    payback period =capacitor cost

    Net saving per year

    Net saving per year

    = Saving demand charge per year total depreciation interest

    total depreciation interest

    = capacitor cost depreciation rate + bank interest

    (Answer: RM204,450, 2.8 years)

    EPO521 Nor Farahaida Abdul Rahman 19