Post on 30-Nov-2015
Caracteristicas Geometricas
ANCHO ALTOALTURA LIBRE DE ALBAÑILERIA 2.4 m
ESPESOR EFECTIVO DE LOS MUROS 0.14 mVIGAS SOLERAS Y DINTELES 0.14 0.3 m
ALFEIZAR Y PARAPETOS EN LA AZOTEA 1 mLOSA MACIZA 0.12 m
GARGANTA DE LA ESCALERA 0.12 mDESCANSO DE LA ESCALERA 0.16 m
Caracteristicas de los MaterialesCONCRETO f´c 175 kg/cm2
ACERO fy 4200 kg/cm2
ALBAÑILERIA f'm 850V'm 92
LADRILLO solidoMORTERO 1:04
PORCENTAJE DE REDUCCION DE CARGA VIVA 0.25 ESTE PORCENTAJE DEPENDE DEL TIPO O CATEGORIA DE LA EDIFICACIONCARGAS UNITARIAS
CONCRETO ARMADO 2.4 ton/m3LOSA MACIZA 2.4 0.12 = 0.288 ton/m2
ACABADOS 0.1 ton/m2SOBRECARGA DE AZOTEA 0.1 ton/m2
SOBRECARGA DE VIVIENDA 0.2 ton/m2SOBRECARGA DE ESCALERA 0.2 ton/m2
MUROS DE ALBAÑILERIA TARRAJEADA 1.9 0.16 = 0.304 ton/m2ALFEIZAR Y PARAPETOS TARRAJEADOS 1.4 0.16 = 0.224 ton/m2
VENTANAS 0.02 ton/m2
AREAS TRIBUTARIAS
AX1 6.3AX2 11.7AX3 5.4AX4 1.2AY1 6.3AY2 8.2
ACOLUMNA 5.3
COMPROBACION DEL ESFUERZO AXIAL MAXIMO PARA MURO MAS CARGADO X2
PESO PROPIO= 0.304X2.4X3.39X4 = 10.04
SOLERA= 0.15X0.30X4.47X2.4X4 = 1.828512LOSA= (0.288+0.10)X12.65X4 = 18.1584
SOBRECARGA= 0.25X11.5X3+0.10*11.5 = 8.19Pm 38.216912 ton
79.354 ≤ 129.217 ≤ 127.5
No cumple con el esfuerzo axial
DENSIDAD MINIMA DE MUROS REFORZADOS EN CADA DIRECCION
DATOS: Ʃ Lt ≥ ZUSNZ= 0.4 Ap 56U= 1S= 1.2 ZUSN = 0.034N= 4 56
Ap= 107.04L= EN X-X: Ʃ Lt= 3.7294t= 0.14
Ʃ Lt = 0.035 Cumple con densidad minima
Ap
EN Y-Y: Ʃ Lt= 3.9216
Ʃ Lt = 0.037 Cumple con densidad minima
Ap
METRADO DE CARGAS EN PISO TIPICO
ZONAS O ELEMENTOS ALFEIZER VIGUETA VENTANA VIGA SOLERA Y DINTELALTO PESO ANCHO ALTO P.ESP. ALTO P.ESP. ANCHO ALTO
ZONA DE VENTANAS 0.9 0.224 0.16 0.1 2.4 1.5 0.02 0.14 0.3ZONA DE VIGAS 0.14 0.3
ZONA DE MUROS 0.14 0.3
METRADO DE CARGAS DIRECTAS EN AZOTEA
ZONAS O ELEMENTOS PARAPETO VIGUETA VENTANA VIGA SOLERA Y DINTELALTO PESO ANCHO ALTO P.ESP. ALTO P.ESP. ANCHO ALTO
PARAPETO 0.9 0.224 0.14 0.1 2.4VIGAS CON PARAPETO 0.14 0.3
ðm =
0.16
VIGAS SIN PARAPETO 0.14 0.3MUROS CON PARAPETO 0.14 0.3MUROS SIN PARAPETO 0.14 0.3
CARGAS REPARTIDAS EN LA LOSACARGA REPARTIDA LOSA MACISA 0.288 0.1 = 0.388 tn/m2
ESTE PORCENTAJE DEPENDE DEL TIPO O CATEGORIA DE LA EDIFICACION
COMPROBACION DEL ESFUERZO AXIAL MAXIMO PARA MURO MAS CARGADO X2
DENSIDAD MINIMA DE MUROS REFORZADOS EN CADA DIRECCION
METRADO DE CARGAS EN PISO TIPICOVIGA SOLERA Y DINTEL ACABADO PESO DE MURO TOTAL tn/m
PESO ANCHO PESO ALTO PESO
2.4 0.37082.4 0.14 0.1 0.11482.4 2.4 0.304 0.8304
METRADO DE CARGAS DIRECTAS EN AZOTEAVIGA SOLERA Y DINTEL ACABADO PESO DE MURO TOTAL
PESO ANCHO PESO ALTO PESO
0.23522.4 0.336
0.16
3.24
2.16
11.484 M2
1.5
2.4 0.14 0.1 0.11482.4 1.2 0.304 0.70082.4 0.16 0.1 1.2 0.304 0.4816
CARGAS REPARTIDAS EN LA LOSA
0.16
CALCULO DEL PESO TOTAL DE LA ESTRUCTURA CALCULO DE CARGAS GRAVITACIONALES EN PISO TIPICO
ELEMENTO MEDIDAS
PISO TIPICOMURO X1
CARGAS MUERTASAREA LONG. MED. ANCHO PESO
LOSA 6.3 0.388 2.444 MURO 3.44 0.83 2.857
VENTANA 1.095 0.371 0.406 TOTAL CARGA MUERTA X1 5.707
CARGAS VIVASLOSA 6.3 0.2 1.26
TOTAL CARGA VIVA X1 1.26 TOTAL CARGA MURO X1 6.02
MURO X2CARGAS MUERTASAREA LONG. MED. ANCHO PESO
LOSA 11.7 0.388 4.54 MURO 3.44 0.830 2.86 VIGA 1.095 0.115 0.13
VENTANA 0.371 - ESCALERA -
TOTAL CARGA MUERTA X2 7.52 CARGAS VIVAS
LOSA 11.7 0.2 2.340 VIGA 1.095 0.14 0.2 0.031
ESCALERA - TOTAL CARGA VIVA X2 2.37
TOTAL CARGA MURO X2 8.11
MURO X3CARGAS MUERTASAREA LONG. MED. ANCHO PESO
LOSA 5.4 0.388 2.095 MURO 3.44 0.830 2.857 VIGA 0.115 -
VENTANA 1.095 0.371 0.406 ESCALERA -
TOTAL CARGA MUERTA X3 5.358
PESO TOTAL
MUERTO
CARGAS VIVASLOSA 5.4 0.2 1.080 VIGA 0.2 -
ESCALERA - TOTAL CARGA VIVA X3 1.080
TOTAL CARGA MURO X3 5.63
MURO X4CARGAS MUERTASAREA LONG. MED. ANCHO PESO
LOSA 1.2 0.388 0.466 MURO 3.05 0.83 2.533 VIGA 0.115 -
VENTANA 2.19 0.371 0.812 ESCALERA 2.12 2.120
TOTAL CARGA MUERTA X4 5.930 CARGAS VIVAS
LOSA 1.2 0.2 0.240 VIGA 0.2 -
ESCALERA 1.58 1.580 TOTAL CARGA VIVA X4 1.820
TOTAL CARGA MURO X4 6.39
MURO Y1CARGAS MUERTASAREA LONG. MED. ANCHO PESO
LOSA 6.3 0.388 2.444 MURO 7.48 0.830 6.211 VIGA 0.115 -
VENTANA 0.371 - ESCALERA -
TOTAL CARGA MUERTA Y1 8.656 CARGAS VIVAS
LOSA 6.3 0.2 1.26 VIGA 0.2 -
ESCALERA - TOTAL CARGA VIVA Y1 1.260
TOTAL CARGA MURO Y1 8.97
MURO Y2CARGAS MUERTASAREA LONG. MED. ANCHO PESO
LOSA 8.2 0.388 3.182 MURO 3.32 0.83 2.757
VIGA 4.46 0.115 0.512 VENTANA 0.371 - ESCALERA 1.180
TOTAL CARGA MUERTA Y2 7.631 CARGAS VIVAS
LOSA 8.2 0.200 1.640 VIGA 4.46 0.14 0.200 0.125
ESCALERA 0.760 TOTAL CARGA VIVA Y2 2.525
TOTAL CARGA MURO Y2 8.26
COLUMNACARGAS MUERTASAREA LONG1 ALTURA LONG2 PESO
LOSA 5.3 0.388 2.06 COLUMNA 0.0768 2.70 2.400 0.498
VIGA 3.365 0.115 0.386 VENTANA 1.095 0.371 0.406 ESCALERA -
TOTAL CARGA MUERTA COLUMNA 3.346 CARGAS VIVAS
LOSA 5.3 0.2 1.06 VIGA 3.365 0.14 0.2 0.094
ESCALERA - TOTAL CARGA VIVA COLUMNA 1.15
TOTAL COLUMNA 3.63
CALCULO DE CARGAS GRAVITACIONALES EN LA AZOTEA
ELEMENTO MEDIDAS
AZOTEAMURO X1
CARGAS MUERTASAREA LONG. MED. ANCHO PESO
LOSA 6.3 0.388 2.444 MURO+PARAPETO 3.44 0.701 2.411 VIGA+PARAPETO 1.095 0.336 0.368
MURO SIN PARAPETO 0.482VIGA SIN PARAPETO 0.115
VENTANA - ESCALERA -
TOTAL CARGA MUERTA X1 5.223
PESO TOTAL
MUERTO
CARGAS VIVASLOSA 6.3 0.1 0.63
VIGA SIN PARAPETO 0.1 - MURO SIN PARAPETO 0.1
VIGA 0.1ESCALERA -
TOTAL CARGA VIVA X1 0.630 TOTAL CARGA MURO X1 5.38
MURO X2CARGAS MUERTASAREA LONG. MED. ANCHO PESO
LOSA 11.700 0.388 4.540 MURO+PARAPETO 0.701 - VIGA+PARAPETO 0.336 -
MURO SIN PARAPETO 3.44 0.482 1.657 VIGA SIN PARAPETO 1.095 0.115 0.126
VENTANA - ESCALERA
TOTAL CARGA MUERTA X2 6.322 CARGAS VIVAS
LOSA 11.700 0.1 1.170 VIGA SIN PARAPETO 1.095 0.14 0.1 0.02
MURO SIN PARAPETO 3.44 0.16 0.1 0.06 VIGA 0.1 -
ESCALERA - TOTAL CARGA VIVA X2 1.240
TOTAL CARGA MURO X2 6.63
MURO X3CARGAS MUERTASAREA LONG. MED. ANCHO PESO
LOSA 5.4 0.388 2.095 MURO+PARAPETO 3.44 0.701 2.411 VIGA+PARAPETO 1.095 0.336 0.368
MURO SIN PARAPETO 0.482 - VIGA SIN PARAPETO 0.115 -
VENTANA - ESCALERA
TOTAL CARGA MUERTA X3 4.874 CARGAS VIVAS
LOSA 5.4 0.1 0.540 VIGA SIN PARAPETO 0.1 -
MURO SIN PARAPETO 0.1 - VIGA 0.1 -
ESCALERA - TOTAL CARGA VIVA X3 0.540
TOTAL CARGA MURO X3 5.01
MURO X4CARGAS MUERTASAREA LONG. MED. ANCHO PESO
LOSA 1.2 0.388 0.466 MURO+PARAPETO 3.05 0.701 2.137 VIGA+PARAPETO 2.19 0.336 0.736
MURO SIN PARAPETO 0.482 - VIGA SIN PARAPETO 0.115 -
VENTANA - ESCALERA
TOTAL CARGA MUERTA X4 3.339 CARGAS VIVAS
LOSA 1.2 0.1 0.120 VIGA SIN PARAPETO 0.1 -
MURO SIN PARAPETO 0.1 - VIGA 0.1 -
ESCALERA - TOTAL CARGA VIVA X4 0.120
TOTAL CARGA MURO X4 3.37
MURO Y1CARGAS MUERTASAREA LONG. MED. ANCHO PESO
LOSA 6.3 0.388 2.444 MURO+PARAPETO 7.48 0.701 5.242 VIGA+PARAPETO 0.336 -
MURO SIN PARAPETO 0.482 - VIGA SIN PARAPETO 0.115 -
VENTANA - ESCALERA
TOTAL CARGA MUERTA Y1 7.686 CARGAS VIVAS
LOSA 6.3 0.1 0.630 VIGA SIN PARAPETO 0.1 -
MURO SIN PARAPETO 0.1 - VIGA 0.1 -
ESCALERA - TOTAL CARGA VIVA Y1 0.630
TOTAL CARGA MURO Y1 7.84
MURO Y2CARGAS MUERTASAREA LONG. MED. ANCHO PESO
LOSA 8.2 0.388 3.182 MURO+PARAPETO 3.32 0.701 2.327 VIGA+PARAPETO 0.336 -
MURO SIN PARAPETO 0.482 - VIGA SIN PARAPETO 4.46 0.115 0.512
VENTANA - ESCALERA 0.885
TOTAL CARGA MUERTA Y2 6.905 CARGAS VIVAS
LOSA 8.2 0.1 0.820 VIGA SIN PARAPETO 4.46 0.14 0.1 0.06
MURO SIN PARAPETO 0.1 - VIGA 0.1 -
ESCALERA 0.57 TOTAL CARGA VIVA Y2 1.452
TOTAL CARGA MURO Y2 7.27
COLUMNACARGAS MUERTASAREA LONG ALTO CANT
LOSA 5.3 0.388 2.056 VIGA+PARAPETO 2.46 0.336 0.827
VIGA SIN PARAPETO 2 0.115 0.230 PARAPETO 0.32 0.235 0.075
TOTAL CARGA MUERTA COLUMNA 3.188 CARGAS VIVAS
LOSA 5.3 0.1 0.530 VIGA 0.28 0.1 -
TOTAL CARGA VIVA COLUMNA 0.530 TOTAL CARGA COLUMNA 3.32
CUADRO RESUMEN DE PESOS PESO PARA PRIMER PSIO
MURO PISO TIPICO AZOTEAPD+PL PD+0.25PL PD+PL PD+0.25PL
X1 6.97 6.02 5.85 5.38X2 9.89 8.11 7.56 6.63X3 6.44 5.63 5.41 5.01X4 7.75 6.39 3.46 3.37Y1 9.92 8.97 8.32 7.84Y2 10.16 8.26 8.36 7.27
COLUMNA 4.50 3.63 3.72 3.32
87.65 74.28
PESO TOTAL DE LA EDIFICACION EN LOS CUATRO PISOS337.22
CENTRO DE MASA EN EL EJE Y
MURO X1 X2 X3 X4 Y1
Yi 0 4.16 7.32 7.32 3.66Pi 6.02 8.11 5.63 3.19 8.97
PiYi 0 33.76 41.20 23.37 32.83Yi centro de gravedad en el eje YPi Peso del piso tipico
ƩPiYi 178.58 4.07 mƩ Pi 43.82
7.07 m
EXCENTRICIDAD ACUMULADA
SISMO EN X-X Ea= 7.48x0.05 = 0.37 mSISMO EN Y-Y Ea= 0.05x14.14 = 0.72 m
CARGAS AXIALES ACUMULADAS EN CADA MUROMURO PISO TIP. AZOTEA PISO 4 PISO 3
X1 6.02 5.38 5.38 11.40X2 8.11 6.63 6.63 14.75
Peso del Nivel
YCM =
XCM =
X3 5.63 5.01 5.01 10.64 X4 6.39 3.37 3.37 9.75 Y1 8.97 7.84 7.84 16.81 Y2 8.26 7.27 7.27 15.53
Columna 3.63 3.32 3.32 6.96
FUERZA CORTANTE EN LA BASE (SISMO MODERADO)
DATOS: H= 1/2 (ZUSCP)Z= 0.4 RU= 1S= 1 H= 1/2(0.4*1*1.2*8.33*350.12)
Ct= 60 3T= h/Ct = 0.18 seg
Tp= 0.4 H= 56.20C= 2.5XTp/T = 2.5P= 337.22R= 3
FUERZA DE INERCIA (SISMO MODERADO)
CORTANTE DE ENTREPISO (SISMO MODERADO)
CORTANTE DE ENTREPISO (SISMO SEVERO)
NIVEL hi (m) Pi (ton) Pixhi (tn-m) Fi (ton) Hi (ton)4 10.8 74.28 802.19 20.29 20.293 8.1 87.65 709.96 17.96 38.252 5.4 87.65 473.30 11.97 50.221 2.7 87.65 236.65 5.99 56.20
Ʃ 2222.11 56.20
5.26 → C=
CUADRO RESUMEN DE PESOS
PASOS PREVIOS PISO TIPICO AZOTEAPASO 1 SUMAMOS X1,X2,X3,Y1,Y2,COLUMNA 40.63 35.45PASO 2 MULTIPLICAMOS POR 2 A RESULTADO DE PASO 1 81.26 70.91PASO 3 SUMAMOS VALOR DE X4 A RESULTADO DE PASO2 87.65 74.28
CENTRO DE MASA EN EL EJE Y
Y2 C SUMATORIA
5.740 08.26 3.63 43.82 47.42 0 178.58
EXCENTRICIDAD ACUMULADA
CARGAS AXIALES ACUMULADAS EN CADA MUROPISO 2 PISO 1
17.42 23.45 22.86 30.98
16.26 21.89 16.14 22.52 25.79 34.76 23.79 32.05 10.59 14.23
FUERZA CORTANTE EN LA BASE (SISMO MODERADO)
1/2(0.4*1*1.2*8.33*350.12)3
Tn
FUERZA DE INERCIA (SISMO MODERADO)
CORTANTE DE ENTREPISO (SISMO MODERADO)
CORTANTE DE ENTREPISO (SISMO SEVERO)
VEi (ton)40.5876.49
100.44112.41
altura 1.64peso 60
0.16 3.28 0.16 2.19 0.16 2.73 0.16 2.19 0.16
0.16
3
0.16
4
0.16
0.16 3.28 2.19
0.16 2.73
0.16 2.19 3.28
11.484 M2
5.267 M21.166 M2
1.50
2.4 0.42
1.08
8.11 M2
5.28 M2
6.2 17M2
6.25 M2
2 0.92 1.08
1.4
3.28 0.16
0.16
3
0.16
4
0.16
3.28
0.16
Altura 1.64Peso 60
EJE X EJE YNuevo Ancho 0.2 Nuevo Ancho 0.2muro Muro
0.2 3.28 2.19 0.2 2.73 0.2
0.2 1.5 2.47 0.4 1.1 0.2 1.37 1.37 0.2
0.16 X3 X4 0.16
1.5
3
A(X3)= 5.4 A(X4)= 1.2
Y2
1.5
Y1
A(X2)= 11.7
0.16 X2 0.16
2
4
A (Y2)= 8.2
A (Y1)= 6.3
2A(X1)= 6.3 C= 5.3
0.16 X1 C 0.16
0.2 2 1.47 0.9 1.1 0.2 1.37 1.37 0.2
0.2 3.28 2.19 0.2 2.73 0.2
RESULTADO DE DESPLAZAMIENTO SEGÚN SAP
SISMO EN LA DIRECCION X
Nivel Dx (m) ?x (m) D1 (m) ?d1 (m) ?x/?d14 0 0.000003 0 0.000002 0 0.000001 0 0.00000
SISMO EN LA DIRECCION Y
Nivel Dy (m) ?y (m) D1 (m) ?d1 (m) ?y/?d14 0 03 0 02 0 01 0 0
AMPLIFICAMOS PARA PASAR A CONDICION INELASTICA ANTE SISMO SEVEROγ= 0 < 0.005
Desplazamiento
de Entrepiso
Distorsion
Angular
Desplazamiento
Angular
Desplazamiento
de Entrepiso
Desplazamiento
Relativo
Desplazamiento
Angular
PISO 1
MURO Pg (Ton) Ve (Ton) Me (t-m) L (m)
X1 23.45 3.44X2 30.98 3.44X3 21.89 3.44X4 22.52 3.05Y1 34.76 7.48Y2 32.05 3.32
Columna 14.23
PISO 2
MURO Pg (Ton) Ve (Ton) Me (t-m) L (m)
X1 17.42 3.44X2 22.86 3.44X3 16.26 3.44X4 16.14 3.05Y1 25.79 7.48Y2 23.79 3.32
Columna 10.59
PISO 3
MURO Pg (Ton) Ve (Ton) Me (t-m) L (m)
X1 11.40 3.44X2 14.75 3.44X3 10.64 3.44X4 9.75 3.05Y1 16.81 7.48Y2 15.53 3.32
Columna 6.96
RESISTENCIA AL AGRETAMIENTO DIAGONAL
VERIFICACION AL CORTE - CONTROL DE FISURACION
VERIFICACION DE LA RESISTENCIA AL CORTE DEL EDIFICIOƩ Vmi ≥ Vei
CALCULO DE LAS FUERZAS INTERNAS AMPLIFICADASVui= Vei.Vmi/Vei
Mui= Mei.Vmi/Vei
PISO 1
MURO œVm1/Ve1
X1 23.45 0 0 3.44 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!X2 30.98 0 0 3.44 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!X3 21.89 0 0 3.44 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!X4 22.52 0 0 3.05 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!Y1 34.76 0 0 7.48 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!Y2 32.05 0 0 3.32 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
Columna 14.23 0 0VERIFICAMOS LA RESISTENCIA AL CORTE
SVm (xx) = #DIV/0! > 112.41 #DIV/0!SVm (yy) = #DIV/0! > 112.41 #DIV/0!
PISO 2
MURO œVm1/Ve1
X1 17.42 0 0 3.44 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!X2 22.86 0 0 3.44 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!X3 16.26 0 0 3.44 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!X4 16.14 0 0 3.05 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!Y1 25.79 0 0 7.48 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!Y2 23.79 0 0 3.32 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
Columna 10.59 0 0VERIFICAMOS LA RESISTENCIA AL CORTE
SVm (xx) = #DIV/0! > 100.44 #DIV/0!
Vm=0.5 x V´m x œ x t x L+ 0.23 x Pg
Vc ≤ 0.55Vm
Donde: 2 ≤ Vmi/Vei ≤ 3
Pg
(Ton)
Ve
(ton)
Me
(t-m)
L
(m)
Vm
(ton)
0.55 Vm
(Ton)
Vu
(Ton)
Mu
(t-m)
VERIFICAMOS Ve <
0.55Vm
Pg
(Ton)
Ve
(ton)
Me
(t-m)
L
(m)
Vm
(ton)
0.55 Vm
(Ton)
Vu
(Ton)
Mu
(t-m)
VERIFICAMOS Ve <
0.55Vm
SVm (yy) = #DIV/0! > 100.44 #DIV/0!
PISO 3
MURO œVm1/Ve1
X1 11.40 0 0 3.44 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!X2 14.75 0 0 3.44 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!X3 10.64 0 0 3.44 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!X4 9.75 0 0 3.05 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!Y1 16.81 0 0 7.48 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!Y2 15.53 0 0 3.32 #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!
Columna 6.96 0 0VERIFICAMOS LA RESISTENCIA AL CORTE
SVm (xx) = #DIV/0! > 76.49 #DIV/0!SVm (yy) = #DIV/0! > 76.49 #DIV/0!
Pg
(Ton)
Ve
(ton)
Me
(t-m)
L
(m)
Vm
(ton)
0.55 Vm
(Ton)
Vu
(Ton)
Mu
(t-m)
VERIFICAMOS Ve <
0.55Vm
MUROS DEL PRIMER PISO
MURO X1 X2 X3 X4 Y1 Y2
PD +PL 6.97 9.89 6.44 7.75 9.92 10.16PISO TIPICO
PD + PL 5.85 7.56 5.41 3.46 8.32 8.36AZOTEAPm (ton) 26.75 37.24 24.73 26.71 38.06 38.82
L (m) 3.44 3.44 3.44 3.05 7.48 3.32 Õm (ton/m2) 55.55 77.33 51.34 62.55 36.35 83.53
0.10% 0.10% 0.10% 0.10% 0.10%
MUROS DEL SEGUNDO PISOMURO X1 X2 X3 X4 Y1 Y2PD +PL 6.97 9.89 6.44 7.75 7.75 9.92
PISO TIPICOPD + PL 5.85 7.56 5.41 3.46 8.32 8.36AZOTEAPm (ton) 19.79 27.35 18.29 18.96 23.82 28.19
L (m) 3.28 3.44 3.44 3.05 7.48 3.32 Õm (ton/m2) 43.09 56.78 37.98 44.40 22.74 60.65
0.10% 0.10% 0.10% 0.10%
Pm/Lt ≤ 0.05 f´m Refuerzo
Horizontal
No cumple, pero según norma
E070 se coloca acero
Pm/Lt ≤ 0.05 f´m Refuerzo
Horizontal
No cumple, y no
se colocara acero
No cumple, y no
se colocara acero